1 Table of Contents National Board Pressure Relief Device Certificati ons NB-18 FOREWARD... 1 NATIONAL BOARD PRESSURE RELIEF DEVICE CERTIFICATION... 2 DETERMINATION OF CERTIFIED RELIEVING CAPACITIES... 6 LISTING OF ASSEMBLER AND MANUFACTURER CERTIFICATIONS... 11 LISTING OF CERTIFIED DEVICE TYPES... 124 LISTING OF RUPTURE CCFs BY VALVE MANUFACTURER... 730 LISTING OF VR CERTIFICATE HOLDERS... 756 LISTING OF TESTING ORGANIZATION CERTIFICATE HOLDERS... 795

2 Table of Contents FOREWARD This publication presents the National Board pressure relief device certification program and lists those device designs certified and those organizations authorized to apply the National Board “NB” symbol to devices of certified types. This publication also includes a listing of organizations which have received a National Board certificate of authorization for the use of the “VR” repair symbol stamp in accordance with the National Board -23 and NB- 514, Accreditation of VR Repair Organizations. Inspection Code publication, NB This publication is divided into a series of listings as found in the table of contents. If using a portable document file (pdf) viewer, the user of this document may also use the bookmarks and search features of the this document. Companies which no longer hold certifications or device design certifications viewer to navigate which are no longer in production are not listed. Information on these devices may be obtained by contacting the National Board Pressure Relief Department. This publication is updated weekly and is available free of charge from the National Board Web site, www.nationalboard.org. The capacity rating values listed were determined from tests of samples of the relevant pressure relief device type at a National Board accepted testing laboratory under ideal conditions. Such capacities are certified only for the conditions under which obtained. Since the listed rating values were determined under atmospheric -pressure pressure discharge conditions, the calculated capacities may not be valid when discharge back conditions exist. The National Board has not tested each production device and makes no certification regarding its capacity, manufacturer, or application. Installation, operating conditions and manufacturer’s mendations must be considered in selecting a pressure relief device for service. recom -18 as accurate and complete as Every effort has been made to make the information contained within NB possible. However, this data is subject to change without notice and is neither guaranteed nor warranted. The National Board, its members, and employees assume no liability for the use or misuse of any information contained herein. Organizations with listings are urged to review their listed information for accuracy, and to bring any errors or omissions to the National Board’s attention so that corrections can be made. For further information regarding the National Board “NB” symbol and this program contact: The National Board of Boiler and Pressure Vessel Inspectors 1055 Cr upper Avenue Columbus, Ohio 43229- 1183 Voice: 614.888.8320 Email: [email protected] Page 1 of 812 Effective Date: 2019-05-31

3 Table of Contents ONAL BOARD PRESSURE RELIEF DEVICE CERTIFICATION NATI ADMINISTRATIVE REQUIREMENTS 1.0 INTRODUCTION The National Board Pressure Relief device certification program was developed in the mid- 1930s in an effort to enhance safety to the industry and to the general public. At that time, when jurisdictional authorities expressed concern about relieving capacities, the National Board sponsored tests at The Ohio State University to compare the stamped and actual relieving capacities. They found large differences which prompted the National Board’s membership to resolve that safety valves should be standards and performance must be demonstrated by tests. At the request of constructed to recognized the National Board, the American Society of Mechanical Engineers (ASME) appointed a special committee on safety valve requirements to cooperate with the National Board and developed construction requirements, quality standards and testing procedures. SCOPE 2.0 This National Board program provides for the certification of pressure relief device designs and 2.1 the accreditation of organizations who manufacture or assemble these devices. Accredited organizations are issued a certificate of authorization to apply the National Board "NB” symbol to devices of certified desi gns. 2.2 Technical requirements applied by this program to pressure relief devices are contained in standards called "construction codes.” Abbreviations for these codes are listed below: Construction Code Code Section I ASME Boiler & Pressure Vessel Code (B&PVC) Section I ASME (B&PVC) Section III III IV ASME (B&PVC) Section IV SME (B&PVC) Section VIII VIII A Organizations which have met the program requirements and have paid the proper 2.3 administrative fees will be granted permission to use the National Board’s "NB” mark on devices to denote certification by the National Board of the pressure relieving device design. 3.0 PROGRAM RULES AND PROCEDURES ADMINISTRATION 3.1 Organizations desiring National Board certification and permission to use the "NB” mark shall apply to the National Board on forms available from the Pressure Relief Department. Manufacturers (as defined by the construction code) must supply all information as requested. Assemblers (as defined by the construction code) must indicate the valve manufacturer’s name and valve type to be considered for certification. QUALITY SYSTEM REQUIREMENTS 3.2 Each applicant shall have and maintain a quality system which shall establish that all of these rules and administrative procedures and applicable construction code requirements, including material control, fabrication, machining, welding, examination, setting, testing and inspection, will be met. Page 2 of 812 Effective Date: 2019-05-31

4 Table of Contents A written description of the system the applicant will use shall be available for review and shall contain, as a minimum, the features set forth by the construction code. The system shall include a description of the controls to ensure that the "NB” mark is applied to devices which have been may be brief or voluminous, depending upon certified in accordance with 3.3. This description the circumstances, and shall be treated confidentially. A review for acceptance of the applicant’s quality control system will be performed by a representative of the National Board. The review will include a demonstration of the implementation of the provisions of the applicant’s quality system. Sample production devices will be selected for testing of performance and capacity. Each applicant shall issue a controlled copy of the accepted quality system written description to the National Board. Except for changes which do not affect the quality system, revisions to the written description shall not be implemented until such revisions are accepted at any time by the National Board. CAPACITY CERTIFICATION OF 3.3 DEVICE DESIGNS DESIGN REVIEW (MANUFACTURERS ONLY) 3.3.1 Before a design is tested by a manufacturer, it will be reviewed by the National Board to determine that all applicable mechanical and material requirements of the construction code have been considered and incorporated into the design as necessary. No testing for device certification will be performed on devices which do not meet these requirements. INITIAL TESTING (MANUFACTURERS ONLY) 3.3.2 After completion of the design review per 3.3.1, tests of devices specified by the construction code shall be conducted to determine the certified rating which will be applied to the production device. Agreement shall be reached between the manufacturer and the National Board as to the number, sizes and set pressures of the devices to be tested. These tests will be performed for new designs or when an existing design is modified. Modifications of designs which affect the flow path, lift or performance characteristics must be reviewed by the National Board. Provisions for notifying the National Board of design changes shall be included in the applicant’s quality system. PRODUCTION TESTING 3.3.3 An applicant who has met the requirements of 3.1 and 3.2 may be granted permission to apply the National Board "NB” mark to production pressure relief devices (of designs for which initial testing has been completed) provided the following tests are successfully completed. This permission shall expire on the fifth anniversary of the date it is initially granted. This permission may be extended for 6 year periods if the following tests are successfully repeated within the 6 month period before expiration. (1) Two sample production pressure relief devices of a size and capacity within the capacity of a National Board accepted laboratory shall be selected by a National Board representative. (2) Operational and capacity tests shall be conducted in the presence of a National Board representative at a National Board accepted laboratory. The manufacturer or Page 3 of 812 Effective Date: 2019-05-31

5 Table of Contents assembler shall be notified of the time of the test and may have representatives present to witness the test. (3) Should any device fail to relieve at or above its certified capacity or should it fail to meet performance requirements of the construction code, the test shall be repeated at the rate of two replacement devices, selected in accordance with 3.3.3(1) for each valve that failed. (4) Failure of any of the replacement devices to meet the capacity or the performance requirements of this section shall be cause for revocation within 60 days of the permission to use the "NB” mark on that particular type of pressure relief device. During this period, the manufacturer or assembler shall demonstrate the cause of future occurrence, and the such deficiency and the action taken to guard against requirements of 3.3.3(1) above shall apply. 3.3.4 MARKING When permission to apply the "NB” mark is received, the "NB” mark shall be applied to the nameplate using the National Board supplied stamp or a National Board approved facsimile along with the certified mark required by the construction code. The relieving capacity or flow resistance marked on the device shall be the value certified by the ment National Board as computed in accordance with the construction code. The arrange of the marking is subject to National Board acceptance. 3.3.5 TRANSFER OF DESIGN CERTIFICATIONS A manufacturer may request the results of the initial capacity testing (3.3.2) determined for one location be applied to a device type of identical design manufactured by the same organization at a different location. The following conditions must be met: (1) The manufacturer certifies to the National Board that the design is identical to the originally certified design and that the same production drawings are used at each location. (2) This system shall include provision to provide for the control of drawings and specifications between each location. (3) Device nameplate uniquely identifies the location of manufacture. (4) Each location must meet the production testing requirements of 3.3.3. TRANSFER OF PERMISSION (RELOCATION) 3.3.6 Permission granted to a manufacturer or an assembler in accordance with 3.3.3 may be transferred to a new location when the organization relocated its facility within the same metropolitan area provided that: (1) Ownership, personnel and equipment are essentially unchanged, (2) Two pressure relief devices per test medium are selected for testing and satisfy the performance requirements of the construction code, and, (3) The requirements of 3.1 and 3.2 have been met. Page 4 of 812 Effective Date: 2019-05-31

6 Table of Contents 3.4 LOCATION OF TESTING All testing required by this procedure must be conducted at a facility and supervised by shed individuals who have been accepted by the National Board in accordance with establi s shall be conducted in accordance with ASME PTC -25. procedures. Test Page 5 of 812 Effective Date: 2019-05-31

7 Table of Contents INATION OF CERTIFIED RELIEVING CAPACITIES DETERM 1.0 GENERAL and inimum To determine the relieving capacity which should appear on a valve set between the m maximum listed set pressures: – use the formula as applicable for the Code section and the 1.1 For the coefficient method coefficient and area given for the particular design of the valve. – calculate using the slope or flow factor given. method 1.2 For the slope or flow factor 1.3 Valves certified by the single valve method or three valve average have the certified capacity listed. 2.0 SAFETY VALVES FOR POWER BOILERS (Section I): 2.1 Coefficient Method Formula: For nozzle... ... W = (51.5 APK) W = (51.5 For flat seat DLPK) (low lift)... π ... W = (51.5 π DLPK) (.707) For 45º seat... For steam at pressures over 1500 psi and up to 3200 psi the value W of the certified relieving capacity shall be multiplied by: - 1000 0.1906P - 1061 0.2292P Where W = rated capacity, pounds dry saturated steam per hour developed life, square inches A = actual discharge area through the valve at D = seat diameter, inches K = certified coefficient L = lift, inches P = (stamped set pressure + 2 psi or 3%, whichever is greater) + 14.7, psia 2.2 Slope Method Formula: The values of slope given have units of lbs. per hour per psia. + 14 .7, psia) W = slope x (stamped set pressure + 2 psi or 3%, whichever is greater) 2.3 For superheated conditions the capacity shall be calculated by multiplying the capacity as determined in 2.1 or 2.2 by the appropriate K fa ctor found in Section I table PG -68.7. sh 2.4. For pressures over 1500 psig and up to 3200 psig the capacity shall be calculated by multiplying the capacity as determined in 2.1 or 2.2 by the following only if the correction factor is greater than 1.0: Page 6 of 812 Effective Date: 2019-05-31

8 Table of Contents 0.1906P - 1000 - 1061 0.2292P 2.5 For pressures over 3200 psig the capacity shall be calculated by multiplying the capacity as determined in 2.1 or 2.2 by the appropriate K factor found in Section I table PG -69.2.3. sc SAFETY VALVES FOR NUCLEAR VESSELS 3.0 (Section III): 3.1 Coefficient Method Formula: Steam: For nozzle... ... W = (51.5 APK) ... W = (51.5 π For flat seat (low lift)... DLPK) ... W = (51.5 DLPK) (.707) For 45º seat... π ertified relieving For steam at pressures over 1500 psi and up to 3200 psi the valve W of the c capacity shall be multiplied by: 0.1906P - 1000 0.2292P - 1061 Where W = rated capacity, pounds dry saturated steam per hour For A ir... ... ... W = 18.331APK @ 60º F and 14.7, psia ... W = CAPK √M/T For Gas... ... W = 4.814AK √w(P-P For liquid (water)... ) d Where W = rated capacity, lbs/hr (dry saturated steam), SCFM (air), lbs/hr (gas or vapor), GPM (water) A = actual discharge area through the valve at developed lift, square inches C = constant for gas or vapor based on the ratio of specific heats C /C v p D = seat diameter, inches K = certified coefficient L = lift, inches M = molecular weight P = (stamped set pressure + 3%) + 14.7, psia (for Class 1, 2, and 3 main) - OR - P = (stamped set pressure + 2.5 psi or 10%, whichever is greater) + 14.7, psia (For air, gas, or steam valves other than main stream) P = pressure at discharge from valve, psia d T = absolute temperature at inlet, ºR (degrees Fahrenheit + 460) 3 lbs/ft w = 62.3058 , specific weight of water @ 70ºF Page 7 of 812 Effective Date: 2019-05-31

9 Table of Contents 3.2 Slope Method Formula: of SCFM or lbs. per hour per psia. The values of slope given have the units W = slope x (set pressure + 3% + 14.7, psia), (for Class 1, 2. 3 main stream valves) ure + 3 psi or 10%, whichever is greater) + 14.7, psia], W = slope x [(set press (For air, gas, or steam over than main stream) For Liquid (water): x √ (P – P W = F ) where F = flow factor d The flow factor is a rating number for liquid service determined by a test. It is equal to the capacity in gallons per minute divided by the square root of the differential flowing pressure. It is equivalent to the “slope” for an air or steam valve. 3.3 Values less than 15 psig and Vacuum Relief Valves: Consult ASME Code Section III subsections NC, ND, or NE for applicable capacity equations. 4.0 SAFETY AND SAFETY RELIEF VALVES FOR HEATING BOILERS (Section IV): 4.1 Coefficient Method Formula: For nozzle... ... W = (51.5 APK) ... ... W = (51.5 π DLPK) For flat seat... ... ... W = (51.5 For 45º seat... π DLPK) (.707) Where W = rated capacity, pounds dry saturated steam per hour A = actual discharge area through the valve at developed lift, square inches D = seat diameter, inches K = certified coefficient L = lift, inches P = (15 + 33.3%) + 14.7, psia = 34.7, psia for 15 psi steam safety valves - OR - P = (stamped set pressure + 10%) + 14.7, psia for safety relief valves for hot water boilers 4.2 Slope Method Formula: The values of slope given have the units of BTUs per hour per psia or lbs. per hour per psia. W = slope x (set pressure + 10% + 14.7, psia) Page 8 of 812 Effective Date: 2019-05-31

10 Table of Contents 5.0 SAFETY VALVES FOR PRESSURE VESSELS (Section VIII, Divisions 1 & 2): fi 5.1 Coef cient Method Formula: For Steam: ... ... W = (51.5 APK) For nozzle... DLPK) For flat seat... ... ... W = (51.5 π π DLPK) (.707) W = (51.5 For 45º seat... ... For steam at pressures over 1500 psi and up to 3200 psi the value W of the certified relieving capacity shall be multiplied by: - 1000 0.1906P 0.2292P - 1061 W = 18.331APK @ 60ºF and 14.7, psia For air: W = CKAP √M/T For Gas or Vapor: W = 4.814AK √w(P – P For Liquid (water): ) d Where W = rated capacity, lbs/hr (dry saturated steam), SCFM (air), lbs/hr (gas or vapor), GPM (water) A = nozzle throat area, square inches C = constant for gas or vapor based on ratio of specific heats C /C v p D = seat diameter, inches coefficient K = certified L = lift, inches M = molecular weight P = (stamped set pressure + 3 psia or 10%, whichever is greater) + 14.7, psia OR – - P = (stamped set pressure + 20%) + 14.7, psia for test per UG -131(c)(2) Pd = pressure at discharge from valve, psia T = absolute temperature at inlet, ºR (degrees Fahrenheit + 460) 3 w = 62.3058 lbs/ft , specific weight @ 70ºF 5.2 Slop e Method Formula: slope given have of SCFM or lbs. per hour per psia. The values of units W = slope x [(set pressure + 10%) + 14.7, psia] - OR – W = slope x [(stamped set pressure + 20%) + 14.7, psia for test per UG- 131(c)(2) ] Page 9 of 812 Effective Date: 2019-05-31

11 Table of Contents For Liquid (water) : – P W = F x √(P ) w here F = flow factor d The flow factor is a rating number for liquid service determined by a test. It is equal to the capacity in gallons per minute divided by the square root of the differential flowing pressure. It is equivalent to the “slope” for an air or steam valv e. 5.3 Flow Resistance (Non -reclosing devices) certified by the Flow Resistance Device designs method are not marked with a relieving (K capacity value. The certified flow resistance , K , K ) appears on the nameplate and is to be rg rgl rl used when determining total flow resistance of the pressure relief system and the flowing The flow resistance capacity it will relieve through the use of accepted engineering practices. icate that the device has been certified for gas (k subscripts “g,” “l,” or “gl” ind ), or ), liquid (K rg rl both gases and liquids (K across a certified non- ). Unless otherwise noted, the pressure drop rgl reclosing device shall be calculated using dimensions for standard pipe (STD). -reclosing For pressure relief systems discharging directly to atmosphere which includes a non device installed within 8 pipe diameters of the vessel nozzle and having a discharge pipe no longer than 5 pipe diameters, system capacity determined from the equations found in can be (MNFA) marked on the nameplate and an assumed 5.1 above using the minimum net flow area coefficient of discharge equal to 0.62. Page 10 of 812 Effective Date: 2019-05-31

12 Table of Contents LISTING OF ASSEMBLER AND MANUFACTURER CERTIFICATIONS This section lists National Board pressure relief device certifications issued to device manufacturers and assemblers who organization is presented by company hold National Board Certificates of Authorizations to use the "NB” symbol. Each name, National Board three letter designation and location. Listed is the device type, certification category, name, type tion date and page number classification, Code Section, National Board capacity certification number, certification expira where detailed technical information for the subject design type may be found. The following is an example and explanation of the information found in the Index: 1 2 3 - Ridgway OH , Location (IVC) IDEAL VALVE COMPANY 5 4 7 8 10 6 9 Code Section s Type Classification NB Capacity Device Type Page Expiration Certification Category Date Certification Number M 102K 32 7/12/06 Safety Relief Valve 50005 VIII 1 Full Name of the Manufacturer or Assembler. National Board Th ree Letter Designation. This is part of the National Board certification number and is derived 2 from the manufacturer or assemblers company name. 3 Location of the organization. The country or province for companies located outside the United States is also listed. The certification category of either "M” for Manufacturer or "A” for Assembler. 4 The design type name is the commercial designation specified by the manufacturer. 5 The National Board certification number has been instituted to provide a better 6 means of identifying manufacturers and their design type designations. See description below on its use. Type Classification indicates the type of pressure relief device (I.e. Relief valve, rupture disk). 7 8 The Code Section indicates the Construction Co de requirements which were met to obtain National Board certification. The expiration date is the date when the certification expires for the listed type. National Board certification is valid 9 for a period of five years. Please note that when the index i ndicates an expiration date which is close to the present date, it will be necessary to consult with the National Board Pressure Relief Department for more information. 10 The page listed where detailed information on the design type can be found. tional Board certification number is used in all National Board correspondence with manufacturers and The Na assemblers. The following is an example of how the number is presented in correspondence: 1 3 2 M (NB Cap Cert No IVC ) 50005 - This is a three letter design ation which is derived from the manufacturer or assemblers name. In this example, the 1 designation is the company’s initials. 2 This portion of the number will always be either an "M” or an "A”, indicating whether the company is a manufacturer or an assembl er. 3 Each individual valve type has been given its own number (it is this number that is indicated on the index). We - sum” concept for this number. For example, we have issued the number for the valve type have devised a "check u add the first four digits of this number, the sum is 5. The last number of the listed above as 50005. If yo designation is then 5. Should the sum of the first four numbers be greater than 10, we always use the second number. Page 11 of 812 Effective Date: 2019-05-31

13 Table of Contents Ademco 1 GmbH (HAG) location: Mosbach, GERMANY Acceptable Abbrev.: Ademco 1 GmbH (cont'd) Devices designed by: Ademco 1 GmbH (HAG) Cert Cat Expiration Date Code Section Device Type Type Classification NB Cert # M 90009 S245 Safety Relief Valve VIII Div. 1 Mar 21, 2023 Admiral Valve Repair and Supply, Inc. (ASR) location: North Chicago, IL, UNITED STATES Acceptable Abbrev.: Admiral Valve Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) NB Cert # Cert Cat Expiration Date Code Section Device Type Type Classification 300,600 36076 A I & VIII Div. 1 May 6, 2021 Safety Valve A 920, 921, 927, Agco A (High Temp. water) 36098 I & VIII Div. 1 Feb 24, 2021 Safety Valve 36100 A 910 to 919 Safety Relief Valve VIII Div. 1 Jun 10, 2021 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) 36111 A Relief Valve Mar 22, 2021 VIII Div. 1 36267 A Kunkle 264, 265, 266 & 267 VIII Div. 1 Safety Relief Valve Mar 16, 2021 A Kunkle 337 36278 VIII Div. 1 Mar 22, 2021 Safety Relief Valve A 36324 Kunkle 6000, 6252 Series Safety Valve I & VIII Div. 1 Feb 24, 2021 Advance Valve, Incorporated (ADV) location: Fenton, MO, UNITED STATES Acceptable Abbrev.: ADV Devices designed by: Aquatrol, Incorporated (AQT) Device Type Expiration Date Cert Cat Type Classification Code Section NB Cert # 02080 560, 570 A Jan 24, 2020 Safety Valve I & VIII Div. 1 02091 A Series 740 Safety Relief Valve Jan 24, 2020 VIII Div. 1 Series 740 (Liquid) 02103 A VIII Div. 1 Safety Relief Valve Jan 24, 2020 Devices designed by: ARI-Armaturen Albert Richter GmbH & Co. KG (ARI) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 901/902/911/912 A 08008 VIII Div. 1 Safety Relief Valve May 10, 2024 08019 A 901/902/911/912 (Liquids) Relief Valve VIII Div. 1 Apr 2, 2024 08031 901/902/911/912 {15-30} A Safety Relief Valve VIII Div. 1 May 10, 2024 Devices designed by: Conbraco Industries, Incorporated (CNB) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 11361 A 119 Series I & VIII Div. 1 May 1, 2024 Safety Valve Page 12 of 812 Effective Date: 2019-05-31

14 Table of Contents Advance Valve, Incorporated (ADV) location: (continued) Fenton, MO, UNITED STATES Acceptable Abbrev.: ADV Devices designed by: LESER GmbH & Company KG (LES) Expiration Date Cert Cat Type Classification Device Type Code Section NB Cert # 488 37022 A Safety Relief Valve VIII Div. 1 Feb 20, 2021 A 37033 488 (Liquids) VIII Div. 1 Feb 20, 2021 Relief Valve 441/442/444 A 37044 VIII Div. 1 Safety Relief Valve May 26, 2020 A 441/442/444 liquids 37055 Relief Valve Feb 2, 2021 VIII Div. 1 459/462 liquids 37101 A VIII Div. 1 Dec 8, 2020 Relief Valve 459/462 37112 A VIII Div. 1 Safety Relief Valve Dec 8, 2020 A 37145 483, 484, 485 (1") Safety Relief Valve VIII Div. 1 Jul 6, 2024 483, 484, 485 (1") Liquids 37156 A VIII Div. 1 Jun 6, 2024 Relief Valve 37167 A 483, 484, 485 (1.5") Jun 6, 2024 Safety Relief Valve VIII Div. 1 483, 484, 485 (1.5") Liquids A 37178 Relief Valve VIII Div. 1 Jun 15, 2024 37190 438 Sub Types 481, 439 A VIII Div. 1 Sep 17, 2024 Safety Relief Valve 438 Sub Types 481, 439, Liquids A 37202 Safety Relief Valve VIII Div. 1 Oct 11, 2024 437 A 37213 VIII Div. 1 Jun 6, 2024 Safety Relief Valve 37224 526 A VIII Div. 1 Jun 6, 2024 Safety Relief Valve 526 (Liquids) 37235 A VIII Div. 1 Relief Valve Jun 6, 2024 Devices designed by: Spence Engineering Company, Incorporated (SEC) NB Cert # Cert Cat Type Classification Code Section Device Type Expiration Date A Fig 31, 41, 41A 65045 I & VIII Div. 1 May 8, 2024 Safety Valve Aeon PEC, Inc. (HGO) location: Shreveport, LA, UNITED STATES Acceptable Abbrev.: Aeon PEC Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) NB Cert # Code Section Type Classification Expiration Date Device Type Cert Cat 01089 81, 81P, 83, 86 A VIII Div. 1 Safety Relief Valve Mar 12, 2020 81P (Liquids) A 01102 VIII Div. 1 Relief Valve Mar 11, 2020 01292 A 243/249/443/449/546/843/849/943/5046/5049/8043/8049 Mar 12, 2020 VIII Div. 1 Pilot Operated Pressure Relief Valve 253/259/453/459/853/859/953/959/5059/8053/8059 01304 A Mar 12, 2020 Pilot Operated Pressure Relief Valve VIII Div. 1 A 01315 263/269/463/469/566/863/869/963/969/5066/5069 Mar 11, 2020 VIII Div. 1 Pilot Operated Pressure Relief Valve 453/459/853/859/953/959/5059 (Liquids) 01326 A Pilot Operated Pressure Relief Valve VIII Div. 1 Mar 12, 2020 443/449/546/843/849/943/949/5046/5049(Liquids) 01337 A VIII Div. 1 Mar 11, 2020 Pilot Operated Pressure Relief Valve 01348 463/469/566/863/869/963/969/5066/5069 (Liquids) A Pilot Operated Pressure Relief Valve Mar 11, 2020 VIII Div. 1 15095 A JLT (Liquids) Jun 6, 2020 VIII Div. 1 Safety Relief Valve 15208 A JOS-E/JBS-E/JOS-H-E 8400 AC/AB Safety Relief Valve VIII Div. 1 Mar 12, 2020 900 Series, 7700, SNC 15411 A Safety Relief Valve Mar 12, 2020 VIII Div. 1 15499 900 Series (Liquid), 7700, SNC A Mar 11, 2020 Relief Valve VIII Div. 1 JLT-JOS, JLT-JBS, 8500, ACL/ABL 15512 A Safety Relief Valve VIII Div. 1 Jun 6, 2020 Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Type Classification Cert Cat Code Section NB Cert # Expiration Date Device Type 36470 A 82 Series D Orifice Safety Valve VIII Div. 1 Jun 6, 2020 82 Series E Orifice 36481 A Jun 6, 2020 VIII Div. 1 Safety Valve Devices designed by: LESER GmbH & Company KG (LES) NB Cert # Cert Cat Expiration Date Device Type Code Section Type Classification 37112 459/462 A Safety Relief Valve May 23, 2024 VIII Div. 1 37224 A 526 VIII Div. 1 Safety Relief Valve May 23, 2024 A 526 (Liquids) 37235 VIII Div. 1 May 23, 2024 Relief Valve 37268 820 (liquid) (821) A Pilot Operated Pressure Relief Valve May 23, 2024 VIII Div. 1 810/820 (811/821) 37280 A Pilot Operated Pressure Relief Valve May 23, 2024 VIII Div. 1 Page 13 of 812 Effective Date: 2019-05-31

15 Table of Contents Albert Handtmann Armaturenfabrik GmbH & Co. KG (AHA) location: Biberach/Riss, GERMANY Devices designed by: Albert Handtmann Armaturenfabrik GmbH & Co. KG (AHA) Type Classification Expiration Date NB Cert # Cert Cat Code Section Device Type 33551 and 33651 00639 M Jan 6, 2022 VIII Div. 1 Safety Relief Valve 33551 and 33651 (Liquid) 00640 M Safety Relief Valve Jan 6, 2022 VIII Div. 1 Allied Valve, Inc. - Riverdale, IA (VRS) location: Riverdale, IA, UNITED STATES Acceptable Abbrev.: Allied Valve, Inc. Devices designed by: Dresser, LLC (DRJ) Cert Cat Type Classification Expiration Date Device Type Code Section NB Cert # 18122 1811, 1511 A Jun 23, 2021 I & VIII Div. 1 Safety Valve 1900, 1900-30, 1900-35 A 18201 VIII Div. 1 Jun 23, 2021 Safety Relief Valve 19000 Series 18706 A Safety Relief Valve Jun 23, 2021 VIII Div. 1 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) Jun 23, 2021 VIII Div. 1 Relief Valve Allied Valve, Inc. (ALC) location: Chicago, IL, UNITED STATES Acceptable Abbrev.: Allied Valve, Inc. Devices designed by: Dresser, LLC (DRJ) Cert Cat NB Cert # Expiration Date Type Classification Code Section Device Type 1541, 1543, 1541-3, 1543-3 18032 A I & VIII Div. 1 Feb 17, 2021 Safety Valve A 1811, 1511 18122 I & VIII Div. 1 Feb 17, 2021 Safety Valve 18144 A 1900D-2, 1900-30D-2 Safety Relief Valve VIII Div. 1 Feb 17, 2021 A 1900E-2, 1900-30E-2 18166 VIII Div. 1 Feb 17, 2021 Safety Relief Valve A 18201 1900, 1900-30, 1900-35 Safety Relief Valve Feb 17, 2021 VIII Div. 1 18706 A 19000 Series Feb 18, 2024 VIII Div. 1 Safety Relief Valve A 18717 19000 Series, Liquid Feb 15, 2024 Relief Valve VIII Div. 1 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A VIII Div. 1 Feb 17, 2021 Relief Valve 18762 A 1900E-2, 1900-30E-2 LA & DALA (Liquids) Relief Valve Feb 17, 2021 VIII Div. 1 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) A Relief Valve VIII Div. 1 Apr 17, 2021 19077 19110M & 19110H (Liquids) A Apr 17, 2021 Relief Valve VIII Div. 1 Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) NB Cert # Cert Cat Code Section Expiration Date Device Type Type Classification A 36076 300,600 Safety Valve I & VIII Div. 1 Feb 15, 2024 36100 A 910 to 919 VIII Div. 1 Feb 15, 2024 Safety Relief Valve 36111 A 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) Relief Valve VIII Div. 1 Feb 15, 2024 Kunkle 264, 265, 266 & 267 A 36267 Safety Relief Valve Feb 18, 2024 VIII Div. 1 Kunkle 337 36278 A VIII Div. 1 Feb 18, 2024 Safety Relief Valve Kunkle 548-A (.295 Orifice) 36290 A Safety Relief Valve VIII Div. 1 Aug 16, 2020 36302 Kunkle 541-C/542-C/548-C (.422 Orifice) A Feb 15, 2024 Safety Relief Valve VIII Div. 1 Kunkle 6000, 6252 Series 36324 A Safety Valve Jun 26, 2021 I & VIII Div. 1 36335 A Kunkle 30 VIII Div. 1 Feb 15, 2024 Safety Relief Valve Page 14 of 812 Effective Date: 2019-05-31

16 Table of Contents Allied Valve, Inc. (AVB) location: Bismarck, ND, UNITED STATES Devices designed by: Dresser, LLC (DRJ) Type Classification Code Section NB Cert # Expiration Date Cert Cat Device Type 1811, 1511 18122 A Jun 24, 2020 I & VIII Div. 1 Safety Valve A 18201 1900, 1900-30, 1900-35 Jun 23, 2020 VIII Div. 1 Safety Relief Valve 19000 Series 18706 A Safety Relief Valve VIII Div. 1 Jun 23, 2020 19000 Series, Liquid 18717 A VIII Div. 1 Relief Valve Jun 23, 2020 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) VIII Div. 1 Jun 23, 2020 Relief Valve Allied Valve, Inc. (TPW) location: Appleton, WI, UNITED STATES Devices designed by: Dresser, LLC (DRJ) Cert Cat Code Section Device Type Type Classification Expiration Date NB Cert # A 18100 1700 & 2700 Sep 1, 2021 Safety Valve I & VIII Div. 1 18111 1700 & 2700 (Restricted Lift version of Cert. # 18100) A Safety Valve I & VIII Div. 1 Sep 1, 2021 18122 1811, 1511 A Sep 1, 2021 Safety Valve I & VIII Div. 1 1900, 1900-30, 1900-35 18201 A Safety Relief Valve Nov 1, 2024 VIII Div. 1 1982 A 18379 VIII Div. 1 Safety Relief Valve Dec 15, 2022 18380 A 1982 LS, 820000LS VIII Div. 1 Sep 20, 2024 Relief Valve 18447 A 3900 (39PV, 39MV pilots) Pilot Operated Pressure Relief Valve VIII Div. 1 Sep 1, 2021 3900 (39PV, 39MV pilots, liquid) 18458 A Pilot Operated Pressure Relief Valve VIII Div. 1 Nov 1, 2024 18706 A 19000 Series Safety Relief Valve VIII Div. 1 Sep 20, 2024 19000 Series, Liquid A 18717 Relief Valve Sep 20, 2024 VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Nov 11, 2024 VIII Div. 1 Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Expiration Date Device Type Code Section Cert Cat Type Classification NB Cert # A 36100 910 to 919 Safety Relief Valve Sep 1, 2021 VIII Div. 1 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) 36111 A VIII Div. 1 Sep 1, 2021 Relief Valve Kunkle 6000, 6252 Series 36324 A Safety Valve Dec 15, 2021 I & VIII Div. 1 Page 15 of 812 Effective Date: 2019-05-31

17 Table of Contents Allied Valve, Inc. (VSS) location: Cannon Falls, MN, UNITED STATES Acceptable Abbrev.: Allied Valve, Inc. Devices designed by: Dresser, LLC (DRJ) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 1541, 1543, 1541-3, 1543-3 18032 A Mar 28, 2024 I & VIII Div. 1 Safety Valve 1700 & 2700 A 18100 Safety Valve Jun 29, 2020 I & VIII Div. 1 1700 & 2700 (Restricted Lift version of Cert. # 18100) 18111 A I & VIII Div. 1 Safety Valve Jun 24, 2020 A 18122 1811, 1511 Safety Valve Mar 28, 2024 I & VIII Div. 1 1900D-2, 1900-30D-2 18144 A Safety Relief Valve VIII Div. 1 Mar 28, 2024 1900E-2, 1900-30E-2 18166 A VIII Div. 1 Safety Relief Valve Mar 28, 2024 A 18201 1900, 1900-30, 1900-35 Safety Relief Valve VIII Div. 1 Mar 28, 2024 3900 (39PV, 39MV pilots) 18447 A VIII Div. 1 Sep 21, 2020 Pilot Operated Pressure Relief Valve 18706 A 19000 Series Jun 24, 2020 Safety Relief Valve VIII Div. 1 19000 Series, Liquid A 18717 Mar 28, 2024 Relief Valve VIII Div. 1 18751 A 1900D-2, 1900-30D-2 LA & DALA (Liquids) Jun 22, 2020 VIII Div. 1 Relief Valve 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 A Jul 19, 2020 Relief Valve VIII Div. 1 A 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) Mar 28, 2024 VIII Div. 1 Relief Valve 2900 (39PV & 39MV pilots) 18863 A Pilot Operated Pressure Relief Valve VIII Div. 1 Jun 24, 2020 1541, 1543, 1541-3, 1543-3 18032 A I & VIII Div. 1 Mar 28, 2024 Safety Valve 1700 & 2700 18100 A Safety Valve Jun 29, 2020 I & VIII Div. 1 18111 A 1700 & 2700 (Restricted Lift version of Cert. # 18100) Jun 24, 2020 I & VIII Div. 1 Safety Valve 18122 A 1811, 1511 Safety Valve I & VIII Div. 1 Mar 28, 2024 1900D-2, 1900-30D-2 18144 A Safety Relief Valve Mar 28, 2024 VIII Div. 1 18166 1900E-2, 1900-30E-2 A Mar 28, 2024 Safety Relief Valve VIII Div. 1 1900, 1900-30, 1900-35 18201 A Safety Relief Valve Mar 28, 2024 VIII Div. 1 18447 A 3900 (39PV, 39MV pilots) VIII Div. 1 Pilot Operated Pressure Relief Valve Sep 21, 2020 18706 A 19000 Series Jun 24, 2020 VIII Div. 1 Safety Relief Valve A 18717 19000 Series, Liquid Mar 28, 2024 Relief Valve VIII Div. 1 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A Jun 22, 2020 VIII Div. 1 Relief Valve A 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) Jul 19, 2020 Relief Valve VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Mar 28, 2024 VIII Div. 1 18863 A 2900 (39PV & 39MV pilots) VIII Div. 1 Pilot Operated Pressure Relief Valve Jun 24, 2020 Anderson Greenwood Crosby Sanmar Limited (TYC) location: Pudukottai District, Tamilnadu, INDIA Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type Cert Cat Expiration Date Type Classification Code Section NB Cert # 243/249/443/449/546/843/849/943/5046/5049/8043/8049 M 01292 Dec 12, 2023 VIII Div. 1 Pilot Operated Pressure Relief Valve 253/259/453/459/853/859/953/959/5059/8053/8059 01304 M VIII Div. 1 Dec 12, 2023 Pilot Operated Pressure Relief Valve 01315 263/269/463/469/566/863/869/963/969/5066/5069 M Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 12, 2023 01326 M 453/459/853/859/953/959/5059 (Liquids) Dec 11, 2023 VIII Div. 1 Pilot Operated Pressure Relief Valve 01337 M 443/449/546/843/849/943/949/5046/5049(Liquids) Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 13, 2023 01348 463/469/566/863/869/963/969/5066/5069 (Liquids) M Pilot Operated Pressure Relief Valve Jun 26, 2019 VIII Div. 1 15006 M H Series (HCI, HSJ, HCA, HA, HB, HC, HCB, HCP, HJO, HN, Safety Valve I May 31, 2025 JLT (Liquids) M 15095 Safety Relief Valve Nov 15, 2023 VIII Div. 1 JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 M Safety Relief Valve VIII Div. 1 Feb 13, 2023 15411 M 900 Series, 7700, SNC Safety Relief Valve VIII Div. 1 Feb 13, 2023 800 M 15466 Safety Relief Valve Jan 8, 2021 VIII Div. 1 900 Series (Liquid), 7700, SNC 15499 M Relief Valve Mar 9, 2023 VIII Div. 1 H Series (Restricted Lift version of Cert # 15006) 15567 M Safety Valve May 31, 2025 I Page 16 of 812 Effective Date: 2019-05-31

18 Table of Contents Apparecchi Di Sicurezza e Tenuta S.p.A. (ADS) location: Cornaredo (Milano), ITALY Acceptable Abbrev.: A.S.T. S.p.A. Devices designed by: Apparecchi Di Sicurezza e Tenuta S.p.A. (ADS) Device Type Expiration Date NB Cert # Code Section Type Classification Cert Cat SVP-7200 Restrict Lift (Liquid) M 07108 Pilot Operated Pressure Relief Valve Dec 17, 2019 VIII Div. 1 07119 M SVP-7200 Restrict Lift Mar 19, 2020 VIII Div. 1 Pilot Operated Pressure Relief Valve SVP-7200 (Full Lift) (Liquid) M 07120 Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 17, 2019 M SVP-7200 (Full Lift) 07131 Mar 19, 2020 Pilot Operated Pressure Relief Valve VIII Div. 1 SMG-7000 07175 M Safety Relief Valve VIII Div. 1 Sep 25, 2021 07186 SML-7000 (Liquid) M Sep 25, 2021 Relief Valve VIII Div. 1 07197 M SMG-7000 (Restricted Lift) Jan 28, 2022 VIII Div. 1 Safety Relief Valve M 07209 SML-7000 (Liquid) (Restricted Lift) Sep 25, 2021 Relief Valve VIII Div. 1 SML-7000 (Steam & Air/Gas) 07210 M Relief Valve VIII Div. 1 Nov 30, 2022 07221 SML-7000 (Steam & Air/Gas) (Restricted Lift) M Relief Valve Jul 19, 2023 VIII Div. 1 07232 M SHL-7000 / SUL-7000 Safety Relief Valve VIII Div. 1 Jul 19, 2023 07243 SHL-7000 / SUL-7000 (Liquid) M Relief Valve VIII Div. 1 Jul 19, 2023 Applied Control Equipment, LLLP (APP) location: Commerce City, CO, Acceptable Abbrev.: Applied Control; ACE Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat 01089 A 81, 81P, 83, 86 VIII Div. 1 Feb 5, 2025 Safety Relief Valve A 01292 243/249/443/449/546/843/849/943/5046/5049/8043/8049 Feb 5, 2025 Pilot Operated Pressure Relief Valve VIII Div. 1 253/259/453/459/853/859/953/959/5059/8053/8059 01304 A Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 5, 2025 263/269/463/469/566/863/869/963/969/5066/5069 01315 A Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 5, 2025 01337 A 443/449/546/843/849/943/949/5046/5049(Liquids) Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 6, 2025 01348 463/469/566/863/869/963/969/5066/5069 (Liquids) A Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 5, 2025 JLT (Liquids) 15095 A VIII Div. 1 Feb 6, 2025 Safety Relief Valve 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB A Safety Relief Valve VIII Div. 1 Feb 5, 2025 15411 A 900 Series, 7700, SNC Safety Relief Valve VIII Div. 1 Feb 5, 2025 15512 JLT-JOS, JLT-JBS, 8500, ACL/ABL A Feb 5, 2025 VIII Div. 1 Safety Relief Valve Applied Valve Technology, Inc. (AVT) location: Chattanooga, TN, UNITED STATES Acceptable Abbrev.: A.V.T. Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date A 910 to 919 36100 VIII Div. 1 Mar 1, 2024 Safety Relief Valve A 36111 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) Relief Valve Jun 20, 2024 VIII Div. 1 Kunkle 6000, 6252 Series 36324 A Safety Valve Jun 20, 2024 I & VIII Div. 1 Page 17 of 812 Effective Date: 2019-05-31

19 Table of Contents Aquatrol, Incorporated (AQT) location: Elburn, IL, UNITED STATES Devices designed by: Aquatrol, Incorporated (AQT) Type Classification Code Section NB Cert # Expiration Date Cert Cat Device Type 88A, 89A 02002 M Nov 26, 2024 VIII Div. 1 Safety Relief Valve 88B, 89B 02013 M Safety Relief Valve Nov 26, 2024 VIII Div. 1 88C, 89C 02024 M Safety Relief Valve Nov 26, 2024 VIII Div. 1 88D, 89D 02035 M Nov 26, 2024 Safety Relief Valve VIII Div. 1 88E, 89E M 02046 VIII Div. 1 Nov 26, 2024 Safety Relief Valve M 02057 88F, 89F Nov 26, 2024 Safety Relief Valve VIII Div. 1 120, 121, 125, 126 02068 M Safety Relief Valve VIII Div. 1 Nov 26, 2024 02079 130, 132, 133, 135 M Safety Relief Valve VIII Div. 1 Nov 26, 2024 02080 M 560, 570 Jan 19, 2022 I & VIII Div. 1 Safety Valve M 02091 Series 740 Feb 11, 2025 Safety Relief Valve VIII Div. 1 Series 740 (Liquid) 02103 M VIII Div. 1 Feb 11, 2025 Safety Relief Valve 02114 M 140-A Safety Relief Valve Feb 22, 2025 VIII Div. 1 02125 140-B M Safety Relief Valve Feb 22, 2025 VIII Div. 1 ARI - Armaturen USA, LP (TAR) location: Webster, TX, UNITED STATES Devices designed by: ARI - Armaturen USA, LP (TAR) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # 73000 Reyco R, RB & RO (Fig. 971, 973, 974) M Safety Relief Valve Jan 19, 2021 VIII Div. 1 Reyco R, RB, RO, RBO (Fig. 971, 973, 974) (liquid) M 73011 VIII Div. 1 Safety Relief Valve Nov 25, 2020 73044 RL-14 & RLO-14 M Safety Relief Valve VIII Div. 1 Nov 2, 2022 M 73055 RL-14 & RLO-14 (Liquids) Safety Relief Valve VIII Div. 1 May 18, 2023 RL40, RLO40, RL41, RLO41 73145 M Safety Relief Valve VIII Div. 1 Jul 26, 2022 73156 M RL40, RLO40, RL41, RLO41 (Liquids) Jul 26, 2022 VIII Div. 1 Safety Relief Valve 73167 RL40, RL040 (0.847 in. orif.) M Safety Relief Valve Feb 24, 2023 VIII Div. 1 73178 M RL40, RL040 (0.847 in. orif.)(liquid) VIII Div. 1 Feb 18, 2023 Safety Relief Valve RL14 & RLO14 (0.394 in.) M 73202 Safety Relief Valve Nov 21, 2020 VIII Div. 1 RL14 & RLO14 (0.394 in.) (Liquid) 73213 M Relief Valve Nov 21, 2020 VIII Div. 1 RL40, RLO40, RL41, RLO41 (0.547 in orifice), Design Rev. A M 73224 VIII Div. 1 Safety Relief Valve Sep 29, 2020 73235 M RL40, RLO40, RL41, RLO41 (0.547 in. orifice) (Liquid), Design Relief Valve VIII Div. 1 Apr 10, 2023 Devices designed by: ARI-Armaturen Albert Richter GmbH & Co. KG (ARI) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # 08008 901/902/911/912 M VIII Div. 1 Safety Relief Valve Nov 21, 2023 M 901/902/911/912 (Liquids) 08019 VIII Div. 1 Mar 29, 2024 Relief Valve M 08020 901/902/911/912 (1" liquid) Relief Valve Nov 21, 2023 VIII Div. 1 901/902/911/912 {15-30} 08031 M Safety Relief Valve Nov 21, 2023 VIII Div. 1 Page 18 of 812 Effective Date: 2019-05-31

20 Table of Contents ARI-Armaturen Albert Richter GmbH & Co. KG (ARI) location: D-33758 Schloss Holte-Stukenbrock, GERMANY Acceptable Abbrev.: ARI Devices designed by: ARI - Armaturen USA, LP (TAR) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification Reyco R, RB & RO (Fig. 971, 973, 974) 73000 M Jun 17, 2024 VIII Div. 1 Safety Relief Valve M 73011 Reyco R, RB, RO, RBO (Fig. 971, 973, 974) (liquid) Safety Relief Valve Nov 15, 2023 VIII Div. 1 RL-14 & RLO-14 73044 M Jul 26, 2023 VIII Div. 1 Safety Relief Valve RL-14 & RLO-14 (Liquids) 73055 M Safety Relief Valve VIII Div. 1 Jul 26, 2023 RL40, RLO40, RL41, RLO41 73145 M VIII Div. 1 Jul 26, 2023 Safety Relief Valve RL40, RLO40, RL41, RLO41 (Liquids) 73156 M Safety Relief Valve VIII Div. 1 Jul 26, 2023 M 73167 RL40, RL040 (0.847 in. orif.) Apr 19, 2024 Safety Relief Valve VIII Div. 1 RL40, RL040 (0.847 in. orif.)(liquid) M 73178 Safety Relief Valve VIII Div. 1 Jul 26, 2023 73202 M RL14 & RLO14 (0.394 in.) Jul 26, 2023 VIII Div. 1 Safety Relief Valve M 73213 RL14 & RLO14 (0.394 in.) (Liquid) Jul 26, 2023 Relief Valve VIII Div. 1 RL40, RLO40, RL41, RLO41 (0.547 in orifice), Design Rev. A 73224 M Safety Relief Valve VIII Div. 1 Apr 19, 2024 73235 RL40, RLO40, RL41, RLO41 (0.547 in. orifice) (Liquid), Design M Relief Valve Jul 26, 2023 VIII Div. 1 Devices designed by: ARI-Armaturen Albert Richter GmbH & Co. KG (ARI) NB Cert # Cert Cat Type Classification Expiration Date Device Type Code Section 08008 M 901/902/911/912 Safety Relief Valve VIII Div. 1 Dec 12, 2023 08019 M 901/902/911/912 (Liquids) VIII Div. 1 Relief Valve Dec 12, 2023 901/902/911/912 (1" liquid) 08020 M Relief Valve VIII Div. 1 Nov 12, 2022 08031 M 901/902/911/912 {15-30} VIII Div. 1 Safety Relief Valve Nov 29, 2023 Atlantic Valve Services LLC (AGN) location: Swedesboro, NJ, UNITED STATES Acceptable Abbrev.: AVS Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Expiration Date Device Type Code Section Cert Cat NB Cert # Type Classification 01045 A JOS-E-RL/JBS-E-RL (Restricted Lift version of cert 15208) Safety Relief Valve VIII Div. 1 Mar 22, 2025 01067 63B (.437", #7 orifice) A Oct 28, 2019 VIII Div. 1 Safety Relief Valve A 81, 81P, 83, 86 01089 VIII Div. 1 May 8, 2025 Safety Relief Valve 01102 A 81P (Liquids) Relief Valve VIII Div. 1 Mar 22, 2025 A 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 VIII Div. 1 Mar 22, 2025 Pilot Operated Pressure Relief Valve 01304 253/259/453/459/853/859/953/959/5059/8053/8059 A Pilot Operated Pressure Relief Valve VIII Div. 1 Mar 22, 2025 01315 A 263/269/463/469/566/863/869/963/969/5066/5069 Pilot Operated Pressure Relief Valve VIII Div. 1 Mar 22, 2025 15095 JLT (Liquids) A Safety Relief Valve VIII Div. 1 Mar 29, 2021 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB A Safety Relief Valve Mar 22, 2025 VIII Div. 1 900 Series, 7700, SNC 15411 A VIII Div. 1 Safety Relief Valve Mar 22, 2025 A 900 Series (Liquid), 7700, SNC 15499 VIII Div. 1 Mar 22, 2025 Relief Valve Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Device Type Cert Cat Expiration Date Type Classification Code Section NB Cert # 36278 Kunkle 337 A Safety Relief Valve Oct 28, 2019 VIII Div. 1 Page 19 of 812 Effective Date: 2019-05-31

21 Table of Contents AVP Valve, Inc. (AVP) location: Lakeland, FL, UNITED STATES Devices designed by: Dresser, LLC (DRJ) Cert Cat Type Classification NB Cert # Expiration Date Code Section Device Type 1541, 1543, 1541-3, 1543-3 18032 A Jun 27, 2024 I & VIII Div. 1 Safety Valve 1700 & 2700 18100 A Safety Valve Jul 30, 2024 I 1700 & 2700 (Restricted Lift version of Cert. # 18100) 18111 A Safety Valve Jul 30, 2024 I & VIII Div. 1 1811, 1511 18122 A Jul 30, 2024 Safety Valve I & VIII Div. 1 1900, 1900-30, 1900-35 A 18201 VIII Div. 1 Jul 30, 2024 Safety Relief Valve A 18447 3900 (39PV, 39MV pilots) Jun 15, 2021 Pilot Operated Pressure Relief Valve VIII Div. 1 3900 (39PV, 39MV pilots, liquid) 18458 A Pilot Operated Pressure Relief Valve VIII Div. 1 Jun 16, 2021 18706 19000 Series A Safety Relief Valve Jul 30, 2024 VIII Div. 1 18717 A 19000 Series, Liquid VIII Div. 1 Jun 14, 2021 Relief Valve 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) Jul 31, 2024 VIII Div. 1 Relief Valve AWC, Inc. (AWI) location: Baton Rouge, LA, Seal Identification: BTR Devices designed by: Farris Engineering (TFO) Cert Cat NB Cert # Expiration Date Type Classification Code Section Device Type 3800 57024 A Mar 18, 2025 VIII Div. 1 Pilot Operated Pressure Relief Valve 57035 A 3800FP VIII Div. 1 Pilot Operated Pressure Relief Valve Mar 18, 2025 57057 A 2600 & 2600S Safety Relief Valve VIII Div. 1 Mar 18, 2025 2600L (Liquids) 57068 A Relief Valve Mar 18, 2025 VIII Div. 1 3800L, PCL, PCM pilots 57215 A VIII Div. 1 Mar 18, 2025 Pilot Operated Pressure Relief Valve 2700, 2700S, 3700, 3700S 57237 A Safety Relief Valve VIII Div. 1 Mar 18, 2025 57248 2700L, 3700L (Liquids) A VIII Div. 1 Mar 18, 2025 Relief Valve 2600L (Air & Steam) A 57260 Safety Relief Valve Mar 18, 2025 VIII Div. 1 AWC-Inc. (AIN) location: Westlake, LA, Devices designed by: Farris Engineering (TFO) Device Type NB Cert # Cert Cat Expiration Date Code Section Type Classification 57024 3800 A Apr 2, 2025 Pilot Operated Pressure Relief Valve VIII Div. 1 57035 A 3800FP VIII Div. 1 Apr 2, 2025 Pilot Operated Pressure Relief Valve 57057 A 2600 & 2600S Safety Relief Valve VIII Div. 1 Apr 2, 2025 2600L (Liquids) A 57068 Relief Valve Apr 2, 2025 VIII Div. 1 3800L, PCL, PCM pilots 57215 A VIII Div. 1 Apr 2, 2025 Pilot Operated Pressure Relief Valve 2700, 2700S, 3700, 3700S 57237 A Safety Relief Valve VIII Div. 1 Apr 2, 2025 57248 A 2700L, 3700L (Liquids) Apr 2, 2025 VIII Div. 1 Relief Valve 57260 A 2600L (Air & Steam) Safety Relief Valve VIII Div. 1 Apr 2, 2025 Baird Manufacturing (BRD) location: Tulsa, OK, UNITED STATES Devices designed by: Baird Manufacturing (BRD) NB Cert # Cert Cat Type Classification Device Type Expiration Date Code Section 731-1-GS 04004 M Safety Relief Valve VIII Div. 1 Aug 29, 2023 M 831 04037 VIII Div. 1 Jul 31, 2023 Safety Relief Valve M 04048 7100-2 G Safety Relief Valve May 31, 2023 VIII Div. 1 7100-2 GHP 04059 M Safety Relief Valve Aug 27, 2023 VIII Div. 1 Page 20 of 812 Effective Date: 2019-05-31

22 Table of Contents Basin Valve Company (BVS) location: Signal Hill, CA, UNITED STATES Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Type Classification Code Section NB Cert # Expiration Date Cert Cat Device Type 15095 JLT (Liquids) A VIII Div. 1 Jul 31, 2020 Safety Relief Valve A 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB Safety Relief Valve Jul 31, 2020 VIII Div. 1 900 Series, 7700, SNC 15411 A Jul 31, 2020 VIII Div. 1 Safety Relief Valve 900 Series (Liquid), 7700, SNC A 15499 Relief Valve VIII Div. 1 Jul 31, 2020 H Series (Restricted Lift version of Cert # 15006) 15567 A Safety Valve Jul 31, 2020 I Devices designed by: Farris Engineering (TFO) Device Type Cert Cat Expiration Date Code Section Type Classification NB Cert # 6400/6600 (previously 2500 & 4600) 57046 A Safety Valve Jan 5, 2024 I & VIII Div. 1 2600 & 2600S 57057 A VIII Div. 1 Jan 5, 2024 Safety Relief Valve 57068 2600L (Liquids) A Relief Valve VIII Div. 1 Jan 5, 2023 57237 A 2700, 2700S, 3700, 3700S Jan 5, 2024 VIII Div. 1 Safety Relief Valve A 57248 2700L, 3700L (Liquids) Jan 8, 2023 Relief Valve VIII Div. 1 2600L (Air & Steam) 57260 A Jan 5, 2023 VIII Div. 1 Safety Relief Valve A 57282 4200 / 4400 Jan 5, 2024 Safety Valve I & VIII Div. 1 Bay Valve Service & Engineering, LLC (MLV) location: Odessa, TX, UNITED STATES Acceptable Abbrev.: Bay Valve Service - Odessa, TX Devices designed by: Dresser, LLC (DRJ) NB Cert # Cert Cat Type Classification Device Type Code Section Expiration Date 18032 A 1541, 1543, 1541-3, 1543-3 I & VIII Div. 1 Safety Valve Sep 7, 2019 18122 A 1811, 1511 Safety Valve I & VIII Div. 1 Sep 7, 2019 1900D-2, 1900-30D-2 18144 A VIII Div. 1 Safety Relief Valve Sep 7, 2019 18166 A 1900E-2, 1900-30E-2 VIII Div. 1 Safety Relief Valve Sep 7, 2019 18201 A 1900, 1900-30, 1900-35 Sep 7, 2019 VIII Div. 1 Safety Relief Valve A 18447 3900 (39PV, 39MV pilots) Feb 9, 2022 Pilot Operated Pressure Relief Valve VIII Div. 1 19000 Series 18706 A Safety Relief Valve VIII Div. 1 Sep 19, 2019 18717 19000 Series, Liquid A Relief Valve VIII Div. 1 Sep 18, 2019 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) A Relief Valve Sep 25, 2019 VIII Div. 1 18762 A 1900E-2, 1900-30E-2 LA & DALA (Liquids) VIII Div. 1 Aug 13, 2019 Relief Valve 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) A Relief Valve VIII Div. 1 Sep 9, 2019 Bay Valve Service & Engineering, LLC. (CRS) location: Benicia, CA, UNITED STATES Seal Identification: BVS/ BEN Devices designed by: Dresser, LLC (DRJ) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat 18122 A 1811, 1511 Safety Valve Nov 30, 2023 I & VIII Div. 1 18144 1900D-2, 1900-30D-2 A Safety Relief Valve VIII Div. 1 Nov 29, 2023 18166 1900E-2, 1900-30E-2 A Safety Relief Valve Nov 29, 2023 VIII Div. 1 18201 A 1900, 1900-30, 1900-35 VIII Div. 1 Nov 29, 2023 Safety Relief Valve 18706 19000 Series A Safety Relief Valve VIII Div. 1 Nov 29, 2023 18717 A 19000 Series, Liquid Relief Valve VIII Div. 1 Nov 29, 2023 1900D-2, 1900-30D-2 LA & DALA (Liquids) A 18751 Relief Valve Nov 29, 2023 VIII Div. 1 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 A Relief Valve Nov 30, 2023 VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Nov 30, 2023 VIII Div. 1 Page 21 of 812 Effective Date: 2019-05-31

23 Table of Contents Bay Valve Service & Engineering, LLC. (WAR) location: Aurora, CO, UNITED STATES Devices designed by: Dresser, LLC (DRJ) Type Classification Expiration Date NB Cert # Cert Cat Code Section Device Type 1900D-2, 1900-30D-2 18144 A Mar 9, 2023 VIII Div. 1 Safety Relief Valve 18166 1900E-2, 1900-30E-2 A Safety Relief Valve Mar 9, 2023 VIII Div. 1 1900, 1900-30, 1900-35 18201 A Jun 26, 2023 VIII Div. 1 Safety Relief Valve 18706 A 19000 Series Jun 26, 2023 VIII Div. 1 Safety Relief Valve A 18717 19000 Series, Liquid Mar 9, 2023 Relief Valve VIII Div. 1 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A Relief Valve VIII Div. 1 Mar 9, 2023 1900E-2, 1900-30E-2 LA & DALA (Liquids) A 18762 Mar 9, 2023 Relief Valve VIII Div. 1 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) Mar 10, 2023 VIII Div. 1 Relief Valve Bay Valve Service & Engineering, LLC. (WSL) location: Salt Lake City, UT, UNITED STATES Acceptable Abbrev.: Bay Valve Service - Salt Lake City, UT Devices designed by: Dresser, LLC (DRJ) Cert Cat NB Cert # Expiration Date Type Classification Code Section Device Type 1811, 1511 18122 A I & VIII Div. 1 Mar 13, 2025 Safety Valve A 1900, 1900-30, 1900-35 18201 VIII Div. 1 Mar 13, 2025 Safety Relief Valve 18706 A 19000 Series Safety Relief Valve VIII Div. 1 Dec 20, 2024 A 19000 Series, Liquid 18717 VIII Div. 1 Dec 20, 2024 Relief Valve 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) A Relief Valve VIII Div. 1 Mar 13, 2025 19077 A 19110M & 19110H (Liquids) Apr 9, 2025 VIII Div. 1 Relief Valve Bay Valve Service, LLC. (BAY) location: Seattle, WA, UNITED STATES Acceptable Abbrev.: Bay Valve Service - Seattle, WA Devices designed by: Dresser, LLC (DRJ) Cert Cat NB Cert # Expiration Date Type Classification Code Section Device Type 1541, 1543, 1541-3, 1543-3 18032 A Safety Valve Nov 22, 2022 I & VIII Div. 1 18122 1811, 1511 A Safety Valve Feb 7, 2023 I & VIII Div. 1 18144 A 1900D-2, 1900-30D-2 VIII Div. 1 Nov 21, 2022 Safety Relief Valve 1900E-2, 1900-30E-2 A 18166 Safety Relief Valve Feb 7, 2023 VIII Div. 1 1900, 1900-30, 1900-35 18201 A Safety Relief Valve Feb 6, 2023 VIII Div. 1 18447 A 3900 (39PV, 39MV pilots) VIII Div. 1 Pilot Operated Pressure Relief Valve Nov 21, 2022 18706 A 19000 Series VIII Div. 1 Feb 6, 2023 Safety Relief Valve 19000 Series, Liquid A 18717 VIII Div. 1 Feb 6, 2023 Relief Valve A 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) Relief Valve VIII Div. 1 Nov 28, 2022 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) A Nov 28, 2022 Relief Valve VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Feb 6, 2023 VIII Div. 1 19077 A 19110M & 19110H (Liquids) VIII Div. 1 Aug 22, 2022 Relief Valve Page 22 of 812 Effective Date: 2019-05-31

24 Table of Contents Bay Valve Service, LLC. (BYS) location: Ferndale, WA, UNITED STATES Acceptable Abbrev.: Bay Valve Service - Ferndale, WA Devices designed by: Dresser, LLC (DRJ) Device Type Expiration Date NB Cert # Code Section Type Classification Cert Cat 1900D-2, 1900-30D-2 A 18144 Safety Relief Valve Oct 19, 2020 VIII Div. 1 1900E-2, 1900-30E-2 18166 A Safety Relief Valve Oct 20, 2020 VIII Div. 1 A 18201 1900, 1900-30, 1900-35 Safety Relief Valve Oct 20, 2020 VIII Div. 1 19000 Series A 18706 Safety Relief Valve VIII Div. 1 Oct 19, 2020 A 19000 Series, Liquid 18717 Oct 19, 2020 Relief Valve VIII Div. 1 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A Jul 30, 2020 VIII Div. 1 Relief Valve A 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) Jul 30, 2020 Relief Valve VIII Div. 1 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) A Relief Valve Oct 20, 2020 VIII Div. 1 Beaumont Manufacturing and Distribution Company, LLC (MPV) location: Beaumont, TX, Acceptable Abbrev.: BMD Devices designed by: Beaumont Manufacturing and Distribution Company, LLC (MPV) Type Classification NB Cert # Device Type Cert Cat Code Section Expiration Date M 00910 RV10 Nov 3, 2022 VIII Div. 1 Safety Relief Valve Beijing Aerospace Petrochemical Technology & Equipment Engineering Corporation Limited (BAP) location: Beijing, PEOPLES REP/CHINA Acceptable Abbrev.: BAPC Beijing Aerospace Petrochemical Technology & Equipment Engineering Corporation Limited Devices designed by: (BAP) NB Cert # Cert Cat Expiration Date Type Classification Code Section Device Type 12407 M HT Series Safety Relief Valve Jul 6, 2024 VIII Div. 1 12418 HTXO Series (Liquid) M Safety Relief Valve VIII Div. 1 Nov 13, 2020 12429 HT Series (Liquid) M Safety Relief Valve Nov 13, 2020 VIII Div. 1 12430 M HTXD Series (Liquid) VIII Div. 1 Nov 13, 2020 Pilot Operated Pressure Relief Valve HTXD Series 12441 M Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 14, 2021 12452 M HTXO Series Dec 14, 2021 VIII Div. 1 Safety Relief Valve M 12463 HTBPO May 17, 2023 Buckling Pin Non-reclosing Device VIII Div. 1 HTBPX 12474 M May 17, 2023 VIII Div. 1 Buckling Pin Non-reclosing Device M 12485 HTGS Aug 1, 2024 Safety Valve I & VIII Div. 1 Bermingham Controls, Incorporated (LSL) location: Cerritos, CA, UNITED STATES Seal Identification: BERM Devices designed by: Dresser, LLC (DRJ) Type Classification Cert Cat Code Section Device Type NB Cert # Expiration Date 18032 A 1541, 1543, 1541-3, 1543-3 Safety Valve I & VIII Div. 1 Nov 9, 2022 18111 1700 & 2700 (Restricted Lift version of Cert. # 18100) A Safety Valve Jul 29, 2022 I & VIII Div. 1 1811, 1511 18122 A I & VIII Div. 1 Dec 9, 2022 Safety Valve 1900D-2, 1900-30D-2 18144 A Safety Relief Valve VIII Div. 1 Apr 4, 2022 18166 A 1900E-2, 1900-30E-2 VIII Div. 1 Apr 4, 2022 Safety Relief Valve 18201 A 1900, 1900-30, 1900-35 Safety Relief Valve VIII Div. 1 Apr 4, 2022 19000 Series A 18706 Safety Relief Valve Sep 14, 2022 VIII Div. 1 19000 Series, Liquid 18717 A VIII Div. 1 Sep 14, 2022 Relief Valve 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A Relief Valve VIII Div. 1 Apr 4, 2022 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) A Jul 28, 2022 Relief Valve VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Apr 4, 2022 VIII Div. 1 19077 A 19110M & 19110H (Liquids) VIII Div. 1 Apr 4, 2022 Relief Valve Page 23 of 812 Effective Date: 2019-05-31

25 Table of Contents Bermingham Controls, Incorporated (LSL) location: (continued) Cerritos, CA, UNITED STATES Seal Identification: BERM Devices designed by: Spence Engineering Company, Incorporated (SEC) Expiration Date Cert Cat Type Classification Device Type Code Section NB Cert # Fig 31, 41, 41A 65045 A Safety Valve Sep 24, 2022 I & VIII Div. 1 Berstscheiben Schlesinger GmbH (BER) location: Schalksmühle, GERMANY Devices designed by: Berstscheiben Schlesinger GmbH (BER) NB Cert # Cert Cat Expiration Date Type Classification Code Section Device Type 43029 BK M VIII Div. 1 Jun 8, 2024 Rupture Disk Device C 43030 M VIII Div. 1 Rupture Disk Device Oct 16, 2024 Binzagr Factory for Insulation Materials Co. Ltd. (BFI) location: Jubail, Eastern Province, SAUDI ARABIA Acceptable Abbrev.: LB Devices designed by: LESER GmbH & Company KG (LES) Cert Cat Type Classification Expiration Date Code Section NB Cert # Device Type 441/442/444 37044 A Safety Relief Valve Apr 16, 2025 VIII Div. 1 37055 A 441/442/444 liquids Apr 16, 2025 VIII Div. 1 Relief Valve A 37101 459/462 liquids Apr 16, 2025 Relief Valve VIII Div. 1 459/462 37112 A VIII Div. 1 Safety Relief Valve Apr 16, 2025 A 37189 437 (Liquids) Apr 16, 2025 Relief Valve VIII Div. 1 438 Sub Types 481, 439 37190 A Safety Relief Valve Apr 15, 2025 VIII Div. 1 37202 A 438 Sub Types 481, 439, Liquids Safety Relief Valve VIII Div. 1 Apr 16, 2025 37213 437 A Safety Relief Valve VIII Div. 1 Apr 15, 2025 37224 526 A Safety Relief Valve Apr 16, 2025 VIII Div. 1 526 (Liquids) 37235 A Relief Valve Apr 16, 2025 VIII Div. 1 37246 A 526D VIII Div. 1 Safety Relief Valve Apr 15, 2025 37257 A 526D Liquids Apr 15, 2025 VIII Div. 1 Relief Valve A 37268 820 (liquid) (821) Apr 9, 2025 Pilot Operated Pressure Relief Valve VIII Div. 1 810/820 (811/821) 37280 A Pilot Operated Pressure Relief Valve VIII Div. 1 Apr 9, 2025 37044 441/442/444 A Safety Relief Valve VIII Div. 1 Apr 16, 2025 37055 441/442/444 liquids A Relief Valve Apr 16, 2025 VIII Div. 1 37101 A 459/462 liquids VIII Div. 1 Apr 16, 2025 Relief Valve 37112 459/462 A Safety Relief Valve VIII Div. 1 Apr 16, 2025 437 (Liquids) 37189 A VIII Div. 1 Apr 16, 2025 Relief Valve 37190 438 Sub Types 481, 439 A Safety Relief Valve VIII Div. 1 Apr 15, 2025 37202 A 438 Sub Types 481, 439, Liquids VIII Div. 1 Apr 16, 2025 Safety Relief Valve 37213 A 437 Safety Relief Valve VIII Div. 1 Apr 15, 2025 526 A 37224 Safety Relief Valve Apr 16, 2025 VIII Div. 1 526 (Liquids) 37235 A VIII Div. 1 Apr 16, 2025 Relief Valve 526D 37246 A Safety Relief Valve VIII Div. 1 Apr 15, 2025 37257 526D Liquids A Apr 15, 2025 Relief Valve VIII Div. 1 820 (liquid) (821) 37268 A Pilot Operated Pressure Relief Valve Apr 9, 2025 VIII Div. 1 37280 A 810/820 (811/821) VIII Div. 1 Apr 9, 2025 Pilot Operated Pressure Relief Valve Page 24 of 812 Effective Date: 2019-05-31

26 Table of Contents Bliss Anand Private Limited (BLS) location: HSIIDC, Bawal, Haryana, INDIA Devices designed by: Farris Engineering (TFO) Type Classification Expiration Date NB Cert # Cert Cat Code Section Device Type M 57024 3800 Apr 24, 2020 VIII Div. 1 Pilot Operated Pressure Relief Valve 2600 & 2600S 57057 M May 29, 2020 VIII Div. 1 Safety Relief Valve 57068 M 2600L (Liquids) Apr 3, 2020 VIII Div. 1 Relief Valve 57215 M 3800L, PCL, PCM pilots Pilot Operated Pressure Relief Valve VIII Div. 1 Apr 3, 2020 57237 2700, 2700S, 3700, 3700S M Safety Relief Valve Apr 2, 2020 VIII Div. 1 57248 2700L, 3700L (Liquids) M Relief Valve VIII Div. 1 Apr 2, 2020 The Blythe Company, LLC (BLY) location: Indian Land, SC, UNITED STATES Acceptable Abbrev.: TBC Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type Cert Cat Expiration Date Type Classification Code Section NB Cert # 01089 A 81, 81P, 83, 86 VIII Div. 1 Nov 3, 2025 Safety Relief Valve Devices designed by: Mercer Valve Company, Incorporated (MVC) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # A 38056 9100 Safety Relief Valve VIII Div. 1 Nov 3, 2025 38067 A 9100L (Liquids) Jul 30, 2019 VIII Div. 1 Relief Valve A 38078 9500, S, M, E Pilots Nov 3, 2025 Pilot Operated Pressure Relief Valve VIII Div. 1 9500 (Full Port), S, M, E Pilots 38089 A Pilot Operated Pressure Relief Valve VIII Div. 1 Nov 3, 2025 1400 Series A 38113 Apr 25, 2025 Safety Relief Valve VIII Div. 1 Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Expiration Date NB Cert # Cert Cat Code Section Type Classification Device Type 81, 81P, 83, 86 A 01089 Safety Relief Valve Nov 3, 2025 VIII Div. 1 Devices designed by: Mercer Valve Company, Incorporated (MVC) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 38056 A 9100 VIII Div. 1 Safety Relief Valve Nov 3, 2025 A 9100L (Liquids) 38067 VIII Div. 1 Jul 30, 2019 Relief Valve A 38078 9500, S, M, E Pilots Pilot Operated Pressure Relief Valve Nov 3, 2025 VIII Div. 1 9500 (Full Port), S, M, E Pilots 38089 A VIII Div. 1 Nov 3, 2025 Pilot Operated Pressure Relief Valve 1400 Series 38113 A Safety Relief Valve Apr 25, 2025 VIII Div. 1 Page 25 of 812 Effective Date: 2019-05-31

27 Table of Contents Bopp & Reuther Valves GmbH (BOP) location: Mannheim, GERMANY Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Devices designed by: Bopp & Reuther Valves GmbH (BOP) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification Si 81/83/84 72009 M Mar 23, 2021 VIII Div. 1 Safety Relief Valve M 72010 Si/83/84/81 (RL) Safety Relief Valve Mar 23, 2021 III & VIII Div.1 Si 81/83/84 (Liquids) (RL) 72021 M Sep 20, 2021 III & VIII Div.1 Relief Valve SiZ 2507 72032 M Safety Valve III Nov 30, 2022 SiC 11/13/14 72043 M III & VIII Div.1 Oct 15, 2020 Safety Relief Valve SiC 11/13/14 (Liquids) 72054 M Relief Valve III & VIII Div.1 Apr 15, 2022 M 72065 Si 83/84/81 (Liquids) Sep 20, 2021 Relief Valve III & VIII Div.1 Si 91/95, SiZ 2507 RL M 72076 Aug 9, 2021 Safety Valve I, III, & VIII Div. 1 72087 M Si 91/95 01-07 Type L + H (restricted lift) Dec 22, 2023 I, III, & VIII Div. 1 Safety Valve M 72098 Si 41/43/44 02-05 May 14, 2021 Safety Valve VIII Div. 1 Si 41/43/44 02-05 (Liquids) 72100 M VIII Div. 1 Safety Valve May 17, 2021 M 72122 Si 11, Si 13, Si 14 (B, C, D, E orif.) Jan 17, 2020 Safety Relief Valve VIII Div. 1 Si 11, Si 13, Si 14 (F orif.) 72133 M Safety Relief Valve May 13, 2020 VIII Div. 1 72144 M Si 11, Si 13, Si 14 (B, C, D, E orif., Liquid) Safety Relief Valve VIII Div. 1 Dec 10, 2019 72155 Si 11, Si 13, Si 14 (F orif. , Liquid) M Safety Relief Valve VIII Div. 1 Dec 9, 2019 72166 Si 63 (High Press.) M Safety Relief Valve Dec 6, 2024 III NB, NC Si 63 (Low Press.) 72177 M Safety Relief Valve III NB, NC Dec 4, 2024 Si 25/ Si 63RL (Low Press., Restricted lift) M 72188 III NB, NC Safety Relief Valve Dec 6, 2024 72199 M Si 25/ Si 63RL (High Press., Restricted lift) Dec 6, 2024 III NB, NC Safety Relief Valve M 72201 Si 91 / 95, SiZ 2507 Jan 27, 2021 Safety Valve III NC, ND Si 91 / 95, SiZ 2507 (Restricted Lift) 72212 M III NC, ND Jan 27, 2021 Safety Valve 72223 M SiZ 2507 Safety Relief Valve Dec 18, 2024 VIII Div. 1 Broady Flow Control Limited (BVL) location: East Yorkshire, UNITED KINGDOM Acceptable Abbrev.: Broady - Valvitalia Devices designed by: Broady Flow Control Limited (BVL) Expiration Date NB Cert # Cert Cat Type Classification Code Section Device Type 3500 (Liquid) M 93013 Safety Relief Valve Nov 17, 2019 VIII Div. 1 3600 (Liquid) 93035 M VIII Div. 1 Safety Relief Valve Mar 14, 2025 4000 (Full Bore, Modulating & Snap Acting Pilot, Air/gas)) M 93046 VIII Div. 1 Pilot Operated Pressure Relief Valve May 23, 2022 93068 M 4000 (API Nozzle -Modulating & Snap Acting Pilot, Air/gas) Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 20, 2022 4000 (API Nozzle -Modulating & Snap Acting Pilot, Liquid) 93079 M Mar 14, 2025 VIII Div. 1 Pilot Operated Pressure Relief Valve BS & B PREMCO LATINOAMERICA S.A. de C.V. (BSP) location: Santa Catarina, Nuevo Leon, Devices designed by: BS & B Premco LLC (PRL) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date M BPRV, BPIV 77813 VIII Div. 1 Dec 14, 2023 Buckling Pin Non-reclosing Device M 77970 BPAV (Liquid) Buckling Pin Non-reclosing Device Apr 10, 2023 VIII Div. 1 BPAV (air/gas) 77981 M Buckling Pin Non-reclosing Device Apr 10, 2023 VIII Div. 1 Page 26 of 812 Effective Date: 2019-05-31

28 Table of Contents BS & B Premco Latinoamerica S.A. De C.V. (PLS) location: Guadalupe, Nuevo Leon, MEXICO Devices designed by: BS & B Premco Latinoamerica S.A. De C.V. (PLS) Cert Cat Type Classification NB Cert # Expiration Date Code Section Device Type REL 13004 M Jan 24, 2024 VIII Div. 1 Rupture Disk Device 13015 REV M Rupture Disk Device Feb 5, 2024 VIII Div. 1 RE 13026 M Feb 16, 2024 VIII Div. 1 Rupture Disk Device 13037 M AMBV & MBV W/Bar Type Vacuum Support Feb 5, 2024 VIII Div. 1 Rupture Disk Device M 13048 IMB, AIMB, IMBL, AIMBL, FSM, AFSM Apr 27, 2024 Rupture Disk Device VIII Div. 1 MB & AMB 13059 M Rupture Disk Device VIII Div. 1 Apr 27, 2024 13060 MBV, AMBV w. Dial Vac. Support M Rupture Disk Device Jan 12, 2023 VIII Div. 1 BS & B Premco LLC (PRL) location: Tulsa, OK, UNITED STATES Acceptable Abbrev.: BSB Devices designed by: BS & B Premco LLC (PRL) Expiration Date Cert Cat Type Classification NB Cert # Code Section Device Type M BPRV, BPIV 77813 Apr 24, 2024 VIII Div. 1 Buckling Pin Non-reclosing Device 77970 M BPAV (Liquid) Sep 19, 2023 Buckling Pin Non-reclosing Device VIII Div. 1 BPAV (air/gas) M 77981 Buckling Pin Non-reclosing Device VIII Div. 1 Feb 8, 2023 77992 M BPPV Buckling Pin Non-reclosing Device VIII Div. 1 Jun 19, 2024 78218 EORV M Buckling Pin Non-reclosing Device VIII Div. 1 Sep 27, 2024 BPCV (Air/Gas) 78386 M VIII Div. 1 Sep 27, 2024 Buckling Pin Non-reclosing Device 78397 BPCV (Liquid) M Buckling Pin Non-reclosing Device VIII Div. 1 Oct 16, 2024 78409 IDV M Safety Relief Valve Sep 26, 2024 VIII Div. 1 M 79017 RDV-HP Safety Relief Valve VIII Div. 1 Jun 9, 2020 Devices designed by: BS & B Safety Systems, LLC (BSB) Cert Cat Type Classification Code Section Device Type NB Cert # Expiration Date 77824 MRB M Rupture Disk Device VIII Div. 1 Mar 28, 2025 BS & B Safety Systems (India) Limited (BIN) location: Chennai, Tamil Nadu 600097, INDIA Devices designed by: BS & B Safety Systems, LLC (BSB) Cert Cat Type Classification NB Cert # Device Type Code Section Expiration Date 77026 M BV, BRV, BSV, BRSV VIII Div. 1 Rupture Disk Device Jan 14, 2022 77037 M B, BR, BRR VIII Div. 1 Jan 14, 2022 Rupture Disk Device RLS, RLS Welded Assemly 77059 M Rupture Disk Device May 19, 2020 VIII Div. 1 77060 M GFN, GFA Rupture Disk Device VIII Div. 1 May 15, 2023 77082 S90, S90 Welded Assembly M Rupture Disk Device VIII Div. 1 May 23, 2023 77307 RLS, RLS Welded Assembly (liquid) M Rupture Disk Device Jan 13, 2022 VIII Div. 1 BS & B Safety Systems Ltda. (BDD) location: Sao Paulo, BRAZIL Acceptable Abbrev.: BS & B Devices designed by: BS & B Premco LLC (PRL) Device Type NB Cert # Cert Cat Expiration Date Type Classification Code Section BPAV (Liquid) 77970 M Buckling Pin Non-reclosing Device Jul 9, 2024 VIII Div. 1 77981 M BPAV (air/gas) VIII Div. 1 Jul 9, 2024 Buckling Pin Non-reclosing Device Page 27 of 812 Effective Date: 2019-05-31

29 Table of Contents BS & B Safety Systems Ltda. (BDD) location: (continued) Sao Paulo, BRAZIL Acceptable Abbrev.: BS & B Devices designed by: BS & B Safety Systems, LLC (BSB) Device Type Cert Cat Code Section Type Classification NB Cert # Expiration Date JRS M 77015 Rupture Disk Device May 23, 2024 VIII Div. 1 77059 RLS, RLS Welded Assemly M Rupture Disk Device VIII Div. 1 Aug 15, 2022 77082 S90, S90 Welded Assembly M Rupture Disk Device VIII Div. 1 Aug 16, 2022 77307 RLS, RLS Welded Assembly (liquid) M Rupture Disk Device VIII Div. 1 Aug 16, 2022 77420 GCR-S,SE,SM,SS,SES,SMS, SW, N, NS (2") M Rupture Disk Device Aug 17, 2022 VIII Div. 1 GCR-S, SE, SM, SS, SES, SMS, SW, N, NS 77611 M Rupture Disk Device VIII Div. 1 Aug 15, 2022 GCR-S, SE, SM, SS, SES, SMS, SW, N, NS (liquids) M 78195 VIII Div. 1 Rupture Disk Device Aug 16, 2022 78207 M GCR-S,SE,SM,SS,SES,SMS, SW, N, NS (2" liquids) Rupture Disk Device VIII Div. 1 Aug 16, 2022 Devices designed by: BS & B Safety Systems, Ltd. (BSI) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # SKR, SKR Welded Assemly (Liquids) 77329 M Rupture Disk Device VIII Div. 1 Aug 16, 2022 M LPS, LPS Welded Assembly 77745 VIII Div. 1 Aug 15, 2022 Rupture Disk Device 77756 LPS, LPS Welded Assembly (liquid) M Rupture Disk Device May 23, 2024 VIII Div. 1 Page 28 of 812 Effective Date: 2019-05-31

30 Table of Contents BS & B Safety Systems, LLC (BSB) location: Tulsa, OK, UNITED STATES Acceptable Abbrev.: BSB Devices designed by: BS & B Safety Systems, LLC (BSB) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification CSR 77004 M Oct 10, 2019 VIII Div. 1 Rupture Disk Device 77015 JRS M Rupture Disk Device VIII Div. 1 Mar 27, 2020 M BV, BRV, BSV, BRSV 77026 Rupture Disk Device Aug 4, 2020 VIII Div. 1 77037 M B, BR, BRR Aug 4, 2020 VIII Div. 1 Rupture Disk Device M 77048 DV, D, DR, DRR, DRV Oct 3, 2019 Rupture Disk Device VIII Div. 1 RLS, RLS Welded Assemly 77059 M Rupture Disk Device VIII Div. 1 Oct 16, 2019 GFN, GFA 77060 M Rupture Disk Device Dec 18, 2019 VIII Div. 1 ECR M 77071 Rupture Disk Device Nov 25, 2019 VIII Div. 1 S90, S90 Welded Assembly M 77082 Dec 18, 2020 VIII Div. 1 Rupture Disk Device M CSR (liquid) 77093 Oct 3, 2019 VIII Div. 1 Rupture Disk Device 77105 M GFR-S, -SM, -SE, -SS, -SMS, -SES (1") Rupture Disk Device VIII Div. 1 Apr 9, 2020 GFR-S, -SM, -SE, -SS, -SMS, -SES (1.5") M 77116 Apr 9, 2020 Rupture Disk Device VIII Div. 1 77127 M GFR-S, -SM, -SE, -SS, -SMS, -SES (2") Dec 19, 2019 VIII Div. 1 Rupture Disk Device RB-90 77138 M May 2, 2022 VIII Div. 1 Rupture Disk Device 77194 GFR-S, -SM, -SE, -SS, -SMS, -SES (Combined) M Rupture Disk Device Apr 9, 2020 VIII Div. 1 S-90 (Inconel) 77206 M VIII Div. 1 Rupture Disk Device May 12, 2020 1/2" FRB A-6 M x F & M x M Stakul M 77217 VIII Div. 1 Aug 20, 2020 Rupture Disk Device 77228 M 3/4" B assembly Rupture Disk Device VIII Div. 1 Mar 5, 2021 GFR-S, -SM, -SE, -SS, -SMS, -SES 1 1/2" Liquid 77239 M Rupture Disk Device May 12, 2020 VIII Div. 1 77273 BV,BRV,BSV,BRSV (liquid) M Rupture Disk Device VIII Div. 1 Aug 6, 2020 FRS 77284 M VIII Div. 1 Rupture Disk Device Jan 22, 2021 77307 RLS, RLS Welded Assembly (liquid) M Rupture Disk Device VIII Div. 1 Aug 6, 2020 77318 B, BR, BRR (liquid) M Rupture Disk Device VIII Div. 1 Aug 6, 2020 77341 AV M Rupture Disk Device Feb 28, 2021 VIII Div. 1 D Series (liquid) DR, DRR 77352 M VIII Div. 1 Rupture Disk Device Mar 1, 2021 77420 M GCR-S,SE,SM,SS,SES,SMS, SW, N, NS (2") VIII Div. 1 Rupture Disk Device Mar 24, 2021 77442 M 1/2" Welded FRB with 3/4" Sanitary Clamp Connection (A/G/L) Apr 12, 2021 VIII Div. 1 Rupture Disk Device 2" BV 77486 M Dec 20, 2019 Rupture Disk Device VIII Div. 1 M 77497 2" B Oct 3, 2019 VIII Div. 1 Rupture Disk Device CSI 77565 M Rupture Disk Device VIII Div. 1 Sep 19, 2022 A-10 SK 1" SCD B 77587 M VIII Div. 1 Sep 13, 2022 Rupture Disk Device 77598 A-2 SK 0.5 FRB M Rupture Disk Device VIII Div. 1 Sep 15, 2022 77600 0.5" FRB WFT M Rupture Disk Device VIII Div. 1 Sep 15, 2022 GCR-S, SE, SM, SS, SES, SMS, SW, N, NS 77611 M VIII Div. 1 Rupture Disk Device Jan 4, 2023 A-6 with B Disk 77633 M May 24, 2023 Rupture Disk Device VIII Div. 1 77644 A19 with Scored B Disk M Rupture Disk Device Jul 15, 2023 VIII Div. 1 77688 M RLS DD (liquid) Rupture Disk Device VIII Div. 1 Jun 21, 2024 RLS DD M 77699 Rupture Disk Device Jun 20, 2024 VIII Div. 1 77712 S90 DD M Rupture Disk Device VIII Div. 1 Jun 21, 2024 77723 M SVI Assembly VIII Div. 1 Jun 20, 2024 Rupture Disk Device M 77734 DV, DRV, DSV, DRSV (liquids) Jun 21, 2024 Rupture Disk Device VIII Div. 1 Welded 1" FRB, w. 1/2" VCR connections 77778 M Rupture Disk Device VIII Div. 1 Oct 2, 2024 1/2" Welded FRB w. 3/4" Sanitary Connection (air/gas) M 77789 Rupture Disk Device VIII Div. 1 Feb 10, 2025 77824 M MRB Rupture Disk Device VIII Div. 1 May 20, 2020 FRB (welded cassette) M 77835 Rupture Disk Device Apr 9, 2020 VIII Div. 1 SKA 77846 M Rupture Disk Device VIII Div. 1 Nov 17, 2020 77868 M X 90 Welded Rupture Disk Device VIII Div. 1 Jun 30, 2021 B, BR, BRR-LTF 77879 M Rupture Disk Device VIII Div. 1 Nov 2, 2022 BV, BRV, BSV, BRSV-LTF 77880 M Rupture Disk Device Dec 15, 2022 VIII Div. 1 M D, DR, DRR-LTF 77891 VIII Div. 1 Nov 2, 2022 Rupture Disk Device 77925 FVA M Rupture Disk Device Oct 2, 2019 VIII Div. 1 Page 29 of 812 Effective Date: 2019-05-31

31 Table of Contents BS & B Safety Systems, LLC (BSB) location: (continued) Tulsa, OK, UNITED STATES Acceptable Abbrev.: BSB Devices designed by: BS & B Safety Systems, LLC (BSB) Expiration Date Cert Cat Type Classification Device Type Code Section NB Cert # M Welded FRB w/ 3/4" VCR Connections 77936 VIII Div. 1 Rupture Disk Device Jun 28, 2023 M 78151 Scored B -LTF, Scd B-LTF, XB-LTF Dec 11, 2020 VIII Div. 1 Rupture Disk Device CSI (liquid) 78162 M VIII Div. 1 Oct 14, 2021 Rupture Disk Device PLD 78173 M VIII Div. 1 Rupture Disk Device Oct 14, 2021 PLDV 78184 M Oct 14, 2021 Rupture Disk Device VIII Div. 1 GCR-S, SE, SM, SS, SES, SMS, SW, N, NS (liquids) M 78195 Jan 13, 2022 Rupture Disk Device VIII Div. 1 78207 M GCR-S,SE,SM,SS,SES,SMS, SW, N, NS (2" liquids) Jan 14, 2022 VIII Div. 1 Rupture Disk Device M 78274 ECV Mar 29, 2025 Rupture Disk Device VIII Div. 1 AV-E, AV-EL 78285 M Rupture Disk Device VIII Div. 1 Apr 20, 2023 AVV M 78364 Oct 5, 2023 Rupture Disk Device VIII Div. 1 78375 M Welded QRB Rupture Disk Device VIII Div. 1 Oct 5, 2023 Scored B, SCD B, XB M 84046 Mar 22, 2025 VIII Div. 1 Rupture Disk Device BS & B Safety Systems, Ltd. (BSI) location: Limerick, IRELAND Devices designed by: BS & B Safety Systems, LLC (BSB) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat 77015 M JRS VIII Div. 1 May 26, 2021 Rupture Disk Device M 77037 B, BR, BRR Jan 11, 2023 Rupture Disk Device VIII Div. 1 RLS, RLS Welded Assemly 77059 M Rupture Disk Device VIII Div. 1 May 26, 2021 GFN, GFA 77060 M Rupture Disk Device VIII Div. 1 Apr 30, 2020 77082 M S90, S90 Welded Assembly Rupture Disk Device VIII Div. 1 Oct 27, 2023 77138 RB-90 M Rupture Disk Device VIII Div. 1 Jan 11, 2023 S-90 (Inconel) 77206 M VIII Div. 1 Oct 27, 2023 Rupture Disk Device 77307 RLS, RLS Welded Assembly (liquid) M Rupture Disk Device VIII Div. 1 Oct 27, 2023 77318 M B, BR, BRR (liquid) Rupture Disk Device VIII Div. 1 Sep 21, 2022 77420 GCR-S,SE,SM,SS,SES,SMS, SW, N, NS (2") M Rupture Disk Device VIII Div. 1 Mar 12, 2020 77486 2" BV M Rupture Disk Device Aug 9, 2022 VIII Div. 1 GCR-S, SE, SM, SS, SES, SMS, SW, N, NS (liquids) 77622 M Rupture Disk Device Mar 16, 2020 VIII Div. 1 M DV, DRV, DSV, DRSV (liquids) 77734 VIII Div. 1 Jan 11, 2023 Rupture Disk Device M 78195 GCR-S, SE, SM, SS, SES, SMS, SW, N, NS (liquids) Rupture Disk Device Jan 12, 2023 VIII Div. 1 GCR-S,SE,SM,SS,SES,SMS, SW, N, NS (2" liquids) 78207 M Rupture Disk Device Jan 11, 2023 VIII Div. 1 Page 30 of 812 Effective Date: 2019-05-31

32 Table of Contents BS & B Safety Systems, Ltd. (BSI) location: (continued) Limerick, IRELAND Devices designed by: BS & B Safety Systems, Ltd. (BSI) Cert Cat Code Section Device Type Type Classification NB Cert # Expiration Date 77149 XT M VIII Div. 1 Oct 27, 2023 Rupture Disk Device M 77161 SKR, SKR Welded Assembly Rupture Disk Device Apr 30, 2020 VIII Div. 1 SKR, SKR Welded Assemly (Liquids) 77329 M Jan 22, 2020 VIII Div. 1 Rupture Disk Device SIGMA, SIGMA EXL, UBR M 77464 Rupture Disk Device VIII Div. 1 Sep 19, 2022 SIGMA, SIGMA EXL, UBR (liquid) 77475 M Rupture Disk Device Sep 19, 2022 VIII Div. 1 M 77509 Skr-U 1/2" Sep 18, 2022 Rupture Disk Device VIII Div. 1 SKr-U 3/4" 77510 M VIII Div. 1 Rupture Disk Device Sep 11, 2022 M 77521 SKr-U 1" Sep 18, 2022 Rupture Disk Device VIII Div. 1 SKr-U 3/4" Liquid 77543 M Rupture Disk Device Sep 11, 2022 VIII Div. 1 77554 SKr-U 1" Liquid M Rupture Disk Device Sep 14, 2022 VIII Div. 1 MVB Cassette 77655 M VIII Div. 1 Rupture Disk Device Oct 27, 2023 M 77745 LPS, LPS Welded Assembly Rupture Disk Device VIII Div. 1 Oct 2, 2024 LPS, LPS Welded Assembly (liquid) 77756 M VIII Div. 1 Oct 1, 2024 Rupture Disk Device 77767 M SRC Sep 6, 2019 Rupture Disk Device VIII Div. 1 GLP-S 77790 M Rupture Disk Device Sep 6, 2019 VIII Div. 1 77958 M SSR (liquid) VIII Div. 1 Oct 27, 2023 Rupture Disk Device 77969 M SSR Rupture Disk Device VIII Div. 1 Oct 27, 2023 XT (Liquid) M 78094 Rupture Disk Device Sep 11, 2020 VIII Div. 1 SKr DD 78106 M VIII Div. 1 Dec 20, 2019 Rupture Disk Device 78117 SKr DD (Liquid) M Rupture Disk Device VIII Div. 1 Dec 20, 2019 78128 M 1.5" SLP-S, SLP-SE, SLP-SM, SLP-N, SLP-SS, SLP-SES, SLP- Jan 21, 2021 VIII Div. 1 Rupture Disk Device 2" SLP-S, SLP-SE, SLP-SM, SLP-N, SLP-SS, SLP-SES, SLP- 78139 M Jan 22, 2021 Rupture Disk Device VIII Div. 1 M 78140 3" SLP-S, SLP-SE, SLP-SM, SLP-N, SLP-SS, SLP-SES, SLP- Jan 22, 2021 VIII Div. 1 Rupture Disk Device SRD & CCS 78229 M Rupture Disk Device VIII Div. 1 Aug 15, 2022 SRD & CCS (Liquid) 78230 M VIII Div. 1 Aug 16, 2022 Rupture Disk Device SRD-L & CCS-L 78241 M Rupture Disk Device Aug 16, 2022 VIII Div. 1 78252 M SRD-L & CCS-L (Liquid) Jan 11, 2023 VIII Div. 1 Rupture Disk Device 78308 M LPS-U 0.5" Rupture Disk Device VIII Div. 1 Jan 24, 2024 LPS-U 0.5" (Liquid) 78319 M Rupture Disk Device Jan 24, 2024 VIII Div. 1 78320 LPS-U 0.75" M Jan 24, 2024 Rupture Disk Device VIII Div. 1 LPS-U 0.75" 78331 M Rupture Disk Device VIII Div. 1 Jan 24, 2024 78342 M LPS-U 1.0" VIII Div. 1 Rupture Disk Device Dec 14, 2023 78410 M SKI Rupture Disk Device VIII Div. 1 Oct 18, 2024 SKI (Liquid) 78421 M Rupture Disk Device Oct 18, 2024 VIII Div. 1 Buckeye Valve and Equipment, LLC (BKV) location: Canonsburg, PA, Acceptable Abbrev.: Buckeye Valve Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat A 910 to 919 36100 VIII Div. 1 Oct 22, 2021 Safety Relief Valve A 36111 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) Relief Valve Oct 22, 2021 VIII Div. 1 Kunkle 337 36278 A VIII Div. 1 Oct 22, 2021 Safety Relief Valve Kunkle 6000, 6252 Series 36324 A Safety Valve Oct 22, 2021 I & VIII Div. 1 Page 31 of 812 Effective Date: 2019-05-31

33 Table of Contents Burns Pressure Systems Enterprises, Incorporated (BPS) location: Broken Arrow, OK, UNITED STATES Acceptable Abbrev.: BPS, INC. Devices designed by: Burns Pressure Systems Enterprises, Incorporated (BPS) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 05016 3MBF/ MBP-2 M Jun 19, 2023 VIII Div. 1 Safety Relief Valve 05061 MBP-1 (revised) M NLG (20% OP) PRV Jun 29, 2023 VIII Div. 1 CALTROL, INC. (THI) location: Santa Fe Springs, CA, UNITED STATES Acceptable Abbrev.: CALTROL Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Expiration Date NB Cert # Type Classification Cert Cat Code Section Device Type A 81, 81P, 83, 86 01089 Apr 23, 2024 VIII Div. 1 Safety Relief Valve 01102 A 81P (Liquids) Relief Valve VIII Div. 1 Apr 23, 2024 243/249/443/449/546/843/849/943/5046/5049/8043/8049 A 01292 Pilot Operated Pressure Relief Valve VIII Div. 1 Apr 23, 2024 01304 A 253/259/453/459/853/859/953/959/5059/8053/8059 VIII Div. 1 Apr 23, 2024 Pilot Operated Pressure Relief Valve A 01326 453/459/853/859/953/959/5059 (Liquids) Apr 23, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 443/449/546/843/849/943/949/5046/5049(Liquids) 01337 A Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 25, 2024 15095 JLT (Liquids) A Safety Relief Valve Apr 23, 2024 VIII Div. 1 15208 A JOS-E/JBS-E/JOS-H-E 8400 AC/AB Safety Relief Valve VIII Div. 1 Apr 23, 2024 15411 900 Series, 7700, SNC A Safety Relief Valve VIII Div. 1 Apr 23, 2024 900 Series (Liquid), 7700, SNC 15499 A VIII Div. 1 Apr 23, 2024 Relief Valve A 15512 JLT-JOS, JLT-JBS, 8500, ACL/ABL Safety Relief Valve VIII Div. 1 Apr 23, 2024 Devices designed by: Farris Engineering (TFO) Expiration Date Code Section Cert Cat Device Type Type Classification NB Cert # A 57237 2700, 2700S, 3700, 3700S May 14, 2020 VIII Div. 1 Safety Relief Valve 57248 A 2700L, 3700L (Liquids) Relief Valve VIII Div. 1 Jul 14, 2020 Devices designed by: LESER GmbH & Company KG (LES) NB Cert # Cert Cat Expiration Date Type Classification Code Section Device Type 37101 A 459/462 liquids Relief Valve VIII Div. 1 Jun 9, 2023 459/462 37112 A Mar 2, 2023 VIII Div. 1 Safety Relief Valve 37189 A 437 (Liquids) Mar 2, 2023 Relief Valve VIII Div. 1 438 Sub Types 481, 439 37190 A VIII Div. 1 Safety Relief Valve Mar 2, 2023 37202 A 438 Sub Types 481, 439, Liquids VIII Div. 1 Safety Relief Valve Mar 2, 2023 37213 A 437 Safety Relief Valve VIII Div. 1 Mar 2, 2023 526 37224 A Safety Relief Valve Mar 2, 2023 VIII Div. 1 526 (Liquids) 37235 A VIII Div. 1 Mar 2, 2023 Relief Valve 37246 526D A Safety Relief Valve VIII Div. 1 Mar 2, 2023 37257 526D Liquids A Mar 2, 2023 Relief Valve VIII Div. 1 820 (liquid) (821) 37268 A Pilot Operated Pressure Relief Valve Mar 2, 2023 VIII Div. 1 37280 A 810/820 (811/821) VIII Div. 1 Mar 2, 2023 Pilot Operated Pressure Relief Valve Page 32 of 812 Effective Date: 2019-05-31

34 Table of Contents CALTROL, INC. (THI) location: (continued) Santa Fe Springs, CA, UNITED STATES Acceptable Abbrev.: CALTROL Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Expiration Date Cert Cat Type Classification Device Type Code Section NB Cert # 81, 81P, 83, 86 A 01089 Safety Relief Valve Apr 23, 2024 VIII Div. 1 A 01102 81P (Liquids) Relief Valve Apr 23, 2024 VIII Div. 1 01292 243/249/443/449/546/843/849/943/5046/5049/8043/8049 A Apr 23, 2024 VIII Div. 1 Pilot Operated Pressure Relief Valve 01304 253/259/453/459/853/859/953/959/5059/8053/8059 A Pilot Operated Pressure Relief Valve VIII Div. 1 Apr 23, 2024 453/459/853/859/953/959/5059 (Liquids) 01326 A VIII Div. 1 Pilot Operated Pressure Relief Valve Apr 23, 2024 443/449/546/843/849/943/949/5046/5049(Liquids) 01337 A Jul 25, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 JLT (Liquids) A 15095 Apr 23, 2024 Safety Relief Valve VIII Div. 1 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB A Safety Relief Valve Apr 23, 2024 VIII Div. 1 900 Series, 7700, SNC 15411 A Apr 23, 2024 Safety Relief Valve VIII Div. 1 900 Series (Liquid), 7700, SNC 15499 A Relief Valve Apr 23, 2024 VIII Div. 1 15512 JLT-JOS, JLT-JBS, 8500, ACL/ABL A Safety Relief Valve Apr 23, 2024 VIII Div. 1 Devices designed by: Farris Engineering (TFO) NB Cert # Cert Cat Type Classification Expiration Date Device Type Code Section 57237 A 2700, 2700S, 3700, 3700S May 14, 2020 Safety Relief Valve VIII Div. 1 57248 A 2700L, 3700L (Liquids) VIII Div. 1 Relief Valve Jul 14, 2020 Devices designed by: LESER GmbH & Company KG (LES) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 459/462 liquids A 37101 VIII Div. 1 Relief Valve Jun 9, 2023 37112 459/462 A Safety Relief Valve VIII Div. 1 Mar 2, 2023 A 37189 437 (Liquids) Relief Valve VIII Div. 1 Mar 2, 2023 438 Sub Types 481, 439 37190 A Safety Relief Valve VIII Div. 1 Mar 2, 2023 37202 A 438 Sub Types 481, 439, Liquids Mar 2, 2023 VIII Div. 1 Safety Relief Valve 37213 437 A Safety Relief Valve Mar 2, 2023 VIII Div. 1 37224 A 526 VIII Div. 1 Mar 2, 2023 Safety Relief Valve 526 (Liquids) A 37235 Relief Valve Mar 2, 2023 VIII Div. 1 526D 37246 A Safety Relief Valve VIII Div. 1 Mar 2, 2023 526D Liquids A 37257 VIII Div. 1 Relief Valve Mar 2, 2023 37268 A 820 (liquid) (821) Pilot Operated Pressure Relief Valve VIII Div. 1 Mar 2, 2023 810/820 (811/821) 37280 A Mar 2, 2023 VIII Div. 1 Pilot Operated Pressure Relief Valve Carraro s.r.l. (CAO) location: Segrate (MI), ITALY Devices designed by: Carraro s.r.l. (CAO) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date M CS 35 / G 95408 VIII Div. 1 Aug 12, 2021 Safety Relief Valve 95419 CS 35 / J M Safety Relief Valve Feb 2, 2021 VIII Div. 1 Page 33 of 812 Effective Date: 2019-05-31

35 Table of Contents Cash Acme (Part of Reliance Worldwide Corporation) (CSH) location: Cullman, AL, UNITED STATES Devices designed by: Cash Acme (Part of Reliance Worldwide Corporation) (CSH) Type Classification Code Section NB Cert # Expiration Date Cert Cat Device Type F-30 (3/4") 09009 M Jul 10, 2024 Safety Relief Valve IV 09010 F-82, P3000BR (3/4") M Safety Relief Valve Feb 20, 2025 IV F-82, P3000BR (1") 09021 M IV Safety Relief Valve May 12, 2024 M F-82, P3000BR (1-1/4") 09032 Jun 17, 2024 IV Safety Relief Valve 09043 M F-82, P3000BR (1-1/2") Sep 16, 2024 IV Safety Relief Valve F-82, P3000BR (2") 09054 M Safety Relief Valve Jul 10, 2024 IV 09098 (1-1/2")FVX-4 (2") FVMX-3 (T&P) M Temperature and Pressure Relief Valve IV Oct 4, 2024 M 1 FVX-5L/Series 15, 1-1/4 FVMX4L, FVX-8L 09100 May 21, 2024 IV Temperature and Pressure Relief Valve FVX, FVMX-1-3-5-8, FVMX-5LS-SST Ser. 4 (3/4") 09111 M Nov 5, 2024 IV Temperature and Pressure Relief Valve 09122 M 1 FVX, FVMX3-5C, 3LS-6LS Ser. 4 (T&P) Temperature and Pressure Relief Valve Jun 15, 2024 IV 09155 NCLX-1, -5, -8; NCLX-5L, -5LX, -5S, -LS, -A;S-14 and FWL-2 ,- M Temperature and Pressure Relief Valve Jun 21, 2024 IV 09199 M F-95, P3000CI Safety Relief Valve Sep 16, 2024 IV Cavagna Group S.p.A. - OMECA Division (CAV) location: Ponte San Marco, Brescia, ITALY Acceptable Abbrev.: OMECA Devices designed by: Cavagna Group S.p.A. - OMECA Division (CAV) Expiration Date Cert Cat Device Type Type Classification Code Section NB Cert # 69083 M 700073 Jun 26, 2024 VIII Div. 1 Safety Relief Valve M 69139 1129 Jan 31, 2024 Safety Relief Valve VIII Div. 1 1130 69140 M Safety Relief Valve VIII Div. 1 Feb 24, 2020 69151 1135 M Safety Relief Valve VIII Div. 1 Dec 5, 2024 69173 M 1335 Safety Relief Valve VIII Div. 1 Jul 2, 2021 69184 1361 M Safety Relief Valve VIII Div. 1 Jul 18, 2022 PV60 69195 M VIII Div. 1 Apr 7, 2023 Safety Relief Valve 69229 PV29 (700217) M Safety Relief Valve VIII Div. 1 Jul 16, 2024 69230 M PV19 (700214) Safety Relief Valve VIII Div. 1 Jul 2, 2024 69241 PV24 (700216) M Jul 3, 2024 VIII Div. 1 Safety Relief Valve Centrium Industries Ltd. (CIL) location: Kaohsiung City, Acceptable Abbrev.: CIL Devices designed by: Dresser, LLC (DRJ) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date A 1900D-2, 1900-30D-2 18144 VIII Div. 1 Sep 7, 2022 Safety Relief Valve A 18166 1900E-2, 1900-30E-2 Safety Relief Valve Sep 7, 2022 VIII Div. 1 1900, 1900-30, 1900-35 18201 A Safety Relief Valve Sep 7, 2022 VIII Div. 1 Page 34 of 812 Effective Date: 2019-05-31

36 Table of Contents Chalmers & Kubeck - AL (CKD) location: Decatur, AL, Acceptable Abbrev.: CKD Devices designed by: Dresser, LLC (DRJ) Expiration Date Cert Cat Device Type Type Classification Code Section NB Cert # A 1541, 1543, 1541-3, 1543-3 18032 I & VIII Div. 1 Safety Valve Sep 22, 2021 A 18122 1811, 1511 Sep 22, 2021 I & VIII Div. 1 Safety Valve 1900D-2, 1900-30D-2 A 18144 Safety Relief Valve VIII Div. 1 Sep 22, 2021 1900E-2, 1900-30E-2 18166 A VIII Div. 1 Sep 22, 2021 Safety Relief Valve 1900, 1900-30, 1900-35 18201 A Sep 22, 2021 Safety Relief Valve VIII Div. 1 1982 18379 A Safety Relief Valve VIII Div. 1 Sep 22, 2021 1982 LS, 820000LS 18380 A Relief Valve Sep 22, 2021 VIII Div. 1 18447 3900 (39PV, 39MV pilots) A Pilot Operated Pressure Relief Valve Sep 22, 2021 VIII Div. 1 3900 (39PV, 39MV pilots, liquid) 18458 A VIII Div. 1 Sep 22, 2021 Pilot Operated Pressure Relief Valve 19000 Series 18706 A Safety Relief Valve VIII Div. 1 Sep 22, 2021 A 18717 19000 Series, Liquid Sep 22, 2021 Relief Valve VIII Div. 1 1900D-2, 1900-30D-2 LA & DALA (Liquids) A 18751 Sep 22, 2021 Relief Valve VIII Div. 1 18762 A 1900E-2, 1900-30E-2 LA & DALA (Liquids) Relief Valve VIII Div. 1 Sep 22, 2021 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) A Sep 22, 2021 VIII Div. 1 Relief Valve Chalmers & Kubeck - NC (CHK) location: Gastonia, NC, Seal Identification: CKNC Devices designed by: Dresser, LLC (DRJ) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 18032 A 1541, 1543, 1541-3, 1543-3 I, III, & VIII Div. 1 Safety Valve Jun 12, 2024 18100 A 1700 & 2700 I & VIII Div. 1 May 2, 2024 Safety Valve A 18122 1811, 1511 May 2, 2024 Safety Valve I & VIII Div. 1 1900D-2, 1900-30D-2 18144 A Safety Relief Valve III & VIII Div.1 May 2, 2024 1900E-2, 1900-30E-2 18166 A Safety Relief Valve III & VIII Div.1 May 2, 2024 18201 A 1900, 1900-30, 1900-35 Safety Relief Valve III & VIII Div.1 May 2, 2024 18223 1900, 1900-30, 1900-35 (R.L.) A Safety Relief Valve III & VIII Div.1 May 2, 2023 1982 18379 A III & VIII Div.1 May 2, 2024 Safety Relief Valve 18380 1982 LS, 820000LS A Relief Valve VIII Div. 1 May 2, 2024 18447 A 3900 (39PV, 39MV pilots) Pilot Operated Pressure Relief Valve VIII Div. 1 May 2, 2024 18706 19000 Series A Safety Relief Valve VIII Div. 1 May 2, 2024 18717 19000 Series, Liquid A Relief Valve May 2, 2024 VIII Div. 1 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A Relief Valve May 2, 2024 III & VIII Div.1 A 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 III & VIII Div.1 May 2, 2024 Relief Valve A 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) Relief Valve May 2, 2024 III & VIII Div.1 19110M & 19110H (Liquids) 19077 A Relief Valve Jun 12, 2024 III & VIII Div.1 Page 35 of 812 Effective Date: 2019-05-31

37 Table of Contents Chalmers & Kubeck - NC (IVG) location: Charlotte, NC, UNITED STATES Acceptable Abbrev.: NC Devices designed by: Dresser, LLC (DRJ) Expiration Date Cert Cat Device Type Type Classification NB Cert # Code Section A 1541, 1543, 1541-3, 1543-3 18032 Safety Valve Jul 19, 2019 I & VIII Div. 1 1811, 1511 A 18122 Safety Valve I & VIII Div. 1 May 16, 2023 1900D-2, 1900-30D-2 18144 A VIII Div. 1 Safety Relief Valve Mar 19, 2023 1900E-2, 1900-30E-2 18166 A VIII Div. 1 Safety Relief Valve Mar 19, 2023 18380 A 1982 LS, 820000LS VIII Div. 1 Relief Valve Mar 9, 2020 A 3900 (39PV, 39MV pilots) 18447 VIII Div. 1 Mar 15, 2023 Pilot Operated Pressure Relief Valve 18751 A 1900D-2, 1900-30D-2 LA & DALA (Liquids) Relief Valve May 16, 2023 VIII Div. 1 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) A Relief Valve VIII Div. 1 May 16, 2023 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) A Relief Valve May 16, 2023 VIII Div. 1 Chalmers & Kubeck - North (MON) location: Westfield, MA, UNITED STATES Acceptable Abbrev.: CKN Devices designed by: Dresser, LLC (DRJ) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 18032 A 1541, 1543, 1541-3, 1543-3 I & VIII Div. 1 Safety Valve Apr 27, 2024 18122 A 1811, 1511 I & VIII Div. 1 May 28, 2024 Safety Valve 18144 A 1900D-2, 1900-30D-2 Safety Relief Valve VIII Div. 1 Apr 27, 2024 1900E-2, 1900-30E-2 18166 A Safety Relief Valve VIII Div. 1 Apr 27, 2024 18201 A 1900, 1900-30, 1900-35 Safety Relief Valve VIII Div. 1 May 29, 2024 1982 A 18379 Safety Relief Valve Mar 22, 2024 VIII Div. 1 18380 1982 LS, 820000LS A Relief Valve VIII Div. 1 May 28, 2024 18706 A 19000 Series Safety Relief Valve VIII Div. 1 May 28, 2024 19000 Series, Liquid 18717 A Relief Valve VIII Div. 1 May 28, 2024 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A Relief Valve Aug 22, 2024 VIII Div. 1 A 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 VIII Div. 1 Aug 23, 2024 Relief Valve 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) A Relief Valve Mar 22, 2024 VIII Div. 1 Page 36 of 812 Effective Date: 2019-05-31

38 Table of Contents Chalmers & Kubeck - SC (KSC) location: Cayce, SC, UNITED STATES Acceptable Abbrev.: C&K - SC Devices designed by: Dresser, LLC (DRJ) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat 1541, 1543, 1541-3, 1543-3 A 18032 Safety Valve Dec 14, 2022 I & VIII Div. 1 18122 A 1811, 1511 Dec 15, 2022 I & VIII Div. 1 Safety Valve 1900D-2, 1900-30D-2 A 18144 Oct 27, 2019 VIII Div. 1 Safety Relief Valve 1900E-2, 1900-30E-2 18166 A VIII Div. 1 Oct 27, 2019 Safety Relief Valve 1900, 1900-30, 1900-35 18201 A Safety Relief Valve VIII Div. 1 Dec 15, 2022 A 18447 3900 (39PV, 39MV pilots) Oct 27, 2019 Pilot Operated Pressure Relief Valve VIII Div. 1 18706 19000 Series A Dec 15, 2022 Safety Relief Valve VIII Div. 1 18717 A 19000 Series, Liquid VIII Div. 1 Dec 15, 2022 Relief Valve A 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) Oct 25, 2022 Relief Valve VIII Div. 1 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 A VIII Div. 1 Relief Valve Oct 25, 2022 A 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) Dec 15, 2022 Relief Valve VIII Div. 1 19110M & 19110H (Liquids) A 19077 Relief Valve VIII Jul 22, 2022 18032 A 1541, 1543, 1541-3, 1543-3 Safety Valve I & VIII Div. 1 Dec 14, 2022 18122 1811, 1511 A Safety Valve I & VIII Div. 1 Dec 15, 2022 1900D-2, 1900-30D-2 18144 A VIII Div. 1 Oct 27, 2019 Safety Relief Valve 1900E-2, 1900-30E-2 18166 A Safety Relief Valve VIII Div. 1 Oct 27, 2019 18201 A 1900, 1900-30, 1900-35 Dec 15, 2022 VIII Div. 1 Safety Relief Valve A 18447 3900 (39PV, 39MV pilots) Oct 27, 2019 Pilot Operated Pressure Relief Valve VIII Div. 1 19000 Series 18706 A VIII Div. 1 Safety Relief Valve Dec 15, 2022 A 18717 19000 Series, Liquid Dec 15, 2022 Relief Valve VIII Div. 1 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A Relief Valve VIII Div. 1 Oct 25, 2022 18762 A 1900E-2, 1900-30E-2 LA & DALA (Liquids) Relief Valve VIII Div. 1 Oct 25, 2022 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) A Dec 15, 2022 VIII Div. 1 Relief Valve 19110M & 19110H (Liquids) 19077 A VIII Jul 22, 2022 Relief Valve Chalmers & Kubeck - South (CKS) location: Watkinsville, GA, UNITED STATES Devices designed by: Dresser, LLC (DRJ) NB Cert # Cert Cat Code Section Device Type Type Classification Expiration Date 18032 A 1541, 1543, 1541-3, 1543-3 I & VIII Div. 1 Safety Valve Jun 14, 2021 18122 A 1811, 1511 Safety Valve I & VIII Div. 1 Jun 15, 2021 1900, 1900-30, 1900-35 18201 A Safety Relief Valve Aug 12, 2021 VIII Div. 1 A 19000 Series 18706 VIII Div. 1 Jun 16, 2021 Safety Relief Valve A 18717 19000 Series, Liquid Relief Valve Jun 14, 2021 VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Jun 16, 2021 VIII Div. 1 Page 37 of 812 Effective Date: 2019-05-31

39 Table of Contents Chalmers & Kubeck - TN (VSI) location: Chattanooga, TN, UNITED STATES Acceptable Abbrev.: VSI Devices designed by: Dresser, LLC (DRJ) Expiration Date Cert Cat Device Type Type Classification Code Section NB Cert # 1541, 1543, 1541-3, 1543-3 18032 A Safety Valve Sep 18, 2024 I & VIII Div. 1 1811, 1511 A 18122 Safety Valve Dec 17, 2024 I & VIII Div. 1 1900D-2, 1900-30D-2 18144 A Sep 19, 2024 Safety Relief Valve VIII Div. 1 18166 1900E-2, 1900-30E-2 A Sep 19, 2024 VIII Div. 1 Safety Relief Valve 1900, 1900-30, 1900-35 18201 A VIII Div. 1 Sep 18, 2024 Safety Relief Valve 1982 18379 A Sep 18, 2024 Safety Relief Valve VIII Div. 1 3900 (39PV, 39MV pilots) 18447 A Pilot Operated Pressure Relief Valve VIII Div. 1 Aug 29, 2024 3900 (39PV, 39MV pilots, liquid) 18458 A VIII Div. 1 Aug 6, 2021 Pilot Operated Pressure Relief Valve A 19000 Series 18706 VIII Div. 1 Sep 18, 2024 Safety Relief Valve 18717 A 19000 Series, Liquid Jan 23, 2025 VIII Div. 1 Relief Valve A 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) Dec 17, 2024 Relief Valve VIII Div. 1 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 A VIII Div. 1 Jan 23, 2025 Relief Valve 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) Sep 19, 2024 VIII Div. 1 Relief Valve 19077 A 19110M & 19110H (Liquids) VIII Div. 1 Relief Valve Aug 6, 2021 Chalmers & Kubeck, Inc. (BRU) location: New Brunswick, NJ, UNITED STATES Acceptable Abbrev.: Chalmers & Kubeck NB/NJ Devices designed by: Dresser, LLC (DRJ) NB Cert # Code Section Type Classification Expiration Date Device Type Cert Cat 18144 1900D-2, 1900-30D-2 A Safety Relief Valve Jul 9, 2019 VIII Div. 1 18166 A 1900E-2, 1900-30E-2 VIII Div. 1 Safety Relief Valve Jul 9, 2019 18201 A 1900, 1900-30, 1900-35 Oct 9, 2019 VIII Div. 1 Safety Relief Valve A 18706 19000 Series Oct 9, 2019 Safety Relief Valve VIII Div. 1 19000 Series, Liquid 18717 A VIII Div. 1 Aug 15, 2019 Relief Valve 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) Relief Valve Aug 15, 2019 VIII Div. 1 Chalmers & Kubeck, Inc. (CKB) location: Beaver Falls, PA, UNITED STATES Devices designed by: Dresser, LLC (DRJ) Expiration Date NB Cert # Cert Cat Type Classification Code Section Device Type 1541, 1543, 1541-3, 1543-3 A 18032 Apr 11, 2020 I & VIII Div. 1 Safety Valve 1811, 1511 18122 A I & VIII Div. 1 Feb 13, 2020 Safety Valve 18144 1900D-2, 1900-30D-2 A Safety Relief Valve VIII Div. 1 Feb 18, 2020 18166 A 1900E-2, 1900-30E-2 VIII Div. 1 Feb 18, 2020 Safety Relief Valve 18201 A 1900, 1900-30, 1900-35 Safety Relief Valve VIII Div. 1 Apr 10, 2020 19000 Series A 18706 Safety Relief Valve Feb 18, 2020 VIII Div. 1 19000 Series, Liquid 18717 A VIII Div. 1 Feb 19, 2020 Relief Valve 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A Relief Valve VIII Div. 1 Feb 18, 2020 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) A Feb 18, 2020 Relief Valve VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Feb 19, 2020 VIII Div. 1 19077 A 19110M & 19110H (Liquids) VIII Div. 1 Feb 19, 2020 Relief Valve Page 38 of 812 Effective Date: 2019-05-31

40 Table of Contents Chalmers & Kubeck, Incorporated (CKI) location: Aston, PA, UNITED STATES Devices designed by: Dresser, LLC (DRJ) Cert Cat Type Classification NB Cert # Expiration Date Code Section Device Type A 18032 1541, 1543, 1541-3, 1543-3 Feb 2, 2025 I & VIII Div. 1 Safety Valve 1700 & 2700 18100 A Nov 14, 2022 I Safety Valve 18111 A 1700 & 2700 (Restricted Lift version of Cert. # 18100) Sep 27, 2022 I Safety Valve 18122 A 1811, 1511 Safety Valve I & VIII Div. 1 Feb 2, 2025 18144 1900D-2, 1900-30D-2 A Safety Relief Valve VIII Div. 1 Feb 2, 2025 18166 1900E-2, 1900-30E-2 A Safety Relief Valve VIII Div. 1 Feb 2, 2025 1900, 1900-30, 1900-35 18201 A VIII Div. 1 Safety Relief Valve Feb 2, 2025 1982 18379 A Feb 2, 2025 Safety Relief Valve VIII Div. 1 18380 1982 LS, 820000LS A Relief Valve Nov 15, 2022 VIII Div. 1 18447 A 3900 (39PV, 39MV pilots) Pilot Operated Pressure Relief Valve VIII Div. 1 Aug 23, 2023 3900 (39PV, 39MV pilots, liquid) A 18458 Pilot Operated Pressure Relief Valve Aug 23, 2023 VIII Div. 1 18706 19000 Series A Safety Relief Valve VIII Div. 1 Aug 23, 2023 18717 A 19000 Series, Liquid Sep 14, 2023 VIII Div. 1 Relief Valve A 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) Sep 18, 2023 Relief Valve VIII Div. 1 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 A Relief Valve VIII Div. 1 Sep 18, 2023 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve VIII Div. 1 Aug 18, 2023 19077 A 19110M & 19110H (Liquids) Relief Valve VIII Div. 1 Apr 10, 2024 Circor Aerospace, Inc. (CSC) location: Corona, CA, UNITED STATES Acceptable Abbrev.: Circle Seal Devices designed by: Circor Aerospace, Inc. (CSC) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 10001 M D-500-2M VIII Div. 1 Safety Relief Valve Apr 29, 2020 M M5100-1M 10012 VIII Div. 1 Apr 29, 2020 Safety Relief Valve M 10023 M5100-2M & 3M Safety Relief Valve Apr 29, 2020 VIII Div. 1 M5100-4M 10034 M VIII Div. 1 Apr 29, 2020 Safety Relief Valve M5100-6M & 8M 100 - 1200 10056 M Safety Relief Valve Apr 29, 2020 VIII Div. 1 Page 39 of 812 Effective Date: 2019-05-31

41 Table of Contents Circor Energy Products (HDS) location: Oklahoma City, OK, UNITED STATES Acceptable Abbrev.: Hydroseal Devices designed by: Circor Energy Products (HDS) Expiration Date Cert Cat Device Type Type Classification Code Section NB Cert # 1-BV thru 3-BV, 1EV thru 4EV, FL 30003 M Safety Relief Valve Apr 16, 2025 VIII Div. 1 5-BV thru 7-BV, FL-5-FV thru FL M 30014 Safety Relief Valve Sep 23, 2021 VIII Div. 1 1-CRV thru 3-CRV, 1-FRV thru 4-F 30025 M Apr 16, 2025 Safety Relief Valve VIII Div. 1 5-CRV, thru 8-CRV, FL-5-CRV M 30036 Safety Relief Valve VIII Div. 1 Apr 16, 2025 5, 6, 7, 8 CV, FL 30047 M Safety Relief Valve Sep 23, 2021 VIII Div. 1 CXV, FXV, AXV, FL-XV M 30058 Safety Relief Valve VIII Div. 1 Apr 16, 2025 3FT, 4FT, 5FT, FT flanged series M 30069 VIII Div. 1 Safety Relief Valve Sep 23, 2021 M 30081 5HC, 6HC & 7HC Sep 22, 2022 Safety Relief Valve VIII Div. 1 2500 (Liquids) 30115 M VIII Div. 1 Sep 20, 2021 Relief Valve M Series 1500 30126 VIII Div. 1 Apr 16, 2025 Safety Relief Valve 30137 M Series 1500 (Liquids) Apr 16, 2025 VIII Div. 1 Relief Valve M 30182 2500 Series ER (25MR, 25SER, B25ER) Sep 22, 2021 Safety Relief Valve VIII Div. 1 5HD thru 7HD, HD Flanged Series 30205 M VIII Div. 1 Relief Valve Apr 16, 2025 M 30250 1200B Apr 16, 2025 Relief Valve VIII Div. 1 30261 M 1200B (liquid) Apr 16, 2025 Relief Valve VIII Div. 1 30272 M 1400B Safety Relief Valve VIII Div. 1 Apr 16, 2025 30283 1400B (Liquid) M Safety Relief Valve Apr 16, 2025 VIII Div. 1 30294 M 3500 w/ Modulating & Snap Pilots Pilot Operated Pressure Relief Valve Oct 27, 2020 VIII Div. 1 CIV/Barsatech (CIV) location: St-Laurent, Seal Identification: BAR Devices designed by: Farris Engineering (TFO) Type Classification Cert Cat Code Section NB Cert # Expiration Date Device Type 57057 A 2600 & 2600S Feb 13, 2025 VIII Div. 1 Safety Relief Valve A 57068 2600L (Liquids) Feb 11, 2025 Relief Valve VIII Div. 1 2700, 2700S, 3700, 3700S 57237 A VIII Div. 1 Safety Relief Valve Feb 13, 2025 A 57248 2700L, 3700L (Liquids) Feb 11, 2025 Relief Valve VIII Div. 1 Cleveland Valve and Gauge, Co. (CVG) location: Cleveland, OH, UNITED STATES Acceptable Abbrev.: Cleveland Valve & Gauge Devices designed by: Dresser, LLC (DRJ) Type Classification Device Type NB Cert # Cert Cat Expiration Date Code Section 18032 1541, 1543, 1541-3, 1543-3 A Jul 13, 2020 Safety Valve I & VIII Div. 1 18122 1811, 1511 A Jul 24, 2020 Safety Valve I & VIII Div. 1 1900D-2, 1900-30D-2 18144 A Safety Relief Valve Apr 22, 2020 VIII Div. 1 18166 A 1900E-2, 1900-30E-2 VIII Div. 1 Safety Relief Valve Apr 22, 2020 18201 A 1900, 1900-30, 1900-35 Safety Relief Valve VIII Div. 1 Jul 24, 2020 3900 (39PV, 39MV pilots) 18447 A Pilot Operated Pressure Relief Valve Jun 1, 2020 VIII Div. 1 19000 Series 18706 A VIII Div. 1 Jul 1, 2020 Safety Relief Valve A 18717 19000 Series, Liquid Relief Valve VIII Div. 1 Jul 30, 2020 18751 A 1900D-2, 1900-30D-2 LA & DALA (Liquids) Relief Valve VIII Div. 1 Apr 22, 2020 1900E-2, 1900-30E-2 LA & DALA (Liquids) A 18762 Relief Valve Apr 22, 2020 VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Jul 1, 2020 VIII Div. 1 19110M & 19110H (Liquids) 19077 A Relief Valve Apr 22, 2020 VIII Div. 1 Page 40 of 812 Effective Date: 2019-05-31

42 Table of Contents Conbraco Industries, Incorporated (CNB) location: Pageland, SC, UNITED STATES Devices designed by: Conbraco Industries, Incorporated (CNB) Cert Cat Type Classification NB Cert # Expiration Date Code Section Device Type 10-102/104 (RVW10) 11002 M Jul 24, 2023 IV Safety Relief Valve 11024 10-301/303 (RVW30) M Safety Relief Valve May 7, 2024 IV 10-321 (RVW32) 11035 M Mar 24, 2021 IV Safety Relief Valve 11046 M 10-322 (RVS32) Mar 30, 2022 VIII Div. 1 Safety Relief Valve M 11057 10-407 & 10-408 (30 psig) Nov 17, 2024 Safety Relief Valve IV 10-512 (RVS52) 11080 M Safety Relief Valve VIII Div. 1 Nov 4, 2023 11091 10-600 (RVW60) M Safety Relief Valve IV Nov 3, 2024 11103 10-610 (RVW61) M Safety Relief Valve IV Aug 13, 2024 12-205 (RVS12) 11114 M IV Nov 16, 2020 Safety Valve 12-206 (RVS12) 11125 M Safety Valve IV Jul 23, 2024 M 11136 12-208 (RVS12) Nov 16, 2020 Safety Valve IV 11147 13-101 (RVS13T) M Safety Valve Nov 17, 2020 IV 11169 M 13-202 (RVS13) Safety Valve IV Mar 24, 2021 11170 13-211 (RVS13) M Safety Valve IV Jun 21, 2020 13-213 (RVS13) 11181 M IV Nov 17, 2024 Safety Valve M 11192 13-214 (RVS13) Safety Valve IV Nov 17, 2024 11215 M 14-205 (RVS14) Nov 16, 2020 IV Safety Valve M 11226 14-206 (RVS14) Apr 16, 2023 Safety Valve IV 14-207 (RVS14) 11237 M IV Safety Valve Feb 9, 2020 M 11248 15-112 (RVA15) Jul 31, 2024 Safety Relief Valve VIII Div. 1 15-115/117 (RVA15) 11259 M Safety Relief Valve Oct 2, 2022 VIII Div. 1 11282 M 19 Series Safety Valve I & VIII Div. 1 Nov 13, 2023 11293 29-102, 29-202, 29-302 M Safety Valve I & VIII Div. 1 Nov 17, 2024 11305 29-303, 29-402, 29-501 M Safety Valve Jul 31, 2024 I & VIII Div. 1 13-511/512 (RVS13L) 11350 M Safety Relief Valve Apr 16, 2023 IV 11361 M 119 Series I & VIII Div. 1 Safety Valve Sep 29, 2024 11372 M 15-118 (RVA15) Safety Relief Valve VIII Div. 1 Aug 28, 2019 15-119 (RVA15) 11383 M Safety Relief Valve Oct 23, 2019 VIII Div. 1 17-402 (RVW17) 11440 M IV Mar 6, 2021 Safety Relief Valve 11451 10-417/418 (RVW40) M Safety Relief Valve IV Sep 27, 2020 11462 500 Series M Dec 5, 2021 Safety Valve VIII Div. 1 500 Series (Liquids) 11473 M Safety Relief Valve Jul 31, 2021 VIII Div. 1 11518 M 10-624/634 (RVW62) IV Nov 17, 2024 Safety Relief Valve Page 41 of 812 Effective Date: 2019-05-31

43 Table of Contents Continental Disc Corporation (CDC) location: Liberty, MO, UNITED STATES Devices designed by: Continental Disc Corporation (CDC) Cert Cat Type Classification NB Cert # Expiration Date Code Section Device Type CDC (FS) 75002 M Mar 24, 2025 VIII Div. 1 Rupture Disk Device M 75013 ENVIRO-SEAL, Isolation Seal VIII Div. 1 Mar 24, 2025 Rupture Disk Device ZAP 75024 M Rupture Disk Device Mar 24, 2025 VIII Div. 1 KBA 75035 M VIII Div. 1 Feb 13, 2024 Rupture Disk Device 75046 M CDCV (FS) VIII Div. 1 Rupture Disk Device Mar 24, 2025 75057 M CDC/LD/ (LL) Feb 13, 2025 Rupture Disk Device VIII Div. 1 MICRO X, MX-9T & SCORED FLAT SEAT M 75079 VIII Div. 1 Mar 24, 2025 Rupture Disk Device MICRO X-V, MX-9T-V & SCORED FLAT SEAT 75080 M Mar 24, 2025 Rupture Disk Device VIII Div. 1 M 75091 STANDARD Mar 24, 2025 VIII Div. 1 Rupture Disk Device ULTRX, ULTRX HP 75125 M Rupture Disk Device VIII Div. 1 Mar 24, 2025 RCS 75147 M VIII Div. 1 Feb 13, 2025 Rupture Disk Device 75169 PL, PLV, LPL, LPLV (Flat Seat) M Rupture Disk Device VIII Div. 1 May 13, 2025 75170 PL, PLV, LPL, LPLV (Angular seat) M Rupture Disk Device VIII Div. 1 May 14, 2025 75181 MICRO-X-V, MX-9T-V Flat Seat (liquid) M Rupture Disk Device VIII Div. 1 May 13, 2025 M 75215 CDCV (FS) (No Options) Rupture Disk Device Oct 27, 2025 VIII Div. 1 RCS (No Options) 75226 M May 14, 2025 VIII Div. 1 Rupture Disk Device MINTRX (No Options) 75237 M VIII Div. 1 May 13, 2025 Rupture Disk Device ULTRX, ULTRX HP (No Options) 75248 M VIII Div. 1 Rupture Disk Device May 14, 2025 75259 M CD30935 May 9, 2025 VIII Div. 1 Rupture Disk Device 75260 CD30936 M Rupture Disk Device May 9, 2025 VIII Div. 1 ULTRX (DD) 75271 M VIII Div. 1 Rupture Disk Device Oct 27, 2025 SRA (FS) 75282 M Apr 30, 2020 Rupture Disk Device VIII Div. 1 Standard-V (flat seat threaded) 75293 M Rupture Disk Device Apr 30, 2020 VIII Div. 1 75305 M Standard (angle seat threaded) Rupture Disk Device VIII Div. 1 Apr 30, 2020 Standard-V (Angle seat threaded) M 75316 Rupture Disk Device Apr 30, 2020 VIII Div. 1 75327 Standard (flat seat threaded) M Rupture Disk Device VIII Div. 1 Apr 30, 2020 75338 M CDCV (FS threaded) Apr 30, 2020 VIII Div. 1 Rupture Disk Device PL (CF) 75349 M Aug 2, 2022 VIII Div. 1 Rupture Disk Device 75350 PLV (CF) M Rupture Disk Device Aug 2, 2022 VIII Div. 1 CDC (CF) 75361 M VIII Div. 1 Rupture Disk Device Aug 2, 2022 CDCV (CF) M 75372 VIII Div. 1 Aug 2, 2022 Rupture Disk Device 75383 M MICRO X, MX-9T (CF) Rupture Disk Device VIII Div. 1 Aug 2, 2022 75394 Micro-X-V, MX-9T-V (CF) M Rupture Disk Device Mar 17, 2021 VIII Div. 1 75406 M SRA RVI (FS) VIII Div. 1 Mar 17, 2021 Rupture Disk Device M 75428 VRD Feb 22, 2024 Rupture Disk Device VIII Div. 1 Sanitrx, Sanitrx LP-NA (liquid) 75439 M Rupture Disk Device VIII Div. 1 Jan 17, 2025 Sanitrx LP, Sanitrx LP-NA M 75440 Rupture Disk Device VIII Div. 1 Jan 17, 2025 75451 M Sanitrx , Sanitrx NA (liquid) Rupture Disk Device VIII Div. 1 Jan 17, 2025 Sanitrx , Sanitrx-NA(Air/Gas) M 75462 Rupture Disk Device Jan 17, 2025 VIII Div. 1 MICRO X-V(DD), MICRO X, MX-9T-V, MX-9T 75473 M Rupture Disk Device VIII Div. 1 Jan 17, 2025 75484 M CD 31074 VIII Div. 1 Jan 17, 2025 Rupture Disk Device M 75495 Standard V (LL) Oct 3, 2025 Rupture Disk Device VIII Div. 1 CDCV , LDV (LL) 75507 M Rupture Disk Device VIII Div. 1 Oct 3, 2025 RCS (DD) M 75518 Rupture Disk Device VIII Div. 1 Oct 3, 2025 75529 M STAR X, STAR X HP (gas) Rupture Disk Device VIII Div. 1 Feb 20, 2025 STAR X, STAR X HP (liquid) M 75530 Rupture Disk Device Feb 20, 2025 VIII Div. 1 MINTRX (liquid) 75541 M Rupture Disk Device VIII Div. 1 Sep 18, 2025 75552 M MINTRX (gas) Rupture Disk Device VIII Div. 1 Sep 18, 2025 SANITRX MP (SF, NA, IS) (liquid) 75563 M Rupture Disk Device VIII Div. 1 Mar 11, 2020 SANITRX MP (SF, NA, IS) (gas) 75574 M Rupture Disk Device Mar 11, 2020 VIII Div. 1 M HPX (FS)(GAS) 75585 VIII Div. 1 Dec 3, 2020 Rupture Disk Device 75596 HPX (FS)(Liquid) M Rupture Disk Device Dec 3, 2020 VIII Div. 1 Page 42 of 812 Effective Date: 2019-05-31

44 Table of Contents Continental Disc Corporation (CDC) location: (continued) Liberty, MO, UNITED STATES Devices designed by: Continental Disc Corporation (CDC) Code Section Type Classification Device Type NB Cert # Cert Cat Expiration Date HPX Sanitary, Sanitrx HPX, Sanitrx LPX (SF,NA,IS)(Gas) 75608 M Dec 2, 2020 VIII Div. 1 Rupture Disk Device HPX Sanitary, Sanitrx HPX, Sanitrx LPX (SF,NA,IS)(Liquid) 75619 M Rupture Disk Device Dec 3, 2020 VIII Div. 1 LOTRX (Gas) 75620 M Rupture Disk Device Apr 21, 2021 VIII Div. 1 LOTRX (Liquid) 75631 M Apr 22, 2021 VIII Div. 1 Rupture Disk Device 75642 M CDC, CDCV (DD) Sep 2, 2022 VIII Div. 1 Rupture Disk Device M 75653 CD 31327 Sep 1, 2022 Rupture Disk Device VIII Div. 1 HPX (DD) 75664 M VIII Div. 1 Rupture Disk Device Oct 27, 2023 M 75675 SANITRX HPX II (SF, NA, IS)(GAS) Oct 27, 2023 Rupture Disk Device VIII Div. 1 SANITRX HPX II (SF, NA, IS)(Liquid) M 75686 Oct 26, 2023 Rupture Disk Device VIII Div. 1 75697 M SRA (Gas) Dec 5, 2024 VIII Div. 1 Rupture Disk Device M 75709 SRA (Liquid) Dec 5, 2024 Rupture Disk Device VIII Div. 1 WMP (Gas) 75710 M Dec 5, 2025 VIII Div. 1 Rupture Disk Device M 75721 WMP (Liquid) Dec 5, 2024 Rupture Disk Device VIII Div. 1 CD31159 75732 M Rupture Disk Device Jun 15, 2023 VIII Div. 1 Continental NH3 Products Co., Inc. (CNT) location: Dallas, TX, UNITED STATES Devices designed by: Continental NH3 Products Co., Inc. (CNT) Expiration Date NB Cert # Cert Cat Type Classification Device Type Code Section 12003 AA-402VA M Jul 12, 2023 Safety Relief Valve VIII Div. 1 12025 AA-402VA (265 psig) M Jul 12, 2023 Safety Relief Valve VIII Div. 1 AA-417-AB 12036 M Safety Relief Valve Jan 11, 2020 VIII Div. 1 Contro Valve Equipment Inc. (CBU) location: Burlington, CANADA Acceptable Abbrev.: Contro Valve Inc. Burlington Devices designed by: Conbraco Industries, Incorporated (CNB) Device Type Expiration Date NB Cert # Code Section Type Classification Cert Cat A 11282 19 Series Safety Valve I & VIII Div. 1 Mar 19, 2024 119 Series A 11361 Safety Valve Mar 19, 2024 I & VIII Div. 1 500 Series 11462 A VIII Div. 1 Mar 19, 2024 Safety Valve 500 Series (Liquids) 11473 A Safety Relief Valve VIII Div. 1 Mar 19, 2024 Devices designed by: Dresser, LLC (DRJ) Expiration Date NB Cert # Cert Cat Type Classification Device Type Code Section 18032 1541, 1543, 1541-3, 1543-3 A Mar 5, 2025 Safety Valve I & VIII Div. 1 18122 1811, 1511 A Mar 5, 2025 Safety Valve I & VIII Div. 1 1900D-2, 1900-30D-2 18144 A Safety Relief Valve Mar 6, 2025 VIII Div. 1 18166 A 1900E-2, 1900-30E-2 VIII Div. 1 Safety Relief Valve Mar 6, 2025 18201 A 1900, 1900-30, 1900-35 Safety Relief Valve VIII Div. 1 Mar 6, 2025 1982 LS, 820000LS 18380 A Relief Valve Jan 29, 2020 VIII Div. 1 19000 Series 18706 A VIII Div. 1 Mar 5, 2025 Safety Relief Valve A 18717 19000 Series, Liquid Relief Valve VIII Div. 1 Mar 4, 2025 18751 A 1900D-2, 1900-30D-2 LA & DALA (Liquids) Relief Valve VIII Div. 1 Mar 4, 2025 1900E-2, 1900-30E-2 LA & DALA (Liquids) A 18762 Relief Valve Mar 4, 2025 VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Mar 4, 2025 VIII Div. 1 19110M & 19110H (Liquids) 19077 A Relief Valve Feb 13, 2025 VIII Div. 1 Page 43 of 812 Effective Date: 2019-05-31

45 Table of Contents Contro Valve Equipment Inc. (VAL) location: Brossard, CANADA Acceptable Abbrev.: Contro Valve Inc. Brossard Devices designed by: Conbraco Industries, Incorporated (CNB) Expiration Date Cert Cat Code Section Device Type Type Classification NB Cert # 19 Series 11282 A Safety Valve Apr 25, 2023 I & VIII Div. 1 119 Series A 11361 Safety Valve Apr 25, 2023 I & VIII Div. 1 500 Series 11462 A Sep 13, 2023 Safety Valve VIII Div. 1 500 Series (Liquids) 11473 A VIII Div. 1 Apr 25, 2023 Safety Relief Valve Devices designed by: Dresser, LLC (DRJ) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification A 1541, 1543, 1541-3, 1543-3 18032 Feb 4, 2020 Safety Valve I & VIII Div. 1 1811, 1511 18122 A I & VIII Div. 1 Apr 16, 2023 Safety Valve A 1900D-2, 1900-30D-2 18144 VIII Div. 1 Feb 5, 2020 Safety Relief Valve 18166 A 1900E-2, 1900-30E-2 Feb 5, 2020 VIII Div. 1 Safety Relief Valve A 18201 1900, 1900-30, 1900-35 Feb 13, 2020 Safety Relief Valve VIII Div. 1 3900 (39PV, 39MV pilots) 18447 A Pilot Operated Pressure Relief Valve VIII Div. 1 Mar 5, 2020 18458 3900 (39PV, 39MV pilots, liquid) A Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 8, 2020 18706 A 19000 Series Safety Relief Valve VIII Div. 1 Jan 22, 2023 18717 19000 Series, Liquid A Relief Valve VIII Div. 1 Jan 23, 2024 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A VIII Div. 1 Jan 23, 2024 Relief Valve 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 A Relief Valve VIII Div. 1 Jan 23, 2024 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) Mar 5, 2020 VIII Div. 1 Relief Valve A 19110M & 19110H (Liquids) 19077 Dec 21, 2023 VIII Div. 1 Relief Valve Contro Valve Equipment, Inc. (CTR) location: Sarnia, CANADA Seal Identification: CVS Devices designed by: Dresser, LLC (DRJ) Code Section Expiration Date Device Type NB Cert # Cert Cat Type Classification 18032 1541, 1543, 1541-3, 1543-3 A Safety Valve VIII Div. 1 Feb 5, 2020 18144 A 1900D-2, 1900-30D-2 Safety Relief Valve VIII Div. 1 Feb 18, 2024 18166 1900E-2, 1900-30E-2 A Safety Relief Valve VIII Div. 1 Apr 8, 2025 1900, 1900-30, 1900-35 18201 A VIII Div. 1 Feb 18, 2024 Safety Relief Valve 3900 (39PV, 39MV pilots) 18447 A Pilot Operated Pressure Relief Valve VIII Div. 1 Mar 13, 2025 18458 A 3900 (39PV, 39MV pilots, liquid) Pilot Operated Pressure Relief Valve VIII Div. 1 Mar 13, 2025 18706 19000 Series A Safety Relief Valve VIII Div. 1 Mar 7, 2021 18717 19000 Series, Liquid A Relief Valve Mar 2, 2021 VIII Div. 1 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A Relief Valve Feb 18, 2024 VIII Div. 1 A 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 VIII Div. 1 Feb 18, 2024 Relief Valve A 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) Relief Valve Feb 18, 2024 VIII Div. 1 19110M & 19110H (Liquids) 19077 A Relief Valve Jan 13, 2020 VIII Div. 1 Page 44 of 812 Effective Date: 2019-05-31

46 Table of Contents Control Devices, LLC (CDV) location: Fenton, MO, UNITED STATES Acceptable Abbrev.: CD STL, MO Devices designed by: Control Devices, LLC (CDV) Expiration Date Cert Cat Device Type Type Classification Code Section NB Cert # M ST 14016 VIII Div. 1 Safety Relief Valve Nov 16, 2024 M 14038 SA Jun 3, 2023 VIII Div. 1 Safety Relief Valve 14049 SP M Mar 22, 2024 VIII Div. 1 Safety Relief Valve SF 14050 M VIII Div. 1 May 29, 2025 Safety Relief Valve SB 14061 M VIII Div. 1 Safety Relief Valve Mar 20, 2023 14072 M SW VIII Div. 1 Mar 20, 2023 Safety Relief Valve M SCB 14083 VIII Div. 1 Sep 22, 2023 Safety Relief Valve 14094 SN M Safety Relief Valve VIII Div. 1 Apr 7, 2025 Control Southern, Inc (CSM) location: Macon, GA, Seal Identification: CSM Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) NB Cert # Cert Cat Code Section Type Classification Expiration Date Device Type 01067 63B (.437", #7 orifice) A Safety Relief Valve VIII Div. 1 Aug 29, 2023 01089 A 81, 81P, 83, 86 Safety Relief Valve VIII Div. 1 Aug 29, 2023 81P (Liquids) 01102 A VIII Div. 1 Relief Valve Aug 29, 2023 243/249/443/449/546/843/849/943/5046/5049/8043/8049 A 01292 VIII Div. 1 Pilot Operated Pressure Relief Valve Aug 29, 2023 01304 A 253/259/453/459/853/859/953/959/5059/8053/8059 Aug 29, 2023 VIII Div. 1 Pilot Operated Pressure Relief Valve A 01315 263/269/463/469/566/863/869/963/969/5066/5069 Aug 29, 2023 Pilot Operated Pressure Relief Valve VIII Div. 1 453/459/853/859/953/959/5059 (Liquids) 01326 A Pilot Operated Pressure Relief Valve VIII Div. 1 Oct 19, 2023 01337 443/449/546/843/849/943/949/5046/5049(Liquids) A Pilot Operated Pressure Relief Valve Aug 29, 2023 VIII Div. 1 01348 A 463/469/566/863/869/963/969/5066/5069 (Liquids) Pilot Operated Pressure Relief Valve VIII Div. 1 Oct 19, 2023 JLT (Liquids) 15095 A Safety Relief Valve VIII Div. 1 Aug 29, 2023 JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 A Safety Relief Valve Aug 29, 2023 VIII Div. 1 900 Series, 7700, SNC A 15411 VIII Div. 1 Safety Relief Valve Aug 29, 2023 15499 A 900 Series (Liquid), 7700, SNC Relief Valve VIII Div. 1 Aug 29, 2023 Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # 910 to 919 36100 A Safety Relief Valve VIII Div. 1 Oct 19, 2023 A 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) 36111 VIII Div. 1 Aug 29, 2023 Relief Valve 36324 Kunkle 6000, 6252 Series A Safety Valve Oct 19, 2023 I & VIII Div. 1 Page 45 of 812 Effective Date: 2019-05-31

47 Table of Contents ControlWorx (GEG) location: Geismar, LA, UNITED STATES Seal Identification: GEG Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type Expiration Date NB Cert # Code Section Type Classification Cert Cat JOS-E-RL/JBS-E-RL (Restricted Lift version of cert 15208) A 01045 Safety Relief Valve Aug 17, 2023 VIII Div. 1 01056 A 63B (.312", #5 orifice) Aug 17, 2023 VIII Div. 1 Safety Relief Valve 63B (.437", #7 orifice) A 01067 Safety Relief Valve VIII Div. 1 Aug 17, 2023 A 81, 81P, 83, 86 01089 Aug 17, 2023 Safety Relief Valve VIII Div. 1 81P (Liquids) 01102 A Relief Valve VIII Div. 1 Aug 17, 2023 01292 243/249/443/449/546/843/849/943/5046/5049/8043/8049 A Dec 7, 2023 Pilot Operated Pressure Relief Valve VIII Div. 1 01304 A 253/259/453/459/853/859/953/959/5059/8053/8059 Aug 17, 2023 VIII Div. 1 Pilot Operated Pressure Relief Valve A 01315 263/269/463/469/566/863/869/963/969/5066/5069 Dec 7, 2023 Pilot Operated Pressure Relief Valve VIII Div. 1 453/459/853/859/953/959/5059 (Liquids) 01326 A Pilot Operated Pressure Relief Valve VIII Div. 1 Aug 17, 2023 01337 443/449/546/843/849/943/949/5046/5049(Liquids) A Pilot Operated Pressure Relief Valve Aug 17, 2023 VIII Div. 1 01348 A 463/469/566/863/869/963/969/5066/5069 (Liquids) Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 7, 2023 01382 JLT-JOS-RL/JLT-JBS-RL (Restricted Lift version of A Safety Relief Valve VIII Div. 1 Aug 17, 2023 JLT-JOS-RL/JLT-JBS-RL (Liquids) (Restricted lift version of 01393 A VIII Div. 1 Aug 17, 2023 Safety Relief Valve A 15095 JLT (Liquids) Safety Relief Valve VIII Div. 1 Aug 17, 2023 15208 A JOS-E/JBS-E/JOS-H-E 8400 AC/AB Aug 17, 2023 VIII Div. 1 Safety Relief Valve A 15411 900 Series, 7700, SNC Aug 17, 2023 Safety Relief Valve VIII Div. 1 900 Series (Liquid), 7700, SNC 15499 A Aug 17, 2023 VIII Div. 1 Relief Valve A 15512 JLT-JOS, JLT-JBS, 8500, ACL/ABL Aug 17, 2023 Safety Relief Valve VIII Div. 1 Devices designed by: Farris Engineering (TFO) NB Cert # Cert Cat Code Section Expiration Date Device Type Type Classification A 3800 57024 VIII Div. 1 Dec 19, 2020 Pilot Operated Pressure Relief Valve 57215 A 3800L, PCL, PCM pilots VIII Div. 1 Pilot Operated Pressure Relief Valve Nov 18, 2020 2700, 2700S, 3700, 3700S 57237 A Safety Relief Valve Feb 23, 2020 VIII Div. 1 2700L, 3700L (Liquids) A 57248 VIII Div. 1 Relief Valve Feb 23, 2020 ControlWorx (GRG) location: Sulphur, LA, UNITED STATES Acceptable Abbrev.: GRG Devices designed by: Farris Engineering (TFO) NB Cert # Code Section Type Classification Expiration Date Device Type Cert Cat 57057 2600 & 2600S A VIII Div. 1 Safety Relief Valve Mar 12, 2020 A 2600L (Liquids) 57068 VIII Div. 1 Feb 23, 2020 Relief Valve A 57237 2700, 2700S, 3700, 3700S Safety Relief Valve Feb 23, 2020 VIII Div. 1 2700L, 3700L (Liquids) 57248 A Relief Valve Feb 23, 2020 VIII Div. 1 Page 46 of 812 Effective Date: 2019-05-31

48 Table of Contents Corix Control Solutions, LP (BRB) location: Edmonton, CANADA Acceptable Abbrev.: Corix Control Solutions Devices designed by: Dresser, LLC (DRJ) Expiration Date Cert Cat Device Type Type Classification Code Section NB Cert # 1541, 1543, 1541-3, 1543-3 18032 A Safety Valve I & VIII Div. 1 Jul 25, 2022 A 18122 1811, 1511 I & VIII Div. 1 Dec 19, 2023 Safety Valve 1900D-2, 1900-30D-2 A 18144 VIII Div. 1 Safety Relief Valve Jul 26, 2022 A 1900E-2, 1900-30E-2 18166 Safety Relief Valve Jul 26, 2022 VIII Div. 1 18201 1900, 1900-30, 1900-35 A Jul 26, 2022 VIII Div. 1 Safety Relief Valve 3900 (39PV, 39MV pilots) 18447 A Pilot Operated Pressure Relief Valve Jan 17, 2023 VIII Div. 1 3900 (39PV, 39MV pilots, liquid) A 18458 Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 25, 2022 19000 Series A 18706 VIII Div. 1 Safety Relief Valve Jul 25, 2022 A 18717 19000 Series, Liquid Jul 25, 2022 Relief Valve VIII Div. 1 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A VIII Div. 1 Jul 25, 2022 Relief Valve A 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 VIII Div. 1 Jul 25, 2022 Relief Valve 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) VIII Div. 1 Jul 25, 2022 Relief Valve Crosby Valve, LLC (CVM) location: Mansfield, MA, UNITED STATES Acceptable Abbrev.: CVM Devices designed by: Crosby Valve, LLC (CVM) Device Type NB Cert # Expiration Date Code Section Type Classification Cert Cat M HA-HAA (Class 1) 15017 Mar 1, 2023 Safety Valve III HB (Class 1) 15028 M Safety Valve III Mar 1, 2023 15073 JB M Safety Relief Valve III & VIII Div.1 Oct 23, 2021 15129 M JMBL (Liquids) III & VIII Div.1 Feb 15, 2022 Relief Valve JMB-WR 15174 M Safety Relief Valve III & VIII Div.1 Jul 11, 2020 15196 M JO/HSU (Class 2 and 3) Jul 11, 2020 III & VIII Div.1 Safety Relief Valve JPV-A 15231 M VIII Div. 1 Safety Relief Valve Sep 23, 2021 JRAK-BS (Class 1, 2, 3 Liquids) M 15309 III & VIII Div.1 Relief Valve Aug 30, 2022 15310 JRL (Liquids) M III & VIII Div.1 Aug 30, 2022 Relief Valve JRU M 15332 Safety Relief Valve Mar 28, 2023 III & VIII Div.1 JO/JB-WR (Class 1, 2, 3 Liquids) M 15343 Mar 1, 2023 III Relief Valve 15398 M CV1B Vacuum Relief Valve III Dec 11, 2025 15422 M JMAK (Liquid Service) May 29, 2025 Relief Valve III NB, NC, ND VR (1") 15488 M Mar 1, 2023 III NB, NC, ND Vacuum Relief Valve M VR (3") 15556 III NB, NC, ND Aug 15, 2023 Vacuum Relief Valve 15578 M VR (2") Vacuum Relief Valve Mar 1, 2023 III Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type Cert Cat NB Cert # Type Classification Code Section Expiration Date 01089 M 81, 81P, 83, 86 III & VIII Div.1 Safety Relief Valve Oct 21, 2021 81P (Liquids) 01102 M Relief Valve III Aug 24, 2022 15006 M H Series (HCI, HSJ, HCA, HA, HB, HC, HCB, HCP, HJO, HN, I & VIII Div. 1 Safety Valve Jun 14, 2019 15039 M HE Safety Valve Oct 24, 2024 III NB, NC, ND 15095 JLT (Liquids) M Safety Relief Valve III & VIII Div.1 Jan 9, 2023 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB M Safety Relief Valve Jun 29, 2019 III & VIII Div.1 15411 M 900 Series, 7700, SNC III & VIII Div.1 Jun 7, 2023 Safety Relief Valve 15466 800 M Safety Relief Valve III & VIII Div.1 Dec 6, 2022 15499 M 900 Series (Liquid), 7700, SNC Relief Valve III & VIII Mar 17, 2023 BP M 15501 Relief Valve Nov 28, 2023 III & VIII Div.1 BP (Liquids) 15534 M Relief Valve Nov 28, 2023 VIII Div. 1 H Series (Restricted Lift version of Cert # 15006) 15567 M Safety Valve Apr 3, 2020 I Page 47 of 812 Effective Date: 2019-05-31

49 Table of Contents Curtiss Wright (Tianjin) Flow Control Co., Ltd. (FTC) location: Tianjin City, PEOPLES REP/CHINA Acceptable Abbrev.: Farris Engineering Devices designed by: Farris Engineering (TFO) Expiration Date Cert Cat Code Section Device Type Type Classification NB Cert # 3800 57024 M Pilot Operated Pressure Relief Valve VIII Div. 1 Sep 22, 2021 M 57035 3800FP VIII Div. 1 Sep 22, 2022 Pilot Operated Pressure Relief Valve 2600 & 2600S M 57057 VIII Div. 1 Safety Relief Valve Jun 21, 2024 M 2600L (Liquids) 57068 Relief Valve Sep 21, 2021 VIII Div. 1 57215 3800L, PCL, PCM pilots M VIII Div. 1 Sep 22, 2021 Pilot Operated Pressure Relief Valve 2700, 2700S, 3700, 3700S 57237 M Sep 22, 2021 VIII Div. 1 Safety Relief Valve 2700L, 3700L (Liquids) 57248 M Sep 23, 2021 Relief Valve VIII Div. 1 57260 2600L (Air & Steam) M Safety Relief Valve VIII Div. 1 Sep 21, 2021 Cv Techserv, Inc. (CVT) location: Hastings, MN, UNITED STATES Acceptable Abbrev.: CvT Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) NB Cert # Cert Cat Type Classification Code Section Device Type Expiration Date A 300,600 36076 I & VIII Div. 1 May 3, 2025 Safety Valve 36098 A 920, 921, 927, Agco A (High Temp. water) May 3, 2025 I Safety Valve A 36100 910 to 919 May 1, 2025 Safety Relief Valve VIII Div. 1 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) 36111 A Relief Valve VIII Div. 1 Aug 28, 2025 36267 Kunkle 264, 265, 266 & 267 A Safety Relief Valve Jun 26, 2025 VIII Div. 1 36278 A Kunkle 337 Nov 19, 2024 VIII Div. 1 Safety Relief Valve 36324 A Kunkle 6000, 6252 Series Safety Valve I & VIII Div. 1 Nov 19, 2024 Cyrus Shank Company (SHK) location: Cicero, IL, UNITED STATES Devices designed by: Cyrus Shank Company (SHK) NB Cert # Cert Cat Type Classification Expiration Date Code Section Device Type 804, 804QR Series 51017 M Safety Relief Valve VIII Div. 1 Sep 15, 2020 51028 M 805-T, 805QR, 815, 815QR Series VIII Div. 1 Safety Relief Valve Sep 26, 2021 51039 M 803 LQ 75 psig (liquids) VIII Div. 1 Mar 23, 2021 Relief Valve M 51040 900, 901, 902, 903 Dec 14, 2024 Safety Relief Valve VIII Div. 1 850, 851 51051 M VIII Div. 1 Safety Relief Valve Aug 24, 2019 M 51062 805 LQ 100 psig Aug 24, 2019 Relief Valve VIII Div. 1 803 LQ 100 psig liquid, 803 LQ QC 100 psig liquid 51073 M Relief Valve VIII Div. 1 Nov 2, 2019 51129 M 803, 803QC Nov 14, 2020 VIII Div. 1 Safety Relief Valve 51130 M 814 Safety Relief Valve VIII Div. 1 May 17, 2023 813 M 51141 Safety Relief Valve Sep 25, 2023 VIII Div. 1 801, 801D, 801QR, 801QRW 51152 M VIII Div. 1 Sep 21, 2023 Safety Relief Valve 51163 800, 800D, 800QR, 800QRW, 800QRM M Safety Relief Valve VIII Div. 1 Dec 14, 2024 51174 M 812 Jan 27, 2021 VIII Div. 1 Safety Relief Valve 51185 M CS 5602A, CS5602AQR Safety Relief Valve VIII Div. 1 Sep 27, 2022 CS 5602B, CS 5602BQR, CS 5602C, CS 5602CQR 51196 M Safety Relief Valve Sep 23, 2022 VIII Div. 1 51208 801DHC/801DHC QR M Jun 17, 2023 Safety Relief Valve VIII Div. 1 804R, 804R-QR 51219 M Safety Relief Valve Oct 12, 2024 VIII Div. 1 51220 M 805R, 805R-QR VIII Div. 1 Safety Relief Valve Oct 12, 2024 M 850DR, 851DR, 850AR, 851AR 51231 VIII Div. 1 Aug 13, 2019 Safety Relief Valve 51253 800OP, 800OPQR, 800D OP, 800SS OP, 800QRW OP M Safety Relief Valve Sep 21, 2023 VIII Div. 1 CS 5602R 51264 M Safety Relief Valve Sep 21, 2023 VIII Div. 1 Page 48 of 812 Effective Date: 2019-05-31

50 Table of Contents Dante Valve Company, Incorporated (DAN) location: Bellflower, CA, UNITED STATES Acceptable Abbrev.: DVC Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Expiration Date Cert Cat Code Section Device Type Type Classification NB Cert # 300,600 36076 A Safety Valve Oct 25, 2023 I & VIII Div. 1 910 to 919 A 36100 Safety Relief Valve Feb 10, 2024 VIII Div. 1 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) 36111 A Oct 18, 2023 Relief Valve VIII Div. 1 36267 Kunkle 264, 265, 266 & 267 A VIII Div. 1 Feb 10, 2024 Safety Relief Valve Kunkle 337 36278 A Oct 18, 2023 Safety Relief Valve VIII Div. 1 Kunkle 6000, 6252 Series 36324 A I & VIII Div. 1 Safety Valve May 17, 2024 DonadonSDD Srl (DON) location: Corbetta Milano, ITALY Acceptable Abbrev.: DonadonSDD Devices designed by: DonadonSDD Srl (DON) NB Cert # Cert Cat Type Classification Expiration Date Code Section Device Type M KRD 00516 VIII Div. 1 Mar 25, 2021 Rupture Disk Device 00527 SCD M Rupture Disk Device Mar 25, 2021 VIII Div. 1 SCR 00538 M Mar 25, 2021 Rupture Disk Device VIII Div. 1 Dowco Valve Company, Inc. (DWC) location: Hastings, MN, UNITED STATES Acceptable Abbrev.: Dowco Valve Devices designed by: Conbraco Industries, Incorporated (CNB) NB Cert # Code Section Type Classification Expiration Date Device Type Cert Cat A 19 Series 11282 I & VIII Div. 1 Nov 8, 2022 Safety Valve 11361 A 119 Series I & VIII Div. 1 Safety Valve Nov 21, 2022 500 Series 11462 A VIII Div. 1 Safety Valve Mar 20, 2020 500 Series (Liquids) A 11473 VIII Div. 1 Safety Relief Valve Nov 8, 2022 Devices designed by: Farris Engineering (TFO) Expiration Date Device Type Cert Cat Type Classification Code Section NB Cert # A 57024 3800 Nov 8, 2022 VIII Div. 1 Pilot Operated Pressure Relief Valve 57035 A 3800FP Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 9, 2023 2600 & 2600S 57057 A Safety Relief Valve VIII Div. 1 Nov 21, 2022 57068 A 2600L (Liquids) Relief Valve VIII Div. 1 Feb 9, 2023 3800L, PCL, PCM pilots 57215 A Pilot Operated Pressure Relief Valve Nov 8, 2022 VIII Div. 1 57237 A 2700, 2700S, 3700, 3700S Nov 8, 2022 Safety Relief Valve VIII Div. 1 2700L, 3700L (Liquids) 57248 A VIII Div. 1 Relief Valve Nov 8, 2022 2600L (Air & Steam) A 57260 VIII Div. 1 Safety Relief Valve Nov 8, 2022 57282 A 4200 / 4400 Safety Valve I & VIII Div. 1 Nov 21, 2022 Dowco Valve Company, Inc. Iowa Division (DIA) location: DeWitt, IA, UNITED STATES Acceptable Abbrev.: Dowco Devices designed by: Farris Engineering (TFO) NB Cert # Cert Cat Type Classification Code Section Device Type Expiration Date 2600 & 2600S 57057 A Safety Relief Valve VIII Div. 1 Jul 17, 2024 A 2600L (Liquids) 57068 VIII Div. 1 Jul 17, 2024 Relief Valve A 57237 2700, 2700S, 3700, 3700S Safety Relief Valve Jul 17, 2024 VIII Div. 1 2700L, 3700L (Liquids) 57248 A Relief Valve Jul 17, 2024 VIII Div. 1 Page 49 of 812 Effective Date: 2019-05-31

51 Table of Contents Dresser Al Rushaid Valve & Instrument Company, Ltd. (DAR) location: Jubail Industrial City, SAUDI ARABIA Acceptable Abbrev.: DARVICO Devices designed by: Dresser, LLC (DRJ) Expiration Date Cert Cat Device Type Type Classification Code Section NB Cert # 1900D-2, 1900-30D-2 18144 M Safety Relief Valve Mar 12, 2024 VIII Div. 1 1900E-2, 1900-30E-2 M 18166 Safety Relief Valve Mar 12, 2024 VIII Div. 1 1900, 1900-30, 1900-35 18201 M Mar 12, 2024 Safety Relief Valve VIII Div. 1 18447 3900 (39PV, 39MV pilots) M Mar 12, 2024 VIII Div. 1 Pilot Operated Pressure Relief Valve 3900 (39PV, 39MV pilots, liquid) 18458 M VIII Div. 1 Mar 13, 2024 Pilot Operated Pressure Relief Valve 19000 Series 18706 M Mar 12, 2024 Safety Relief Valve VIII Div. 1 19000 Series, Liquid 18717 M Relief Valve VIII Div. 1 Mar 12, 2024 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 M VIII Div. 1 Jun 26, 2024 Relief Valve M 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 VIII Div. 1 Mar 12, 2024 Relief Valve 18784 M 1900, 1900-30 1900-35 LA & DALA (Liquids) Mar 13, 2024 VIII Div. 1 Relief Valve M 18863 2900 (39PV & 39MV pilots) Feb 25, 2020 Pilot Operated Pressure Relief Valve VIII Div. 1 2900 (39PV & 39MV pilots - Liquid) 18874 M VIII Div. 1 May 20, 2025 Pilot Operated Pressure Relief Valve 19077 M 19110M & 19110H (Liquids) May 20, 2025 VIII Div. 1 Relief Valve Dresser de Mexico, S.A. de C.V. (DMX) location: Tlalnepantla, Estado de Mexico, MEXICO Acceptable Abbrev.: DMX Devices designed by: Dresser, LLC (DRJ) Expiration Date NB Cert # Cert Cat Type Classification Code Section Device Type 1900D-2, 1900-30D-2 A 18144 Safety Relief Valve Nov 14, 2024 VIII Div. 1 1900E-2, 1900-30E-2 18166 A VIII Div. 1 Safety Relief Valve Nov 14, 2024 19000 Series A 18706 VIII Div. 1 Safety Relief Valve Nov 19, 2024 18717 19000 Series, Liquid A VIII Div. 1 Nov 14, 2024 Relief Valve 1900D-2, 1900-30D-2 LA & DALA (Liquids) A 18751 Relief Valve VIII Div. 1 Dec 7, 2024 1900E-2, 1900-30E-2 LA & DALA (Liquids) A 18762 Nov 18, 2021 VIII Div. 1 Relief Valve A 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) Nov 18, 2021 Relief Valve VIII Div. 1 19110M & 19110H (Liquids) 19077 A Mar 10, 2021 VIII Div. 1 Relief Valve M 1900, 1900-30, 1900-35 18201 VIII Div. 1 Apr 11, 2025 Safety Relief Valve Dresser International LLC. (DRA) location: Johannesburg, Acceptable Abbrev.: DRA Devices designed by: Dresser, LLC (DRJ) NB Cert # Code Section Type Classification Expiration Date Device Type Cert Cat 1900D-2, 1900-30D-2 18144 A Safety Relief Valve VIII Div. 1 Jun 30, 2022 18166 A 1900E-2, 1900-30E-2 VIII Div. 1 Safety Relief Valve Jun 30, 2022 18201 A 1900, 1900-30, 1900-35 Safety Relief Valve VIII Div. 1 Jun 30, 2022 19000 Series 18706 A Safety Relief Valve Jun 30, 2022 VIII Div. 1 19000 Series, Liquid 18717 A VIII Div. 1 Jun 30, 2022 Relief Valve 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) A Relief Valve VIII Div. 1 Apr 3, 2023 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) A Apr 3, 2023 Relief Valve VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Apr 3, 2023 VIII Div. 1 19077 A 19110M & 19110H (Liquids) VIII Div. 1 Jun 30, 2022 Relief Valve Page 50 of 812 Effective Date: 2019-05-31

52 Table of Contents Dresser International, Inc. (DIU) location: Dubai, UNITED ARAB EMIRATES Acceptable Abbrev.: Dresser JA Devices designed by: Dresser, LLC (DRJ) Device Type Expiration Date NB Cert # Code Section Type Classification Cert Cat 1900D-2, 1900-30D-2 M 18144 Safety Relief Valve Oct 3, 2019 VIII Div. 1 18166 M 1900E-2, 1900-30E-2 Oct 2, 2019 VIII Div. 1 Safety Relief Valve 1900, 1900-30, 1900-35 M 18201 Safety Relief Valve VIII Div. 1 Oct 2, 2019 M 3900 (39PV, 39MV pilots) 18447 Dec 16, 2021 Pilot Operated Pressure Relief Valve VIII Div. 1 3900 (39PV, 39MV pilots, liquid) 18458 M Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 16, 2021 18706 19000 Series M Apr 24, 2020 Safety Relief Valve VIII Div. 1 18717 M 19000 Series, Liquid Oct 2, 2019 VIII Div. 1 Relief Valve M 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) Oct 1, 2019 Relief Valve VIII Div. 1 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 M Relief Valve VIII Div. 1 Oct 2, 2019 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) M Relief Valve Oct 3, 2019 VIII Div. 1 18863 M 2900 (39PV & 39MV pilots) Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 16, 2021 18874 2900 (39PV & 39MV pilots - Liquid) M Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 16, 2021 19110M & 19110H (Liquids) 19077 M VIII Div. 1 Dec 16, 2021 Relief Valve Dresser Italia SRL (GOI) location: Casavatore, Napoli, ITALY Seal Identification: NAP Devices designed by: Dresser, LLC (DRJ) Expiration Date Type Classification Cert Cat Device Type Code Section NB Cert # M 1900D-2, 1900-30D-2 18144 Nov 20, 2023 Safety Relief Valve VIII Div. 1 18166 1900E-2, 1900-30E-2 M Safety Relief Valve Nov 20, 2023 VIII Div. 1 18201 M 1900, 1900-30, 1900-35 VIII Div. 1 Mar 12, 2025 Safety Relief Valve 18447 M 3900 (39PV, 39MV pilots) Dec 9, 2021 Pilot Operated Pressure Relief Valve VIII Div. 1 M 3900 (39PV, 39MV pilots, liquid) 18458 VIII Div. 1 Dec 9, 2021 Pilot Operated Pressure Relief Valve M 18706 19000 Series Safety Relief Valve VIII Div. 1 Nov 20, 2023 18717 M 19000 Series, Liquid Relief Valve VIII Div. 1 Sep 26, 2023 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) M Relief Valve VIII Div. 1 Jan 16, 2021 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) M Relief Valve Jan 16, 2021 VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 M Relief Valve Jan 16, 2021 VIII Div. 1 M 2900 (39PV & 39MV pilots) 18863 VIII Div. 1 Dec 9, 2021 Pilot Operated Pressure Relief Valve M 18874 2900 (39PV & 39MV pilots - Liquid) Pilot Operated Pressure Relief Valve Dec 9, 2021 VIII Div. 1 19110M & 19110H (Liquids) 19077 M Relief Valve Nov 20, 2023 VIII Div. 1 Page 51 of 812 Effective Date: 2019-05-31

53 Table of Contents Dresser LLC (DDT) location: Deer Park, TX, UNITED STATES Acceptable Abbrev.: DDT Devices designed by: Dresser, LLC (DRJ) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 1541, 1543, 1541-3, 1543-3 18032 M Jan 14, 2020 I & VIII Div. 1 Safety Valve M 18100 1700 & 2700 Safety Valve Mar 17, 2020 I & VIII Div. 1 1700 & 2700 (Restricted Lift version of Cert. # 18100) 18111 M Apr 20, 2023 I & VIII Div. 1 Safety Valve 1811, 1511 18122 M Safety Valve I & VIII Div. 1 Mar 2, 2020 1900D-2, 1900-30D-2 18144 M VIII Div. 1 Jan 14, 2020 Safety Relief Valve 1900E-2, 1900-30E-2 18166 M Safety Relief Valve VIII Div. 1 Jan 14, 2020 M 18201 1900, 1900-30, 1900-35 Jan 14, 2020 Safety Relief Valve VIII Div. 1 1900, 1900-30, 1900-35 (R.L.) M 18223 Jan 11, 2025 Safety Relief Valve VIII Div. 1 18256 M 1900D/P, 1900-30D/P (Rest. Lift) Oct 27, 2022 I & VIII Div. 1 Safety Relief Valve M 18278 1900E/P, 1900-30E/P (Rest. Lift) Oct 27, 2022 Safety Relief Valve I & VIII Div. 1 1900/P, 1900-30/P 18290 M I & VIII Div. 1 Safety Relief Valve Feb 14, 2023 M 18379 1982 Feb 9, 2020 Safety Relief Valve VIII Div. 1 1982 LS, 820000LS 18380 M Relief Valve Mar 17, 2020 VIII Div. 1 18447 M 3900 (39PV, 39MV pilots) Pilot Operated Pressure Relief Valve VIII Div. 1 Jan 14, 2020 18458 3900 (39PV, 39MV pilots, liquid) M Pilot Operated Pressure Relief Valve VIII Div. 1 Jan 13, 2020 18706 19000 Series M Safety Relief Valve Jan 14, 2020 VIII Div. 1 19000 Series, Liquid 18717 M VIII Div. 1 Relief Valve Mar 15, 2020 18751 M 1900D-2, 1900-30D-2 LA & DALA (Liquids) VIII Div. 1 Relief Valve Mar 3, 2020 18762 M 1900E-2, 1900-30E-2 LA & DALA (Liquids) Mar 17, 2020 VIII Div. 1 Relief Valve M 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) Jan 13, 2020 Relief Valve VIII Div. 1 2900 (39PV & 39MV pilots) 18863 M Pilot Operated Pressure Relief Valve VIII Div. 1 Jan 14, 2020 18874 2900 (39PV & 39MV pilots - Liquid) M Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 11, 2020 18964 2900 POSRV (39 PV, 39 MV Pilots) M Pilot Operated Pressure Relief Valve Jan 11, 2025 I 18997 M 1900-UM VIII Div. 1 Dec 4, 2022 Safety Relief Valve 19000 1900-UM (Liquids) M Safety Relief Valve VIII Div. 1 Oct 7, 2022 1900-UM-D 19011 M VIII Div. 1 Dec 4, 2022 Safety Relief Valve 19022 1900 UM-D (Liquids) M Safety Relief Valve VIII Div. 1 Apr 19, 2023 19033 M 1900-UM-E Dec 4, 2022 VIII Div. 1 Safety Relief Valve 19044 M 1900-UM-E (Liquids) Safety Relief Valve VIII Div. 1 Apr 19, 2023 19110M & 19110H (Liquids) 19077 M Relief Valve Aug 12, 2020 VIII Div. 1 Dresser Machinery (Suzhou) Co., Ltd. (DMS) location: Suzhou Industrial Park, Suzhou, Jiangsu, PEOPLES REP/CHINA Seal Identification: DMS Devices designed by: Dresser Machinery (Suzhou) Co., Ltd. (DMS) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date M 11000 E Liquid 00864 VIII Div. 1 Aug 25, 2022 Safety Relief Valve M 00875 11000 E gas Safety Relief Valve Aug 25, 2022 VIII Div. 1 11000 D gas 00886 M Safety Relief Valve Aug 25, 2022 VIII Div. 1 Page 52 of 812 Effective Date: 2019-05-31

54 Table of Contents Dresser Machinery (Suzhou) Co., Ltd. (DMS) location: (continued) Suzhou Industrial Park, Suzhou, Jiangsu, PEOPLES REP/CHINA Seal Identification: DMS Devices designed by: Dresser, LLC (DRJ) Device Type Expiration Date NB Cert # Type Classification Code Section Cert Cat 1541, 1543, 1541-3, 1543-3 M 18032 Safety Valve Sep 9, 2019 I & VIII Div. 1 1700 & 2700 (4" #7 & Ovrszd Q) 18087 M Safety Valve Jul 23, 2021 I & VIII Div. 1 M 18098 1700 & 2700 (4" #7 & Ovrszd Q) (Restricted Lift version of Cert. Safety Valve Jul 23, 2021 I & VIII Div. 1 1700 & 2700 M 18100 Safety Valve I & VIII Div. 1 Jun 14, 2023 M 1700 & 2700 (Restricted Lift version of Cert. # 18100) 18111 Dec 9, 2021 Safety Valve I & VIII Div. 1 1811, 1511 18122 M Jun 15, 2023 I & VIII Div. 1 Safety Valve M 18144 1900D-2, 1900-30D-2 Jun 15, 2023 Safety Relief Valve VIII Div. 1 18166 1900E-2, 1900-30E-2 M Safety Relief Valve VIII Div. 1 Jun 15, 2023 18201 1900, 1900-30, 1900-35 M Safety Relief Valve Jun 15, 2023 VIII Div. 1 M 1900, 1900-30, 1900-35 (R.L.) 18223 Nov 18, 2020 VIII Div. 1 Safety Relief Valve 1900D/P, 1900-30D/P (Rest. Lift) 18256 M Aug 25, 2022 I & VIII Div. 1 Safety Relief Valve M 18278 1900E/P, 1900-30E/P (Rest. Lift) Aug 25, 2022 Safety Relief Valve I & VIII Div. 1 18290 1900/P, 1900-30/P M Safety Relief Valve I & VIII Div. 1 Aug 25, 2022 18379 1982 M Safety Relief Valve VIII Div. 1 Sep 9, 2019 18380 M 1982 LS, 820000LS VIII Div. 1 Sep 9, 2019 Relief Valve 3900 (39PV, 39MV pilots) 18447 M Pilot Operated Pressure Relief Valve VIII Div. 1 May 13, 2021 18458 M 3900 (39PV, 39MV pilots, liquid) May 11, 2021 VIII Div. 1 Pilot Operated Pressure Relief Valve 19000 Series 18706 M Safety Relief Valve VIII Div. 1 Jun 15, 2023 19000 Series, Liquid M 18717 VIII Div. 1 Relief Valve Jun 15, 2023 18751 M 1900D-2, 1900-30D-2 LA & DALA (Liquids) Jun 15, 2023 VIII Div. 1 Relief Valve M 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) Jun 15, 2023 Relief Valve VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 M VIII Div. 1 Relief Valve Jul 11, 2023 M 18863 2900 (39PV & 39MV pilots) Nov 18, 2020 Pilot Operated Pressure Relief Valve VIII Div. 1 18874 2900 (39PV & 39MV pilots - Liquid) M Pilot Operated Pressure Relief Valve Nov 18, 2020 VIII Div. 1 18964 M 2900 POSRV (39 PV, 39 MV Pilots) Pilot Operated Pressure Relief Valve I Nov 18, 2020 18997 1900-UM M Safety Relief Valve VIII Div. 1 Aug 25, 2022 19000 1900-UM (Liquids) M Safety Relief Valve May 12, 2023 VIII Div. 1 1900-UM-D 19011 M Safety Relief Valve May 12, 2023 VIII Div. 1 1900 UM-D (Liquids) M 19022 VIII Div. 1 Safety Relief Valve May 10, 2023 19033 M 1900-UM-E Safety Relief Valve VIII Div. 1 May 12, 2023 1900-UM-E (Liquids) 19044 M May 10, 2023 VIII Div. 1 Safety Relief Valve 19077 M 19110M & 19110H (Liquids) Aug 25, 2022 Relief Valve VIII Div. 1 Devices designed by: Dresser Machinery (Suzhou) Co., Ltd. (DMS) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date M 11000 E Liquid 00864 VIII Div. 1 Aug 25, 2022 Safety Relief Valve M 00875 11000 E gas Safety Relief Valve Aug 25, 2022 VIII Div. 1 11000 D gas 00886 M Safety Relief Valve Aug 25, 2022 VIII Div. 1 Page 53 of 812 Effective Date: 2019-05-31

55 Table of Contents Dresser Machinery (Suzhou) Co., Ltd. (DMS) location: (continued) Suzhou Industrial Park, Suzhou, Jiangsu, PEOPLES REP/CHINA Seal Identification: DMS Devices designed by: Dresser, LLC (DRJ) Expiration Date Cert Cat Type Classification Device Type Code Section NB Cert # 1541, 1543, 1541-3, 1543-3 M 18032 Safety Valve Sep 9, 2019 I & VIII Div. 1 M 18087 1700 & 2700 (4" #7 & Ovrszd Q) Safety Valve Jul 23, 2021 I & VIII Div. 1 18098 1700 & 2700 (4" #7 & Ovrszd Q) (Restricted Lift version of Cert. M Jul 23, 2021 I & VIII Div. 1 Safety Valve 18100 1700 & 2700 M Safety Valve I & VIII Div. 1 Jun 14, 2023 1700 & 2700 (Restricted Lift version of Cert. # 18100) 18111 M I & VIII Div. 1 Safety Valve Dec 9, 2021 1811, 1511 18122 M Jun 15, 2023 Safety Valve I & VIII Div. 1 18144 1900D-2, 1900-30D-2 M Safety Relief Valve Jun 15, 2023 VIII Div. 1 18166 M 1900E-2, 1900-30E-2 VIII Div. 1 Jun 15, 2023 Safety Relief Valve M 18201 1900, 1900-30, 1900-35 Jun 15, 2023 Safety Relief Valve VIII Div. 1 1900, 1900-30, 1900-35 (R.L.) 18223 M VIII Div. 1 Safety Relief Valve Nov 18, 2020 M 18256 1900D/P, 1900-30D/P (Rest. Lift) Aug 25, 2022 Safety Relief Valve I & VIII Div. 1 1900E/P, 1900-30E/P (Rest. Lift) M 18278 Safety Relief Valve I & VIII Div. 1 Aug 25, 2022 18290 M 1900/P, 1900-30/P Safety Relief Valve I & VIII Div. 1 Aug 25, 2022 18379 1982 M Safety Relief Valve VIII Div. 1 Sep 9, 2019 1982 LS, 820000LS 18380 M VIII Div. 1 Sep 9, 2019 Relief Valve 3900 (39PV, 39MV pilots) 18447 M Pilot Operated Pressure Relief Valve VIII Div. 1 May 13, 2021 18458 M 3900 (39PV, 39MV pilots, liquid) VIII Div. 1 May 11, 2021 Pilot Operated Pressure Relief Valve M 18706 19000 Series Jun 15, 2023 Safety Relief Valve VIII Div. 1 19000 Series, Liquid 18717 M VIII Div. 1 Relief Valve Jun 15, 2023 M 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) Jun 15, 2023 Relief Valve VIII Div. 1 1900E-2, 1900-30E-2 LA & DALA (Liquids) M 18762 Relief Valve VIII Div. 1 Jun 15, 2023 18784 M 1900, 1900-30 1900-35 LA & DALA (Liquids) Relief Valve VIII Div. 1 Jul 11, 2023 18863 2900 (39PV & 39MV pilots) M Pilot Operated Pressure Relief Valve VIII Div. 1 Nov 18, 2020 2900 (39PV & 39MV pilots - Liquid) 18874 M VIII Div. 1 Nov 18, 2020 Pilot Operated Pressure Relief Valve 2900 POSRV (39 PV, 39 MV Pilots) 18964 M Pilot Operated Pressure Relief Valve I Nov 18, 2020 18997 M 1900-UM Safety Relief Valve VIII Div. 1 Aug 25, 2022 19000 1900-UM (Liquids) M Safety Relief Valve VIII Div. 1 May 12, 2023 19011 1900-UM-D M Safety Relief Valve May 12, 2023 VIII Div. 1 1900 UM-D (Liquids) 19022 M Safety Relief Valve May 10, 2023 VIII Div. 1 M 1900-UM-E 19033 VIII Div. 1 May 12, 2023 Safety Relief Valve M 19044 1900-UM-E (Liquids) Safety Relief Valve May 10, 2023 VIII Div. 1 19110M & 19110H (Liquids) 19077 M Relief Valve Aug 25, 2022 VIII Div. 1 Page 54 of 812 Effective Date: 2019-05-31

56 Table of Contents Dresser, LLC (DRJ) location: Jacksonville, FL, UNITED STATES Acceptable Abbrev.: JAX Devices designed by: Dresser, LLC (DRJ) Device Type Expiration Date NB Cert # Code Section Type Classification Cert Cat 1541, 1543, 1541-3, 1543-3 M 18032 Safety Valve May 25, 2022 I & VIII Div. 1 1700 & 2700 (4" #7 & Ovrszd Q) 18087 M Safety Valve Nov 11, 2022 I & VIII Div. 1 M 18098 1700 & 2700 (4" #7 & Ovrszd Q) (Restricted Lift version of Cert. Safety Valve Nov 30, 2022 I & VIII Div. 1 1700 & 2700 M 18100 Safety Valve I & VIII Div. 1 Nov 2, 2024 M 1700 & 2700 (Restricted Lift version of Cert. # 18100) 18111 Apr 26, 2022 Safety Valve I & VIII Div. 1 1811, 1511 18122 M Mar 24, 2022 I & VIII Div. 1 Safety Valve M 18144 1900D-2, 1900-30D-2 Dec 22, 2021 Safety Relief Valve III & VIII Div.1 18166 1900E-2, 1900-30E-2 M Safety Relief Valve Nov 4, 2021 III & VIII Div.1 18201 M 1900, 1900-30, 1900-35 III & VIII Div.1 Dec 22, 2021 Safety Relief Valve 18223 M 1900, 1900-30, 1900-35 (R.L.) Sep 25, 2023 VIII Div. 1 Safety Relief Valve M 18256 1900D/P, 1900-30D/P (Rest. Lift) Sep 29, 2022 Safety Relief Valve I, III, & VIII Div. 1 1900E/P, 1900-30E/P (Rest. Lift) 18278 M Safety Relief Valve I & VIII Div. 1 Apr 25, 2022 18290 1900/P, 1900-30/P M Safety Relief Valve Apr 25, 2022 I & VIII Div. 1 18379 M 1982 Mar 23, 2022 VIII Div. 1 Safety Relief Valve 18380 M 1982 LS, 820000LS Relief Valve VIII Div. 1 May 25, 2022 1990 - 3999 LS & DL (Liquids) 18403 M Relief Valve III Feb 14, 2021 18414 3700-RT M Safety Valve Dec 15, 2022 III NB, NC, ND 3900 (39PV, 39MV pilots) 18447 M VIII Div. 1 Pilot Operated Pressure Relief Valve Mar 23, 2022 18458 M 3900 (39PV, 39MV pilots, liquid) III & VIII Div.1 Pilot Operated Pressure Relief Valve Jan 27, 2022 18469 M 13900 TRH Oct 18, 2024 VIII Div. 1 Pilot Operated Pressure Relief Valve M 18470 13900 TRH 20" Oct 18, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 19000 Series 18706 M Safety Relief Valve VIII Div. 1 Nov 1, 2024 18717 19000 Series, Liquid M Relief Valve III & VIII Div.1 Nov 2, 2024 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) M Relief Valve Nov 4, 2021 I, III, & VIII Div. 1 18762 M 1900E-2, 1900-30E-2 LA & DALA (Liquids) I, III, & VIII Div. 1 Nov 4, 2021 Relief Valve 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) M Relief Valve I, III, & VIII Div. 1 Nov 4, 2021 2900 (39PV & 39MV pilots) 18863 M VIII Div. 1 Apr 25, 2022 Pilot Operated Pressure Relief Valve M 18874 2900 (39PV & 39MV pilots - Liquid) Pilot Operated Pressure Relief Valve VIII Div. 1 Apr 25, 2022 18885 M 4900 (49PV & 49MV pilots) Mar 23, 2022 VIII Div. 1 Pilot Operated Pressure Relief Valve 18964 M 2900 POSRV (39 PV, 39 MV Pilots) Pilot Operated Pressure Relief Valve I May 25, 2022 1900-UM 18997 M Safety Relief Valve Jan 27, 2022 VIII Div. 1 19000 1900-UM (Liquids) M May 25, 2022 Safety Relief Valve VIII Div. 1 1900-UM-D 19011 M Safety Relief Valve Jan 27, 2022 VIII Div. 1 19022 M 1900 UM-D (Liquids) VIII Div. 1 Safety Relief Valve Dec 22, 2021 M 1900-UM-E 19033 VIII Div. 1 Jan 27, 2022 Safety Relief Valve 19044 1900-UM-E (Liquids) M Safety Relief Valve May 29, 2022 VIII Div. 1 19110M & 19110H (Liquids) 19077 M Relief Valve Nov 4, 2021 III & VIII Div.1 Page 55 of 812 Effective Date: 2019-05-31

57 Table of Contents DS Controls (DSC) location: Velikiy Novgorod, RUSSIAN FEDERATION Acceptable Abbrev.: DSC Devices designed by: Dresser, LLC (DRJ) Device Type Expiration Date NB Cert # Code Section Type Classification Cert Cat A 18144 1900D-2, 1900-30D-2 Safety Relief Valve VIII Div. 1 Aug 24, 2021 1900E-2, 1900-30E-2 A 18166 Safety Relief Valve Aug 24, 2021 VIII Div. 1 1900, 1900-30, 1900-35 18201 A VIII Div. 1 Aug 24, 2021 Safety Relief Valve 18447 3900 (39PV, 39MV pilots) A Pilot Operated Pressure Relief Valve Dec 12, 2022 VIII Div. 1 18458 A 3900 (39PV, 39MV pilots, liquid) VIII Div. 1 Dec 12, 2022 Pilot Operated Pressure Relief Valve 18706 A 19000 Series Safety Relief Valve Aug 24, 2021 VIII Div. 1 18717 19000 Series, Liquid A Relief Valve Dec 12, 2022 VIII Div. 1 18751 A 1900D-2, 1900-30D-2 LA & DALA (Liquids) Aug 24, 2021 VIII Div. 1 Relief Valve A 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 VIII Div. 1 Dec 12, 2022 Relief Valve 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A VIII Div. 1 Relief Valve Dec 12, 2022 19110M & 19110H (Liquids) A 19077 VIII Div. 1 Relief Valve Dec 12, 2022 Elfab Limited (ELF) location: North Shields, Tyne & Wear, UNITED KINGDOM Acceptable Abbrev.: ELFAB Devices designed by: Elfab Limited (ELF) Device Type Expiration Date Cert Cat Type Classification Code Section NB Cert # 88062 DSC-FCD M Rupture Disk Device Apr 25, 2024 VIII Div. 1 88118 OPR M Nov 12, 2019 Rupture Disk Device VIII Div. 1 DSC-AGS 88129 M VIII Div. 1 Rupture Disk Device Aug 6, 2025 88141 M DSC-OPS VIII Div. 1 Rupture Disk Device Mar 29, 2025 M DSC-CDD 88152 VIII Div. 1 Oct 31, 2023 Rupture Disk Device M 88185 DSC-OPR Rupture Disk Device Jan 28, 2020 VIII Div. 1 DSC-SGD 88196 M VIII Div. 1 Apr 25, 2024 Rupture Disk Device FCD (Flat or Domed Composite Discs) 88208 M Rupture Disk Device Jan 28, 2020 VIII Div. 1 Page 56 of 812 Effective Date: 2019-05-31

58 Table of Contents Emerson Automation Solutions Final Control (Shanghai) Co., Ltd. (SAG) location: Shanghai, PEOPLES REP/CHINA Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Cert Cat Type Classification NB Cert # Expiration Date Code Section Device Type JOS-E-RL/JBS-E-RL (Restricted Lift version of cert 15208) 01045 M Jul 24, 2023 VIII Div. 1 Safety Relief Valve 81, 81P, 83, 86 01089 M Safety Relief Valve Sep 18, 2024 VIII Div. 1 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 M Pilot Operated Pressure Relief Valve Sep 18, 2024 VIII Div. 1 253/259/453/459/853/859/953/959/5059/8053/8059 01304 M Sep 18, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 263/269/463/469/566/863/869/963/969/5066/5069 M 01315 VIII Div. 1 Sep 18, 2024 Pilot Operated Pressure Relief Valve M 01326 453/459/853/859/953/959/5059 (Liquids) Sep 18, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 443/449/546/843/849/943/949/5046/5049(Liquids) 01337 M Pilot Operated Pressure Relief Valve VIII Div. 1 Sep 18, 2024 01348 463/469/566/863/869/963/969/5066/5069 (Liquids) M Pilot Operated Pressure Relief Valve VIII Div. 1 Sep 18, 2024 01382 JLT-JOS-RL/JLT-JBS-RL (Restricted Lift version of M Safety Relief Valve VIII Div. 1 Jan 17, 2023 01393 JLT-JOS-RL/JLT-JBS-RL (Liquids) (Restricted lift version of M Safety Relief Valve VIII Div. 1 Jan 17, 2023 M 15006 H Series (HCI, HSJ, HCA, HA, HB, HC, HCB, HCP, HJO, HN, Oct 10, 2020 I & VIII Div. 1 Safety Valve HE 15039 M Safety Valve Aug 31, 2020 I JLT (Liquids) 15095 M Feb 14, 2023 VIII Div. 1 Safety Relief Valve 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB M Safety Relief Valve VIII Div. 1 Aug 14, 2023 15411 M 900 Series, 7700, SNC VIII Div. 1 Feb 14, 2023 Safety Relief Valve 800 15466 M Safety Relief Valve VIII Div. 1 Feb 14, 2023 900 Series (Liquid), 7700, SNC 15499 M VIII Div. 1 Feb 14, 2023 Relief Valve M 15501 BP Relief Valve VIII Div. 1 Feb 14, 2023 15512 JLT-JOS, JLT-JBS, 8500, ACL/ABL M VIII Div. 1 Feb 14, 2023 Safety Relief Valve BP (Liquids) M 15534 Relief Valve VIII Div. 1 Feb 14, 2023 H Series (Restricted Lift version of Cert # 15006) M 15567 Mar 4, 2021 I Safety Valve 15589 M HL, HSL Oct 9, 2020 Safety Valve I & VIII Div. 1 36458 5200 Series (Water K = 0.674) M Pilot Operated Pressure Relief Valve Mar 4, 2021 I & VIII Div. 1 Emerson Automation Solutions Final Control Australia Pty Ltd (PFP) location: Wangara, Perth, Seal Identification: PVC WA Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Cert Cat Code Section Device Type NB Cert # Expiration Date Type Classification 01089 A 81, 81P, 83, 86 VIII Div. 1 Safety Relief Valve May 11, 2021 01292 A 243/249/443/449/546/843/849/943/5046/5049/8043/8049 VIII Div. 1 May 11, 2021 Pilot Operated Pressure Relief Valve 253/259/453/459/853/859/953/959/5059/8053/8059 01304 A Pilot Operated Pressure Relief Valve May 11, 2021 VIII Div. 1 01315 A 263/269/463/469/566/863/869/963/969/5066/5069 VIII Div. 1 Pilot Operated Pressure Relief Valve May 11, 2021 01326 A 453/459/853/859/953/959/5059 (Liquids) Pilot Operated Pressure Relief Valve VIII Div. 1 Sep 13, 2024 443/449/546/843/849/943/949/5046/5049(Liquids) 01337 A Pilot Operated Pressure Relief Valve May 12, 2021 VIII Div. 1 463/469/566/863/869/963/969/5066/5069 (Liquids) 01348 A VIII Div. 1 May 12, 2021 Pilot Operated Pressure Relief Valve A 15095 JLT (Liquids) Safety Relief Valve VIII Div. 1 May 12, 2021 15208 A JOS-E/JBS-E/JOS-H-E 8400 AC/AB Safety Relief Valve VIII Div. 1 Sep 12, 2024 900 Series, 7700, SNC A 15411 Safety Relief Valve May 11, 2021 VIII Div. 1 900 Series (Liquid), 7700, SNC 15499 A Relief Valve May 12, 2021 VIII Div. 1 JLT-JOS, JLT-JBS, 8500, ACL/ABL 15512 A Safety Relief Valve May 11, 2021 VIII Div. 1 Page 57 of 812 Effective Date: 2019-05-31

59 Table of Contents EMERSON AUTOMATION SOLUTIONS FINAL CONTROL SINGAPORE PTE LTD (TSG) location: Singapore, SINGAPORE Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Cert Cat Type Classification NB Cert # Expiration Date Code Section Device Type 81, 81P, 83, 86 01089 A Oct 12, 2023 VIII Div. 1 Safety Relief Valve 81P (Liquids) 01102 A Relief Valve Oct 12, 2023 VIII Div. 1 JLT (Liquids) 15095 A Safety Relief Valve Oct 17, 2023 VIII Div. 1 JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 A Oct 11, 2023 VIII Div. 1 Safety Relief Valve 15411 A 900 Series, 7700, SNC Oct 11, 2023 VIII Div. 1 Safety Relief Valve A 15499 900 Series (Liquid), 7700, SNC Oct 12, 2023 VIII Div. 1 Relief Valve Emerson Automation Solutions Final Control UK, Ltd. (BRK) location: Worsley, Manchester, Lancashire, UNITED KINGDOM Devices designed by: Emerson Automation Solutions Final Control UK, Ltd. (BRK) Device Type NB Cert # Cert Cat Type Classification Code Section Expiration Date 06006 B Series M Safety Valve Dec 15, 2019 VIII Div. 1 06017 M C Series VIII Div. 1 Nov 18, 2019 Relief Valve 06028 M WB 100/200 (Liquids) Dec 15, 2019 VIII Div. 1 Relief Valve M 06039 WB 300/400 Sep 19, 2024 Safety Relief Valve VIII Div. 1 746-1, JCE/1 06062 M VIII Div. 1 Safety Relief Valve Dec 13, 2022 M 06073 746-3, JCE/3 (Liquids) Dec 12, 2022 Relief Valve VIII Div. 1 06084 WB 300B M Safety Relief Valve VIII Div. 1 Dec 19, 2023 06095 M 20R (Liquid) (4, 5, 8, 9 pilots) 4FR3, 4FR9, 8FR3, 8FR9 Dec 19, 2023 VIII Div. 1 Pilot Operated Pressure Relief Valve 06107 M 20F (Liquid) (B, C, 4, 5, 8, 9 pilots) 4FF3, 4FF9, 8FF3, 8FF9 Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 19, 2023 20F(2,4,5,8,9 pilots) 2FF3, 2FF9, 4FF3, 4FF9, 8FF3, 8FF9 M 06118 Pilot Operated Pressure Relief Valve Dec 19, 2023 VIII Div. 1 20R (2,4,5,8,9 pilots) 2FR3, 2FR9, 4FR3, 4FR9, 8FR3, 8FR9 06129 M VIII Div. 1 Dec 15, 2023 Pilot Operated Pressure Relief Valve D Series, 716H7 06130 M Safety Relief Valve Dec 7, 2020 VIII Div. 1 06141 M D Series (Liquids), 716H7 Dec 7, 2020 VIII Div. 1 Safety Relief Valve M 06185 776 Feb 5, 2020 Safety Relief Valve VIII Div. 1 RBH 81010 M Jul 7, 2021 VIII Div. 1 Rupture Disk Device M 81122 SANIVENT Oct 27, 2021 Rupture Disk Device VIII Div. 1 LRF 81133 M Rupture Disk Device Jul 9, 2021 VIII Div. 1 Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Expiration Date Cert Cat Code Section NB Cert # Type Classification Device Type 01089 M 81, 81P, 83, 86 Safety Relief Valve VIII Div. 1 Aug 19, 2020 01102 81P (Liquids) M Relief Valve Oct 31, 2020 VIII Div. 1 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 M VIII Div. 1 Aug 19, 2020 Pilot Operated Pressure Relief Valve 01304 253/259/453/459/853/859/953/959/5059/8053/8059 M Pilot Operated Pressure Relief Valve VIII Div. 1 Aug 19, 2020 01315 M 263/269/463/469/566/863/869/963/969/5066/5069 Aug 19, 2020 VIII Div. 1 Pilot Operated Pressure Relief Valve 01326 M 453/459/853/859/953/959/5059 (Liquids) Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 22, 2020 443/449/546/843/849/943/949/5046/5049(Liquids) 01337 M Pilot Operated Pressure Relief Valve Jul 22, 2020 VIII Div. 1 01348 463/469/566/863/869/963/969/5066/5069 (Liquids) M Jul 22, 2020 Pilot Operated Pressure Relief Valve VIII Div. 1 JLT (Liquids) 15095 M Safety Relief Valve Aug 19, 2020 VIII Div. 1 15208 M JOS-E/JBS-E/JOS-H-E 8400 AC/AB VIII Div. 1 Safety Relief Valve Aug 22, 2020 M 900 Series, 7700, SNC 15411 VIII Div. 3 Aug 19, 2020 Safety Relief Valve 15499 900 Series (Liquid), 7700, SNC M Relief Valve Aug 19, 2020 VIII Div. 1 JLT-JOS, JLT-JBS, 8500, ACL/ABL 15512 M Safety Relief Valve Aug 19, 2020 VIII Div. 1 Page 58 of 812 Effective Date: 2019-05-31

60 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) location: Stafford, TX, UNITED STATES Acceptable Abbrev.: EMRT Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat JOS-E-RL/JBS-E-RL (Restricted Lift version of cert 15208) M 01045 Safety Relief Valve Sep 23, 2021 VIII Div. 1 63B (.312", #5 orifice) 01056 M Safety Relief Valve Sep 13, 2022 VIII Div. 1 M 01067 63B (.437", #7 orifice) Safety Relief Valve Sep 13, 2022 VIII Div. 1 81, 81P, 83, 86 M 01089 Nov 9, 2022 VIII Div. 1 Safety Relief Valve 81P (Liquids) 01102 M I & VIII Div. 1 Relief Valve Sep 20, 2022 M 01113 83F Safety Relief Valve VIII Div. 1 Sep 13, 2022 91/94 01124 M VIII Div. 1 Nov 9, 2022 Pilot Operated Pressure Relief Valve 01135 M 93 Sep 13, 2022 Pilot Operated Pressure Relief Valve VIII Div. 1 01146 95 M Pilot Operated Pressure Relief Valve Sep 13, 2022 VIII Div. 1 01247 M 727 VIII Div. 1 Dec 18, 2022 Pilot Operated Pressure Relief Valve 01258 M 9340/9390 VIII Div. 1 Sep 14, 2022 Pilot Operated Pressure Relief Valve M 01292 243/249/443/449/546/843/849/943/5046/5049/8043/8049 Nov 20, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 253/259/453/459/853/859/953/959/5059/8053/8059 01304 M VIII Div. 1 Pilot Operated Pressure Relief Valve Nov 6, 2024 M 01315 263/269/463/469/566/863/869/963/969/5066/5069 Nov 20, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 453/459/853/859/953/959/5059 (Liquids) 01326 M Pilot Operated Pressure Relief Valve VIII Div. 1 Nov 6, 2024 01337 443/449/546/843/849/943/949/5046/5049(Liquids) M Pilot Operated Pressure Relief Valve VIII Div. 1 Nov 6, 2024 01348 M 463/469/566/863/869/963/969/5066/5069 (Liquids) VIII Div. 1 Dec 4, 2024 Pilot Operated Pressure Relief Valve JLT-JOS-RL/JLT-JBS-RL (Restricted Lift version of 01382 M Safety Relief Valve VIII Div. 1 Feb 3, 2022 01393 M JLT-JOS-RL/JLT-JBS-RL (Liquids) (Restricted lift version of Nov 24, 2021 I & VIII Div. 1 Safety Relief Valve 243/249/443/449/843/849-RL (Restriced Lift version of Cert No. 01562 M Pilot Operated Pressure Relief Valve VIII Div. 1 Jun 13, 2023 01573 M 443/449/843/849-RL (Restricted Lift version of Cert No. 01337) - VIII Div. 1 Pilot Operated Pressure Relief Valve Jun 13, 2023 15006 M H Series (HCI, HSJ, HCA, HA, HB, HC, HCB, HCP, HJO, HN, I & VIII Div. 1 Jun 7, 2021 Safety Valve M 15039 HE Jun 14, 2024 Safety Valve I JLT (Liquids) 15095 M I & VIII Div. 1 Safety Relief Valve Oct 22, 2019 M 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB Oct 22, 2019 Safety Relief Valve VIII Div. 1 JQU - 1.5 (with breaking pin) 15275 M Safety Relief Valve VIII Div. 1 Jun 21, 2024 15286 M JQU - 1.5 (without breaking pin) Apr 18, 2024 VIII Div. 1 Safety Relief Valve 15297 M JQU - 4 (with breaking pin) Safety Relief Valve VIII Div. 1 Jun 21, 2024 PVR-3 M 15354 Safety Relief Valve Aug 29, 2023 VIII Div. 1 PVR-4 15365 M VIII Div. 1 Aug 29, 2023 Safety Relief Valve 15411 900 Series, 7700, SNC M Safety Relief Valve VIII Div. 1 Oct 22, 2019 15466 M 800 Oct 23, 2019 VIII Div. 1 Safety Relief Valve 15499 M 900 Series (Liquid), 7700, SNC Relief Valve I & VIII Div. 1 Oct 22, 2019 BP 15501 M Relief Valve Oct 22, 2019 VIII Div. 1 15512 JLT-JOS, JLT-JBS, 8500, ACL/ABL M Oct 22, 2019 Safety Relief Valve VIII Div. 1 BP (Liquids) 15534 M Relief Valve Oct 22, 2019 I & VIII Div. 1 15567 M H Series (Restricted Lift version of Cert # 15006) I Safety Valve Sep 2, 2023 M HL, HSL 15589 I & VIII Div. 1 Aug 22, 2023 Safety Valve 36368 LCP M Pilot Operated Pressure Relief Valve Jul 28, 2020 VIII Div. 1 5200 Series (Water K = 0.674) 36458 M Pilot Operated Pressure Relief Valve Jan 5, 2024 I & VIII Div. 1 Page 59 of 812 Effective Date: 2019-05-31

61 Table of Contents Emerson Automation Solutions Final Control, US LP (KBM) location: Black Mountain, NC, UNITED STATES Acceptable Abbrev.: EMRN Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification Kunkle 189, 363, 389 36043 M Dec 12, 2020 VIII Div. 1 Safety Relief Valve M 36076 300,600 Jul 1, 2020 I & VIII Div. 1 Safety Valve 330. 330S, 333S 36087 M Safety Relief Valve VIII Div. 1 Nov 4, 2024 920, 921, 927, Agco A (High Temp. water) 36098 M I Safety Valve Dec 12, 2020 910 to 919 36100 M Dec 12, 2020 Safety Relief Valve VIII Div. 1 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) M 36111 Feb 24, 2024 Relief Valve I & VIII Div. 1 36122 M Kunkle Fig. 930 Jul 28, 2023 IV Safety Valve M 36223 1, 2 Oct 20, 2019 Safety Valve VIII Div. 1 Kunkle 264, 265, 266 & 267 36267 M Safety Relief Valve VIII Div. 1 Feb 24, 2024 Kunkle 337 36278 M Safety Relief Valve Sep 18, 2023 VIII Div. 1 36289 M Kunkle 537 Safety Relief Valve IV Jun 28, 2021 Kunkle 548-A (.295 Orifice) 36290 M Safety Relief Valve VIII Div. 1 Oct 20, 2019 Kunkle 541-C/542-C/548-C (.422 Orifice) 36302 M Safety Relief Valve VIII Div. 1 Oct 20, 2019 36313 M Kunkle 6933, 6934, 6935, 6254 IV Safety Valve Sep 1, 2020 36324 M Kunkle 6000, 6252 Series I & VIII Div. 1 Oct 5, 2020 Safety Valve 36335 M Kunkle 30 Safety Relief Valve VIII Div. 1 Jun 28, 2021 C776 36425 M Safety Relief Valve VIII Div. 1 Sep 9, 2024 36469 M Kunkle 541-A/542-A (.295 orifice) Safety Relief Valve VIII Div. 1 Jun 7, 2023 82 Series D Orifice M 36470 Safety Valve Mar 7, 2024 VIII Div. 1 M 36492 Cash C600 Safety Valve VIII Div. 1 Mar 16, 2022 Emerson Process Management Regulator Technologies, Inc. (FCF) location: Nuevo Laredo, Tamaulipas, MEXICO Acceptable Abbrev.: Fromex S.A. de C.V. Devices designed by: Emerson Process Management Regulator Technologies, Inc. (FCF) NB Cert # Cert Cat Expiration Date Type Classification Code Section Device Type M H722/ H822 22262 VIII Div. 1 Apr 11, 2025 Safety Relief Valve H732/H832/H732F3/H832F3/H732A/H832A 22273 M Safety Relief Valve Mar 26, 2025 VIII Div. 1 H282/ H284/ H882/ H884/ H5112/ H5114/ H8112/ 22284 M VIII Div. 1 Mar 26, 2025 Safety Relief Valve H733/H833/H733F3/H833F3 22295 M Safety Relief Valve Jul 1, 2019 VIII Div. 1 Page 60 of 812 Effective Date: 2019-05-31

62 Table of Contents Energy Power, Incorporated (ENG) location: Port Arthur, TX, UNITED STATES Acceptable Abbrev.: EPI Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type Cert Cat Code Section Type Classification Expiration Date NB Cert # JOS-E-RL/JBS-E-RL (Restricted Lift version of cert 15208) A 01045 Safety Relief Valve VIII Div. 1 Dec 18, 2024 81, 81P, 83, 86 01089 A VIII Div. 1 Apr 3, 2024 Safety Relief Valve 01102 81P (Liquids) A Relief Valve Apr 3, 2024 VIII Div. 1 01292 A 243/249/443/449/546/843/849/943/5046/5049/8043/8049 VIII Div. 1 Apr 3, 2024 Pilot Operated Pressure Relief Valve 01304 A 253/259/453/459/853/859/953/959/5059/8053/8059 Pilot Operated Pressure Relief Valve VIII Div. 1 Apr 3, 2024 263/269/463/469/566/863/869/963/969/5066/5069 01315 A Pilot Operated Pressure Relief Valve VIII Div. 1 Apr 3, 2024 01326 453/459/853/859/953/959/5059 (Liquids) A Pilot Operated Pressure Relief Valve Apr 3, 2024 VIII Div. 1 443/449/546/843/849/943/949/5046/5049(Liquids) 01337 A Pilot Operated Pressure Relief Valve VIII Div. 1 Apr 3, 2024 01382 A JLT-JOS-RL/JLT-JBS-RL (Restricted Lift version of VIII Div. 1 Safety Relief Valve Dec 18, 2024 01393 A JLT-JOS-RL/JLT-JBS-RL (Liquids) (Restricted lift version of Safety Relief Valve VIII Div. 1 Dec 18, 2024 H Series (HCI, HSJ, HCA, HA, HB, HC, HCB, HCP, HJO, HN, 15006 A Safety Valve Aug 24, 2024 I & VIII Div. 1 JLT (Liquids) 15095 A VIII Div. 1 Jul 12, 2023 Safety Relief Valve 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB A Safety Relief Valve VIII Div. 1 Jul 12, 2023 15411 900 Series, 7700, SNC A Jul 12, 2023 Safety Relief Valve VIII Div. 1 900 Series (Liquid), 7700, SNC 15499 A Relief Valve Jul 12, 2023 VIII Div. 1 15512 A JLT-JOS, JLT-JBS, 8500, ACL/ABL VIII Div. 1 Apr 3, 2024 Safety Relief Valve Page 61 of 812 Effective Date: 2019-05-31

63 Table of Contents Engineered Controls International, LLC (REG) location: Elon, NC, UNITED STATES Acceptable Abbrev.: ECII, RegO Devices designed by: Engineered Controls International, LLC (REG) Device Type Expiration Date NB Cert # Code Section Type Classification Cert Cat AA3130A250 M 46000 Safety Relief Valve Oct 4, 2023 VIII Div. 1 AA3130UA250 46011 M Safety Relief Valve Feb 22, 2023 VIII Div. 1 M 46022 AA3130UA265 Safety Relief Valve May 22, 2023 VIII Div. 1 3131 (20% OP) M 46033 Safety Relief Valve VIII Div. 1 Apr 28, 2020 M AA3135A150 46055 May 23, 2023 Safety Relief Valve VIII Div. 1 AA3135A300 46066 M Apr 23, 2023 VIII Div. 1 Safety Relief Valve M 46077 A3149 (20% OP) Feb 3, 2024 Safety Relief Valve VIII Div. 1 46099 7534 (20% OP) M Safety Relief Valve Feb 3, 2024 VIII Div. 1 46101 M 7583 (20% OP) VIII Div. 1 May 22, 2023 Safety Relief Valve 46112 M A8434G Apr 29, 2025 VIII Div. 1 Safety Relief Valve M 46123 A8434N Apr 23, 2023 Safety Relief Valve VIII Div. 1 A8436G, VA8436G 46134 M Safety Relief Valve VIII Div. 1 Mar 6, 2025 46145 A8436N, VA8436N (20% OP) M Safety Relief Valve May 8, 2024 VIII Div. 1 46156 M 8543 (20% OP) Feb 3, 2021 VIII Div. 1 Safety Relief Valve 46167 M 8544 (20% OP) Safety Relief Valve VIII Div. 1 Nov 17, 2020 8684 (20% OP) 46178 M Safety Relief Valve VIII Div. 1 Feb 25, 2023 46189 8685 (20% OP) M Safety Relief Valve Apr 23, 2023 VIII Div. 1 B-19434B & C-19434B 46190 M VIII Div. 1 Safety Relief Valve Feb 22, 2024 46213 M UA3149A VIII Div. 1 Safety Relief Valve Feb 3, 2021 46268 M AA3135 (20% OP) Apr 23, 2023 VIII Div. 1 Safety Relief Valve M 46279 PRV19430 , PRV29430 Aug 27, 2020 Safety Relief Valve VIII Div. 1 A3149 (20% OP) 46291 M Safety Relief Valve VIII Div. 1 Mar 6, 2025 46303 AA3135A (20% OP) M Safety Relief Valve VIII Div. 1 Nov 17, 2020 46314 6555 Series M Safety Relief Valve Feb 28, 2023 VIII Div. 1 46325 M B-19434B350-375 & C-19434B350-375 VIII Div. 1 Nov 9, 2023 Safety Relief Valve 46336 8546T (20% OP) M Relief Valve VIII Div. 1 Nov 20, 2019 8546G (20% OP) 46347 M VIII Div. 1 Nov 20, 2019 Safety Relief Valve M 46358 3135 (20% OP) Safety Relief Valve VIII Div. 1 Jan 6, 2023 46369 M AR4106A, AR5106A Mar 13, 2024 VIII Div. 1 Safety Relief Valve 46370 M AR4108A, AR5108A Safety Relief Valve VIII Div. 1 Mar 13, 2024 AR4112A, AR5112A 46381 M Safety Relief Valve Mar 13, 2024 VIII Div. 1 46392 AR4104A, AR5104A M Nov 13, 2019 Safety Relief Valve VIII Div. 1 NG9008M 46404 M VIII Div. 1 Safety Relief Valve May 12, 2020 PRV19430, PRV29430 (Low Pressure) M 46415 VIII Div. 1 Safety Relief Valve Nov 14, 2023 Enviro Valve Inc (ENV) location: Broken Arrow, OK, UNITED STATES Acceptable Abbrev.: EnviroValve Devices designed by: Enviro Valve Inc (ENV) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 58025 M EVSP VIII Div. 1 Oct 17, 2024 Breaking Bar Non-reclosing Device Page 62 of 812 Effective Date: 2019-05-31

64 Table of Contents Equipment and Controls, Inc. (ICE) location: Monessen, PA, UNITED STATES Acceptable Abbrev.: ECI Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 81, 81P, 83, 86 01089 A Jul 24, 2023 VIII Div. 1 Safety Relief Valve 01102 81P (Liquids) A Relief Valve Sep 22, 2023 VIII Div. 1 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 A VIII Div. 1 Pilot Operated Pressure Relief Valve Jul 24, 2023 01304 A 253/259/453/459/853/859/953/959/5059/8053/8059 Jul 24, 2023 VIII Div. 1 Pilot Operated Pressure Relief Valve A 01315 263/269/463/469/566/863/869/963/969/5066/5069 Jul 24, 2023 Pilot Operated Pressure Relief Valve VIII Div. 1 453/459/853/859/953/959/5059 (Liquids) 01326 A Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 24, 2023 443/449/546/843/849/943/949/5046/5049(Liquids) A 01337 Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 24, 2023 01348 A 463/469/566/863/869/963/969/5066/5069 (Liquids) VIII Div. 1 Jul 24, 2023 Pilot Operated Pressure Relief Valve A 15095 JLT (Liquids) Jul 24, 2023 Safety Relief Valve VIII Div. 1 JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 A Safety Relief Valve VIII Div. 1 Jul 24, 2023 900 Series, 7700, SNC A 15411 Jul 24, 2023 Safety Relief Valve VIII Div. 1 15499 A 900 Series (Liquid), 7700, SNC Relief Valve Jul 25, 2023 VIII Div. 1 Devices designed by: LESER GmbH & Company KG (LES) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # 37112 459/462 A Safety Relief Valve Jul 9, 2020 VIII Div. 1 526 A 37224 VIII Div. 1 Safety Relief Valve Jul 9, 2020 37235 A 526 (Liquids) Jul 9, 2020 VIII Div. 1 Relief Valve Exion Asia Pte Ltd (OSA) location: Singapore, SINGAPORE Acceptable Abbrev.: OSA Valve Devices designed by: Dresser, LLC (DRJ) Cert Cat Type Classification Expiration Date Device Type Code Section NB Cert # 18144 1900D-2, 1900-30D-2 A Safety Relief Valve Mar 26, 2024 VIII Div. 1 18166 A 1900E-2, 1900-30E-2 Safety Relief Valve VIII Div. 1 Mar 26, 2024 1900, 1900-30, 1900-35 18201 A Safety Relief Valve VIII Div. 1 Mar 26, 2024 3900 (39PV, 39MV pilots) 18447 A VIII Div. 1 Pilot Operated Pressure Relief Valve May 26, 2021 18458 A 3900 (39PV, 39MV pilots, liquid) VIII Div. 1 Pilot Operated Pressure Relief Valve May 26, 2021 18706 A 19000 Series VIII Div. 1 Mar 6, 2024 Safety Relief Valve 19000 Series, Liquid A 18717 VIII Div. 1 Nov 10, 2021 Relief Valve A 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) Relief Valve VIII Div. 1 Mar 26, 2024 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) A Mar 26, 2024 Relief Valve VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Jun 26, 2024 VIII Div. 1 19077 A 19110M & 19110H (Liquids) VIII Div. 1 May 26, 2021 Relief Valve Page 63 of 812 Effective Date: 2019-05-31

65 Table of Contents Experitec, Inc. (EXP) location: St. Peters , MO, Acceptable Abbrev.: EXP Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat 81, 81P, 83, 86 A 01089 Safety Relief Valve Apr 5, 2024 VIII Div. 1 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 A Pilot Operated Pressure Relief Valve Apr 9, 2024 VIII Div. 1 A 01304 253/259/453/459/853/859/953/959/5059/8053/8059 Pilot Operated Pressure Relief Valve Apr 5, 2024 VIII Div. 1 263/269/463/469/566/863/869/963/969/5066/5069 A 01315 Apr 5, 2024 VIII Div. 1 Pilot Operated Pressure Relief Valve 453/459/853/859/953/959/5059 (Liquids) 01326 A VIII Div. 1 Pilot Operated Pressure Relief Valve Apr 5, 2024 A 01337 443/449/546/843/849/943/949/5046/5049(Liquids) Pilot Operated Pressure Relief Valve VIII Div. 1 Apr 5, 2024 463/469/566/863/869/963/969/5066/5069 (Liquids) 01348 A VIII Div. 1 Apr 5, 2024 Pilot Operated Pressure Relief Valve 15095 A JLT (Liquids) Apr 5, 2024 Safety Relief Valve VIII Div. 1 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB A Apr 5, 2024 Safety Relief Valve VIII Div. 1 15411 A 900 Series, 7700, SNC VIII Div. 1 Apr 5, 2024 Safety Relief Valve 900 Series (Liquid), 7700, SNC 15499 A Apr 5, 2024 Relief Valve VIII Div. 1 A 15512 JLT-JOS, JLT-JBS, 8500, ACL/ABL Apr 5, 2024 VIII Div. 1 Safety Relief Valve 81, 81P, 83, 86 01089 A Safety Relief Valve VIII Div. 1 Apr 5, 2024 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 A VIII Div. 1 Apr 9, 2024 Pilot Operated Pressure Relief Valve 253/259/453/459/853/859/953/959/5059/8053/8059 A 01304 Pilot Operated Pressure Relief Valve VIII Div. 1 Apr 5, 2024 01315 A 263/269/463/469/566/863/869/963/969/5066/5069 Apr 5, 2024 VIII Div. 1 Pilot Operated Pressure Relief Valve 01326 A 453/459/853/859/953/959/5059 (Liquids) Pilot Operated Pressure Relief Valve VIII Div. 1 Apr 5, 2024 443/449/546/843/849/943/949/5046/5049(Liquids) A 01337 Pilot Operated Pressure Relief Valve Apr 5, 2024 VIII Div. 1 463/469/566/863/869/963/969/5066/5069 (Liquids) 01348 A VIII Div. 1 Apr 5, 2024 Pilot Operated Pressure Relief Valve A 15095 JLT (Liquids) Safety Relief Valve Apr 5, 2024 VIII Div. 1 15208 A JOS-E/JBS-E/JOS-H-E 8400 AC/AB Apr 5, 2024 VIII Div. 1 Safety Relief Valve 900 Series, 7700, SNC 15411 A Apr 5, 2024 VIII Div. 1 Safety Relief Valve 15499 900 Series (Liquid), 7700, SNC A Relief Valve Apr 5, 2024 VIII Div. 1 JLT-JOS, JLT-JBS, 8500, ACL/ABL 15512 A VIII Div. 1 Apr 5, 2024 Safety Relief Valve F. C. Kingston Company (KNG) location: Torrance, CA, UNITED STATES Acceptable Abbrev.: Kingston Div. of Storm Manufacturing Group Devices designed by: F. C. Kingston Company (KNG) NB Cert # Cert Cat Type Classification Expiration Date Code Section Device Type M 110C 35008 VIII Div. 1 Oct 18, 2022 Safety Relief Valve 35019 M 112C (.250" Orif.) Safety Relief Valve VIII Div. 1 Feb 22, 2021 35020 112C (.375" Orif.) M Safety Relief Valve Feb 22, 2021 VIII Div. 1 Fig. 114 (.437" Orif.) 35031 M VIII Div. 1 Oct 24, 2020 Safety Relief Valve 35042 Fig. 114 (.625" Orif.) M Safety Relief Valve VIII Div. 1 Dec 22, 2020 35053 M Fig. 114 & 115 (.219" Orif.) Dec 20, 2022 VIII Div. 1 Safety Relief Valve 35064 M Fig. 114 & 115 (.265 Orif.) Safety Relief Valve VIII Div. 1 Oct 24, 2020 35075 Fig. 114 & 115 (.312" Orif.) M Safety Relief Valve Oct 24, 2020 VIII Div. 1 35086 M Fig. 118C & 119 (.302" Orif.) Safety Relief Valve VIII Div. 1 Dec 18, 2022 Fig. 118C & 119 (.359" Orif.) M 35097 Safety Relief Valve Mar 12, 2021 VIII Div. 1 Fig. 118C & 119 (.578" Orif) 35109 M Safety Relief Valve VIII Div. 1 Apr 13, 2025 35121 M KSV12P-1 & KSV25P-2 Safety Relief Valve VIII Div. 1 Aug 17, 2024 KSV10-1 & KSV10-2 M 35132 Safety Relief Valve May 22, 2024 VIII Div. 1 112C Steam Service 35143 M Safety Relief Valve Apr 16, 2020 VIII Div. 1 710D 35154 M Safety Relief Valve Feb 28, 2025 VIII Div. 1 Page 64 of 812 Effective Date: 2019-05-31

66 Table of Contents F. H. Gaskins Company, Incorporated (FHG) location: Norfolk, VA, UNITED STATES Seal Identification: FHG Devices designed by: Dresser, LLC (DRJ) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat 1541, 1543, 1541-3, 1543-3 A 18032 Safety Valve Dec 6, 2022 I & VIII Div. 1 18122 A 1811, 1511 Dec 6, 2022 I & VIII Div. 1 Safety Valve 1900, 1900-30, 1900-35 A 18201 Jul 22, 2023 VIII Div. 1 Safety Relief Valve 3900 (39PV, 39MV pilots) 18447 A VIII Div. 1 Aug 26, 2020 Pilot Operated Pressure Relief Valve 19000 Series 18706 A Safety Relief Valve VIII Div. 1 May 14, 2025 A 18717 19000 Series, Liquid Nov 1, 2022 Relief Valve VIII Div. 1 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) A Relief Valve Nov 15, 2023 VIII Div. 1 F.W. Webb Process Controls Division (SEV) location: Winslow, ME, UNITED STATES Acceptable Abbrev.: Sevco Devices designed by: Conbraco Industries, Incorporated (CNB) Device Type Expiration Date Type Classification Cert Cat Code Section NB Cert # A 19 Series 11282 Jan 14, 2020 I & VIII Div. 1 Safety Valve A 11361 119 Series Dec 13, 2019 Safety Valve I & VIII Div. 1 500 Series 11462 A VIII Div. 1 Safety Valve Sep 20, 2024 A 500 Series (Liquids) 11473 VIII Div. 1 Mar 20, 2024 Safety Relief Valve Fainger LESER Valves Pvt. Ltd. (FLV) location: Maharashtra, Devices designed by: LESER GmbH & Company KG (LES) NB Cert # Cert Cat Code Section Device Type Type Classification Expiration Date 459/462 liquids 37101 M VIII Div. 1 Relief Valve Jun 15, 2021 37112 M 459/462 VIII Div. 1 Safety Relief Valve Jun 15, 2021 37224 M 526 VIII Div. 1 Jun 15, 2021 Safety Relief Valve M 37235 526 (Liquids) Jun 15, 2021 Relief Valve VIII Div. 1 526D 37246 M Safety Relief Valve VIII Div. 1 Jun 15, 2021 526D Liquids 37257 M Relief Valve VIII Div. 1 Jun 15, 2021 37325 M 237, 237IC, 237CC Safety Relief Valve VIII Div. 1 Aug 21, 2024 37336 237, 237IC, 237CC (Liquid) M Relief Valve VIII Div. 1 Aug 21, 2024 Farris Brasil Indústria de Válvulas Ltda, a Division of Curtiss-Wright Flow Control (FBV) location: Sao Carlos - S.P., Acceptable Abbrev.: Farris Brasil Devices designed by: Farris Engineering (TFO) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat 57024 A 3800 Pilot Operated Pressure Relief Valve VIII Div. 1 Nov 5, 2020 3800FP 57035 A Pilot Operated Pressure Relief Valve Nov 5, 2020 VIII Div. 1 2600 & 2600S 57057 A VIII Div. 1 Nov 5, 2020 Safety Relief Valve A 57068 2600L (Liquids) Relief Valve VIII Div. 1 Nov 5, 2020 57215 A 3800L, PCL, PCM pilots Pilot Operated Pressure Relief Valve VIII Div. 1 Nov 5, 2020 2700, 2700S, 3700, 3700S A 57237 Safety Relief Valve Nov 5, 2020 VIII Div. 1 2700L, 3700L (Liquids) 57248 A Relief Valve Nov 5, 2020 VIII Div. 1 2600L (Air & Steam) 57260 A Safety Relief Valve Nov 5, 2020 VIII Div. 1 Page 65 of 812 Effective Date: 2019-05-31

67 Table of Contents FARRIS ENGINEERING - A Division of CWFC (UK) LTD. (FEE) location: Corby, UNITED KINGDOM Acceptable Abbrev.: FARRIS ENGINEERING, Div. of Curtiss-Wright F.C. UK LTD, Corby, UK Devices designed by: Farris Engineering (TFO) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 3800 57024 M Jan 27, 2020 VIII Div. 1 Pilot Operated Pressure Relief Valve M 57035 3800FP Aug 13, 2019 VIII Div. 1 Pilot Operated Pressure Relief Valve 2600 & 2600S 57057 M Safety Relief Valve VIII Div. 1 Aug 13, 2019 2600L (Liquids) 57068 M VIII Div. 1 Relief Valve Aug 13, 2019 3800L, PCL, PCM pilots 57215 M Jan 27, 2020 Pilot Operated Pressure Relief Valve VIII Div. 1 57237 2700, 2700S, 3700, 3700S M Safety Relief Valve Aug 13, 2019 VIII Div. 1 57248 M 2700L, 3700L (Liquids) Aug 13, 2019 VIII Div. 1 Relief Valve M 2600L (Air & Steam) 57260 Aug 13, 2019 VIII Div. 1 Safety Relief Valve Farris Engineering (FIC) location: Brantford, CANADA Acceptable Abbrev.: Farris Engineering, Div. of Curtiss-Wright F.C.C. Division of Curtiss - Wright Flow Control Corporation Devices designed by: Farris Engineering (FIC) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # M 4700L (liquids) 57259 III & VIII Div.1 Sep 10, 2020 Relief Valve 57383 M 954C55-120/S4 III ND Vacuum Relief Valve Mar 24, 2021 SS-114-657 59116 M III NB Power Actuated Relief Valve Jul 23, 2021 Devices designed by: Farris Engineering (TFO) Type Classification Cert Cat Code Section NB Cert # Expiration Date Device Type 57002 M 1850, 1850H, 1851, 1852, 1855, 1856M, 2850, 2852, 2856, 2850H Oct 18, 2024 VIII Div. 1 Safety Relief Valve 57013 M 1890, 1892, 1895, 1896 Safety Relief Valve III & VIII Div.1 Oct 15, 2021 57024 3800 M Pilot Operated Pressure Relief Valve Aug 18, 2020 VIII Div. 1 57035 M 3800FP Aug 18, 2020 VIII Div. 1 Pilot Operated Pressure Relief Valve 57046 M 6400/6600 (previously 2500 & 4600) I & VIII Div. 1 Safety Valve Aug 27, 2019 57057 M 2600 & 2600S Safety Relief Valve III & VIII Div.1 Sep 18, 2020 2600L (Liquids) 57068 M Relief Valve III & VIII Div.1 Oct 15, 2021 57192 M 1890L, 1892L, 1895L, 1896L (Liquids) VIII Div. 1 Relief Valve Jun 30, 2019 57215 M 3800L, PCL, PCM pilots VIII Div. 1 Sep 10, 2020 Pilot Operated Pressure Relief Valve 2700, 2700S, 3700, 3700S M 57237 VIII Div. 1 Nov 19, 2024 Safety Relief Valve 57248 2700L, 3700L (Liquids) M Relief Valve Oct 18, 2024 VIII Div. 1 2600L (Air & Steam) 57260 M VIII Div. 1 Aug 10, 2020 Safety Relief Valve 4200 / 4400 57282 M Safety Valve Oct 15, 2021 I & VIII Div. 1 Page 66 of 812 Effective Date: 2019-05-31

68 Table of Contents Farris Engineering (TFO) location: Brecksville, OH, UNITED STATES Division of Curtiss-Wright Flow Control Corporation Devices designed by: Farris Engineering (TFO) Cert Cat Code Section Device Type Type Classification NB Cert # Expiration Date M 1850, 1850H, 1851, 1852, 1855, 1856M, 2850, 2852, 2856, 2850H 57002 Nov 7, 2023 VIII Div. 1 Safety Relief Valve 1890, 1892, 1895, 1896 M 57013 Safety Relief Valve VIII Div. 1 Aug 2, 2021 3800 57024 M Pilot Operated Pressure Relief Valve Aug 2, 2021 VIII Div. 1 57035 M 3800FP Pilot Operated Pressure Relief Valve VIII Div. 1 Aug 1, 2021 6400/6600 (previously 2500 & 4600) 57046 M I & VIII Div. 1 Jul 16, 2021 Safety Valve M 2600 & 2600S 57057 VIII Div. 1 Aug 2, 2021 Safety Relief Valve 57068 M 2600L (Liquids) Aug 7, 2021 VIII Div. 1 Relief Valve 57192 M 1890L, 1892L, 1895L, 1896L (Liquids) Relief Valve VIII Div. 1 Aug 2, 2021 57215 3800L, PCL, PCM pilots M Pilot Operated Pressure Relief Valve Apr 27, 2021 VIII Div. 1 57237 2700, 2700S, 3700, 3700S M Aug 2, 2021 Safety Relief Valve VIII Div. 1 2700L, 3700L (Liquids) 57248 M VIII Div. 1 Relief Valve Aug 7, 2021 57260 M 2600L (Air & Steam) VIII Div. 1 Safety Relief Valve Jul 6, 2020 57282 M 4200 / 4400 I & VIII Div. 1 Oct 10, 2021 Safety Valve 57394 M 3800L PCM Pilot Operated Pressure Relief Valve VIII Div. 1 Jan 31, 2023 2600 Series Restricted lift 57406 M Safety Valve VIII Div. 1 Aug 31, 2023 57417 M 2600L (Liquids) Series Restricted lift Safety Relief Valve VIII Div. 1 Jun 12, 2023 2600L (Air & Steam) Series Restricted Lift M 57439 Safety Relief Valve Jul 17, 2024 VIII Div. 1 FDC Co., Ltd. (FDC) location: Juchon-myeon, Gimhae-si, Gyeongsangnam-do, Devices designed by: FDC Co., Ltd. (FDC) Expiration Date NB Cert # Cert Cat Type Classification Device Type Code Section KSRC 00695 M Rupture Disk Device Aug 18, 2022 VIII Div. 1 KSRSR 00943 M Rupture Disk Device Aug 18, 2022 VIII Div. 1 M KSRSR(C) 01528 VIII Div. 1 Oct 17, 2024 Rupture Disk Device 01539 KSRO M Rupture Disk Device Oct 17, 2024 VIII Div. 1 Page 67 of 812 Effective Date: 2019-05-31

69 Table of Contents Fike Corporation (FIK) location: Blue Springs, MO, UNITED STATES Devices designed by: Fike Corporation (FIK) Type Classification Expiration Date NB Cert # Cert Cat Code Section Device Type Poly-SD Single Hinge 80008 M Nov 23, 2019 VIII Div. 1 Rupture Disk Device Poly-SD Double Hinge 80019 M Rupture Disk Device VIII Div. 1 Sep 11, 2019 M 80020 Poly-SD Cross Score VIII Div. 1 Rupture Disk Device Dec 6, 2024 80031 M SRL Rupture Disk Device VIII Div. 1 Sep 11, 2019 M SRX 80042 Sep 16, 2025 VIII Div. 1 Rupture Disk Device 80053 M PV, CP-C, CPV, CPV-C May 17, 2024 VIII Div. 1 Rupture Disk Device HO/HOV 80064 M Jan 14, 2020 Rupture Disk Device VIII Div. 1 M 80075 FSR Scored Sep 11, 2025 VIII Div. 1 Rupture Disk Device SR-H 80097 M Rupture Disk Device VIII Div. 1 Nov 23, 2019 MRK, RKB, Reverse Knife Blade 80109 M VIII Div. 1 May 17, 2024 Rupture Disk Device P, CP,CPC 80132 M Rupture Disk Device Aug 21, 2025 VIII Div. 1 80154 M SCRD FSR-VT Oct 28, 2023 VIII Div. 1 Rupture Disk Device SCRD-FSR-VT (Liquid) 80187 M Dec 19, 2023 Rupture Disk Device VIII Div. 1 M 80200 SCRD-V Cross Score Oct 20, 2023 VIII Div. 1 Rupture Disk Device SRL (gas/liq.) 80277 M Rupture Disk Device VIII Div. 1 Dec 10, 2021 3/4" Poly SD Double Hinge (DH) 80288 M VIII Div. 1 May 16, 2024 Rupture Disk Device 80299 1/2" Poly SD Double Hinge (DH) M Rupture Disk Device Apr 15, 2023 VIII Div. 1 80301 M 1/2" Poly SD Double Hinge (DH) liquid Apr 13, 2023 VIII Div. 1 Rupture Disk Device 80334 M Poly SD Cross Score, Liquid Rupture Disk Device VIII Div. 1 Apr 14, 2023 80345 1/2" Poly SD Cross Score (liquid) M Rupture Disk Device Sep 13, 2024 VIII Div. 1 80356 M 1/2" Poly SD Cross Score Rupture Disk Device VIII Div. 1 Jun 12, 2024 1/2" Poly SD Cross Score w. Liner M 80367 Rupture Disk Device Nov 9, 2023 VIII Div. 1 M 80402 A8701-X Rupture Disk Device VIII Div. 1 Oct 18, 2024 80457 M P, CP, CPC - Union Type Holder VIII Div. 1 Aug 19, 2020 Rupture Disk Device PV, CP-P, CPV, CPV-C with Union Type Holder 80468 M Aug 21, 2025 VIII Div. 1 Rupture Disk Device 80479 HO, HOV with Union Type holder M Rupture Disk Device Aug 22, 2025 VIII Div. 1 FSR Scored (Liquid) 80514 M VIII Div. 1 Rupture Disk Device May 7, 2020 1/2 " P ST FS M 80525 VIII Div. 1 Oct 10, 2020 Rupture Disk Device 80536 M 1/2 " SCRD ST FS Cross Scored Rupture Disk Device VIII Div. 1 Oct 9, 2020 1/2 " SCRD ST FS Double Hinge M 80547 Rupture Disk Device VIII Div. 1 Oct 9, 2020 80558 M Axius, RD320, RD520 VIII Div. 1 Dec 10, 2021 Rupture Disk Device 80569 M A8991-X Rupture Disk Device VIII Div. 1 Jun 13, 2024 80570 HOV Flat Seat Single Hinge M Rupture Disk Device Dec 10, 2021 VIII Div. 1 80581 M HOV Flat Seat Multi-Petal Rupture Disk Device VIII Div. 1 Oct 20, 2023 Poly-SD, SCRD-V (Double Disc) M 80592 Rupture Disk Device Dec 21, 2023 VIII Div. 1 Axius, RD320, RD520 (liquid) 80604 M Rupture Disk Device VIII Div. 1 Sep 9, 2022 80615 Axius, RD320, RD520 (gas) M Rupture Disk Device VIII Div. 1 May 24, 2022 Axius SC 80626 M VIII Div. 1 Rupture Disk Device Nov 19, 2023 80637 A9172-X M Rupture Disk Device VIII Div. 1 May 24, 2024 80648 A9182-X M Rupture Disk Device VIII Div. 1 Apr 28, 2023 80659 A9111-X M Rupture Disk Device Oct 31, 2019 VIII Div. 1 A9180-X 80660 M Rupture Disk Device Feb 13, 2025 VIII Div. 1 80716 M ATLAS, RD300, RD500 VIII Div. 1 Rupture Disk Device Mar 29, 2024 M ATLAS, RD300, RD500 (Liquid) 80727 VIII Div. 1 May 17, 2024 Rupture Disk Device M 80749 Axius, RD320, RD520 Double Disc (Axius DD) Rupture Disk Device Oct 31, 2019 VIII Div. 1 Axius, RD320, RD520 Double Disc (Axius DD) (Liquid) 80750 M VIII Div. 1 Oct 31, 2019 Rupture Disk Device SCRD-FSR-SQ 80761 M Rupture Disk Device Aug 19, 2021 VIII Div. 1 Page 68 of 812 Effective Date: 2019-05-31

70 Table of Contents Flotech, Inc. - Charleston Div. (SCI) location: North Charleston, SC, UNITED STATES Seal Identification: VS/CHSN Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 63B (.312", #5 orifice) 01056 A Sep 1, 2022 VIII Div. 1 Safety Relief Valve A 01067 63B (.437", #7 orifice) Aug 25, 2022 VIII Div. 1 Safety Relief Valve 81, 81P, 83, 86 01089 A Safety Relief Valve VIII Div. 1 Aug 25, 2022 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 A VIII Div. 1 Pilot Operated Pressure Relief Valve Sep 1, 2022 253/259/453/459/853/859/953/959/5059/8053/8059 01304 A Sep 1, 2022 Pilot Operated Pressure Relief Valve VIII Div. 1 01315 263/269/463/469/566/863/869/963/969/5066/5069 A Pilot Operated Pressure Relief Valve Aug 25, 2022 VIII Div. 1 01348 A 463/469/566/863/869/963/969/5066/5069 (Liquids) Sep 1, 2022 VIII Div. 1 Pilot Operated Pressure Relief Valve A 15006 H Series (HCI, HSJ, HCA, HA, HB, HC, HCB, HCP, HJO, HN, Aug 31, 2022 Safety Valve I & VIII Div. 1 JLT (Liquids) 15095 A VIII Div. 1 Aug 23, 2022 Safety Relief Valve 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB A VIII Div. 1 Aug 31, 2022 Safety Relief Valve A 900 Series, 7700, SNC 15411 VIII Div. 1 Sep 1, 2022 Safety Relief Valve 15499 A 900 Series (Liquid), 7700, SNC Relief Valve VIII Div. 1 Aug 23, 2022 Flotech, Inc. (FLO) location: Jacksonville, FL, UNITED STATES Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 910 to 919 A 36100 VIII Div. 1 Safety Relief Valve Jan 11, 2024 36111 A 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) Jan 11, 2024 VIII Div. 1 Relief Valve 36278 A Kunkle 337 Jan 11, 2024 VIII Div. 1 Safety Relief Valve Kunkle 6000, 6252 Series 36324 A Safety Valve Jan 11, 2024 I & VIII Div. 1 Devices designed by: Farris Engineering (TFO) Expiration Date Cert Cat Type Classification NB Cert # Code Section Device Type A 3800 57024 VIII Div. 1 Jan 11, 2024 Pilot Operated Pressure Relief Valve 3800FP 57035 A VIII Div. 1 Pilot Operated Pressure Relief Valve Jan 11, 2024 57057 A 2600 & 2600S VIII Div. 1 Safety Relief Valve Jan 11, 2024 57068 A 2600L (Liquids) VIII Div. 1 Jan 11, 2024 Relief Valve 2700, 2700S, 3700, 3700S A 57237 VIII Div. 1 Jan 11, 2024 Safety Relief Valve 57248 2700L, 3700L (Liquids) A Relief Valve Jan 11, 2024 VIII Div. 1 2600L (Air & Steam) 57260 A VIII Div. 1 Jan 11, 2024 Safety Relief Valve 4200 / 4400 57282 A Safety Valve Jan 11, 2024 I & VIII Div. 1 Page 69 of 812 Effective Date: 2019-05-31

71 Table of Contents Flow Safe Inc. (FSS) location: Houston, TX, UNITED STATES Acceptable Abbrev.: FSI Devices designed by: Flow Safe, Inc. (FLW) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat F7100, F7200, F7300, F7400, F7500 M 28000 Pilot Operated Pressure Relief Valve Jan 2, 2024 VIII Div. 1 28011 M F7100, F7300, F7400, F7500 (Liquids) Apr 25, 2020 VIII Div. 1 Pilot Operated Pressure Relief Valve F8100, F8200, F8300, F8400, F8500 M 28022 Jun 14, 2024 VIII Div. 1 Pilot Operated Pressure Relief Valve F84L-4, F88-4 (Liquids) 28044 M VIII Div. 1 Apr 25, 2020 Relief Valve F84L, F88 (liquids) 28055 M Safety Relief Valve VIII Div. 1 Apr 25, 2020 M 28066 F84, F85 Jan 2, 2024 Safety Relief Valve VIII Div. 1 28077 F88-8 M Safety Valve Apr 25, 2020 VIII Div. 1 28088 M F88-4 VIII Div. 1 Apr 25, 2020 Safety Valve 28099 M F8100, F8300, F8500 (liquid) VIII Div. 1 Apr 25, 2020 Pilot Operated Pressure Relief Valve M 28101 F88-J Apr 25, 2020 Safety Valve VIII Div. 1 F88-G 28112 M Safety Valve VIII Div. 1 Apr 25, 2020 F84L-2 28123 M Safety Relief Valve VIII Div. 1 Apr 25, 2020 28134 F88-3 M Safety Valve VIII Div. 1 Aug 10, 2021 28145 F84L-3, F88-3 (Liquid) M Safety Relief Valve VIII Div. 1 Aug 10, 2021 28156 F8100, F8300, F8500 (High Beta Ratio Sizes) (Liquid) M Pilot Operated Pressure Relief Valve Jul 21, 2021 VIII Div. 1 F84L-2 LP 28167 M Safety Relief Valve VIII Div. 1 Feb 22, 2023 28000 M F7100, F7200, F7300, F7400, F7500 VIII Div. 1 Pilot Operated Pressure Relief Valve Jan 2, 2024 28011 M F7100, F7300, F7400, F7500 (Liquids) VIII Div. 1 Apr 25, 2020 Pilot Operated Pressure Relief Valve M 28022 F8100, F8200, F8300, F8400, F8500 Jun 14, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 F84L-4, F88-4 (Liquids) 28044 M Relief Valve VIII Div. 1 Apr 25, 2020 F84L, F88 (liquids) 28055 M Safety Relief Valve VIII Div. 1 Apr 25, 2020 28066 M F84, F85 Safety Relief Valve VIII Div. 1 Jan 2, 2024 28077 F88-8 M Safety Valve VIII Div. 1 Apr 25, 2020 F88-4 28088 M VIII Div. 1 Apr 25, 2020 Safety Valve 28099 F8100, F8300, F8500 (liquid) M Pilot Operated Pressure Relief Valve VIII Div. 1 Apr 25, 2020 28101 M F88-J Safety Valve VIII Div. 1 Apr 25, 2020 28112 F88-G M Safety Valve VIII Div. 1 Apr 25, 2020 28123 F84L-2 M Safety Relief Valve Apr 25, 2020 VIII Div. 1 F88-3 28134 M Safety Valve Aug 10, 2021 VIII Div. 1 M F84L-3, F88-3 (Liquid) 28145 VIII Div. 1 Aug 10, 2021 Safety Relief Valve M 28156 F8100, F8300, F8500 (High Beta Ratio Sizes) (Liquid) Pilot Operated Pressure Relief Valve Jul 21, 2021 VIII Div. 1 F84L-2 LP 28167 M Safety Relief Valve Feb 22, 2023 VIII Div. 1 Page 70 of 812 Effective Date: 2019-05-31

72 Table of Contents Flow Safe, Inc. (FLW) location: Orchard Park, NY, UNITED STATES Devices designed by: Flow Safe, Inc. (FLW) Type Classification Expiration Date NB Cert # Cert Cat Code Section Device Type F7100, F7200, F7300, F7400, F7500 28000 M Dec 18, 2023 VIII Div. 1 Pilot Operated Pressure Relief Valve F7100, F7300, F7400, F7500 (Liquids) 28011 M Pilot Operated Pressure Relief Valve Oct 28, 2023 VIII Div. 1 F8100, F8200, F8300, F8400, F8500 28022 M Pilot Operated Pressure Relief Valve Oct 6, 2021 VIII Div. 1 F84L-4, F88-4 (Liquids) 28044 M Dec 18, 2023 Relief Valve VIII Div. 1 F84L, F88 (liquids) M 28055 VIII Div. 1 Dec 18, 2023 Safety Relief Valve M 28066 F84, F85 Jan 18, 2023 Safety Relief Valve VIII Div. 1 F88-8 28077 M Safety Valve VIII Div. 1 Jan 8, 2021 F88-4 28088 M Safety Valve Sep 26, 2019 VIII Div. 1 28099 M F8100, F8300, F8500 (liquid) VIII Div. 1 Sep 26, 2019 Pilot Operated Pressure Relief Valve M 28101 F88-J Dec 21, 2022 Safety Valve VIII Div. 1 F88-G 28112 M VIII Div. 1 Safety Valve Dec 21, 2022 M 28123 F84L-2 Dec 21, 2022 Safety Relief Valve VIII Div. 1 F88-3 M 28134 Safety Valve VIII Div. 1 Jan 15, 2021 28145 M F84L-3, F88-3 (Liquid) Safety Relief Valve VIII Div. 1 Jan 15, 2021 28156 F8100, F8300, F8500 (High Beta Ratio Sizes) (Liquid) M Pilot Operated Pressure Relief Valve VIII Div. 1 May 27, 2021 F84L-2 LP 28167 M VIII Div. 1 Sep 1, 2022 Safety Relief Valve Fluid Handling LLC (Bell & Gossett, McDonnell & Miller) (BGT) location: Morton Grove, IL, UNITED STATES Devices designed by: Fluid Handling LLC (Bell & Gossett, McDonnell & Miller) (BGT) NB Cert # Cert Cat Code Section Expiration Date Device Type Type Classification 31004 M 790 & McDonnell & Miller 250-3/4 Mar 8, 2025 IV Safety Relief Valve M 31015 1170 & McDonnell & Miller 250-1 Feb 23, 2025 Safety Relief Valve IV 3301 & McDonnell & Miller 260-1-1/2 31026 M Safety Relief Valve IV Oct 11, 2024 31037 4100 & McDonnell & Miller 250-2 M Safety Relief Valve IV Nov 7, 2024 Fluid Mechanics Valve Company (FMV) location: Houston, TX, UNITED STATES Acceptable Abbrev.: F/M Devices designed by: Fluid Mechanics Valve Company (FMV) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat M 1511, 1521, 1611, 1621 25007 VIII Div. 1 Mar 31, 2021 Safety Relief Valve 25018 1513, 1523, 1613, 1623 M Safety Relief Valve VIII Div. 1 Jun 28, 2021 25029 M 1524 - 1548, 1624 - 1648 Dec 15, 2020 VIII Div. 1 Safety Relief Valve 25030 M 4000 & 4200 (.312 soft seat) Safety Relief Valve VIII Div. 1 Mar 31, 2021 4000 & 4200 Model (405 & 425) 25041 M Safety Relief Valve Jun 28, 2021 VIII Div. 1 3900 Model (392 Series), .250 Soft Seat 25063 M VIII Div. 1 Dec 15, 2020 Relief Valve Forum Severe Service Valves, LLC. (CPV) location: Stafford, TX, Devices designed by: Forum Severe Service Valves, LLC. (CPV) Device Type NB Cert # Cert Cat Expiration Date Type Classification Code Section ARV Series 1 00909 M Power Actuated Relief Valve Mar 18, 2021 I 00921 M ARV Series 2 I Mar 18, 2021 Power Actuated Relief Valve Page 71 of 812 Effective Date: 2019-05-31

73 Table of Contents Fukui Seisakusho Company, Limited (FKI) location: Hirakata City, Osaka, JAPAN Devices designed by: Fukui Seisakusho Company, Limited (FKI) Cert Cat Type Classification NB Cert # Expiration Date Code Section Device Type PSL Series 27021 M Jan 22, 2025 VIII Div. 1 Pilot Operated Pressure Relief Valve 27032 RE Series M Safety Relief Valve Sep 29, 2024 VIII Div. 1 RECL & REBL (Liquids) 27043 M May 29, 2024 VIII Div. 1 Relief Valve 27054 M RP Series Sep 9, 2024 VIII Div. 1 Pilot Operated Pressure Relief Valve M 27065 RPSL (Liquids) Sep 9, 2024 Relief Valve VIII Div. 1 SL Series 27076 M Safety Valve I & VIII Div. 1 Jun 5, 2024 27098 PSH 2-1/2 K 4 M Power Actuated Relief Valve Oct 9, 2021 I 27100 M PSH 2-1/2 L 4 I Oct 9, 2021 Power Actuated Relief Valve 27133 M RTE Liquid Feb 22, 2021 VIII Div. 1 Relief Valve M 27144 RTE Feb 22, 2021 Safety Relief Valve VIII Div. 1 RPE (Water K = 0.681) 27177 M Pilot Operated Pressure Relief Valve I & VIII Div. 1 Sep 27, 2023 27188 PCV M Power Actuated Relief Valve I Sep 27, 2024 27199 M SL-xxxx PA Power Actuated Relief Valve I Sep 30, 2021 GE Measurement and Control (Singapore) PTE LTD (DSP) location: Singapore, SINGAPORE Acceptable Abbrev.: DSP Devices designed by: Dresser, LLC (DRJ) Type Classification Expiration Date Device Type NB Cert # Cert Cat Code Section M 18144 1900D-2, 1900-30D-2 Safety Relief Valve VIII Div. 1 Oct 3, 2025 18166 M 1900E-2, 1900-30E-2 Apr 24, 2025 VIII Div. 1 Safety Relief Valve M 18201 1900, 1900-30, 1900-35 Apr 24, 2025 Safety Relief Valve VIII Div. 1 3900 (39PV, 39MV pilots) 18447 M VIII Div. 1 Pilot Operated Pressure Relief Valve Nov 17, 2021 M 18458 3900 (39PV, 39MV pilots, liquid) Nov 17, 2021 Pilot Operated Pressure Relief Valve VIII Div. 1 19000 Series 18706 M Safety Relief Valve Apr 24, 2025 VIII Div. 1 18717 M 19000 Series, Liquid Relief Valve VIII Div. 1 Apr 24, 2025 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) M Relief Valve VIII Div. 1 Nov 19, 2020 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) M Relief Valve Apr 24, 2025 VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 M VIII Div. 1 Relief Valve Apr 24, 2025 19110M & 19110H (Liquids) M 19077 VIII Div. 1 Relief Valve May 26, 2021 GEA AWP GmbH (GEA) location: Prenzlau, GERMANY Acceptable Abbrev.: GEA AWP GMBH PRENZLAU, GERMANY Devices designed by: GEA AWP GmbH (GEA) NB Cert # Cert Cat Code Section Type Classification Expiration Date Device Type 07085 M SVA type 455, 456 / SVU type 457, 458 (1.189 orifice) Aug 28, 2019 Safety Relief Valve VIII Div. 1 SVA type 455, 456 / SVU 457, 458 (0.648 orifice) 07096 M Safety Relief Valve VIII Div. 1 Aug 29, 2019 M SVA type 455, 456/ SVU type 457, 458 (0.953 orifice) 07142 VIII Div. 1 Aug 29, 2019 Safety Relief Valve M 07153 SVA type 455, 456/ SVU type 457, 458 (0.480 orifice) Safety Relief Valve Aug 29, 2019 VIII Div. 1 SVA type 455, 456 / SVU type 457, 458 (0.795 orifice) 07164 M Safety Relief Valve Aug 28, 2019 VIII Div. 1 Page 72 of 812 Effective Date: 2019-05-31

74 Table of Contents GLM Corporation (GCM) location: Kenai, AK, UNITED STATES Acceptable Abbrev.: GLM Corp Devices designed by: Dresser, LLC (DRJ) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 1541, 1543, 1541-3, 1543-3 18032 A Jun 19, 2019 I & VIII Div. 1 Safety Valve A 18122 1811, 1511 Jun 19, 2025 I & VIII Div. 1 Safety Valve 1900D-2, 1900-30D-2 18144 A Safety Relief Valve VIII Div. 1 Jul 10, 2025 1900E-2, 1900-30E-2 18166 A VIII Div. 1 Safety Relief Valve Jul 10, 2025 1900, 1900-30, 1900-35 18201 A Jul 10, 2025 Safety Relief Valve VIII Div. 1 1982 A 18379 Jul 10, 2025 Safety Relief Valve VIII Div. 1 18380 A 1982 LS, 820000LS Jul 10, 2019 VIII Div. 1 Relief Valve A 18447 3900 (39PV, 39MV pilots) Jul 10, 2025 Pilot Operated Pressure Relief Valve VIII Div. 1 3900 (39PV, 39MV pilots, liquid) 18458 A Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 10, 2025 19000 Series 18706 A Safety Relief Valve Jul 10, 2025 VIII Div. 1 18717 A 19000 Series, Liquid Relief Valve VIII Div. 1 Jul 10, 2025 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A Relief Valve VIII Div. 1 Jul 10, 2025 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 A Relief Valve VIII Div. 1 Jul 10, 2025 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) VIII Div. 1 Relief Valve Jul 10, 2025 18997 A 1900-UM VIII Div. 1 Jul 10, 2019 Safety Relief Valve 19000 A 1900-UM (Liquids) Safety Relief Valve VIII Div. 1 Jul 10, 2019 1900-UM-D 19011 A Safety Relief Valve VIII Div. 1 Jul 10, 2019 19022 A 1900 UM-D (Liquids) Safety Relief Valve VIII Div. 1 Jul 10, 2019 1900-UM-E A 19033 Safety Relief Valve Jul 10, 2019 VIII Div. 1 A 19044 1900-UM-E (Liquids) Safety Relief Valve VIII Div. 1 Jul 10, 2019 Global Engg. Solutions FzCo (A Bliss Anand-India Group Company) (GES) location: Dubai, UNITED ARAB EMIRATES Acceptable Abbrev.: GES Devices designed by: Farris Engineering (TFO) NB Cert # Cert Cat Expiration Date Type Classification Code Section Device Type A 2600 & 2600S 57057 VIII Div. 1 Oct 31, 2023 Safety Relief Valve 2600L (Liquids) 57068 A Relief Valve Oct 31, 2023 VIII Div. 1 2700, 2700S, 3700, 3700S 57237 A VIII Div. 1 Oct 31, 2023 Safety Relief Valve 2700L, 3700L (Liquids) 57248 A Relief Valve Oct 31, 2023 VIII Div. 1 Page 73 of 812 Effective Date: 2019-05-31

75 Table of Contents Goetze KG Armaturen (GTZ) location: Ludwigsburg, GERMANY Acceptable Abbrev.: Goetze KG Devices designed by: Goetze KG Armaturen (GTZ) Expiration Date Cert Cat Code Section Device Type Type Classification NB Cert # 812, 412, 1812 96005 M Safety Relief Valve VIII Div. 1 Nov 20, 2019 M 96038 451, 851 VIII Div. 1 May 5, 2022 Safety Relief Valve 451, 851 Liquids M 96049 VIII Div. 1 Safety Relief Valve Jan 12, 2023 M 451-1/2", 851-1/2" 96050 Safety Relief Valve Oct 3, 2022 VIII Div. 1 451-1/2", 851-1/2" (Liquids) 96061 M VIII Div. 1 May 4, 2022 Safety Relief Valve 2400 / 2480 96072 M VIII Div. 1 Safety Relief Valve Jan 13, 2023 M 96083 2400 / 2480 Liquids Safety Relief Valve VIII Div. 1 Jan 12, 2023 410, 810, 1809, 1810 96094 M VIII Div. 1 Jan 13, 2023 Safety Relief Valve 96106 M 812-2", 412-2" Jan 12, 2023 Safety Relief Valve VIII Div. 1 96117 492 (6 mm orifice) M Safety Relief Valve VIII Div. 1 Jan 13, 2023 96128 492 (9 mm orifice) M VIII Div. 1 Jan 13, 2023 Safety Relief Valve 642/6420 (1/2" to 1-1/4"), 645/6450 (1/2" to 1") M 96139 Safety Relief Valve VIII Div. 1 May 16, 2024 642/6420 (1/2" to 1-1/4"), 645/6450 (1/2" to 1") (Liquid) M 96140 May 15, 2024 VIII Div. 1 Relief Valve 96151 M 4000 Dec 13, 2023 Safety Relief Valve VIII Div. 1 96162 4000 (Liquids) M Relief Valve Dec 13, 2023 VIII Div. 1 96195 M 642/6420 (1-1/2" to 2-1/2"), 645/6450 (1-1/4" to 2") VIII Div. 1 May 16, 2024 Safety Relief Valve 96207 M 642/6420 (1-1/2" to 2-1/2"), 645/6450 (1-1/4" to 2") (Liquid) Relief Valve VIII Div. 1 May 15, 2024 GRISS (SPG) location: BP159, Armentieres, FRANCE Acceptable Abbrev.: GRISS Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) NB Cert # Cert Cat Type Classification Device Type Code Section Expiration Date 01045 JOS-E-RL/JBS-E-RL (Restricted Lift version of cert 15208) M VIII Div. 1 Safety Relief Valve Feb 13, 2025 81, 81P, 83, 86 M 01089 VIII Div. 1 Safety Relief Valve May 1, 2021 01102 M 81P (Liquids) Apr 27, 2021 VIII Div. 1 Relief Valve M 01292 243/249/443/449/546/843/849/943/5046/5049/8043/8049 Mar 23, 2021 Pilot Operated Pressure Relief Valve VIII Div. 1 253/259/453/459/853/859/953/959/5059/8053/8059 01304 M VIII Div. 1 Pilot Operated Pressure Relief Valve Dec 5, 2021 M 01315 263/269/463/469/566/863/869/963/969/5066/5069 Dec 5, 2021 Pilot Operated Pressure Relief Valve VIII Div. 1 01326 453/459/853/859/953/959/5059 (Liquids) M Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 25, 2023 01337 443/449/546/843/849/943/949/5046/5049(Liquids) M Pilot Operated Pressure Relief Valve VIII Div. 1 Mar 23, 2021 M 01348 463/469/566/863/869/963/969/5066/5069 (Liquids) May 12, 2021 Pilot Operated Pressure Relief Valve VIII Div. 1 01382 M JLT-JOS-RL/JLT-JBS-RL (Restricted Lift version of Feb 13, 2025 VIII Div. 1 Safety Relief Valve 01393 JLT-JOS-RL/JLT-JBS-RL (Liquids) (Restricted lift version of M Safety Relief Valve Feb 13, 2025 VIII Div. 1 JLT (Liquids) M 15095 VIII Div. 1 Apr 26, 2021 Safety Relief Valve JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 M Safety Relief Valve VIII Div. 1 Feb 25, 2023 15411 M 900 Series, 7700, SNC Apr 12, 2021 VIII Div. 1 Safety Relief Valve 15499 M 900 Series (Liquid), 7700, SNC Relief Valve VIII Div. 1 Apr 11, 2021 BP 15501 M Relief Valve Apr 27, 2021 VIII Div. 1 15512 JLT-JOS, JLT-JBS, 8500, ACL/ABL M Apr 27, 2021 Safety Relief Valve VIII Div. 1 BP (Liquids) 15534 M VIII Div. 1 Relief Valve Apr 26, 2021 Devices designed by: GRISS (SPG) Type Classification Cert Cat Code Section NB Cert # Expiration Date Device Type M 5780-2 & 5781-2 49003 VIII Div. 1 Jun 17, 2019 Safety Relief Valve 8100 49047 M Safety Valve VIII Div. 1 Aug 29, 2020 49058 M 8200 VIII Div. 1 Feb 22, 2025 Relief Valve Page 74 of 812 Effective Date: 2019-05-31

76 Table of Contents Gulf Valve Service Co., LLC (GVS) location: Baton Rouge, LA, UNITED STATES Devices designed by: Dresser, LLC (DRJ) Type Classification Code Section NB Cert # Expiration Date Cert Cat Device Type 1541, 1543, 1541-3, 1543-3 18032 A Aug 16, 2021 I & VIII Div. 1 Safety Valve 1811, 1511 A 18122 Safety Valve Nov 6, 2024 I & VIII Div. 1 1900D-2, 1900-30D-2 18144 A VIII Div. 1 Safety Relief Valve Oct 12, 2024 A 18166 1900E-2, 1900-30E-2 Safety Relief Valve Jun 17, 2024 VIII Div. 1 1900, 1900-30, 1900-35 18201 A Safety Relief Valve VIII Div. 1 Aug 16, 2021 1982 18379 A VIII Div. 1 Nov 5, 2024 Safety Relief Valve 1990 - 3999 LS & DL (Liquids) 18403 A Jun 17, 2019 Relief Valve VIII Div. 1 19000 Series 18706 A Safety Relief Valve VIII Div. 1 Aug 16, 2021 19000 Series, Liquid 18717 A VIII Div. 1 Jun 17, 2024 Relief Valve A 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 VIII Div. 1 Nov 6, 2024 Relief Valve 18762 A 1900E-2, 1900-30E-2 LA & DALA (Liquids) Aug 16, 2021 VIII Div. 1 Relief Valve A 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) Aug 16, 2021 VIII Div. 1 Relief Valve Hansen Technologies Corporation (HTL) location: Commerce, GA, UNITED STATES Devices designed by: Hansen Technologies Corporation (HTL) Device Type NB Cert # Cert Cat Type Classification Code Section Expiration Date 70007 M H5613 Sep 4, 2020 Safety Relief Valve VIII Div. 1 70018 M H5600, H5601 & H5602 Safety Relief Valve VIII Div. 1 Sep 2, 2020 70029 H5604 M Safety Relief Valve VIII Div. 1 Sep 4, 2020 70030 H5600A M Safety Relief Valve Sep 24, 2020 VIII Div. 1 H5600R, H5602R 70041 M VIII Div. 1 Safety Relief Valve Sep 24, 2020 70052 M H5632R VIII Div. 1 Safety Relief Valve Sep 24, 2020 70063 M H5633R Sep 24, 2020 VIII Div. 1 Safety Relief Valve M 70074 H5634R Sep 4, 2020 Safety Relief Valve VIII Div. 1 EZLQ 70085 M VIII Div. 1 Sep 16, 2023 Safety Relief Valve 70096 M EZC Safety Relief Valve Sep 16, 2023 VIII Div. 1 70108 M EZB VIII Div. 1 Safety Relief Valve Nov 23, 2023 70120 M EZE Safety Relief Valve VIII Div. 1 Aug 7, 2023 EZF 70131 M Aug 7, 2023 VIII Div. 1 Safety Relief Valve Henry Technologies Ltd (HNL) location: Hillington Park, Glasgow, Scotland, UNITED KINGDOM Acceptable Abbrev.: HENRY Devices designed by: Henry Technologies Ltd (HNL) Expiration Date Cert Cat Device Type Type Classification Code Section NB Cert # 01764 M 5702, 5702A, 5702B, 5702C Safety Relief Valve VIII Div. 1 May 9, 2025 5230A-S, 5231A-S, 5231B-S 01911 M Safety Valve May 8, 2025 VIII Div. 1 01922 M 5232A-S, 5240-S, 5242-S, 5340-S, 5342-S VIII Div. 1 Safety Valve May 8, 2025 M 5601 & 5602 29113 VIII Div. 1 May 8, 2025 Safety Relief Valve 29124 5603 M Safety Relief Valve VIII Div. 1 Oct 29, 2024 29135 M 5604, 5604-YM, 5604-YP Relief Valve May 8, 2025 VIII Div. 1 5600 29146 M VIII Div. 1 Safety Relief Valve May 8, 2025 Devices designed by: Henry Technologies, Inc. (ACR) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 29180 M 5230AX, 5231AX, 5231BX, 5233AX, 5234AX, 5235AX VIII Div. 1 Oct 3, 2024 Relief Valve Page 75 of 812 Effective Date: 2019-05-31

77 Table of Contents HEROSE GMBH Armaturen Und Metalle (HEG) location: Bad Oldesloe, GERMANY Devices designed by: HEROSE GMBH Armaturen Und Metalle (HEG) Cert Cat Type Classification NB Cert # Expiration Date Code Section Device Type 06388/06418/06383/06413.0704/0706 91011 M Dec 9, 2020 VIII Div. 1 Safety Relief Valve 91077 06388/06418/06383/06413.1510 M Safety Relief Valve Dec 9, 2020 VIII Div. 1 06388/06418/06383/06413.1004/1006 91088 M Dec 9, 2020 Safety Relief Valve VIII Div. 1 06388/06418/06383/06413.2312/2314 M 91101 VIII Div. 1 Apr 18, 2024 Safety Relief Valve 91112 M 06216/06217.0600 Safety Relief Valve VIII Div. 1 May 15, 2024 91123 06216/06217.1000 M Safety Relief Valve VIII Div. 1 Apr 18, 2024 91134 06216/06217.1200 M Safety Relief Valve VIII Div. 1 Apr 18, 2024 M 06216/06217.1400 91145 Apr 18, 2024 VIII Div. 1 Safety Relief Valve 06216/06217.2000 91156 M Apr 18, 2024 VIII Div. 1 Safety Relief Valve 91178 M 06216/06217.0400 Oct 23, 2023 VIII Div. 1 Safety Relief Valve 91189 06420/06421/06425/06426/06440/06441/06445/06446.0704/0706 M Safety Relief Valve VIII Div. 1 May 1, 2021 91190 06420/06421/06425/06426/06440/06441/06445/06446.1004/1006 M Safety Relief Valve Jan 7, 2022 VIII Div. 1 91202 M 06420/06421/06425/06426/06440/06441/06445/06446.2312 (23 VIII Div. 1 May 27, 2021 Safety Relief Valve 91213 06002/06012/06006/06016 M Safety Relief Valve May 27, 2021 VIII Div. 1 91224 M 06381/06386/06416 May 27, 2021 VIII Div. 1 Safety Relief Valve M 91246 06002/06012 gas tight May 27, 2021 Safety Relief Valve VIII Div. 1 06420/06421/06425/06426/06440/06441/06445/06446.1406/1410 91257 M Safety Relief Valve VIII Div. 1 May 27, 2021 91279 06420/06421/06425/06426/06440/06441/06445/06446.1406/.1410 M Safety Relief Valve VIII Div. 1 Jan 7, 2022 91280 M 06420/06421/06425/06426/06440/06441/06445/06446.1810/.1812 Safety Relief Valve Jan 7, 2022 VIII Div. 1 Hui Bao Enterprise Co., Ltd (HBO) location: Ho Mei, Chang Hua Hsien, TAIWAN, REPUBLIC OF CHINA Acceptable Abbrev.: THB Devices designed by: Hui Bao Enterprise Co., Ltd (HBO) Expiration Date Cert Cat Device Type Type Classification Code Section NB Cert # 95037 M T102N Safety Relief Valve VIII Div. 1 Jan 23, 2020 Industrial Steel & Boiler Services, Inc. (ISB) location: Chicopee, MA, UNITED STATES Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Code Section Expiration Date Device Type NB Cert # Cert Cat Type Classification 36076 300,600 A Safety Valve I & VIII Div. 1 Nov 6, 2020 36100 910 to 919 A May 7, 2021 Safety Relief Valve VIII Div. 1 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) 36111 A Relief Valve May 12, 2020 VIII Div. 1 36324 A Kunkle 6000, 6252 Series I & VIII Div. 1 Nov 26, 2020 Safety Valve Page 76 of 812 Effective Date: 2019-05-31

78 Table of Contents Industrial Valve Sales & Service, Incorporated (IVE) location: Mobile, AL, UNITED STATES Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Type Classification Expiration Date NB Cert # Cert Cat Code Section Device Type 81, 81P, 83, 86 01089 A Jul 19, 2022 VIII Div. 1 Safety Relief Valve 81P (Liquids) 01102 A Relief Valve Jul 17, 2020 VIII Div. 1 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 A Pilot Operated Pressure Relief Valve Jul 19, 2022 VIII Div. 1 253/259/453/459/853/859/953/959/5059/8053/8059 01304 A Jul 19, 2022 VIII Div. 1 Pilot Operated Pressure Relief Valve 01326 A 453/459/853/859/953/959/5059 (Liquids) Jul 19, 2022 VIII Div. 1 Pilot Operated Pressure Relief Valve A 01337 443/449/546/843/849/943/949/5046/5049(Liquids) Jul 26, 2020 Pilot Operated Pressure Relief Valve VIII Div. 1 H Series (HCI, HSJ, HCA, HA, HB, HC, HCB, HCP, HJO, HN, 15006 A I & VIII Div. 1 Safety Valve Sep 29, 2020 A 15095 JLT (Liquids) Jul 26, 2020 Safety Relief Valve VIII Div. 1 JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 A Safety Relief Valve Jul 21, 2020 VIII Div. 1 15411 A 900 Series, 7700, SNC Jul 22, 2020 VIII Div. 1 Safety Relief Valve A 900 Series (Liquid), 7700, SNC 15499 Sep 22, 2020 VIII Div. 1 Relief Valve JLT-JOS, JLT-JBS, 8500, ACL/ABL A 15512 Safety Relief Valve VIII Div. 1 Jul 17, 2023 Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Cert Cat Code Section Type Classification Device Type NB Cert # Expiration Date 36324 Kunkle 6000, 6252 Series A I & VIII Div. 1 Safety Valve Jul 21, 2020 Integrated Plant Services (IPS) location: Columbus, OH, UNITED STATES Seal Identification: Integrated Plant Services Devices designed by: Dresser, LLC (DRJ) Device Type Cert Cat Expiration Date Type Classification Code Section NB Cert # 18706 19000 Series A Safety Relief Valve VIII Div. 1 Oct 17, 2024 19000 Series, Liquid 18717 A Relief Valve VIII Div. 1 Oct 17, 2024 Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Type Classification Cert Cat Code Section NB Cert # Expiration Date Device Type 01089 A 81, 81P, 83, 86 Aug 3, 2021 VIII Div. 1 Safety Relief Valve A 15095 JLT (Liquids) Mar 9, 2023 Safety Relief Valve VIII Div. 1 JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 A Safety Relief Valve VIII Div. 1 Mar 9, 2023 15411 900 Series, 7700, SNC A Safety Relief Valve Mar 9, 2023 VIII Div. 1 15499 A 900 Series (Liquid), 7700, SNC Mar 9, 2023 VIII Div. 1 Relief Valve Integrated Pressure Management LLC, an affiliate of AWC, Inc (ITG) location: Deer Park, TX, Devices designed by: Farris Engineering (TFO) NB Cert # Cert Cat Type Classification Expiration Date Device Type Code Section 57024 A 3800 Jun 28, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 3800FP 57035 A Pilot Operated Pressure Relief Valve VIII Div. 1 Jun 28, 2024 57046 A 6400/6600 (previously 2500 & 4600) I & VIII Div. 1 Safety Valve Apr 30, 2025 57057 A 2600 & 2600S Safety Relief Valve VIII Div. 1 Jun 28, 2024 2600L (Liquids) 57068 A Relief Valve Jun 28, 2024 VIII Div. 1 3800L, PCL, PCM pilots 57215 A VIII Div. 1 Jun 28, 2024 Pilot Operated Pressure Relief Valve 57237 2700, 2700S, 3700, 3700S A Safety Relief Valve VIII Div. 1 Jun 28, 2024 57248 2700L, 3700L (Liquids) A Jun 28, 2024 Relief Valve VIII Div. 1 2600L (Air & Steam) 57260 A Safety Relief Valve Jun 28, 2024 VIII Div. 1 57282 A 4200 / 4400 I Apr 30, 2025 Safety Valve Page 77 of 812 Effective Date: 2019-05-31

79 Table of Contents Integrated Pressure Management LLC, an affiliate of AWC, Inc (ITP) location: Corpus Christi, TX, Acceptable Abbrev.: IPM Devices designed by: Farris Engineering (TFO) Expiration Date Cert Cat Code Section Device Type Type Classification NB Cert # 3800 A 57024 Pilot Operated Pressure Relief Valve Feb 27, 2024 VIII Div. 1 3800FP 57035 A VIII Div. 1 Pilot Operated Pressure Relief Valve Feb 27, 2024 A 6400/6600 (previously 2500 & 4600) 57046 Safety Valve Feb 20, 2025 I & VIII Div. 1 2600 & 2600S 57057 A Feb 27, 2024 VIII Div. 1 Safety Relief Valve 57068 2600L (Liquids) A Relief Valve Feb 27, 2024 VIII Div. 1 3800L, PCL, PCM pilots 57215 A Feb 27, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 57237 2700, 2700S, 3700, 3700S A Feb 27, 2024 VIII Div. 1 Safety Relief Valve 2700L, 3700L (Liquids) 57248 A VIII Div. 1 Feb 27, 2024 Relief Valve 57260 2600L (Air & Steam) A Safety Relief Valve VIII Div. 1 Feb 27, 2024 57282 A 4200 / 4400 Feb 20, 2025 I & VIII Div. 1 Safety Valve Integrated Pressure Management, an Affiliate of AWC, Inc. (INP) location: Port Arthur , TX, Acceptable Abbrev.: IPM Devices designed by: Farris Engineering (TFO) Cert Cat Device Type Expiration Date NB Cert # Code Section Type Classification 3800 57024 A VIII Div. 1 Feb 27, 2024 Pilot Operated Pressure Relief Valve 57035 3800FP A VIII Div. 1 Pilot Operated Pressure Relief Valve Feb 27, 2024 A 6400/6600 (previously 2500 & 4600) 57046 I & VIII Div. 1 Jan 15, 2025 Safety Valve 57057 A 2600 & 2600S Safety Relief Valve VIII Div. 1 Feb 27, 2024 57068 2600L (Liquids) A Relief Valve VIII Div. 1 Feb 27, 2024 3800L, PCL, PCM pilots 57215 A Pilot Operated Pressure Relief Valve Feb 27, 2024 VIII Div. 1 2700, 2700S, 3700, 3700S A 57237 VIII Div. 1 Safety Relief Valve Feb 27, 2024 57248 A 2700L, 3700L (Liquids) Feb 27, 2024 VIII Div. 1 Relief Valve A 57260 2600L (Air & Steam) Feb 27, 2024 Safety Relief Valve VIII Div. 1 4200 / 4400 57282 A I & VIII Div. 1 Safety Valve Nov 13, 2024 Jiangsu Reliable Mechanical Equipment Co., Ltd. (JRM) location: Nanjing, Jiangsu Province, PEOPLES REP/CHINA Acceptable Abbrev.: JRME Devices designed by: Jiangsu Reliable Mechanical Equipment Co., Ltd. (JRM) NB Cert # Device Type Expiration Date Type Classification Code Section Cert Cat 00583 M AG-D Series Buckling Pin Non-reclosing Device VIII Div. 1 Aug 11, 2021 IN-P Series (2"-10" NPS) 00897 M Buckling Pin Non-reclosing Device Aug 31, 2022 VIII Div. 1 01540 M IN-P Series (12"-78" NPS) VIII Div. 1 Buckling Pin Non-reclosing Device Aug 28, 2024 Jokwang I.L.I. Co., Ltd. (JOK) location: Yangsan-si, Gyeongsangnam-do, SOUTH KOREA Devices designed by: Jokwang I.L.I. Co., Ltd. (JOK) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 89030 M JSV-FF100 VIII Div. 1 Safety Relief Valve Mar 21, 2023 89041 M JSV-FF100 (Liquid) Safety Relief Valve VIII Div. 1 Mar 21, 2023 JSV-PF100 89052 M Pilot Operated Pressure Relief Valve Feb 27, 2025 VIII Div. 1 JSV-PF100 (Liquid) 89063 M VIII Div. 1 Feb 27, 2025 Pilot Operated Pressure Relief Valve 89074 JSV-FF200 M Safety Valve I & VIII Div. 1 Feb 10, 2021 89085 JSV-FT100 M Mar 22, 2022 Safety Relief Valve VIII Div. 1 JSV-FT100 (Liquid) 89096 M Relief Valve Mar 22, 2022 VIII Div. 1 89108 M JSV-PF200 I Apr 10, 2024 Pilot Operated Pressure Relief Valve Page 78 of 812 Effective Date: 2019-05-31

80 Table of Contents Kunshan Xinxinpeng Mechanical Co. Ltd (KUN) location: Jiangsu Province, PEOPLES REP/CHINA Acceptable Abbrev.: XXP Devices designed by: Kunshan Xinxinpeng Mechanical Co. Ltd (KUN) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification AX-15 14915 M Nov 29, 2023 VIII Div. 1 Safety Relief Valve Lakeside Process Controls, Ltd. (TVA) location: Sarnia, Acceptable Abbrev.: LPC Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Cert Cat Code Section Type Classification Expiration Date Device Type NB Cert # 01292 A 243/249/443/449/546/843/849/943/5046/5049/8043/8049 Nov 1, 2023 VIII Div. 1 Pilot Operated Pressure Relief Valve A 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB Jul 31, 2023 Safety Relief Valve VIII Div. 1 900 Series, 7700, SNC 15411 A Safety Relief Valve VIII Div. 1 Jul 31, 2023 900 Series (Liquid), 7700, SNC A 15499 Relief Valve VIII Div. 1 Jul 31, 2023 Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Expiration Date Code Section Cert Cat Device Type Type Classification NB Cert # A 36076 300,600 Nov 1, 2023 I Safety Valve 910 to 919 36100 A Jul 31, 2023 VIII Div. 1 Safety Relief Valve Kunkle 6000, 6252 Series 36324 A I & VIII Div. 1 Safety Valve Nov 1, 2023 Lakeside Process Controls, Ltd. (VAC) location: Guelph, CANADA Acceptable Abbrev.: LPC Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) NB Cert # Code Section Type Classification Expiration Date Device Type Cert Cat 01089 81, 81P, 83, 86 A VIII Div. 1 Safety Relief Valve Jul 31, 2023 243/249/443/449/546/843/849/943/5046/5049/8043/8049 A 01292 VIII Div. 1 Pilot Operated Pressure Relief Valve Nov 1, 2023 01304 253/259/453/459/853/859/953/959/5059/8053/8059 A Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 31, 2023 A 01315 263/269/463/469/566/863/869/963/969/5066/5069 Pilot Operated Pressure Relief Valve VIII Div. 1 Aug 1, 2023 453/459/853/859/953/959/5059 (Liquids) 01326 A Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 31, 2023 01337 A 443/449/546/843/849/943/949/5046/5049(Liquids) Jul 31, 2023 VIII Div. 1 Pilot Operated Pressure Relief Valve 01348 463/469/566/863/869/963/969/5066/5069 (Liquids) A Pilot Operated Pressure Relief Valve Aug 17, 2023 VIII Div. 1 15095 A JLT (Liquids) VIII Div. 1 Jul 31, 2023 Safety Relief Valve JOS-E/JBS-E/JOS-H-E 8400 AC/AB A 15208 Safety Relief Valve Jul 31, 2023 VIII Div. 1 900 Series, 7700, SNC 15411 A Safety Relief Valve VIII Div. 1 Jul 31, 2023 15499 A 900 Series (Liquid), 7700, SNC VIII Div. 1 Relief Valve Jul 31, 2023 Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) NB Cert # Cert Cat Type Classification Expiration Date Code Section Device Type 36100 A 910 to 919 Nov 1, 2023 Safety Relief Valve VIII Div. 1 36111 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) A Relief Valve VIII Div. 1 Jul 31, 2023 Devices designed by: Farris Engineering (TFO) Expiration Date NB Cert # Cert Cat Type Classification Device Type Code Section 3800FP 57035 A Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 12, 2019 Page 79 of 812 Effective Date: 2019-05-31

81 Table of Contents LAM Valves, Incorporated (LMV) location: Houston, TX, UNITED STATES Seal Identification: LAM Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 920, 921, 927, Agco A (High Temp. water) 36098 A Aug 7, 2024 I Safety Valve 910 to 919 36100 A Safety Relief Valve Aug 7, 2024 VIII Div. 1 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) 36111 A Relief Valve Aug 7, 2024 VIII Div. 1 1, 2 36223 A VIII Div. 1 Safety Valve Aug 8, 2024 36267 A Kunkle 264, 265, 266 & 267 Aug 7, 2024 VIII Div. 1 Safety Relief Valve A 36278 Kunkle 337 Aug 8, 2024 Safety Relief Valve VIII Div. 1 Kunkle 548-A (.295 Orifice) 36290 A VIII Div. 1 Safety Relief Valve May 21, 2024 A 36302 Kunkle 541-C/542-C/548-C (.422 Orifice) May 21, 2024 Safety Relief Valve VIII Div. 1 Kunkle 6000, 6252 Series A 36324 May 21, 2024 Safety Valve I & VIII Div. 1 36469 Kunkle 541-A/542-A (.295 orifice) A May 21, 2024 VIII Div. 1 Safety Relief Valve Laurentide Controls Limited (SIE) location: Kirkland, CANADA Acceptable Abbrev.: Laurentide Controls Devices designed by: Conbraco Industries, Incorporated (CNB) Cert Cat NB Cert # Expiration Date Code Section Type Classification Device Type 11248 A 15-112 (RVA15) Safety Relief Valve VIII Div. 1 Jun 3, 2020 11259 15-115/117 (RVA15) A Jun 3, 2020 Safety Relief Valve VIII Div. 1 11372 A 15-118 (RVA15) Safety Relief Valve VIII Div. 1 Jun 3, 2020 Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type Cert Cat Expiration Date Type Classification NB Cert # Code Section 81, 81P, 83, 86 01089 A Jun 19, 2023 VIII Div. 1 Safety Relief Valve 01102 A 81P (Liquids) VIII Div. 1 Jun 19, 2023 Relief Valve 15095 JLT (Liquids) A Safety Relief Valve VIII Div. 1 Sep 15, 2023 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB A Jun 19, 2023 VIII Div. 1 Safety Relief Valve 900 Series, 7700, SNC 15411 A Jun 19, 2023 Safety Relief Valve VIII Div. 1 900 Series (Liquid), 7700, SNC A 15499 Relief Valve Jun 19, 2023 VIII Div. 1 Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Type Classification Code Section Expiration Date Device Type NB Cert # Cert Cat 36100 910 to 919 A Jun 19, 2023 Safety Relief Valve VIII Div. 1 36111 A 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) Jun 19, 2023 VIII Div. 1 Relief Valve 36278 A Kunkle 337 Safety Relief Valve VIII Div. 1 Jun 19, 2023 Kunkle 6000, 6252 Series 36324 A Safety Valve Jun 19, 2023 I & VIII Div. 1 36335 Kunkle 30 A Jun 19, 2023 Safety Relief Valve VIII Div. 1 C776 36425 A VIII Div. 1 Safety Relief Valve Jun 19, 2023 Devices designed by: Farris Engineering (TFO) Type Classification Cert Cat Expiration Date NB Cert # Code Section Device Type 57057 A 2600 & 2600S Safety Relief Valve VIII Div. 1 Jun 3, 2020 57068 2600L (Liquids) A Relief Valve Jun 25, 2019 VIII Div. 1 2700, 2700S, 3700, 3700S 57237 A VIII Div. 1 Mar 17, 2020 Safety Relief Valve A 57248 2700L, 3700L (Liquids) Relief Valve Apr 24, 2020 VIII Div. 1 Devices designed by: Conbraco Industries, Incorporated (CNB) Expiration Date Device Type Code Section Cert Cat Type Classification NB Cert # A 11248 15-112 (RVA15) Safety Relief Valve Jun 3, 2020 VIII Div. 1 15-115/117 (RVA15) 11259 A VIII Div. 1 Jun 3, 2020 Safety Relief Valve 15-118 (RVA15) 11372 A Safety Relief Valve Jun 3, 2020 VIII Div. 1 Page 80 of 812 Effective Date: 2019-05-31

82 Table of Contents Laurentide Controls Limited (SIE) location: (continued) Kirkland, CANADA Acceptable Abbrev.: Laurentide Controls Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Expiration Date Cert Cat Code Section Device Type Type Classification NB Cert # 81, 81P, 83, 86 01089 A Safety Relief Valve Jun 19, 2023 VIII Div. 1 81P (Liquids) A 01102 Relief Valve Jun 19, 2023 VIII Div. 1 JLT (Liquids) 15095 A Sep 15, 2023 Safety Relief Valve VIII Div. 1 JOS-E/JBS-E/JOS-H-E 8400 AC/AB A 15208 Safety Relief Valve VIII Div. 1 Jun 19, 2023 900 Series, 7700, SNC 15411 A VIII Div. 1 Safety Relief Valve Jun 19, 2023 A 15499 900 Series (Liquid), 7700, SNC Relief Valve VIII Div. 1 Jun 19, 2023 Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Code Section Type Classification Expiration Date Device Type NB Cert # Cert Cat 36100 A 910 to 919 Jun 19, 2023 Safety Relief Valve VIII Div. 1 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) 36111 A Relief Valve VIII Div. 1 Jun 19, 2023 36278 Kunkle 337 A Jun 19, 2023 Safety Relief Valve VIII Div. 1 Kunkle 6000, 6252 Series 36324 A Jun 19, 2023 Safety Valve I & VIII Div. 1 Kunkle 30 A 36335 Safety Relief Valve VIII Div. 1 Jun 19, 2023 C776 36425 A VIII Div. 1 Jun 19, 2023 Safety Relief Valve Devices designed by: Farris Engineering (TFO) NB Cert # Cert Cat Expiration Date Type Classification Code Section Device Type 57057 A 2600 & 2600S Safety Relief Valve Jun 3, 2020 VIII Div. 1 57068 2600L (Liquids) A Relief Valve VIII Div. 1 Jun 25, 2019 57237 2700, 2700S, 3700, 3700S A Safety Relief Valve Mar 17, 2020 VIII Div. 1 2700L, 3700L (Liquids) 57248 A Apr 24, 2020 Relief Valve VIII Div. 1 LCM Industries, Inc. (LCM) location: Odessa, TX, UNITED STATES Devices designed by: Farris Engineering (TFO) NB Cert # Cert Cat Code Section Device Type Type Classification Expiration Date 57024 3800 A VIII Div. 1 Sep 7, 2024 Pilot Operated Pressure Relief Valve 3800FP A 57035 Pilot Operated Pressure Relief Valve VIII Div. 1 Jan 14, 2025 2600 & 2600S A 57057 Sep 7, 2024 VIII Div. 1 Safety Relief Valve A 57068 2600L (Liquids) May 22, 2025 Relief Valve VIII Div. 1 3800L, PCL, PCM pilots 57215 A VIII Div. 1 Sep 7, 2024 Pilot Operated Pressure Relief Valve 57237 2700, 2700S, 3700, 3700S A Safety Relief Valve VIII Div. 1 Sep 7, 2024 A 2700L, 3700L (Liquids) 57248 Sep 7, 2024 VIII Div. 1 Relief Valve LESER - The Safety Valve (Tianjin) Ltd. (LST) location: Tianjin, Devices designed by: LESER GmbH & Company KG (LES) NB Cert # Cert Cat Code Section Expiration Date Device Type Type Classification 441/442/444 37044 M Safety Relief Valve VIII Div. 1 Dec 13, 2023 37055 M 441/442/444 liquids VIII Div. 1 Relief Valve Dec 12, 2023 37101 M 459/462 liquids Relief Valve VIII Div. 1 Dec 13, 2023 459/462 37112 M Safety Relief Valve Dec 12, 2023 VIII Div. 1 526 37224 M VIII Div. 1 Dec 13, 2023 Safety Relief Valve M 37235 526 (Liquids) Relief Valve VIII Div. 1 Dec 12, 2023 37246 M 526D Safety Relief Valve VIII Div. 1 Feb 5, 2025 526D Liquids M 37257 Relief Valve Dec 12, 2023 VIII Div. 1 237, 237IC, 237CC 37325 M Safety Relief Valve Dec 12, 2023 VIII Div. 1 237, 237IC, 237CC (Liquid) 37336 M Relief Valve Dec 13, 2023 VIII Div. 1 Page 81 of 812 Effective Date: 2019-05-31

83 Table of Contents LESER GmbH & Company KG (LES) location: Hohenwestedt, GERMANY Devices designed by: LESER GmbH & Company KG (LES) Type Classification Expiration Date NB Cert # Cert Cat Code Section Device Type 488 37022 M Mar 7, 2023 VIII Div. 1 Safety Relief Valve 37033 488 (Liquids) M Relief Valve Mar 7, 2023 VIII Div. 1 441/442/444 37044 M Feb 5, 2024 VIII Div. 1 Safety Relief Valve 37055 M 441/442/444 liquids Feb 5, 2024 VIII Div. 1 Relief Valve M 37066 455/456/457/458 Group 1 Feb 5, 2024 Safety Relief Valve VIII Div. 1 455/456/457/458 Group 1 (Liq) 37077 M Relief Valve VIII Div. 1 Feb 5, 2024 455/456/457/458 Group 2 37088 M Safety Relief Valve Feb 5, 2024 VIII Div. 1 37099 M 455/456/457/458 Group 2 (Liq) Feb 5, 2024 VIII Div. 1 Relief Valve M 37101 459/462 liquids Feb 5, 2024 Relief Valve VIII Div. 1 459/462 37112 M Safety Relief Valve VIII Div. 1 Feb 5, 2024 37123 447 Air/Gas M Safety Relief Valve Feb 5, 2024 VIII Div. 1 37134 M 447 Liquid Relief Valve VIII Div. 1 Feb 5, 2024 37145 483, 484, 485 (1") M Safety Relief Valve VIII Div. 1 Feb 9, 2023 483, 484, 485 (1") Liquids 37156 M VIII Div. 1 Mar 1, 2023 Relief Valve 37167 483, 484, 485 (1.5") M Safety Relief Valve VIII Div. 1 May 14, 2023 37178 483, 484, 485 (1.5") Liquids M Relief Valve Mar 1, 2023 VIII Div. 1 437 (Liquids) 37189 M Feb 5, 2024 Relief Valve VIII Div. 1 438 Sub Types 481, 439 37190 M Safety Relief Valve Feb 5, 2024 VIII Div. 1 37202 438 Sub Types 481, 439, Liquids M Safety Relief Valve VIII Div. 1 Feb 5, 2024 37213 437 M Safety Relief Valve VIII Div. 1 Feb 5, 2024 37224 526 M Safety Relief Valve VIII Div. 1 Feb 5, 2024 37235 526 (Liquids) M Relief Valve Feb 5, 2024 VIII Div. 1 526D 37246 M Safety Relief Valve Feb 5, 2024 VIII Div. 1 37257 M 526D Liquids VIII Div. 1 Relief Valve Feb 5, 2024 37268 M 820 (liquid) (821) VIII Div. 1 Nov 11, 2020 Pilot Operated Pressure Relief Valve 810/820 (811/821) M 37280 VIII Div. 1 Nov 11, 2020 Pilot Operated Pressure Relief Valve M 37303 526FB (Liquid) Safety Relief Valve VIII Div. 1 Sep 18, 2020 37314 526FB M Sep 18, 2020 Safety Relief Valve VIII Div. 1 237, 237IC, 237CC 37325 M Safety Relief Valve Jan 23, 2024 VIII Div. 1 37336 M 237, 237IC, 237CC (Liquid) VIII Div. 1 Dec 7, 2023 Relief Valve Page 82 of 812 Effective Date: 2019-05-31

84 Table of Contents Leser LLC (LSR) location: Charlotte, NC, UNITED STATES Devices designed by: LESER GmbH & Company KG (LES) Cert Cat Type Classification NB Cert # Expiration Date Code Section Device Type 488 37022 A Jul 12, 2024 VIII Div. 1 Safety Relief Valve 488 (Liquids) 37033 A Relief Valve Jul 12, 2024 VIII Div. 1 441/442/444 37044 A Safety Relief Valve Jul 12, 2024 VIII Div. 1 441/442/444 liquids 37055 A Jul 12, 2024 VIII Div. 1 Relief Valve 37101 A 459/462 liquids Jul 12, 2024 VIII Div. 1 Relief Valve A 37112 459/462 Jul 12, 2024 Safety Relief Valve VIII Div. 1 447 Air/Gas 37123 A VIII Div. 1 Safety Relief Valve Jul 12, 2024 A 37134 447 Liquid Jul 12, 2024 Relief Valve VIII Div. 1 37145 483, 484, 485 (1") A Safety Relief Valve VIII Div. 1 Aug 6, 2024 37156 483, 484, 485 (1") Liquids A Relief Valve VIII Div. 1 Jul 12, 2024 483, 484, 485 (1.5") 37167 A VIII Div. 1 Safety Relief Valve Jul 12, 2024 A 37178 483, 484, 485 (1.5") Liquids Relief Valve VIII Div. 1 Jul 12, 2024 437 (Liquids) 37189 A VIII Div. 1 Jul 12, 2024 Relief Valve 37190 A 438 Sub Types 481, 439 Jun 5, 2024 Safety Relief Valve VIII Div. 1 37202 438 Sub Types 481, 439, Liquids A Safety Relief Valve Jul 12, 2024 VIII Div. 1 37213 A 437 VIII Div. 1 Jul 12, 2024 Safety Relief Valve 37224 A 526 Safety Relief Valve VIII Div. 1 Jul 12, 2024 526 (Liquids) A 37235 Relief Valve Jul 12, 2024 VIII Div. 1 526D 37246 A VIII Div. 1 Aug 30, 2024 Safety Relief Valve 526D Liquids 37257 A Relief Valve VIII Div. 1 Jul 12, 2024 37268 A 820 (liquid) (821) Apr 29, 2021 VIII Div. 1 Pilot Operated Pressure Relief Valve 810/820 (811/821) 37280 A Apr 6, 2021 VIII Div. 1 Pilot Operated Pressure Relief Valve LESER Valvulas de Seguranca Ltda. (PLB) location: Rio de Janeiro CEP, BRAZIL Acceptable Abbrev.: LESER BR Devices designed by: LESER GmbH & Company KG (LES) Cert Cat Type Classification Expiration Date Code Section NB Cert # Device Type 37044 A 441/442/444 Safety Relief Valve Nov 13, 2024 VIII Div. 1 37055 441/442/444 liquids A Relief Valve VIII Div. 1 Nov 13, 2024 37101 A 459/462 liquids VIII Div. 1 Nov 13, 2024 Relief Valve 37112 459/462 A Safety Relief Valve Nov 13, 2024 VIII Div. 1 37189 437 (Liquids) A Nov 13, 2024 Relief Valve VIII Div. 1 438 Sub Types 481, 439 37190 A Safety Relief Valve Nov 12, 2024 VIII Div. 1 37202 A 438 Sub Types 481, 439, Liquids VIII Div. 1 Safety Relief Valve Nov 13, 2024 37213 A 437 Safety Relief Valve VIII Div. 1 Nov 12, 2024 526 37224 A Safety Relief Valve Nov 12, 2024 VIII Div. 1 526 (Liquids) 37235 A VIII Div. 1 Nov 12, 2024 Relief Valve A 37246 526D Safety Relief Valve VIII Div. 1 Nov 12, 2024 37257 A 526D Liquids Relief Valve VIII Div. 1 Nov 12, 2024 Leslie Controls, Inc. (LSH) location: Tampa, FL, UNITED STATES Acceptable Abbrev.: Leslie Devices designed by: Spence Engineering Company, Incorporated (SEC) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 47001 M RXSO and RXSO-S VIII Div. 1 Dec 18, 2019 Safety Relief Valve Page 83 of 812 Effective Date: 2019-05-31

85 Table of Contents Linatex Rubber Products SDN BHD (A Weir Minerals Company) (WRM) location: Batu Caves, Selangor, Acceptable Abbrev.: Weir Sarasin - RSBD Linatex Rubber Products SDN BHD. Devices designed by: Weir Power & Industrial - France (SAR) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 9 Series (Liquids) 44020 A Jun 13, 2023 VIII Div. 1 Safety Relief Valve A 92001 P3, P4, P5 Safety Relief Valve Jun 13, 2023 VIII Div. 1 P3, P4 (liquids) 92012 A Jun 13, 2023 VIII Div. 1 Relief Valve LORCH Sicherheitsventile GmbH & Co. KG, Member of Herose Group (LRH) location: Filderstadt-Bernhausen, GERMANY Devices designed by: LORCH Sicherheitsventile GmbH & Co. KG, Member of Herose Group (LRH) Type Classification Expiration Date NB Cert # Cert Cat Code Section Device Type M 2115 00707 May 31, 2023 VIII Div. 1 Safety Relief Valve 00718 M 2125 Safety Relief Valve VIII Div. 1 Jan 9, 2024 2120 M 00729 Jan 9, 2024 Safety Relief Valve VIII Div. 1 00730 M 2108 May 31, 2023 VIII Div. 1 Safety Relief Valve M 00752 2110 May 31, 2023 Safety Relief Valve VIII Div. 1 2207 00774 M May 31, 2023 VIII Div. 1 Safety Relief Valve M 00785 2212 May 31, 2023 Safety Relief Valve VIII Div. 1 2215 00796 M VIII Div. 1 Safety Relief Valve Jan 9, 2024 Luofu Valve Group Co., Ltd (LVG) location: Zhejiang, PEOPLES REP/CHINA Devices designed by: Luofu Valve Group Co., Ltd (LVG) Code Section Expiration Date Device Type NB Cert # Cert Cat Type Classification 23038 LFO-0101CB 4M6 M Safety Valve Nov 4, 2019 VIII Div. 1 LFO-03a01CB 2H3 23049 M VIII Div. 1 Safety Valve Nov 4, 2019 Mec - Tric Control Company (MCT) location: Charlotte, NC, UNITED STATES Acceptable Abbrev.: MTC Devices designed by: Farris Engineering (TFO) Expiration Date Device Type Cert Cat Type Classification Code Section NB Cert # A 57013 1890, 1892, 1895, 1896 Aug 16, 2022 VIII Div. 1 Safety Relief Valve 57057 A 2600 & 2600S Safety Relief Valve VIII Div. 1 Mar 30, 2023 2600L (Liquids) A 57068 Aug 28, 2022 Relief Valve VIII Div. 1 57237 A 2700, 2700S, 3700, 3700S Safety Relief Valve VIII Div. 1 Mar 30, 2023 57248 2700L, 3700L (Liquids) A Aug 14, 2023 VIII Div. 1 Relief Valve 4200 / 4400 57282 A I Mar 30, 2023 Safety Valve Devices designed by: Spence Engineering Company, Incorporated (SEC) Device Type Code Section Expiration Date Type Classification NB Cert # Cert Cat 65045 A Fig 31, 41, 41A Safety Valve Oct 6, 2022 I & VIII Div. 1 Devices designed by: Farris Engineering (TFO) Device Type Cert Cat NB Cert # Type Classification Code Section Expiration Date 57013 A 1890, 1892, 1895, 1896 VIII Div. 1 Safety Relief Valve Aug 16, 2022 2600 & 2600S 57057 A VIII Div. 1 Safety Relief Valve Mar 30, 2023 57068 A 2600L (Liquids) VIII Div. 1 Relief Valve Aug 28, 2022 A 2700, 2700S, 3700, 3700S 57237 VIII Div. 1 Mar 30, 2023 Safety Relief Valve 57248 2700L, 3700L (Liquids) A Relief Valve Aug 14, 2023 VIII Div. 1 4200 / 4400 57282 A Safety Valve Mar 30, 2023 I Page 84 of 812 Effective Date: 2019-05-31

86 Table of Contents Mec - Tric Control Company (MCT) location: (continued) Charlotte, NC, UNITED STATES Acceptable Abbrev.: MTC Devices designed by: Spence Engineering Company, Incorporated (SEC) Device Type Code Section NB Cert # Expiration Date Type Classification Cert Cat Fig 31, 41, 41A A 65045 Safety Valve Oct 6, 2022 I & VIII Div. 1 Mecklenburg Valve Source, LLC (MCK) location: Charlotte, NC, UNITED STATES Acceptable Abbrev.: Mecklenburg Valve Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Cert Cat NB Cert # Expiration Date Code Section Type Classification Device Type A 36076 300,600 Apr 19, 2023 Safety Valve I & VIII Div. 1 920, 921, 927, Agco A (High Temp. water) 36098 A I Safety Valve May 26, 2023 A 36100 910 to 919 Apr 20, 2023 Safety Relief Valve VIII Div. 1 36111 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) A Apr 19, 2023 Relief Valve VIII Div. 1 36267 A Kunkle 264, 265, 266 & 267 Apr 20, 2023 VIII Div. 1 Safety Relief Valve A 36278 Kunkle 337 Apr 20, 2023 Safety Relief Valve VIII Div. 1 Kunkle 6000, 6252 Series 36324 A I & VIII Div. 1 Safety Valve Apr 19, 2023 Mercer Valve Co., Inc. (MCO) location: Mercer, WI, UNITED STATES Acceptable Abbrev.: MVC Mercer Division Devices designed by: Mercer Valve Company, Incorporated (MVC) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # A 81-100000 Series 38001 VIII Div. 1 Jun 14, 2024 Safety Relief Valve 38023 A 81-200000 Series VIII Div. 1 Jun 14, 2024 Safety Relief Valve 9100 A 38056 VIII Div. 1 Jun 14, 2024 Safety Relief Valve Mercer Valve Co., Inc. Canadian Division (MCD) location: MD Rocky View, Acceptable Abbrev.: Mercer Valve., Inc. Calgary Division Devices designed by: Mercer Valve Company, Incorporated (MVC) Expiration Date Type Classification Cert Cat Device Type Code Section NB Cert # A 81-100000 Series 38001 Sep 11, 2024 VIII Div. 1 Safety Relief Valve 38012 81-100000L Liquids A Relief Valve Sep 11, 2024 VIII Div. 1 38023 A 81-200000 Series VIII Div. 1 Sep 11, 2024 Safety Relief Valve 38056 9100 A Safety Relief Valve VIII Div. 1 Sep 11, 2024 38067 A 9100L (Liquids) Relief Valve VIII Div. 1 Sep 11, 2024 38102 8500 Series A Sep 11, 2024 VIII Div. 1 Safety Relief Valve 1400 Series 38113 A VIII Div. 1 Sep 11, 2024 Safety Relief Valve Mercer Valve Company, Inc. (MVV) location: Houston, TX, UNITED STATES Acceptable Abbrev.: MVC Houston Division Devices designed by: Mercer Valve Company, Incorporated (MVC) Type Classification Device Type NB Cert # Cert Cat Code Section Expiration Date 81-100000 Series 38001 A Safety Relief Valve VIII Div. 1 Nov 20, 2022 81-200000 Series 38023 A VIII Div. 1 Nov 20, 2022 Safety Relief Valve 38056 9100 A Safety Relief Valve VIII Div. 1 Nov 20, 2022 38067 9100L (Liquids) A Nov 20, 2022 Relief Valve VIII Div. 1 9500, S, M, E Pilots 38078 A Pilot Operated Pressure Relief Valve Jun 3, 2023 VIII Div. 1 38089 A 9500 (Full Port), S, M, E Pilots VIII Div. 1 Jun 3, 2023 Pilot Operated Pressure Relief Valve Page 85 of 812 Effective Date: 2019-05-31

87 Table of Contents Mercer Valve Company, Inc. Bridgeport Division (MRB) location: Bridgeport, TX, UNITED STATES Acceptable Abbrev.: MVC Bridgeport Division Devices designed by: Mercer Valve Company, Incorporated (MVC) Expiration Date Cert Cat Code Section Device Type Type Classification NB Cert # 81-100000 Series 38001 A Safety Relief Valve Nov 7, 2020 VIII Div. 1 81-200000 Series A 38023 Safety Relief Valve Nov 7, 2020 VIII Div. 1 9100 38056 A Nov 27, 2020 Safety Relief Valve VIII Div. 1 Mercer Valve Company, Incorporated (MVC) location: Oklahoma City, OK, UNITED STATES Devices designed by: Mercer Valve Company, Incorporated (MVC) Cert Cat Type Classification Device Type NB Cert # Code Section Expiration Date M 81-100000 Series 38001 Feb 21, 2024 VIII Div. 1 Safety Relief Valve 38012 M 81-100000L Liquids Relief Valve VIII Div. 1 Jul 11, 2024 38023 81-200000 Series M Safety Relief Valve VIII Div. 1 Jul 11, 2024 38034 81-200000L Liquids M Relief Valve Jul 13, 2020 VIII Div. 1 87-110000 Series 38045 M Jul 13, 2020 Safety Relief Valve VIII Div. 1 9100 38056 M Safety Relief Valve Jul 13, 2020 VIII Div. 1 38067 9100L (Liquids) M Relief Valve VIII Div. 1 Jul 13, 2020 38078 9500, S, M, E Pilots M Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 2, 2024 38089 9500 (Full Port), S, M, E Pilots M Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 21, 2024 38090 9500 L Series M Pilot Operated Pressure Relief Valve Mar 14, 2024 VIII Div. 1 8500 Series 38102 M Safety Relief Valve VIII Div. 1 Mar 1, 2025 1400 Series M 38113 VIII Div. 1 Safety Relief Valve Jun 24, 2021 Mercury Manufacturing Company (MMC) location: Wyandotte, MI, UNITED STATES Acceptable Abbrev.: MMC Devices designed by: Mercury Manufacturing Company (MMC) Expiration Date Device Type Code Section Cert Cat NB Cert # Type Classification 78016 M MMC-0453-2 Safety Relief Valve VIII Div. 1 Feb 7, 2025 78027 M MMC-0270 Mar 13, 2023 VIII Div. 1 Safety Relief Valve 78038 MMC-TV5 M Safety Relief Valve Feb 6, 2025 VIII Div. 1 78049 M MMC00014, MMC00016 VIII Div. 1 Feb 6, 2025 Safety Relief Valve MMC00410, 411, 412, 420 M 78072 Safety Relief Valve Jun 7, 2019 VIII Div. 1 MMC01410, MMC01411, MMC01412, MMC01420, MMC01421, 78083 M Safety Relief Valve VIII Div. 1 Jun 7, 2025 78296 M MMC00521, MMC00522 VIII Div. 1 Safety Relief Valve Sep 12, 2023 Mersen USA - Salem Branch (COA) location: Salem, VA, UNITED STATES Devices designed by: Mersen USA - Salem Branch (COA) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # M 90111 Series 3 Rupture Disk Device VIII Div. 1 Jan 23, 2021 90122 Series 3 w/Bar Vac. Support M Aug 7, 2020 Rupture Disk Device VIII Div. 1 Series 6 90133 M Rupture Disk Device Apr 20, 2024 VIII Div. 1 90144 M Series 3 w. Dial Vac. Support VIII Div. 1 Jan 23, 2021 Rupture Disk Device Page 86 of 812 Effective Date: 2019-05-31

88 Table of Contents MERSEN Xianda Shanghai Co., Ltd. (MXC) location: Shanghai, Devices designed by: Mersen USA - Salem Branch (COA) Type Classification Code Section NB Cert # Expiration Date Cert Cat Device Type 90111 Series 3 M Oct 2, 2021 VIII Div. 1 Rupture Disk Device Series 3 w/Bar Vac. Support 90122 M Rupture Disk Device Oct 2, 2021 VIII Div. 1 Series 6 90133 M Rupture Disk Device Feb 6, 2021 VIII Div. 1 Midwest Valve Services LLC (MWV) location: Mandan, ND, Acceptable Abbrev.: Novaspect/Midwest Valve Services ND Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Type Classification Device Type Code Section NB Cert # Cert Cat Expiration Date A 01089 81, 81P, 83, 86 Feb 1, 2024 VIII Div. 1 Safety Relief Valve 01102 A 81P (Liquids) Feb 1, 2024 VIII Div. 1 Relief Valve 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 A Pilot Operated Pressure Relief Valve Feb 1, 2024 VIII Div. 1 01304 253/259/453/459/853/859/953/959/5059/8053/8059 A Pilot Operated Pressure Relief Valve Feb 1, 2024 VIII Div. 1 A 263/269/463/469/566/863/869/963/969/5066/5069 01315 Feb 1, 2024 VIII Div. 1 Pilot Operated Pressure Relief Valve 453/459/853/859/953/959/5059 (Liquids) 01326 A Jun 22, 2024 VIII Div. 1 Pilot Operated Pressure Relief Valve A 01337 443/449/546/843/849/943/949/5046/5049(Liquids) Jun 22, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 01348 463/469/566/863/869/963/969/5066/5069 (Liquids) A Pilot Operated Pressure Relief Valve VIII Div. 1 Sep 12, 2024 15095 JLT (Liquids) A Safety Relief Valve Feb 1, 2024 VIII Div. 1 15208 A JOS-E/JBS-E/JOS-H-E 8400 AC/AB VIII Div. 1 Feb 1, 2024 Safety Relief Valve 15411 900 Series, 7700, SNC A Safety Relief Valve VIII Div. 1 Jun 22, 2024 900 Series (Liquid), 7700, SNC 15499 A VIII Div. 1 Feb 1, 2024 Relief Valve JLT-JOS, JLT-JBS, 8500, ACL/ABL 15512 A Safety Relief Valve VIII Div. 1 Feb 1, 2024 Midwest Valve Services, LLC (MID) location: Minooka, IL, UNITED STATES Acceptable Abbrev.: Midwest Valve Services Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type Type Classification Code Section Cert Cat Expiration Date NB Cert # A 81, 81P, 83, 86 01089 Aug 23, 2023 VIII Div. 1 Safety Relief Valve A 01102 81P (Liquids) Aug 23, 2023 Relief Valve I & VIII Div. 1 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 A VIII Div. 1 Pilot Operated Pressure Relief Valve Aug 23, 2023 A 253/259/453/459/853/859/953/959/5059/8053/8059 01304 VIII Div. 1 Aug 23, 2023 Pilot Operated Pressure Relief Valve 01315 A 263/269/463/469/566/863/869/963/969/5066/5069 Pilot Operated Pressure Relief Valve VIII Div. 1 Aug 23, 2023 01326 453/459/853/859/953/959/5059 (Liquids) A Pilot Operated Pressure Relief Valve VIII Div. 1 Aug 23, 2023 443/449/546/843/849/943/949/5046/5049(Liquids) 01337 A VIII Div. 1 Pilot Operated Pressure Relief Valve Aug 23, 2023 463/469/566/863/869/963/969/5066/5069 (Liquids) A 01348 VIII Div. 1 Pilot Operated Pressure Relief Valve Nov 14, 2023 15095 A JLT (Liquids) Safety Relief Valve I & VIII Div. 1 Aug 23, 2023 JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 A Aug 23, 2023 VIII Div. 1 Safety Relief Valve 15411 A 900 Series, 7700, SNC Aug 23, 2023 Safety Relief Valve VIII Div. 1 900 Series (Liquid), 7700, SNC 15499 A Relief Valve Aug 23, 2023 I & VIII Div. 1 A JLT-JOS, JLT-JBS, 8500, ACL/ABL 15512 VIII Div. 1 Aug 23, 2023 Safety Relief Valve Devices designed by: Farris Engineering (TFO) Device Type Cert Cat Expiration Date Type Classification Code Section NB Cert # 57260 2600L (Air & Steam) A Safety Relief Valve May 7, 2021 VIII Div. 1 Page 87 of 812 Effective Date: 2019-05-31

89 Table of Contents Millennium Power Services, Inc. (MPS) location: Fairfield, ME, UNITED STATES Acceptable Abbrev.: MPS Devices designed by: Farris Engineering (TFO) Device Type Expiration Date Code Section NB Cert # Type Classification Cert Cat 2600 & 2600S A 57057 Safety Relief Valve Nov 16, 2022 VIII Div. 1 57068 A 2600L (Liquids) Dec 15, 2022 VIII Div. 1 Relief Valve 2700, 2700S, 3700, 3700S 57237 A VIII Div. 1 Nov 16, 2022 Safety Relief Valve 2700L, 3700L (Liquids) 57248 A VIII Div. 1 Relief Valve Nov 16, 2022 Mobile Valve - Tracy (MVT) location: Tracy, CANADA Acceptable Abbrev.: MVT Devices designed by: Dresser, LLC (DRJ) Device Type Cert Cat Expiration Date Type Classification Code Section NB Cert # 18201 A 1900, 1900-30, 1900-35 VIII Div. 1 Aug 12, 2022 Safety Relief Valve A 18706 19000 Series Aug 12, 2022 Safety Relief Valve VIII Div. 1 19000 Series, Liquid 18717 A Relief Valve VIII Div. 1 Aug 12, 2022 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve VIII Div. 1 Aug 12, 2022 Mobile Valve, a division of Source Atlantic (MVR) location: Mt. Uniacke, CANADA Acceptable Abbrev.: MVR Devices designed by: Dresser, LLC (DRJ) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat A 1541, 1543, 1541-3, 1543-3 18032 I & VIII Div. 1 Aug 17, 2020 Safety Valve 1811, 1511 18122 A Safety Valve Jul 10, 2020 I & VIII Div. 1 Mogas Industries, Incorporated (MII) location: Houston, TX, UNITED STATES Acceptable Abbrev.: MOGAS Devices designed by: Mogas Industries, Incorporated (MII) Cert Cat Device Type Expiration Date Code Section Type Classification NB Cert # M PORV-UM, PORV-UMC 64101 May 1, 2021 Power Actuated Relief Valve I 64112 PORV-UD M Power Actuated Relief Valve I Jul 5, 2020 64123 M PORV-UL Power Actuated Relief Valve I Mar 14, 2024 PORV-UN M 64134 Power Actuated Relief Valve Nov 26, 2024 I M 64145 PORV-UK, PORV-UKC Power Actuated Relief Valve I Aug 7, 2023 Motoyama Engineering Works Limited (MTY) location: Kurokawa-gun, Miyagi-Ken, JAPAN Devices designed by: Motoyama Engineering Works Limited (MTY) Device Type Cert Cat Expiration Date Code Section NB Cert # Type Classification H (HS,HSA,HC,HCA, HJ) 40004 M I & VIII Div. 1 Safety Valve Jul 10, 2019 40015 JLT-JNO, JLT-JNB (Liquids) M VIII Div. 1 Relief Valve Jul 10, 2019 M JNO/JNB 40059 VIII Div. 1 Jul 10, 2019 Safety Relief Valve M 40093 900 (Air, Gas and Steam) Safety Relief Valve Jul 10, 2019 VIII Div. 1 900 (Liquids) 40105 M Safety Relief Valve Jul 10, 2019 VIII Div. 1 Page 88 of 812 Effective Date: 2019-05-31

90 Table of Contents Mt. H Control Valves Co., LTD (MHC) location: Ganseo-gu, Busan, Devices designed by: Mt. H Control Valves Co., LTD (MHC) Type Classification Code Section NB Cert # Expiration Date Cert Cat Device Type SC 32 00549 M Apr 5, 2022 VIII Div. 1 Safety Relief Valve M 00550 SC 32 (Liquid) Safety Relief Valve Sep 29, 2021 VIII Div. 1 SP 32 00561 M Apr 5, 2022 VIII Div. 1 Pilot Operated Pressure Relief Valve SP 32 (Liquid) 00572 M Pilot Operated Pressure Relief Valve VIII Div. 1 Sep 29, 2021 Mueller Refrigeration, LLC (MBC) location: Hartsville, TN, UNITED STATES Acceptable Abbrev.: Block style "M" Devices designed by: Mueller Refrigeration, LLC (MBC) Cert Cat Device Type Expiration Date Type Classification Code Section NB Cert # A15502, A15503, A15512, A15513, A17430, A18774, A18933, 41016 M Safety Relief Valve Feb 13, 2023 VIII Div. 1 41027 A15504, A15514, A15515, B35413, A18736, A18737 M Safety Relief Valve May 3, 2021 VIII Div. 1 A-15506 & B-34444 41049 M VIII Div. 1 May 22, 2020 Safety Relief Valve A-17840, A-18735, & B-34519 41050 M Safety Relief Valve VIII Div. 1 Aug 20, 2020 M 41061 A-17834, B-34580, A-18387, A-18473 Mar 31, 2020 Safety Relief Valve VIII Div. 1 A-17970, A-18443 41072 M Safety Relief Valve May 3, 2021 VIII Div. 1 41083 M A-18356, A-18357, A-18358, A-18540 Safety Relief Valve VIII Div. 1 Mar 21, 2024 41106 A-18422 M Relief Valve VIII Div. 1 Apr 9, 2020 A-18425, A-18444 (Teflon seat) 41117 M VIII Div. 1 Jul 28, 2020 Safety Relief Valve A-18424 (Teflon seat) 41128 M Safety Relief Valve VIII Div. 1 Jul 28, 2020 41162 M 3080A (3075TR, 5730) Mar 22, 2023 VIII Div. 1 Safety Relief Valve M 41173 3000A (3000, 3001, 3001X2, 3002, 3012, 3014, 3015, 3212, 3214, Mar 22, 2023 Safety Relief Valve VIII Div. 1 3020A (3016, 3020, 3020X2, 3216, 3220, 5731AX9, 5733, 5733X2, 41184 M VIII Div. 1 Safety Relief Valve Mar 22, 2023 M 41195 3030A (3030, 3031, 3031X1, 3045, 3045TR, 3045X1) Mar 22, 2023 Safety Relief Valve VIII Div. 1 41207 3060A (3060, 3060FL, 3060X1, 3060X7, 3061X1, 3070, 3075) M Safety Relief Valve VIII Div. 1 Mar 22, 2023 41218 M 3090 Feb 26, 2024 VIII Div. 1 Safety Relief Valve Nakakita Seisakusho Company, Limited (NKK) location: Daito City, Osaka, JAPAN Devices designed by: Nakakita Seisakusho Company, Limited (NKK) NB Cert # Cert Cat Code Section Expiration Date Device Type Type Classification NS255 42039 M Safety Relief Valve VIII Div. 1 Jun 17, 2021 42040 M NS255E (Liquids) Relief Valve VIII Div. 1 Jun 17, 2021 42051 NS255F M Safety Valve I & VIII Div. 1 Apr 12, 2024 42062 NS256 M Pilot Operated Pressure Relief Valve Apr 3, 2021 VIII Div. 1 NS 200JMR 42073 M Relief Valve Apr 18, 2024 VIII Div. 1 Ningbo Yuancheng Equipment Manufacturing Co., Ltd. (NYE) location: Ningbo City, Zhejiang Province, Devices designed by: Ningbo Yuancheng Equipment Manufacturing Co., Ltd. (NYE) Expiration Date NB Cert # Cert Cat Type Classification Device Type Code Section ARBP-16Y-A08 01618 M Buckling Pin Non-reclosing Device VIII Div. 1 Mar 25, 2025 Page 89 of 812 Effective Date: 2019-05-31

91 Table of Contents Nirmal Industrial Controls Pvt. Ltd. (NIC) location: District Thane, Maharashtra, Acceptable Abbrev.: NIRMAL INDIA Devices designed by: Nirmal Industrial Controls Pvt. Ltd. (NIC) Device Type Expiration Date NB Cert # Code Section Type Classification Cert Cat Securamax SR-07 Series M 00819 Safety Relief Valve Jan 26, 2023 VIII Div. 1 00820 M Securamax SR-07 Series (Liquid) May 15, 2025 VIII Div. 1 Safety Relief Valve Securamax (SR-08 Series) M 01595 Safety Relief Valve VIII Div. 1 May 15, 2025 M Securamax (SR-08 Series) (Liquid) 01607 May 15, 2025 VIII Div. 1 Safety Relief Valve Norriseal Wellmark Inc. (NWK) location: Houston, TX, Acceptable Abbrev.: NWM Devices designed by: Norriseal Wellmark Inc. (NWK) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat 66057 M W9503 VIII Div. 1 Mar 4, 2022 Safety Relief Valve M 66068 2600 Series Mar 4, 2022 Safety Relief Valve VIII Div. 1 2600 (Liquid) 66079 M Safety Relief Valve VIII Div. 1 Mar 4, 2022 Norriseal Wellmark Inc. (WLM) location: Oklahoma City, OK, UNITED STATES Acceptable Abbrev.: WLM Devices designed by: Norriseal Wellmark Inc. (NWK) Type Classification Device Type NB Cert # Cert Cat Code Section Expiration Date 2600 Series M 66068 Safety Relief Valve Aug 2, 2024 VIII Div. 1 North American Machine Works, Inc. (ANA) location: Folcroft, PA, UNITED STATES Acceptable Abbrev.: NAMW Devices designed by: Farris Engineering (TFO) NB Cert # Cert Cat Code Section Device Type Type Classification Expiration Date 57002 A 1850, 1850H, 1851, 1852, 1855, 1856M, 2850, 2852, 2856, 2850H Jan 4, 2021 VIII Div. 1 Safety Relief Valve 57024 A 3800 Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 20, 2020 57035 3800FP A Pilot Operated Pressure Relief Valve Aug 16, 2022 VIII Div. 1 57057 A 2600 & 2600S Jan 4, 2021 VIII Div. 1 Safety Relief Valve 57068 A 2600L (Liquids) VIII Div. 1 Relief Valve Dec 21, 2020 57215 A 3800L, PCL, PCM pilots Pilot Operated Pressure Relief Valve VIII Div. 1 Oct 3, 2020 2700, 2700S, 3700, 3700S 57237 A Safety Relief Valve VIII Div. 1 Jan 4, 2021 2700L, 3700L (Liquids) A 57248 VIII Div. 1 Relief Valve Dec 20, 2020 57260 A 2600L (Air & Steam) Safety Relief Valve VIII Div. 1 Jul 9, 2020 4200 / 4400 57282 A Nov 10, 2020 I Safety Valve North American Safety Valve Industries, Inc. (NAS) location: North Kansas City, MO, UNITED STATES Seal Identification: NASVI Devices designed by: Conbraco Industries, Incorporated (CNB) NB Cert # Cert Cat Type Classification Device Type Expiration Date Code Section 19 Series 11282 A Safety Valve I & VIII Div. 1 Aug 22, 2023 Page 90 of 812 Effective Date: 2019-05-31

92 Table of Contents North American Safety Valve Industries, Inc. (NAS) location: (continued) North Kansas City, MO, UNITED STATES Seal Identification: NASVI Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Expiration Date Cert Cat Type Classification Device Type Code Section NB Cert # Kunkle 189, 363, 389 A 36043 Safety Relief Valve Jul 22, 2020 VIII Div. 1 300,600 36076 A I & VIII Div. 1 Safety Valve Jul 22, 2020 A 330. 330S, 333S 36087 Safety Relief Valve Jul 22, 2020 VIII Div. 1 920, 921, 927, Agco A (High Temp. water) 36098 A Jul 22, 2020 I Safety Valve 910 to 919 A 36100 VIII Div. 1 Jul 23, 2020 Safety Relief Valve A 36111 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) Jul 22, 2020 Relief Valve VIII Div. 1 1, 2 36223 A Jul 22, 2020 VIII Div. 1 Safety Valve A 36267 Kunkle 264, 265, 266 & 267 Aug 22, 2023 Safety Relief Valve VIII Div. 1 Kunkle 337 36278 A Safety Relief Valve Jul 23, 2020 VIII Div. 1 36290 Kunkle 548-A (.295 Orifice) A Safety Relief Valve Sep 19, 2020 VIII Div. 1 Kunkle 541-C/542-C/548-C (.422 Orifice) 36302 A Jul 22, 2020 VIII Div. 1 Safety Relief Valve Kunkle 6000, 6252 Series 36324 A Aug 22, 2023 Safety Valve I & VIII Div. 1 36335 Kunkle 30 A Safety Relief Valve VIII Div. 1 Jul 22, 2020 Kunkle 541-A/542-A (.295 orifice) 36469 A Jul 22, 2020 Safety Relief Valve VIII Div. 1 NUOVA GENERAL INSTRUMENTS S.r.l. (NGI) location: Pianello Val Tidone (PC), ITALY Acceptable Abbrev.: Logo: Letter "I" encircled by "G" Devices designed by: NUOVA GENERAL INSTRUMENTS S.r.l. (NGI) NB Cert # Cert Cat Code Section Expiration Date Device Type Type Classification 32500 M A001 Safety Valve VIII Div. 1 Dec 2, 2022 32511 A002 M Safety Valve VIII Div. 1 Mar 9, 2023 Oklahoma Safety Equipment Company, Inc. (OSECO) (OSE) location: Broken Arrow, OK, UNITED STATES Acceptable Abbrev.: OSECO Devices designed by: Oklahoma Safety Equipment Company, Inc. (OSECO) (OSE) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 00011 M FAS, WDA/FAS VIII Div. 1 Rupture Disk Device Jan 9, 2020 00022 M STDV VIII Div. 1 Dec 18, 2019 Rupture Disk Device M 00033 (F) COV Aug 27, 2020 Rupture Disk Device VIII Div. 1 PCR, PCRL 00055 M VIII Div. 1 Rupture Disk Device Jan 9, 2020 M 00077 PSR, PSRL, SSR, SSRL Jan 22, 2021 Rupture Disk Device VIII Div. 1 CO (F) Flat Seat 00190 M Rupture Disk Device VIII Div. 1 Apr 27, 2023 00202 M FAS (Liquid) Jan 25, 2025 VIII Div. 1 Rupture Disk Device 00235 M PROS Rupture Disk Device VIII Div. 1 Feb 26, 2025 GR, GRO M 00246 Rupture Disk Device Feb 16, 2023 VIII Div. 1 FST, FSTL, SST, SSTL 00257 M VIII Div. 1 Jan 25, 2025 Rupture Disk Device M 00268 STD Rupture Disk Device VIII Div. 1 Apr 20, 2021 00279 M (F) STD-OTU Jan 25, 2025 VIII Div. 1 Rupture Disk Device 00381 M PRO +, PRO+L, RPRO+, RPRO+L (air/gas) Rupture Disk Device VIII Div. 1 Sep 20, 2022 00426 OPFTK+ M Rupture Disk Device Jun 20, 2021 VIII Div. 1 00437 M OPFTR+ Rupture Disk Device VIII Div. 1 Jun 29, 2021 OPR+ M 00448 Rupture Disk Device Jun 29, 2021 VIII Div. 1 OPK+ 00459 M Rupture Disk Device VIII Div. 1 Sep 20, 2022 00460 M PRO+KRGL, PRO+KRGL-L Rupture Disk Device VIII Div. 1 Oct 22, 2022 HPSR Welded Assembly M 01472 Rupture Disk Device Feb 17, 2023 VIII Div. 1 HPSR (Liquid) 01742 M Rupture Disk Device Oct 16, 2024 VIII Div. 1 HPSR-LP (Liquid) 01843 M Rupture Disk Device Oct 16, 2024 VIII Div. 1 Page 91 of 812 Effective Date: 2019-05-31

93 Table of Contents Parker Hannifin Corporation (RSP) location: Mauston, WI, UNITED STATES Acceptable Abbrev.: Parker Refrigerating Specialties Division Devices designed by: Parker Hannifin Corporation (RSP) Expiration Date Cert Cat Type Classification Device Type Code Section NB Cert # H-2 45009 M Safety Relief Valve Mar 23, 2021 VIII Div. 1 H-3 M 45010 Safety Relief Valve Apr 13, 2025 VIII Div. 1 H-4 45021 M May 6, 2025 Safety Relief Valve VIII Div. 1 H-5 45032 M VIII Div. 1 Apr 13, 2025 Safety Relief Valve SR1, CSR1 45043 M VIII Div. 1 Oct 2, 2024 Safety Relief Valve SR2, CSR2 45054 M Safety Relief Valve VIII Div. 1 Oct 2, 2024 M 45065 SR3, CSR3 Jul 18, 2024 Safety Relief Valve VIII Div. 1 45076 SR4, CSR4 M Jul 18, 2024 Safety Relief Valve VIII Div. 1 45087 SRH1, SRH2, SRH3, CSRH1, CSRH2, CSRH3 M VIII Div. 1 Jul 18, 2024 Safety Relief Valve SRH5, CSRH5 M 45098 Safety Relief Valve VIII Div. 1 May 6, 2025 SRH4, CSRH4 M 45100 May 28, 2025 VIII Div. 1 Safety Relief Valve 45111 M SR Series (1/2 in. Liquid) Feb 1, 2024 Safety Relief Valve VIII Div. 1 45122 SR Series (3/4 in. Liquid) M Feb 1, 2024 Safety Relief Valve VIII Div. 1 45133 M SR1R Mar 17, 2022 VIII Div. 1 Safety Relief Valve Parker Hannifin Corporation PGI Division (FVC) location: Houston, TX, UNITED STATES Acceptable Abbrev.: PGI Devices designed by: Parker Hannifin Corporation PGI Division (FVC) NB Cert # Cert Cat Type Classification Expiration Date Code Section Device Type 24006 M AA1301A VIII Div. 1 Mar 27, 2025 Safety Relief Valve AA1301B 24017 M Safety Relief Valve VIII Div. 1 Mar 27, 2025 24028 M AA1310A Mar 27, 2025 VIII Div. 1 Safety Relief Valve AA1310B 24039 M Jun 19, 2025 VIII Div. 1 Safety Relief Valve PCE Pacific, Inc. (TSR) location: Everett, WA, UNITED STATES Seal Identification: PCE WA Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Cert Cat Type Classification Expiration Date Code Section NB Cert # Device Type 01089 81, 81P, 83, 86 A VIII Div. 1 Jan 31, 2025 Safety Relief Valve A 81P (Liquids) 01102 VIII Div. 1 Jan 19, 2025 Relief Valve 01292 A 243/249/443/449/546/843/849/943/5046/5049/8043/8049 Pilot Operated Pressure Relief Valve VIII Div. 1 Jan 31, 2025 01304 253/259/453/459/853/859/953/959/5059/8053/8059 A Pilot Operated Pressure Relief Valve Jan 31, 2025 VIII Div. 1 263/269/463/469/566/863/869/963/969/5066/5069 01315 A VIII Div. 1 Jan 31, 2025 Pilot Operated Pressure Relief Valve 453/459/853/859/953/959/5059 (Liquids) 01326 A Pilot Operated Pressure Relief Valve VIII Div. 1 Jan 14, 2025 01337 A 443/449/546/843/849/943/949/5046/5049(Liquids) VIII Div. 1 Jan 14, 2025 Pilot Operated Pressure Relief Valve 01348 A 463/469/566/863/869/963/969/5066/5069 (Liquids) Pilot Operated Pressure Relief Valve VIII Div. 1 Jan 11, 2025 H Series (HCI, HSJ, HCA, HA, HB, HC, HCB, HCP, HJO, HN, A 15006 Safety Valve Dec 8, 2021 I & VIII Div. 1 JLT (Liquids) 15095 A VIII Div. 1 Jan 11, 2025 Safety Relief Valve JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 A Safety Relief Valve VIII Div. 1 Feb 2, 2025 15411 900 Series, 7700, SNC A Jan 31, 2025 Safety Relief Valve VIII Div. 1 900 Series (Liquid), 7700, SNC 15499 A Relief Valve Jan 31, 2025 VIII Div. 1 15512 A JLT-JOS, JLT-JBS, 8500, ACL/ABL VIII Div. 1 Oct 9, 2024 Safety Relief Valve Page 92 of 812 Effective Date: 2019-05-31

94 Table of Contents PCE Pacific, Inc. (TSR) location: (continued) Everett, WA, UNITED STATES Seal Identification: PCE WA Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Expiration Date Cert Cat Device Type Type Classification Code Section NB Cert # 300,600 36076 A Safety Valve Jan 31, 2025 I 920, 921, 927, Agco A (High Temp. water) A 36098 Safety Valve Feb 1, 2025 I 910 to 919 36100 A Jan 31, 2025 Safety Relief Valve VIII Div. 1 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) A 36111 Relief Valve VIII Div. 1 Jan 31, 2025 A Kunkle 337 36278 Jan 31, 2025 Safety Relief Valve VIII Div. 1 Kunkle 6000, 6252 Series 36324 A Feb 2, 2025 I & VIII Div. 1 Safety Valve Pioneer Industrial Corporation (PIC) location: Calvert City, KY, Acceptable Abbrev.: Pioneer Industrial Corporation Calvert City, KY Devices designed by: Dresser, LLC (DRJ) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # A 1541, 1543, 1541-3, 1543-3 18032 I & VIII Div. 1 Sep 26, 2022 Safety Valve 18122 A 1811, 1511 I & VIII Div. 1 Sep 26, 2022 Safety Valve A 18201 1900, 1900-30, 1900-35 Sep 26, 2022 Safety Relief Valve VIII Div. 1 1900, 1900-30, 1900-35 (R.L.) 18223 A Safety Relief Valve VIII Div. 1 Oct 24, 2023 19000 Series 18706 A Safety Relief Valve VIII Div. 1 Sep 26, 2022 18717 A 19000 Series, Liquid Relief Valve VIII Div. 1 Sep 26, 2022 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) A Relief Valve VIII Div. 1 Sep 26, 2022 Pioneer Industrial Corporation (PII) location: Kansas City, MO, UNITED STATES Seal Identification: PII/KC Devices designed by: Dresser, LLC (DRJ) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 1900, 1900-30, 1900-35 A 18201 VIII Div. 1 Safety Relief Valve Jun 8, 2024 18706 A 19000 Series VIII Div. 1 Jun 8, 2024 Safety Relief Valve A 18717 19000 Series, Liquid Feb 7, 2024 Relief Valve VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A VIII Div. 1 Jun 8, 2024 Relief Valve Pioneer Industrial Corporation (PLA) location: Hastings, NE, UNITED STATES Acceptable Abbrev.: PIC Devices designed by: Dresser, LLC (DRJ) Type Classification Cert Cat Expiration Date Device Type NB Cert # Code Section 18122 A 1811, 1511 I & VIII Div. 1 Safety Valve Aug 2, 2024 18144 A 1900D-2, 1900-30D-2 Safety Relief Valve VIII Div. 1 Aug 2, 2024 1900E-2, 1900-30E-2 18166 A VIII Div. 1 Safety Relief Valve Aug 2, 2024 18201 A 1900, 1900-30, 1900-35 VIII Div. 1 Safety Relief Valve Aug 2, 2024 18379 A 1982 Safety Relief Valve VIII Div. 1 Aug 2, 2024 1982 LS, 820000LS 18380 A Relief Valve Aug 2, 2024 VIII Div. 1 19000 Series 18706 A VIII Div. 1 Aug 2, 2024 Safety Relief Valve 18717 19000 Series, Liquid A Relief Valve VIII Div. 1 Aug 2, 2024 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) A Aug 2, 2024 Relief Valve VIII Div. 1 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 A Relief Valve Aug 2, 2024 VIII Div. 1 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) VIII Div. 1 Aug 2, 2024 Relief Valve Page 93 of 812 Effective Date: 2019-05-31

95 Table of Contents Pioneer Industrial Corporation (ZLT) location: St. Louis, MO, UNITED STATES Seal Identification: PIC Devices designed by: Dresser, LLC (DRJ) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat 1541, 1543, 1541-3, 1543-3 A 18032 Safety Valve Feb 7, 2024 I & VIII Div. 1 18100 A 1700 & 2700 Feb 7, 2024 I & VIII Div. 1 Safety Valve 1811, 1511 A 18122 Feb 7, 2024 I & VIII Div. 1 Safety Valve 1900D-2, 1900-30D-2 18144 A VIII Div. 1 Feb 7, 2024 Safety Relief Valve 1900E-2, 1900-30E-2 18166 A Safety Relief Valve VIII Div. 1 Feb 7, 2024 A 18201 1900, 1900-30, 1900-35 Feb 7, 2024 Safety Relief Valve VIII Div. 1 18223 1900, 1900-30, 1900-35 (R.L.) A Feb 7, 2024 Safety Relief Valve VIII Div. 1 18379 A 1982 VIII Div. 1 Feb 11, 2020 Safety Relief Valve A 18706 19000 Series Jun 12, 2024 Safety Relief Valve VIII Div. 1 19000 Series, Liquid 18717 A VIII Div. 1 Relief Valve Jun 12, 2024 A 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) Feb 7, 2024 Relief Valve VIII Div. 1 1900E-2, 1900-30E-2 LA & DALA (Liquids) A 18762 Relief Valve VIII Div. 1 Jun 12, 2024 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) Relief Valve VIII Div. 1 Jun 12, 2024 19077 19110M & 19110H (Liquids) A Relief Valve VIII Div. 1 Feb 7, 2024 Portersville PRD LLC (PRK) location: South Point, OH, UNITED STATES Acceptable Abbrev.: PRD Devices designed by: Farris Engineering (TFO) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat 57057 A 2600 & 2600S Dec 13, 2022 VIII Div. 1 Safety Relief Valve A 57068 2600L (Liquids) Dec 13, 2022 Relief Valve VIII Div. 1 2700, 2700S, 3700, 3700S 57237 A Safety Relief Valve VIII Div. 1 Dec 14, 2022 57248 2700L, 3700L (Liquids) A Relief Valve Dec 14, 2022 VIII Div. 1 Portersville PRD LLC (PRT) location: Blountville, TN, Acceptable Abbrev.: TN Devices designed by: Farris Engineering (TFO) Expiration Date NB Cert # Cert Cat Type Classification Code Section Device Type 57057 A 2600 & 2600S Apr 15, 2022 VIII Div. 1 Safety Relief Valve 2600L (Liquids) 57068 A VIII Div. 1 Apr 15, 2022 Relief Valve 57237 2700, 2700S, 3700, 3700S A Safety Relief Valve VIII Div. 1 Apr 15, 2022 57248 A 2700L, 3700L (Liquids) Apr 15, 2022 VIII Div. 1 Relief Valve 57260 A 2600L (Air & Steam) Safety Relief Valve VIII Div. 1 Apr 15, 2022 Portersville PRD LLC (PRV) location: Richmond, VA, Acceptable Abbrev.: VA Devices designed by: Farris Engineering (TFO) Expiration Date Device Type Type Classification Cert Cat Code Section NB Cert # 2600 & 2600S 57057 A Safety Relief Valve VIII Div. 1 Jan 19, 2024 57068 2600L (Liquids) A Jan 19, 2024 Relief Valve VIII Div. 1 2700, 2700S, 3700, 3700S 57237 A Safety Relief Valve Jan 19, 2024 VIII Div. 1 57248 A 2700L, 3700L (Liquids) VIII Div. 1 Jan 19, 2024 Relief Valve Page 94 of 812 Effective Date: 2019-05-31

96 Table of Contents Portersville PRD LLC. (PTI) location: Tallmadge, OH, UNITED STATES Seal Identification: PRD Technologies, Inc. Devices designed by: Farris Engineering (TFO) Expiration Date Cert Cat Type Classification Device Type Code Section NB Cert # A 2600 & 2600S 57057 VIII Div. 1 Safety Relief Valve Oct 21, 2023 A 57068 2600L (Liquids) Aug 28, 2023 VIII Div. 1 Relief Valve 2700, 2700S, 3700, 3700S A 57237 Safety Relief Valve VIII Div. 1 Aug 23, 2023 2700L, 3700L (Liquids) 57248 A VIII Div. 1 Oct 20, 2023 Relief Valve Portersville PRD LLC. (PVE) location: New Castle, PA, UNITED STATES Devices designed by: Farris Engineering (TFO) Code Section Type Classification Expiration Date Device Type NB Cert # Cert Cat 57024 A 3800 Pilot Operated Pressure Relief Valve Feb 7, 2020 VIII Div. 1 57035 3800FP A Pilot Operated Pressure Relief Valve Feb 10, 2020 VIII Div. 1 6400/6600 (previously 2500 & 4600) 57046 A I & VIII Div. 1 Jul 10, 2021 Safety Valve 2600 & 2600S 57057 A Safety Relief Valve VIII Div. 1 Jul 10, 2021 A 57068 2600L (Liquids) Oct 4, 2019 Relief Valve VIII Div. 1 3800L, PCL, PCM pilots 57215 A Pilot Operated Pressure Relief Valve Oct 4, 2019 VIII Div. 1 57237 A 2700, 2700S, 3700, 3700S Safety Relief Valve VIII Div. 1 Jul 10, 2021 57248 2700L, 3700L (Liquids) A Relief Valve VIII Div. 1 Oct 4, 2019 2600L (Air & Steam) 57260 A VIII Div. 1 Feb 7, 2020 Safety Relief Valve A 57282 4200 / 4400 Safety Valve I & VIII Div. 1 Jul 10, 2021 Precision Fitting and Gauge Company (PFG) location: Tulsa, OK, UNITED STATES Acceptable Abbrev.: PF&G Devices designed by: Dresser, LLC (DRJ) Device Type Type Classification Code Section Cert Cat Expiration Date NB Cert # A 1541, 1543, 1541-3, 1543-3 18032 Jun 5, 2024 I & VIII Div. 1 Safety Valve A 18100 1700 & 2700 Nov 15, 2024 Safety Valve I 1700 & 2700 (Restricted Lift version of Cert. # 18100) 18111 A I Safety Valve Nov 15, 2024 A 1811, 1511 18122 I & VIII Div. 1 Apr 22, 2021 Safety Valve 18144 A 1900D-2, 1900-30D-2 Safety Relief Valve VIII Div. 1 Apr 22, 2021 18166 1900E-2, 1900-30E-2 A Safety Relief Valve VIII Div. 1 Apr 22, 2021 1900, 1900-30, 1900-35 18201 A Safety Relief Valve Apr 22, 2021 VIII Div. 1 18223 A 1900, 1900-30, 1900-35 (R.L.) VIII Div. 1 Safety Relief Valve Apr 21, 2023 18447 A 3900 (39PV, 39MV pilots) Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 26, 2023 3900 (39PV, 39MV pilots, liquid) 18458 A Pilot Operated Pressure Relief Valve Jul 26, 2023 VIII Div. 1 19000 Series 18706 A VIII Div. 1 Apr 27, 2021 Safety Relief Valve 18717 19000 Series, Liquid A Relief Valve VIII Div. 1 Apr 27, 2021 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) A Nov 15, 2024 Relief Valve VIII Div. 1 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 A Relief Valve Nov 8, 2023 VIII Div. 1 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) VIII Div. 1 Apr 21, 2023 Relief Valve Page 95 of 812 Effective Date: 2019-05-31

97 Table of Contents Precision Pump & Valve Service, Incorporated (PPV) location: Cross Lanes, WV, UNITED STATES Devices designed by: Dresser, LLC (DRJ) Type Classification Code Section NB Cert # Expiration Date Cert Cat Device Type 1541, 1543, 1541-3, 1543-3 18032 A Apr 14, 2022 I & VIII Div. 1 Safety Valve 1811, 1511 A 18122 Safety Valve May 25, 2024 I & VIII Div. 1 1900D-2, 1900-30D-2 18144 A VIII Div. 1 Safety Relief Valve Apr 14, 2022 A 18166 1900E-2, 1900-30E-2 Safety Relief Valve May 25, 2024 VIII Div. 1 1900, 1900-30, 1900-35 18201 A Safety Relief Valve VIII Div. 1 Apr 14, 2022 1982 18379 A VIII Div. 1 May 25, 2024 Safety Relief Valve 1982 LS, 820000LS 18380 A Apr 14, 2022 Relief Valve VIII Div. 1 19000 Series 18706 A Safety Relief Valve VIII Div. 1 Apr 17, 2025 19000 Series, Liquid 18717 A VIII Div. 1 Aug 8, 2025 Relief Valve A 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 VIII Div. 1 May 25, 2024 Relief Valve 18762 A 1900E-2, 1900-30E-2 LA & DALA (Liquids) VIII Div. 1 Apr 14, 2022 Relief Valve A 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 Apr 17, 2025 VIII Div. 1 Relief Valve 19077 19110M & 19110H (Liquids) A Relief Valve Mar 5, 2024 VIII Div. 1 Precision Services, Inc. (PUM) location: Louisville, KY, UNITED STATES Devices designed by: Dresser, LLC (DRJ) NB Cert # Expiration Date Device Type Type Classification Code Section Cert Cat 18032 A 1541, 1543, 1541-3, 1543-3 Safety Valve I & VIII Div. 1 Jul 2, 2024 1700 & 2700 18100 A Sep 19, 2023 I & VIII Div. 1 Safety Valve 18122 A 1811, 1511 Sep 20, 2023 Safety Valve I & VIII Div. 1 1900D-2, 1900-30D-2 18144 A Safety Relief Valve Sep 20, 2023 VIII Div. 1 18166 A 1900E-2, 1900-30E-2 VIII Div. 1 Safety Relief Valve Dec 20, 2023 18201 A 1900, 1900-30, 1900-35 Sep 19, 2023 VIII Div. 1 Safety Relief Valve A 18223 1900, 1900-30, 1900-35 (R.L.) Jun 29, 2023 Safety Relief Valve VIII Div. 1 1982 18379 A Safety Relief Valve VIII Div. 1 Sep 19, 2023 18380 1982 LS, 820000LS A Relief Valve VIII Div. 1 Sep 18, 2023 18447 3900 (39PV, 39MV pilots) A Pilot Operated Pressure Relief Valve Sep 20, 2023 VIII Div. 1 18458 A 3900 (39PV, 39MV pilots, liquid) VIII Div. 1 Dec 16, 2023 Pilot Operated Pressure Relief Valve 18706 19000 Series A Safety Relief Valve VIII Div. 1 Sep 19, 2023 19000 Series, Liquid 18717 A VIII Div. 1 Sep 18, 2023 Relief Valve A 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) Relief Valve VIII Div. 1 Sep 18, 2023 18762 A 1900E-2, 1900-30E-2 LA & DALA (Liquids) Sep 18, 2023 VIII Div. 1 Relief Valve 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) Relief Valve VIII Div. 1 Sep 18, 2023 19110M & 19110H (Liquids) 19077 A Relief Valve Dec 16, 2023 VIII Div. 1 Puffer Sweiven, LP (PPC) location: Corpus Christi, TX, UNITED STATES Acceptable Abbrev.: Puffer CC Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 15095 A JLT (Liquids) VIII Div. 1 Safety Relief Valve Jul 12, 2023 A JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 VIII Div. 1 Jul 11, 2023 Safety Relief Valve 15411 900 Series, 7700, SNC A Safety Relief Valve Jul 11, 2023 VIII Div. 1 900 Series (Liquid), 7700, SNC 15499 A Relief Valve Jul 11, 2023 VIII Div. 1 Page 96 of 812 Effective Date: 2019-05-31

98 Table of Contents Puffer Sweiven, LP (PPC) location: (continued) Corpus Christi, TX, UNITED STATES Acceptable Abbrev.: Puffer CC Devices designed by: Farris Engineering (TFO) Expiration Date Cert Cat Device Type Code Section Type Classification NB Cert # A 2600 & 2600S 57057 VIII Div. 1 Safety Relief Valve Sep 9, 2022 A 57068 2600L (Liquids) Sep 9, 2022 VIII Div. 1 Relief Valve 2700, 2700S, 3700, 3700S A 57237 Safety Relief Valve VIII Div. 1 Sep 9, 2022 2700L, 3700L (Liquids) 57248 A VIII Div. 1 Sep 9, 2022 Relief Valve Puffer Sweiven, LP (PPH) location: Houston, TX, Seal Identification: PS-HSC Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Cert Cat Type Classification Expiration Date Device Type Code Section NB Cert # 01089 A 81, 81P, 83, 86 Safety Relief Valve Jul 11, 2023 VIII Div. 1 01102 81P (Liquids) A Relief Valve Jul 11, 2023 VIII Div. 1 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 A VIII Div. 1 Jul 11, 2023 Pilot Operated Pressure Relief Valve 253/259/453/459/853/859/953/959/5059/8053/8059 01304 A Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 11, 2023 A 01315 263/269/463/469/566/863/869/963/969/5066/5069 Jul 11, 2023 Pilot Operated Pressure Relief Valve VIII Div. 1 01326 453/459/853/859/953/959/5059 (Liquids) A Pilot Operated Pressure Relief Valve Jul 11, 2023 VIII Div. 1 01337 A 443/449/546/843/849/943/949/5046/5049(Liquids) Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 18, 2023 01348 463/469/566/863/869/963/969/5066/5069 (Liquids) A Pilot Operated Pressure Relief Valve VIII Div. 1 Jun 14, 2023 15006 H Series (HCI, HSJ, HCA, HA, HB, HC, HCB, HCP, HJO, HN, A Safety Valve Mar 15, 2024 I & VIII Div. 1 JLT (Liquids) 15095 A Safety Relief Valve VIII Div. 1 Jul 11, 2023 JOS-E/JBS-E/JOS-H-E 8400 AC/AB A 15208 VIII Div. 1 Safety Relief Valve Jul 18, 2023 15411 A 900 Series, 7700, SNC Jul 11, 2023 VIII Div. 1 Safety Relief Valve A 15499 900 Series (Liquid), 7700, SNC Jul 12, 2023 Relief Valve VIII Div. 1 JLT-JOS, JLT-JBS, 8500, ACL/ABL 15512 A Safety Relief Valve VIII Div. 1 Jul 11, 2023 Devices designed by: Farris Engineering (TFO) Device Type Cert Cat NB Cert # Type Classification Code Section Expiration Date 57013 A 1890, 1892, 1895, 1896 Safety Relief Valve VIII Div. 1 Feb 2, 2022 3800 57024 A Feb 2, 2022 VIII Div. 1 Pilot Operated Pressure Relief Valve 57035 A 3800FP Jun 13, 2022 Pilot Operated Pressure Relief Valve VIII Div. 1 2600 & 2600S 57057 A Safety Relief Valve VIII Div. 1 Feb 2, 2022 57068 A 2600L (Liquids) VIII Div. 1 Relief Valve Feb 2, 2022 57192 A 1890L, 1892L, 1895L, 1896L (Liquids) VIII Div. 1 Feb 2, 2022 Relief Valve 3800L, PCL, PCM pilots A 57215 VIII Div. 1 Feb 2, 2022 Pilot Operated Pressure Relief Valve A 57237 2700, 2700S, 3700, 3700S Safety Relief Valve VIII Div. 1 Feb 2, 2022 57248 2700L, 3700L (Liquids) A Feb 2, 2022 Relief Valve VIII Div. 1 2600L (Air & Steam) 57260 A Safety Relief Valve Feb 2, 2022 VIII Div. 1 57282 A 4200 / 4400 I Jun 13, 2022 Safety Valve Page 97 of 812 Effective Date: 2019-05-31

99 Table of Contents R. Conrader Company (RCC) location: Erie, PA, UNITED STATES Acceptable Abbrev.: R. Conrader Devices designed by: R. Conrader Company (RCC) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat SRV 187 M 13509 Safety Relief Valve Jun 13, 2025 VIII Div. 1 13510 M SRV 250 May 31, 2025 VIII Div. 1 Safety Relief Valve SRV 390 M 13521 May 31, 2025 VIII Div. 1 Safety Relief Valve SRV 530 13532 M VIII Div. 1 May 31, 2025 Safety Relief Valve SRV 765 13543 M Safety Relief Valve VIII Div. 1 Feb 14, 2025 M 13576 SRH 580 May 23, 2021 Safety Relief Valve VIII Div. 1 13598 SRH 250 M Safety Relief Valve VIII Div. 1 May 23, 2021 13600 SRH 375 M Safety Relief Valve May 23, 2021 VIII Div. 1 M SRS250 13611 Apr 20, 2023 VIII Div. 1 Safety Relief Valve REMBE® GmbH Safety + Control (REM) location: Brilon, GERMANY Acceptable Abbrev.: REMBE Safety Division Devices designed by: REMBE® GmbH Safety + Control (REM) Device Type Cert Cat Expiration Date Code Section Type Classification NB Cert # KUB 84002 M Rupture Disk Device Dec 8, 2022 VIII Div. 1 84013 M ODV Rupture Disk Device Jun 1, 2023 VIII Div. 1 84024 M IKB Jul 5, 2023 Rupture Disk Device VIII Div. 1 M IG-UKB-LS-1 84035 VIII Div. 1 Dec 17, 2024 Rupture Disk Device KUB (Liquid) 84057 M Rupture Disk Device VIII Div. 1 Mar 26, 2021 84068 M STAR-HL (HP) Mar 17, 2023 VIII Div. 1 Rupture Disk Device M 84079 SFD-HL(HP) (Air/Gas) Feb 25, 2025 Rupture Disk Device VIII Div. 1 SFD-HL(HP) (Liquid) 84080 M VIII Div. 1 Rupture Disk Device Feb 25, 2025 Renew Valve and Machine Company, Inc. (REN) location: Carleton, MI, UNITED STATES Acceptable Abbrev.: Renew Valve Devices designed by: Dresser, LLC (DRJ) NB Cert # Cert Cat Type Classification Expiration Date Code Section Device Type A 1541, 1543, 1541-3, 1543-3 18032 I & VIII Div. 1 Jul 27, 2020 Safety Valve 18122 A 1811, 1511 Safety Valve I & VIII Div. 1 Sep 15, 2023 A 1900D-2, 1900-30D-2 18144 VIII Div. 1 Sep 15, 2023 Safety Relief Valve 1900E-2, 1900-30E-2 18166 A Safety Relief Valve VIII Div. 1 Sep 15, 2023 18201 A 1900, 1900-30, 1900-35 Safety Relief Valve VIII Div. 1 Jul 27, 2020 18706 19000 Series A Safety Relief Valve VIII Div. 1 May 14, 2025 18717 19000 Series, Liquid A Relief Valve Jul 27, 2020 VIII Div. 1 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A Relief Valve Sep 15, 2023 VIII Div. 1 A 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 VIII Div. 1 May 14, 2025 Relief Valve A 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) Relief Valve Oct 5, 2023 VIII Div. 1 19110M & 19110H (Liquids) 19077 A Relief Valve Nov 18, 2023 VIII Div. 1 Page 98 of 812 Effective Date: 2019-05-31

100 Table of Contents Richter Chemie-Technik GmbH (IRC) location: Kempen, GERMANY Acceptable Abbrev.: Richter Devices designed by: Richter Chemie-Technik GmbH (IRC) Expiration Date Cert Cat Code Section Device Type Type Classification NB Cert # KSEA Series (restricted lift liquid) 14500 M Safety Relief Valve Nov 17, 2020 VIII Div. 1 KSEA Series (liquid) M 14511 Safety Relief Valve Nov 17, 2020 VIII Div. 1 KSEA Series (restricted lift) 14522 M Nov 17, 2020 Safety Relief Valve VIII Div. 1 14533 KSEA Series M VIII Div. 1 Nov 17, 2020 Safety Relief Valve KSEA Series (1" Liq.) 14544 M Nov 16, 2020 Safety Relief Valve VIII Div. 1 KSEA Series (1" Liq. RL) 14555 M VIII Div. 1 Safety Relief Valve Nov 16, 2020 Robert E. Mason & Associates (MCS) location: Charlotte, NC, UNITED STATES Acceptable Abbrev.: Robert E. Mason & Associates Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) NB Cert # Cert Cat Type Classification Code Section Device Type Expiration Date A 81, 81P, 83, 86 01089 VIII Div. 1 Dec 12, 2024 Safety Relief Valve 01102 A 81P (Liquids) Dec 12, 2024 VIII Div. 1 Relief Valve A 01292 243/249/443/449/546/843/849/943/5046/5049/8043/8049 Dec 12, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 253/259/453/459/853/859/953/959/5059/8053/8059 01304 A Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 13, 2024 01315 263/269/463/469/566/863/869/963/969/5066/5069 A Pilot Operated Pressure Relief Valve Dec 12, 2024 VIII Div. 1 01326 A 453/459/853/859/953/959/5059 (Liquids) Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 12, 2024 443/449/546/843/849/943/949/5046/5049(Liquids) 01337 A Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 12, 2024 463/469/566/863/869/963/969/5066/5069 (Liquids) 01348 A Pilot Operated Pressure Relief Valve Dec 12, 2024 VIII Div. 1 JLT (Liquids) A 15095 VIII Div. 1 Safety Relief Valve Dec 12, 2024 15208 A JOS-E/JBS-E/JOS-H-E 8400 AC/AB Mar 21, 2025 VIII Div. 1 Safety Relief Valve A 15499 900 Series (Liquid), 7700, SNC Dec 12, 2024 VIII Div. 1 Relief Valve S & S Valve Service, Inc. (SSV) location: Metuchen, NJ, UNITED STATES Devices designed by: Conbraco Industries, Incorporated (CNB) Device Type NB Cert # Cert Cat Type Classification Code Section Expiration Date 11282 19 Series A Safety Valve Apr 4, 2025 I & VIII Div. 1 11361 A 119 Series Safety Valve I & VIII Div. 1 Jul 9, 2025 11462 500 Series A Jul 1, 2025 VIII Div. 1 Safety Valve 500 Series (Liquids) 11473 A VIII Div. 1 Apr 4, 2025 Safety Relief Valve S V C Inc. (SVK) location: Gimpo-si, Gyeonggi-Do, SOUTH KOREA Acceptable Abbrev.: SVC Devices designed by: S V C Inc. (SVK) Type Classification Device Type NB Cert # Cert Cat Code Section Expiration Date SSR-S8000, SSR-S8000-B 94159 M Safety Relief Valve VIII Div. 1 Mar 31, 2023 SSRW-S8000, SSRW-S8000-B 94160 M VIII Div. 1 Mar 31, 2023 Relief Valve 94227 SSR-S1100 M Safety Valve I Mar 31, 2023 94238 SSR-S8100, SSR-S8100-B M Mar 31, 2023 Safety Relief Valve VIII Div. 1 SSRW-S8100, SSRW-S8100-B 94249 M Relief Valve Mar 31, 2023 VIII Div. 1 94306 M SVR-30 (SVR-06) III NC Mar 13, 2021 Vacuum Relief Valve Page 99 of 812 Effective Date: 2019-05-31

101 Table of Contents Schlumberger Canada Limited, Cameron - Valves and Measurement (SCL) location: Sarnia, Acceptable Abbrev.: Cameron- Valves and Measurement Devices designed by: Farris Engineering (TFO) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 2600 & 2600S 57057 A Aug 11, 2023 VIII Div. 1 Safety Relief Valve 57068 2600L (Liquids) A Relief Valve Aug 11, 2023 VIII Div. 1 2700, 2700S, 3700, 3700S 57237 A VIII Div. 1 Safety Relief Valve Aug 10, 2023 57248 A 2700L, 3700L (Liquids) Aug 11, 2023 VIII Div. 1 Relief Valve A 57057 2600 & 2600S Aug 11, 2023 Safety Relief Valve VIII Div. 1 2600L (Liquids) 57068 A Relief Valve VIII Div. 1 Aug 11, 2023 57237 2700, 2700S, 3700, 3700S A Safety Relief Valve Aug 10, 2023 VIII Div. 1 57248 A 2700L, 3700L (Liquids) Aug 11, 2023 VIII Div. 1 Relief Valve Seetru Ltd (SEE) location: Bristol, UNITED KINGDOM Devices designed by: Seetru Ltd (SEE) Code Section Expiration Date Device Type Type Classification NB Cert # Cert Cat M 06501 81106,81706,84106,84706,81108,81708,81188,81788,84188, Apr 11, 2023 Safety Relief Valve VIII Div. 1 63110, 64110, 65110, 63710, 64710, 65710 06523 M Safety Relief Valve VIII Div. 1 Apr 13, 2023 06545 M 63113, 64113, 65113, 63713, 64713, 65713 Safety Relief Valve VIII Div. 1 Apr 13, 2023 06556 63118, 64118, 65118, 65718 M Safety Relief Valve VIII Div. 1 Apr 10, 2023 63120, 64120, 65120, 63720, 64720, 65720 06567 M VIII Div. 1 Apr 10, 2023 Safety Relief Valve M 06578 63125, 64125, 65125, 63725, 64725, 65725 Safety Relief Valve VIII Div. 1 Apr 10, 2023 06590 M 319 (In Line Type) Apr 11, 2023 VIII Div. 1 Safety Relief Valve M 06602 81113, 84113, 81713, 84713 Apr 11, 2023 Safety Relief Valve VIII Div. 1 81110, 84110, 81710, 84710 06613 M VIII Div. 1 Safety Relief Valve Apr 11, 2023 M 06646 61118, 61718, 62118, 62718 Feb 15, 2023 Safety Relief Valve VIII Div. 1 61120, 61720, 62120, 62720 06657 M Safety Relief Valve Feb 16, 2023 VIII Div. 1 06679 M 10125, 10725 Safety Relief Valve VIII Div. 1 Jul 7, 2023 06680 81115, 81715, 84115, 84715 M Safety Valve VIII Div. 1 Feb 16, 2023 06691 359 M Safety Relief Valve Feb 14, 2023 VIII Div. 1 319000488 06703 M VIII Div. 1 Safety Valve Mar 29, 2024 32931 M 06714 VIII Div. 1 Safety Valve Feb 14, 2023 Sempell GmbH (SML) location: Korschenbroich, GERMANY Acceptable Abbrev.: Sempell Devices designed by: Sempell GmbH (SML) NB Cert # Cert Cat Code Section Type Classification Expiration Date Device Type 64000 M SO, SC & SB Nov 1, 2024 Safety Relief Valve VIII Div. 1 SM (14 MM) 64022 M Safety Relief Valve VIII Div. 1 Nov 1, 2024 M SM (14 MM) (Liquids) 64033 VIII Div. 1 Aug 30, 2024 Relief Valve M 64066 VS99 Pilot Operated Pressure Relief Valve Sep 30, 2023 III NB SEP 64077 M Power Actuated Relief Valve Apr 4, 2024 I Page 100 of 812 Effective Date: 2019-05-31

102 Table of Contents SETPOINT Integrated Solutions Inc. (ALM) location: Mobile, AL, UNITED STATES Acceptable Abbrev.: SETPOINT Integrated Solutions Devices designed by: Dresser, LLC (DRJ) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 1541, 1543, 1541-3, 1543-3 18032 A Jul 11, 2024 I & VIII Div. 1 Safety Valve 18100 1700 & 2700 A Safety Valve Dec 16, 2022 I & VIII Div. 1 1700 & 2700 (Restricted Lift version of Cert. # 18100) 18111 A I & VIII Div. 1 Safety Valve Oct 20, 2022 18122 A 1811, 1511 Feb 9, 2021 I & VIII Div. 1 Safety Valve A 18144 1900D-2, 1900-30D-2 Feb 8, 2021 Safety Relief Valve VIII Div. 1 1900E-2, 1900-30E-2 18166 A Safety Relief Valve VIII Div. 1 Feb 8, 2021 1900, 1900-30, 1900-35 A 18201 Feb 9, 2021 Safety Relief Valve VIII Div. 1 18223 1900, 1900-30, 1900-35 (R.L.) A Safety Relief Valve Jul 11, 2024 VIII Div. 1 3900 (39PV, 39MV pilots) 18447 A Feb 9, 2021 Pilot Operated Pressure Relief Valve VIII Div. 1 3900 (39PV, 39MV pilots, liquid) 18458 A Pilot Operated Pressure Relief Valve Feb 9, 2021 VIII Div. 1 18706 19000 Series A Safety Relief Valve VIII Div. 1 Feb 9, 2021 18717 19000 Series, Liquid A Relief Valve VIII Div. 1 Feb 9, 2021 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) A Relief Valve VIII Div. 1 Mar 22, 2021 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) A Relief Valve Feb 8, 2021 VIII Div. 1 19110M & 19110H (Liquids) 19077 A Relief Valve Jul 11, 2024 VIII Div. 1 SETPOINT Integrated Solutions Inc. (CCM) location: Monroe, LA, UNITED STATES Devices designed by: Dresser, LLC (DRJ) Expiration Date Device Type Cert Cat Code Section Type Classification NB Cert # A 18032 1541, 1543, 1541-3, 1543-3 Apr 9, 2024 I & VIII Div. 1 Safety Valve 18100 A 1700 & 2700 Safety Valve I & VIII Div. 1 Feb 8, 2021 1811, 1511 A 18122 Apr 9, 2024 Safety Valve I & VIII Div. 1 18144 A 1900D-2, 1900-30D-2 Safety Relief Valve VIII Div. 1 Apr 9, 2024 18166 1900E-2, 1900-30E-2 A Safety Relief Valve VIII Div. 1 Apr 9, 2024 1900, 1900-30, 1900-35 18201 A VIII Div. 1 May 6, 2024 Safety Relief Valve 18379 1982 A Safety Relief Valve VIII Div. 1 Apr 9, 2024 18380 A 1982 LS, 820000LS Relief Valve VIII Div. 1 Mar 14, 2024 18447 3900 (39PV, 39MV pilots) A Pilot Operated Pressure Relief Valve VIII Div. 1 Mar 18, 2021 18706 19000 Series A Safety Relief Valve Mar 14, 2024 VIII Div. 1 19000 Series, Liquid 18717 A Relief Valve Jun 11, 2025 VIII Div. 1 A 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 VIII Div. 1 Apr 10, 2024 Relief Valve A 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) Relief Valve Apr 10, 2024 VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Mar 14, 2024 VIII Div. 1 Page 101 of 812 Effective Date: 2019-05-31

103 Table of Contents SETPOINT Integrated Solutions Inc. (CCS) location: Luling, LA, UNITED STATES Seal Identification: CCS Devices designed by: Dresser, LLC (DRJ) Device Type Expiration Date NB Cert # Code Section Type Classification Cert Cat 1541, 1543, 1541-3, 1543-3 A 18032 Safety Valve Dec 13, 2022 I & VIII Div. 1 1700 & 2700 18100 A Safety Valve Mar 23, 2023 I & VIII Div. 1 A 18111 1700 & 2700 (Restricted Lift version of Cert. # 18100) Safety Valve May 20, 2022 I & VIII Div. 1 1811, 1511 A 18122 Safety Valve I & VIII Div. 1 Sep 7, 2021 A 1900D-2, 1900-30D-2 18144 Dec 15, 2019 Safety Relief Valve VIII Div. 1 1900E-2, 1900-30E-2 18166 A Dec 15, 2019 VIII Div. 1 Safety Relief Valve A 18201 1900, 1900-30, 1900-35 Dec 15, 2019 Safety Relief Valve VIII Div. 1 18223 1900, 1900-30, 1900-35 (R.L.) A Safety Relief Valve Nov 5, 2024 VIII Div. 1 18379 A 1982 VIII Div. 1 Sep 23, 2022 Safety Relief Valve 18380 A 1982 LS, 820000LS Oct 3, 2019 VIII Div. 1 Relief Valve A 18447 3900 (39PV, 39MV pilots) Oct 13, 2020 Pilot Operated Pressure Relief Valve VIII Div. 1 3900 (39PV, 39MV pilots, liquid) 18458 A Pilot Operated Pressure Relief Valve VIII Div. 1 Nov 5, 2024 18706 19000 Series A Safety Relief Valve Mar 23, 2023 VIII Div. 1 18717 A 19000 Series, Liquid Oct 3, 2024 VIII Div. 1 Relief Valve 18751 A 1900D-2, 1900-30D-2 LA & DALA (Liquids) Relief Valve VIII Div. 1 Sep 7, 2021 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 A Relief Valve VIII Div. 1 Oct 20, 2022 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) A Relief Valve Sep 8, 2021 VIII Div. 1 2900 (39PV & 39MV pilots) 18863 A Pilot Operated Pressure Relief Valve VIII Div. 1 Nov 14, 2023 2900 (39PV & 39MV pilots - Liquid) A 18874 VIII Div. 1 Pilot Operated Pressure Relief Valve Nov 14, 2023 SETPOINT Integrated Solutions Inc. (CPA) location: Port Arthur, TX, UNITED STATES Seal Identification: CPA Devices designed by: Dresser, LLC (DRJ) Device Type Cert Cat Code Section Expiration Date Type Classification NB Cert # 18032 1541, 1543, 1541-3, 1543-3 A Safety Valve Jul 20, 2023 I & VIII Div. 1 1700 & 2700 18100 A I & VIII Div. 1 Jul 19, 2023 Safety Valve 18111 1700 & 2700 (Restricted Lift version of Cert. # 18100) A Safety Valve Jul 27, 2023 I & VIII Div. 1 18122 A 1811, 1511 Safety Valve I & VIII Div. 1 Jul 19, 2023 18144 1900D-2, 1900-30D-2 A Safety Relief Valve VIII Div. 1 Jul 19, 2023 18166 1900E-2, 1900-30E-2 A Safety Relief Valve Jul 20, 2023 VIII Div. 1 1900, 1900-30, 1900-35 18201 A Safety Relief Valve VIII Div. 1 Jul 18, 2023 18223 A 1900, 1900-30, 1900-35 (R.L.) VIII Div. 1 Safety Relief Valve Jul 21, 2021 18447 A 3900 (39PV, 39MV pilots) Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 18, 2023 19000 Series 18706 A Safety Relief Valve Jul 22, 2023 VIII Div. 1 19000 Series, Liquid 18717 A VIII Div. 1 Jul 20, 2023 Relief Valve 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) A Relief Valve VIII Div. 1 Jul 27, 2023 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) A Jul 19, 2023 Relief Valve VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Jul 19, 2023 VIII Div. 1 19077 A 19110M & 19110H (Liquids) VIII Div. 1 Jul 27, 2023 Relief Valve Page 102 of 812 Effective Date: 2019-05-31

104 Table of Contents SETPOINT Integrated Solutions Inc. (WLS) location: Sulphur, LA, UNITED STATES Acceptable Abbrev.: SETPOINT Integrated Solutions, Inc. Devices designed by: Dresser, LLC (DRJ) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 1541, 1543, 1541-3, 1543-3 18032 A Sep 10, 2024 I & VIII Div. 1 Safety Valve 1811, 1511 18122 A Safety Valve Sep 2, 2021 I & VIII Div. 1 1900D-2, 1900-30D-2 18144 A Safety Relief Valve Jul 19, 2024 VIII Div. 1 1900E-2, 1900-30E-2 18166 A VIII Div. 1 Safety Relief Valve Jul 19, 2024 18201 A 1900, 1900-30, 1900-35 Jul 19, 2024 VIII Div. 1 Safety Relief Valve A 18379 1982 Oct 15, 2024 Safety Relief Valve VIII Div. 1 3900 (39PV, 39MV pilots) 18447 A VIII Div. 1 Pilot Operated Pressure Relief Valve Apr 24, 2021 A 18458 3900 (39PV, 39MV pilots, liquid) Sep 4, 2021 Pilot Operated Pressure Relief Valve VIII Div. 1 19000 Series A 18706 Safety Relief Valve VIII Div. 1 Jul 19, 2024 18717 A 19000 Series, Liquid Jul 19, 2024 VIII Div. 1 Relief Valve A 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) Jul 19, 2024 Relief Valve VIII Div. 1 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 A Jul 10, 2024 VIII Div. 1 Relief Valve A 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) Jul 19, 2024 Relief Valve VIII Div. 1 Setpoint Integrated Solutions, Inc (SEI) location: Southaven, MS, Devices designed by: Dresser, LLC (DRJ) Expiration Date Cert Cat Type Classification NB Cert # Code Section Device Type 18144 A 1900D-2, 1900-30D-2 Safety Relief Valve VIII Div. 1 Aug 22, 2024 18166 1900E-2, 1900-30E-2 A Safety Relief Valve Aug 22, 2024 VIII Div. 1 1900, 1900-30, 1900-35 18201 A VIII Div. 1 Aug 22, 2024 Safety Relief Valve A 18706 19000 Series Safety Relief Valve VIII Div. 1 Aug 22, 2024 18717 A 19000 Series, Liquid Aug 22, 2024 VIII Div. 1 Relief Valve 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 A Aug 22, 2024 Relief Valve VIII Div. 1 A 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) Aug 22, 2024 VIII Div. 1 Relief Valve 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve VIII Div. 1 Aug 22, 2024 SETPOINT Integrated Solutions, Inc. (SIS) location: La Porte, TX, Seal Identification: SIS Devices designed by: Dresser, LLC (DRJ) NB Cert # Cert Cat Type Classification Expiration Date Code Section Device Type A 1541, 1543, 1541-3, 1543-3 18032 I & VIII Div. 1 May 9, 2024 Safety Valve 18100 A 1700 & 2700 Safety Valve I & VIII Div. 1 Feb 6, 2024 18111 1700 & 2700 (Restricted Lift version of Cert. # 18100) A Safety Valve May 9, 2024 I & VIII Div. 1 1811, 1511 18122 A I & VIII Div. 1 Feb 6, 2024 Safety Valve 1900D-2, 1900-30D-2 18144 A Safety Relief Valve VIII Div. 1 Feb 6, 2024 18166 A 1900E-2, 1900-30E-2 May 9, 2024 VIII Div. 1 Safety Relief Valve 18201 A 1900, 1900-30, 1900-35 Safety Relief Valve VIII Div. 1 Feb 6, 2024 3900 (39PV, 39MV pilots) 18447 A Pilot Operated Pressure Relief Valve Feb 6, 2024 VIII Div. 1 18458 3900 (39PV, 39MV pilots, liquid) A May 8, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 19000 Series 18706 A Safety Relief Valve Feb 6, 2024 VIII Div. 1 18717 A 19000 Series, Liquid VIII Div. 1 Relief Valve Feb 8, 2024 A 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 VIII Div. 1 Feb 8, 2024 Relief Valve 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) A Relief Valve Feb 8, 2024 VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Feb 6, 2024 VIII Div. 1 Page 103 of 812 Effective Date: 2019-05-31

105 Table of Contents SETPOINT Integrated Solutions, Inc. (SET) location: Baton Rouge, LA, Seal Identification: SET on one side, BTR on other side Devices designed by: Dresser, LLC (DRJ) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 1541, 1543, 1541-3, 1543-3 18032 A Sep 4, 2021 I & VIII Div. 1 Safety Valve A 18100 1700 & 2700 Safety Valve Sep 4, 2021 I & VIII Div. 1 1700 & 2700 (Restricted Lift version of Cert. # 18100) 18111 A Jun 18, 2021 I & VIII Div. 1 Safety Valve 1811, 1511 18122 A Safety Valve I & VIII Div. 1 Jun 18, 2021 1900D-2, 1900-30D-2 18144 A III & VIII Div.1 Jun 19, 2021 Safety Relief Valve 1900E-2, 1900-30E-2 18166 A Safety Relief Valve III & VIII Div.1 Jun 19, 2021 A 18201 1900, 1900-30, 1900-35 Jun 19, 2021 Safety Relief Valve III & VIII Div.1 1900, 1900-30, 1900-35 (R.L.) A 18223 Mar 16, 2024 Safety Relief Valve VIII Div. 1 18379 A 1982 Mar 16, 2024 VIII Div. 1 Safety Relief Valve A 18380 1982 LS, 820000LS Mar 16, 2024 Relief Valve VIII Div. 1 3900 (39PV, 39MV pilots) 18447 A VIII Div. 1 Pilot Operated Pressure Relief Valve Sep 4, 2021 A 18458 3900 (39PV, 39MV pilots, liquid) Sep 4, 2021 Pilot Operated Pressure Relief Valve VIII Div. 1 19000 Series 18706 A Safety Relief Valve Jun 21, 2021 VIII Div. 1 18717 A 19000 Series, Liquid Relief Valve VIII Div. 1 Jun 18, 2021 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) A Relief Valve III & VIII Div.1 Jun 19, 2021 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) A Relief Valve Jun 19, 2021 III & VIII Div.1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A III & VIII Div.1 Relief Valve Jun 19, 2021 19110M & 19110H (Liquids) A 19077 VIII Div. 1 Relief Valve Mar 16, 2024 SETPOINT Integrated Solutions, Inc. (STC) location: Corpus Christi, TX, Acceptable Abbrev.: SETPOINT Integrated Solutions Inc. Devices designed by: Dresser, LLC (DRJ) Device Type Cert Cat Code Section Expiration Date Type Classification NB Cert # 18032 1541, 1543, 1541-3, 1543-3 A Safety Valve Dec 6, 2023 I & VIII Div. 1 1700 & 2700 (Restricted Lift version of Cert. # 18100) 18111 A I & VIII Div. 1 Dec 6, 2023 Safety Valve 18122 1811, 1511 A Safety Valve Dec 6, 2023 I & VIII Div. 1 18144 A 1900D-2, 1900-30D-2 Safety Relief Valve VIII Div. 1 Dec 6, 2023 18166 1900E-2, 1900-30E-2 A Safety Relief Valve VIII Div. 1 Dec 6, 2023 18201 1900, 1900-30, 1900-35 A Safety Relief Valve Dec 6, 2023 VIII Div. 1 1900, 1900-30, 1900-35 (R.L.) 18223 A Safety Relief Valve VIII Div. 1 Dec 6, 2023 18447 A 3900 (39PV, 39MV pilots) VIII Div. 1 Pilot Operated Pressure Relief Valve Dec 6, 2023 18458 A 3900 (39PV, 39MV pilots, liquid) Pilot Operated Pressure Relief Valve VIII Div. 1 Dec 7, 2023 19000 Series 18706 A Safety Relief Valve Dec 6, 2023 VIII Div. 1 19000 Series, Liquid 18717 A VIII Div. 1 Dec 6, 2023 Relief Valve 18751 1900D-2, 1900-30D-2 LA & DALA (Liquids) A Relief Valve VIII Div. 1 Dec 6, 2023 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) A Dec 6, 2023 Relief Valve VIII Div. 1 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 A Relief Valve Dec 6, 2023 VIII Div. 1 19077 A 19110M & 19110H (Liquids) III & VIII Div.1 Dec 6, 2023 Relief Valve Page 104 of 812 Effective Date: 2019-05-31

106 Table of Contents SETPOINT Integrated Solutions, Inc. (STR) location: Richwood, TX, Acceptable Abbrev.: EVC Devices designed by: Dresser, LLC (DRJ) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 1541, 1543, 1541-3, 1543-3 18032 A Aug 10, 2024 I & VIII Div. 1 Safety Valve 1700 & 2700 18100 A Safety Valve Dec 5, 2023 I & VIII Div. 1 1700 & 2700 (Restricted Lift version of Cert. # 18100) 18111 A Safety Valve Dec 5, 2023 I & VIII Div. 1 1811, 1511 18122 A I & VIII Div. 1 Safety Valve Dec 4, 2023 18144 A 1900D-2, 1900-30D-2 Dec 4, 2023 VIII Div. 1 Safety Relief Valve A 18166 1900E-2, 1900-30E-2 Dec 4, 2023 Safety Relief Valve VIII Div. 1 1900, 1900-30, 1900-35 18201 A VIII Div. 1 Safety Relief Valve Dec 4, 2023 A 18223 1900, 1900-30, 1900-35 (R.L.) Dec 4, 2023 Safety Relief Valve VIII Div. 1 3900 (39PV, 39MV pilots) A 18447 Dec 4, 2023 Pilot Operated Pressure Relief Valve VIII Div. 1 18458 3900 (39PV, 39MV pilots, liquid) A VIII Div. 1 Dec 4, 2023 Pilot Operated Pressure Relief Valve 19000 Series A 18706 Safety Relief Valve VIII Div. 1 Dec 4, 2023 19000 Series, Liquid A 18717 Dec 4, 2023 VIII Div. 1 Relief Valve 18751 A 1900D-2, 1900-30D-2 LA & DALA (Liquids) Dec 4, 2023 Relief Valve VIII Div. 1 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) A Relief Valve VIII Div. 1 Dec 4, 2023 18784 1900, 1900-30 1900-35 LA & DALA (Liquids) A Relief Valve VIII Div. 1 Dec 4, 2023 18863 A 2900 (39PV & 39MV pilots) VIII Div. 1 Dec 4, 2023 Pilot Operated Pressure Relief Valve 2900 (39PV & 39MV pilots - Liquid) 18874 A Pilot Operated Pressure Relief Valve VIII Div. 1 Aug 10, 2024 19077 A 19110M & 19110H (Liquids) Dec 4, 2023 VIII Div. 1 Relief Valve SETPOINT Integrated Solutions, Incorporated (CCT) location: Kilgore, TX, UNITED STATES Acceptable Abbrev.: Setpoint Integrated Solutions, Inc. Devices designed by: Dresser, LLC (DRJ) NB Cert # Cert Cat Code Section Device Type Type Classification Expiration Date 18100 A 1700 & 2700 Dec 20, 2024 I & VIII Div. 1 Safety Valve A 18111 1700 & 2700 (Restricted Lift version of Cert. # 18100) May 13, 2025 Safety Valve I & VIII Div. 1 1811, 1511 18122 A I & VIII Div. 1 Safety Valve Aug 14, 2019 A 18144 1900D-2, 1900-30D-2 May 14, 2025 Safety Relief Valve VIII Div. 1 18166 1900E-2, 1900-30E-2 A Safety Relief Valve VIII Div. 1 May 14, 2025 18201 A 1900, 1900-30, 1900-35 May 13, 2025 VIII Div. 1 Safety Relief Valve 18447 A 3900 (39PV, 39MV pilots) Pilot Operated Pressure Relief Valve VIII Div. 1 Apr 30, 2020 3900 (39PV, 39MV pilots, liquid) A 18458 Pilot Operated Pressure Relief Valve Apr 30, 2020 VIII Div. 1 19000 Series 18706 A VIII Div. 1 Apr 30, 2020 Safety Relief Valve 19000 Series, Liquid 18717 A Relief Valve Apr 30, 2020 VIII Div. 1 18751 A 1900D-2, 1900-30D-2 LA & DALA (Liquids) Relief Valve VIII Div. 1 May 14, 2025 18762 1900E-2, 1900-30E-2 LA & DALA (Liquids) A Relief Valve May 14, 2025 VIII Div. 1 18784 A 1900, 1900-30 1900-35 LA & DALA (Liquids) Relief Valve May 13, 2025 VIII Div. 1 Shanghai Huali Safety Devices Co., Ltd. (SHS) location: Shanghai, Devices designed by: Shanghai Huali Safety Devices Co., Ltd. (SHS) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat M RM90 01630 VIII Div. 1 Sep 25, 2024 Rupture Disk Device M 01641 RS Rupture Disk Device May 24, 2025 VIII Div. 1 FS 01652 M VIII Div. 1 Sep 25, 2024 Rupture Disk Device DS 01663 M Rupture Disk Device May 24, 2025 VIII Div. 1 Page 105 of 812 Effective Date: 2019-05-31

107 Table of Contents Shanghai Kaite Valve Manufacture Co., Ltd. (SKV) location: Anting, Shanghai, Devices designed by: Shanghai Kaite Valve Manufacture Co., Ltd. (SKV) Type Classification Expiration Date NB Cert # Cert Cat Code Section Device Type 00594 11IG14xxxx M VIII Div. 1 Nov 9, 2021 Safety Relief Valve M 00617 11FH13xxxx Safety Relief Valve Nov 9, 2021 VIII Div. 1 11KH19xxxx 00628 M Nov 9, 2021 VIII Div. 1 Safety Relief Valve 11LL25xxxx M 01551 VIII Div. 1 Safety Relief Valve Apr 25, 2024 South Wales Industrial Valves Services Ltd. (SWI) location: Swansea, West Glam, Wales, UNITED KINGDOM Acceptable Abbrev.: IVS Swansea Wales UK Devices designed by: Farris Engineering (TFO) Type Classification NB Cert # Device Type Code Section Cert Cat Expiration Date A 57068 2600L (Liquids) VIII Div. 1 Mar 17, 2023 Relief Valve 57237 A 2700, 2700S, 3700, 3700S Jun 21, 2023 Safety Relief Valve VIII Div. 1 2700L, 3700L (Liquids) A 57248 Jul 12, 2023 Relief Valve VIII Div. 1 Spartan Controls Ltd. (FIE) location: Edmonton, CANADA Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type Cert Cat Code Section Type Classification Expiration Date NB Cert # 81, 81P, 83, 86 A 01089 Safety Relief Valve VIII Div. 1 Jun 22, 2023 81P (Liquids) 01102 A VIII Div. 1 Jun 22, 2023 Relief Valve 01292 243/249/443/449/546/843/849/943/5046/5049/8043/8049 A Pilot Operated Pressure Relief Valve Jun 22, 2023 VIII Div. 1 01304 A 253/259/453/459/853/859/953/959/5059/8053/8059 VIII Div. 1 Jun 22, 2023 Pilot Operated Pressure Relief Valve 01315 A 263/269/463/469/566/863/869/963/969/5066/5069 Pilot Operated Pressure Relief Valve VIII Div. 1 Jun 22, 2023 453/459/853/859/953/959/5059 (Liquids) 01326 A Pilot Operated Pressure Relief Valve VIII Div. 1 Jun 22, 2023 01337 443/449/546/843/849/943/949/5046/5049(Liquids) A Pilot Operated Pressure Relief Valve Jun 22, 2023 VIII Div. 1 JLT (Liquids) 15095 A VIII Div. 1 Safety Relief Valve Jun 22, 2023 15208 A JOS-E/JBS-E/JOS-H-E 8400 AC/AB VIII Div. 1 Safety Relief Valve Jun 22, 2023 15411 900 Series, 7700, SNC A Jun 22, 2023 VIII Div. 1 Safety Relief Valve 900 Series (Liquid), 7700, SNC 15499 A Jun 22, 2023 Relief Valve VIII Div. 1 JLT-JOS, JLT-JBS, 8500, ACL/ABL A 15512 Safety Relief Valve VIII Div. 1 Jun 22, 2023 BP (Liquids) 15534 A VIII Div. 1 Relief Valve Dec 1, 2023 Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) NB Cert # Cert Cat Type Classification Expiration Date Code Section Device Type A 910 to 919 36100 VIII Div. 1 Mar 14, 2024 Safety Relief Valve 36111 A 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) Relief Valve VIII Div. 1 Dec 1, 2023 A Kunkle 337 36278 VIII Div. 1 Dec 1, 2023 Safety Relief Valve A 36324 Kunkle 6000, 6252 Series Safety Valve Dec 1, 2023 VIII Div. 1 36425 A C776 Safety Relief Valve VIII Div. 1 Dec 1, 2023 Devices designed by: Farris Engineering (TFO) Device Type Cert Cat Expiration Date Type Classification NB Cert # Code Section 3800 57024 A Jan 10, 2024 VIII Div. 1 Pilot Operated Pressure Relief Valve 57057 A 2600 & 2600S VIII Div. 1 Jan 10, 2024 Safety Relief Valve 57068 2600L (Liquids) A Relief Valve VIII Div. 1 Jan 10, 2024 57215 A 3800L, PCL, PCM pilots Pilot Operated Pressure Relief Valve VIII Div. 1 Jan 10, 2024 2700, 2700S, 3700, 3700S A 57237 Safety Relief Valve Jan 10, 2024 VIII Div. 1 2700L, 3700L (Liquids) 57248 A Relief Valve Jan 10, 2024 VIII Div. 1 2600L (Air & Steam) 57260 A Safety Relief Valve Sep 22, 2022 VIII Div. 1 Page 106 of 812 Effective Date: 2019-05-31

108 Table of Contents Spence Engineering Company, Incorporated (SEC) location: Walden, NY, UNITED STATES Acceptable Abbrev.: Spence Eng. Co. Devices designed by: Spence Engineering Company, Incorporated (SEC) Expiration Date Cert Cat Type Classification Device Type NB Cert # Code Section M Fig 10 65001 Safety Valve Jun 13, 2023 IV Fig 31, 41, 41A M 65045 Safety Valve I & VIII Div. 1 Jun 13, 2023 Figure 800 65089 M VIII Div. 1 Safety Relief Valve Aug 21, 2023 Spirax Sarco Ind. Com. Ltda. (SSB) location: Cotia, SP, BRAZIL Acceptable Abbrev.: Spirax Sarco-SXS Devices designed by: Spirax Sarco Ind. Com. Ltda. (SSB) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # M SV80H 48103 VIII Div. 1 Jan 23, 2024 Safety Relief Valve 48114 M SV80H (liquid) Safety Relief Valve Jan 23, 2024 VIII Div. 1 48125 SV81H M Safety Relief Valve VIII Div. 1 Jan 23, 2024 48136 SV81H (liquid) M Safety Relief Valve Jan 23, 2024 VIII Div. 1 Spirax Sarco Limited (SSL) location: Cheltenham, Gloucestershire, UNITED KINGDOM Acceptable Abbrev.: Spirax Sarco Devices designed by: Spirax Sarco Limited (SSL) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date SV7 M 71020 I & VIII Div. 1 Safety Valve Oct 12, 2023 Spirax Sarco, Incorporated (SPS) location: Blythewood, SC, UNITED STATES Acceptable Abbrev.: Spirax Sarco Devices designed by: Spirax Sarco Limited (SSL) Device Type Cert Cat Expiration Date Code Section Type Classification NB Cert # SV7 71020 A Safety Valve I & VIII Div. 1 Oct 21, 2019 St. Gabriel Valve Service, LLC (SGV) location: St. Gabriel, LA, UNITED STATES Seal Identification: St. Gabriel Valve Devices designed by: Conbraco Industries, Incorporated (CNB) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 11282 A 19 Series I & VIII Div. 1 Safety Valve Nov 17, 2020 A 119 Series 11361 I & VIII Div. 1 Nov 17, 2020 Safety Valve 11462 500 Series A Safety Valve Jan 17, 2023 VIII Div. 1 500 Series (Liquids) 11473 A Safety Relief Valve Jan 17, 2023 VIII Div. 1 Page 107 of 812 Effective Date: 2019-05-31

109 Table of Contents Stover Controls (RSO) location: Marshalltown, IA, Acceptable Abbrev.: SC Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Expiration Date Cert Cat Code Section Device Type NB Cert # Type Classification A 81, 81P, 83, 86 01089 Safety Relief Valve Aug 27, 2024 VIII Div. 1 81P (Liquids) 01102 A Relief Valve Aug 27, 2024 VIII Div. 1 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 A VIII Div. 1 Aug 27, 2024 Pilot Operated Pressure Relief Valve 253/259/453/459/853/859/953/959/5059/8053/8059 01304 A Pilot Operated Pressure Relief Valve VIII Div. 1 Aug 27, 2024 01315 A 263/269/463/469/566/863/869/963/969/5066/5069 VIII Div. 1 Aug 27, 2024 Pilot Operated Pressure Relief Valve 01326 A 453/459/853/859/953/959/5059 (Liquids) Pilot Operated Pressure Relief Valve VIII Div. 1 Jan 8, 2025 443/449/546/843/849/943/949/5046/5049(Liquids) A 01337 Pilot Operated Pressure Relief Valve Aug 27, 2024 VIII Div. 1 JLT (Liquids) 15095 A III & VIII Div.1 Aug 27, 2024 Safety Relief Valve JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 A Safety Relief Valve Aug 27, 2024 III & VIII Div.1 15411 A 900 Series, 7700, SNC Safety Relief Valve III & VIII Div.1 Aug 27, 2024 15499 900 Series (Liquid), 7700, SNC A Relief Valve Aug 27, 2024 III & VIII Div.1 15512 A JLT-JOS, JLT-JBS, 8500, ACL/ABL Safety Relief Valve Aug 27, 2024 VIII Div. 1 Stritt & Priebe, Incorporated (STP) location: Buffalo, NY, UNITED STATES Devices designed by: Conbraco Industries, Incorporated (CNB) Device Type NB Cert # Expiration Date Type Classification Code Section Cert Cat A 19 Series 11282 I & VIII Div. 1 Oct 12, 2022 Safety Valve A 11361 119 Series Safety Valve Oct 12, 2022 I & VIII Div. 1 500 Series 11462 A VIII Div. 1 Oct 12, 2022 Safety Valve 500 Series (Liquids) 11473 A Safety Relief Valve Oct 12, 2022 VIII Div. 1 Page 108 of 812 Effective Date: 2019-05-31

110 Table of Contents Suzhou BS&B Safety Systems Co., Ltd (SIP) location: Suzhou Industrial Park, Jiangsu, PEOPLES REP/CHINA Devices designed by: BS & B Safety Systems, LLC (BSB) Type Classification Expiration Date NB Cert # Cert Cat Code Section Device Type JRS 77015 M Nov 21, 2019 VIII Div. 1 Rupture Disk Device BV, BRV, BSV, BRSV 77026 M Rupture Disk Device VIII Div. 1 Jun 26, 2025 M 77037 B, BR, BRR Rupture Disk Device VIII Div. 1 Oct 17, 2024 77048 M DV, D, DR, DRR, DRV Rupture Disk Device Jul 10, 2023 VIII Div. 1 RLS, RLS Welded Assemly 77059 M Nov 13, 2024 Rupture Disk Device VIII Div. 1 S90, S90 Welded Assembly M 77082 VIII Div. 1 Oct 17, 2024 Rupture Disk Device M 77105 GFR-S, -SM, -SE, -SS, -SMS, -SES (1") Dec 21, 2022 Rupture Disk Device VIII Div. 1 GFR-S, -SM, -SE, -SS, -SMS, -SES (1.5") 77116 M VIII Div. 1 Rupture Disk Device Feb 10, 2023 M 77127 GFR-S, -SM, -SE, -SS, -SMS, -SES (2") Dec 20, 2022 Rupture Disk Device VIII Div. 1 77138 RB-90 M Rupture Disk Device Nov 21, 2019 VIII Div. 1 77206 M S-90 (Inconel) Oct 17, 2024 VIII Div. 1 Rupture Disk Device GFR-S, -SM, -SE, -SS, -SMS, -SES 1 1/2" Liquid 77239 M Dec 20, 2022 Rupture Disk Device VIII Div. 1 M 77273 BV,BRV,BSV,BRSV (liquid) Oct 18, 2024 VIII Div. 1 Rupture Disk Device FRS 77284 M Rupture Disk Device VIII Div. 1 Jan 12, 2023 RLS, RLS Welded Assembly (liquid) 77307 M VIII Div. 1 Nov 13, 2024 Rupture Disk Device B, BR, BRR (liquid) 77318 M Rupture Disk Device Sep 17, 2020 VIII Div. 1 77341 M AV Nov 21, 2019 VIII Div. 1 Rupture Disk Device 77352 M D Series (liquid) DR, DRR Rupture Disk Device VIII Div. 1 May 2, 2025 GCR-S,SE,SM,SS,SES,SMS, SW, N, NS (2") 77420 M Rupture Disk Device Nov 21, 2019 VIII Div. 1 77486 2" BV M Oct 17, 2024 Rupture Disk Device VIII Div. 1 2" B 77497 M Rupture Disk Device VIII Div. 1 Oct 17, 2024 77611 M GCR-S, SE, SM, SS, SES, SMS, SW, N, NS VIII Div. 1 Rupture Disk Device Feb 11, 2023 77734 M DV, DRV, DSV, DRSV (liquids) Sep 11, 2020 VIII Div. 1 Rupture Disk Device M 78195 GCR-S, SE, SM, SS, SES, SMS, SW, N, NS (liquids) Dec 20, 2022 Rupture Disk Device VIII Div. 1 GCR-S,SE,SM,SS,SES,SMS, SW, N, NS (2" liquids) 78207 M VIII Div. 1 Rupture Disk Device Dec 20, 2022 M 78364 AVV Oct 18, 2024 Rupture Disk Device VIII Div. 1 Devices designed by: BS & B Safety Systems, Ltd. (BSI) NB Cert # Device Type Expiration Date Type Classification Code Section Cert Cat 77149 A XT Rupture Disk Device Sep 11, 2020 VIII Div. 1 78094 XT (Liquid) M Rupture Disk Device VIII Div. 1 Sep 11, 2020 78229 SRD & CCS M Rupture Disk Device Jan 12, 2023 VIII Div. 1 78230 M SRD & CCS (Liquid) VIII Div. 1 Jan 12, 2023 Rupture Disk Device 78241 SRD-L & CCS-L M Rupture Disk Device VIII Div. 1 Jan 12, 2023 78252 M SRD-L & CCS-L (Liquid) Jan 12, 2023 VIII Div. 1 Rupture Disk Device Devices designed by: Suzhou BS&B Safety Systems Co., Ltd (SIP) Device Type Expiration Date Cert Cat Type Classification Code Section NB Cert # 01720 BPSV M Buckling Pin Non-reclosing Device May 2, 2025 VIII Div. 1 Swan Associates, Incorporated (SWA) location: Benicia, CA, UNITED STATES Seal Identification: SAI Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 15095 A JLT (Liquids) VIII Div. 1 Safety Relief Valve Mar 11, 2024 A JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 VIII Div. 1 May 2, 2024 Safety Relief Valve 15411 900 Series, 7700, SNC A Safety Relief Valve Mar 11, 2024 VIII Div. 1 900 Series (Liquid), 7700, SNC 15499 A Relief Valve Mar 11, 2024 VIII Div. 1 Page 109 of 812 Effective Date: 2019-05-31

111 Table of Contents Swan Associates, Incorporated (SWA) location: (continued) Benicia, CA, UNITED STATES Seal Identification: SAI Devices designed by: Farris Engineering (TFO) Expiration Date Cert Cat Type Classification Device Type Code Section NB Cert # A 57057 2600 & 2600S Jan 30, 2020 VIII Div. 1 Safety Relief Valve 2600L (Liquids) 57068 A Relief Valve VIII Div. 1 Nov 5, 2019 57237 A 2700, 2700S, 3700, 3700S Jan 31, 2020 Safety Relief Valve VIII Div. 1 2700L, 3700L (Liquids) 57248 A VIII Div. 1 Relief Valve May 6, 2020 TAI Milano SpA (TAI) location: Guardamiglio (Lodi), ITALY Devices designed by: TAI Milano SpA (TAI) NB Cert # Cert Cat Expiration Date Device Type Type Classification Code Section Series 3000A 45515 M VIII Div. 1 Apr 12, 2021 Safety Valve 45526 M Series 3000W VIII Div. 1 Apr 12, 2021 Safety Relief Valve Series 4000 45537 M Safety Valve VIII Div. 1 Apr 14, 2021 45548 M Series 4000W VIII Div. 1 Safety Relief Valve Jul 18, 2022 45559 M Series 9000 / 60, 70, 90 pilots Air/Gas Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 4, 2022 Series 9000 / 70, 603,701, 703 Pilots (Liquids) 45560 M Pilot Operated Pressure Relief Valve Feb 4, 2022 VIII Div. 1 Series 9000 R / 60, 70, 90 pilots, Air/Gas 45582 M VIII Div. 1 Feb 4, 2022 Pilot Operated Pressure Relief Valve M 45593 Series 9000 R / 70, 603, 701, 703 Pilots (Liquid) Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 4, 2022 45616 M 3000W (Steam & Air/Gas) Safety Relief Valve VIII Div. 1 Apr 12, 2021 Taizhou Luqiao Jia Ben Pump Casting Factory (CBM) location: Taizhou, Zhejiang, Acceptable Abbrev.: Jiaben Devices designed by: Taizhou Luqiao Jia Ben Pump Casting Factory (CBM) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 00673 M V100 VIII Div. 1 Mar 17, 2022 Safety Relief Valve Page 110 of 812 Effective Date: 2019-05-31

112 Table of Contents Target Rock Corporation (TRC) location: East Farmingdale, NY, UNITED STATES Devices designed by: Target Rock Corporation (TRC) Type Classification Expiration Date NB Cert # Cert Cat Code Section Device Type 6AB (Class 1,2 & 3) 55099 M Mar 1, 2023 III Safety Valve 55101 6AC (Class 1,2 & 3) M Safety Valve Mar 1, 2023 III NB, NC, ND 6BH 55123 M Jul 14, 2020 III NC, ND Vacuum Relief Valve 55156 M 6AH (Class 2 & 3) Mar 1, 2023 III Safety Relief Valve M 55167 6AK (78D016 Class 1, 2 & 3) Mar 1, 2023 Safety Relief Valve III 67F 55213 M Pilot Operated Pressure Relief Valve III Mar 1, 2023 69C 55224 M Pilot Operated Pressure Relief Valve Oct 7, 2021 III NB, NC, ND 55235 M 76A Mar 1, 2023 III Safety Valve M 55246 7567F Mar 1, 2023 Pilot Operated Pressure Relief Valve III 2VRES-S-1 55280 M Vacuum Relief Valve III Oct 25, 2024 55291 6AD, Liquids M Safety Relief Valve Jul 10, 2024 III NB, NC, ND 55303 M 6AR Safety Relief Valve III Oct 25, 2024 55314 6AS M Safety Relief Valve III Oct 25, 2024 6AO, 93R-024 55325 M III Oct 25, 2024 Safety Relief Valve 55347 6AM M Safety Relief Valve III Oct 25, 2024 55369 6AN M Safety Relief Valve Oct 25, 2024 III 93R-022A 55370 M Mar 1, 2023 Safety Relief Valve III 6AU 55381 M Relief Valve Jan 25, 2021 III NB, NC, ND 55392 6AV M Safety Relief Valve III Sep 27, 2024 55415 6AW (98V-005-3) M Safety Relief Valve III Jul 7, 2021 55426 6AX (98V-005-2) M Safety Relief Valve III Jun 9, 2021 55437 6AY (97N-006) M Safety Relief Valve Jun 9, 2021 III 6BA (97N-016) 55493 M Vacuum Relief Valve Nov 3, 2021 III NB, NC, ND 55505 M 6AZ (97N-014) III Safety Relief Valve Aug 1, 2021 55516 M 6BB III ND Feb 13, 2023 Vacuum Relief Valve 6BC M 55527 III Oct 31, 2019 Safety Relief Valve M 55538 6BD Safety Valve III NB, NC, ND Mar 20, 2020 55549 6BE (08U-007) M May 27, 2023 Vacuum Relief Valve III ND 6BF (08U-017) 55550 M Vacuum Relief Valve May 5, 2023 III ND 55561 M 6BG (08U-011) III ND Jul 8, 2023 Vacuum Relief Valve Page 111 of 812 Effective Date: 2019-05-31

113 Table of Contents Taylor Valve Technology, Incorporated (TTS) location: Oklahoma City, OK, UNITED STATES Devices designed by: Taylor Valve Technology, Incorporated (TTS) Cert Cat Type Classification NB Cert # Expiration Date Code Section Device Type 83-004000 56045 M Apr 26, 2024 VIII Div. 1 Safety Relief Valve 83-004000 (Liquid) 56078 M Relief Valve Apr 26, 2024 VIII Div. 1 8250 Series 56124 M Safety Relief Valve May 2, 2025 VIII Div. 1 82-025000, 82-035000 56146 M Aug 25, 2024 Safety Relief Valve VIII Div. 1 82-025000, 82-035000 (Liquids) M 56157 VIII Div. 1 Aug 24, 2024 Relief Valve M 56168 82-055000, 82-065000 Aug 24, 2024 Safety Relief Valve VIII Div. 1 82-055000, 82-065000 (Liquids) 56179 M Relief Valve VIII Div. 1 Aug 24, 2024 56180 82-005000 M Safety Relief Valve VIII Div. 1 Jun 23, 2025 56191 83-001000 (Liquids) M Safety Relief Valve VIII Div. 1 Sep 21, 2022 56203 83-001000 (Air and Gas) M Safety Relief Valve VIII Div. 1 Aug 4, 2025 M 56214 83-002000 (Air and Gas) Oct 22, 2025 VIII Div. 1 Safety Relief Valve 82-004000 56225 M Safety Relief Valve Sep 10, 2024 VIII Div. 1 82-007000 56247 M Nov 13, 2025 VIII Div. 1 Safety Relief Valve 56269 82-006000 M Safety Relief Valve VIII Div. 1 Sep 10, 2024 56304 M 632 Series (Liquids) VIII Div. 1 Jun 27, 2021 Relief Valve 9300, 9300M 56315 M Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 3, 2025 9300FB 56326 M VIII Div. 1 Feb 13, 2025 Pilot Operated Pressure Relief Valve 56371 9300M M Pilot Operated Pressure Relief Valve Feb 2, 2024 VIII Div. 1 56382 8250 Series (Liquid) M Safety Relief Valve VIII Div. 1 May 7, 2025 M 56630 Model C- Rupture Pin Relief Valve Buckling Pin Non-reclosing Device VIII Div. 1 Nov 14, 2024 Model C- Rupture Pin Relief Valve (Liquid) 56641 M Buckling Pin Non-reclosing Device VIII Div. 1 Nov 14, 2024 Team Industrial Services Inc. (FAB) location: Benicia, CA, UNITED STATES Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Device Type Cert Cat Expiration Date Type Classification Code Section NB Cert # 01089 A 81, 81P, 83, 86 Safety Relief Valve VIII Div. 1 Nov 12, 2019 81P (Liquids) 01102 A Relief Valve Nov 12, 2019 VIII Div. 1 15006 A H Series (HCI, HSJ, HCA, HA, HB, HC, HCB, HCP, HJO, HN, I & VIII Div. 1 Safety Valve Feb 7, 2020 A JLT (Liquids) 15095 VIII Div. 1 Nov 12, 2019 Safety Relief Valve 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB A Safety Relief Valve Feb 7, 2020 VIII Div. 1 15411 A 900 Series, 7700, SNC Safety Relief Valve Jan 31, 2020 VIII Div. 1 900 Series (Liquid), 7700, SNC 15499 A Relief Valve Nov 12, 2019 VIII Div. 1 Devices designed by: Farris Engineering (TFO) Expiration Date Device Type NB Cert # Cert Cat Type Classification Code Section A 57057 2600 & 2600S Safety Relief Valve VIII Div. 1 Aug 2, 2023 57068 A 2600L (Liquids) Relief Valve VIII Div. 1 Aug 2, 2023 2700, 2700S, 3700, 3700S A 57237 Safety Relief Valve Aug 2, 2023 VIII Div. 1 2700L, 3700L (Liquids) 57248 A Relief Valve Aug 2, 2023 VIII Div. 1 2600L (Air & Steam) 57260 A Safety Relief Valve Aug 2, 2023 VIII Div. 1 Page 112 of 812 Effective Date: 2019-05-31

114 Table of Contents Team Industrial Services Inc. / TeamFurmanite Div. (HMT) location: Kent, WA, UNITED STATES Acceptable Abbrev.: TEAM Devices designed by: Farris Engineering (TFO) Expiration Date Cert Cat Code Section Device Type Type Classification NB Cert # 2600 & 2600S A 57057 Safety Relief Valve Apr 30, 2024 VIII Div. 1 2600L (Liquids) 57068 A VIII Div. 1 Relief Valve Nov 17, 2024 A 2700, 2700S, 3700, 3700S 57237 Safety Relief Valve Apr 30, 2024 VIII Div. 1 2700L, 3700L (Liquids) 57248 A Apr 30, 2024 VIII Div. 1 Relief Valve 57282 4200 / 4400 A Safety Valve Apr 30, 2024 I & VIII Div. 1 2600 & 2600S 57057 A Apr 30, 2024 Safety Relief Valve VIII Div. 1 57068 2600L (Liquids) A Nov 17, 2024 VIII Div. 1 Relief Valve 2700, 2700S, 3700, 3700S 57237 A VIII Div. 1 Apr 30, 2024 Safety Relief Valve 57248 2700L, 3700L (Liquids) A Relief Valve VIII Div. 1 Apr 30, 2024 57282 A 4200 / 4400 Apr 30, 2024 I & VIII Div. 1 Safety Valve Team Industrial Services Inc. / TeamFurmanite Div. (PSL) location: Sulphur, LA, UNITED STATES Acceptable Abbrev.: TeamFurmanite Devices designed by: Farris Engineering (TFO) Cert Cat Device Type Expiration Date NB Cert # Code Section Type Classification 3800 57024 A VIII Div. 1 Feb 5, 2024 Pilot Operated Pressure Relief Valve 57035 3800FP A VIII Div. 1 Pilot Operated Pressure Relief Valve Feb 5, 2024 A 6400/6600 (previously 2500 & 4600) 57046 I & VIII Div. 1 Feb 5, 2024 Safety Valve 57057 A 2600 & 2600S Safety Relief Valve VIII Div. 1 Feb 5, 2024 57068 2600L (Liquids) A Relief Valve VIII Div. 1 Feb 5, 2024 3800L, PCL, PCM pilots 57215 A Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 5, 2024 2700, 2700S, 3700, 3700S A 57237 VIII Div. 1 Safety Relief Valve Feb 5, 2024 57248 2700L, 3700L (Liquids) A Feb 5, 2024 Relief Valve VIII Div. 1 2600L (Air & Steam) 57260 A Feb 5, 2024 Safety Relief Valve VIII Div. 1 4200 / 4400 A 57282 Safety Valve I Feb 5, 2024 Team Industrial Services Inc. / TeamFurmanite Div. (TMF) location: Mobile, AL, Acceptable Abbrev.: TeamFurmanite Devices designed by: Farris Engineering (TFO) NB Cert # Code Section Type Classification Expiration Date Device Type Cert Cat A 1890, 1892, 1895, 1896 57013 VIII Div. 1 Mar 13, 2023 Safety Relief Valve 57024 A 3800 Pilot Operated Pressure Relief Valve VIII Div. 1 May 1, 2023 57035 3800FP A Pilot Operated Pressure Relief Valve VIII Div. 1 Mar 13, 2023 6400/6600 (previously 2500 & 4600) 57046 A Safety Valve I Mar 14, 2023 57057 A 2600 & 2600S VIII Div. 1 Safety Relief Valve Mar 13, 2023 57068 A 2600L (Liquids) Relief Valve VIII Div. 1 Mar 13, 2023 1890L, 1892L, 1895L, 1896L (Liquids) 57192 A Relief Valve Mar 13, 2023 VIII Div. 1 3800L, PCL, PCM pilots 57215 A VIII Div. 1 Mar 13, 2023 Pilot Operated Pressure Relief Valve 57237 2700, 2700S, 3700, 3700S A Safety Relief Valve VIII Div. 1 Mar 14, 2023 57248 2700L, 3700L (Liquids) A Mar 13, 2023 Relief Valve VIII Div. 1 2600L (Air & Steam) 57260 A Safety Relief Valve Mar 13, 2023 VIII Div. 1 57282 A 4200 / 4400 I Mar 14, 2023 Safety Valve Page 113 of 812 Effective Date: 2019-05-31

115 Table of Contents Team Industrial Services, Inc. / D.K. Amans Div. (FTO) location: Long Beach, CA, UNITED STATES Acceptable Abbrev.: DK Amans Valve Devices designed by: Farris Engineering (TFO) Expiration Date Cert Cat Code Section Device Type Type Classification NB Cert # A 2600 & 2600S 57057 VIII Div. 1 Safety Relief Valve Apr 5, 2023 A 57068 2600L (Liquids) Mar 28, 2023 VIII Div. 1 Relief Valve 2700, 2700S, 3700, 3700S 57237 A VIII Div. 1 Mar 28, 2023 Safety Relief Valve 2700L, 3700L (Liquids) 57248 A VIII Div. 1 Relief Valve Mar 28, 2023 2600L (Air & Steam) 57260 A Mar 28, 2023 Safety Relief Valve VIII Div. 1 57282 4200 / 4400 A Safety Valve I Apr 5, 2023 Team Industrial Services, Inc. / TEAMFURMANITE Div. (TME) location: Geismar, LA, Acceptable Abbrev.: TeamFurmanite Devices designed by: Farris Engineering (TFO) Cert Cat Expiration Date Device Type NB Cert # Code Section Type Classification A 57057 2600 & 2600S Safety Relief Valve Mar 19, 2024 VIII Div. 1 57068 2600L (Liquids) A Relief Valve VIII Div. 1 Nov 27, 2023 57215 A 3800L, PCL, PCM pilots Pilot Operated Pressure Relief Valve VIII Div. 1 Nov 27, 2023 2700, 2700S, 3700, 3700S 57237 A Safety Relief Valve Nov 27, 2023 VIII Div. 1 2700L, 3700L (Liquids) A 57248 VIII Div. 1 Relief Valve Nov 27, 2023 57260 2600L (Air & Steam) A Nov 27, 2023 VIII Div. 1 Safety Relief Valve 4200 / 4400 57282 A I Safety Valve Nov 28, 2023 Technical S.R.L. (TCI) location: Vignate, Milano, ITALY Devices designed by: Technical S.R.L. (TCI) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # M Series 10000 74135 VIII Div. 1 Jun 14, 2023 Safety Relief Valve 74146 M Series 20000 Dec 13, 2022 Safety Relief Valve VIII Div. 1 Series 30000 74157 M Safety Relief Valve VIII Div. 1 Dec 13, 2022 74179 M Series 30000 (Liquid) Safety Relief Valve VIII Div. 1 Jan 18, 2023 TOA Valve Engineering Inc. (TOA) location: Amagasaki-shi, Hyogo, JAPAN Acceptable Abbrev.: TVE Devices designed by: TOA Valve Engineering Inc. (TOA) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date M A1700 01450 I & VIII Div. 1 Sep 26, 2023 Safety Valve 01461 A1900 M Power Actuated Relief Valve Aug 25, 2023 I Page 114 of 812 Effective Date: 2019-05-31

116 Table of Contents Total Valve Systems (TVO) location: Broken Arrow, OK, UNITED STATES Acceptable Abbrev.: TVS Devices designed by: Farris Engineering (TFO) Expiration Date Cert Cat Code Section Device Type Type Classification NB Cert # 3800 A 57024 Pilot Operated Pressure Relief Valve Mar 14, 2023 VIII Div. 1 A 57057 2600 & 2600S Safety Relief Valve Apr 11, 2024 VIII Div. 1 57068 2600L (Liquids) A Apr 4, 2023 VIII Div. 1 Relief Valve 57237 2700, 2700S, 3700, 3700S A Safety Relief Valve VIII Div. 1 Apr 11, 2023 2700L, 3700L (Liquids) 57248 A VIII Div. 1 Relief Valve Apr 4, 2023 2600L (Air & Steam) 57260 A Apr 11, 2023 Safety Relief Valve VIII Div. 1 4200 / 4400 57282 A Safety Valve I Apr 11, 2023 Devices designed by: Total Valve Systems (TVO) Expiration Date Code Section Cert Cat Device Type Type Classification NB Cert # 00606 M TRV 6820 VIII Div. 1 Sep 22, 2020 TRANSWATER API SDN. BHD. (TRW) location: Shah Alam, Devices designed by: Farris Engineering (TFO) Device Type Expiration Date Cert Cat Type Classification Code Section NB Cert # 57057 A 2600 & 2600S Safety Relief Valve VIII Div. 1 Oct 21, 2022 57068 2600L (Liquids) A Relief Valve Oct 21, 2022 VIII Div. 1 2700, 2700S, 3700, 3700S 57237 A VIII Div. 1 Oct 21, 2022 Safety Relief Valve A 57248 2700L, 3700L (Liquids) Relief Valve VIII Div. 1 Oct 21, 2022 57260 A 2600L (Air & Steam) VIII Div. 1 Oct 21, 2022 Safety Relief Valve Tristate Valves & Controls, Inc. (PLD) location: Indianapolis, IN, UNITED STATES Acceptable Abbrev.: Tristate Valves & Controls Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Device Type NB Cert # Expiration Date Code Section Type Classification Cert Cat A 300,600 36076 Jan 31, 2020 Safety Valve I & VIII Div. 1 910 to 919 A 36100 Safety Relief Valve VIII Div. 1 Aug 31, 2020 36111 A 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) Relief Valve VIII Div. 1 Oct 28, 2019 36324 Kunkle 6000, 6252 Series A Safety Valve I & VIII Div. 1 Feb 14, 2020 Tundra Process Solutions Ltd. (TPS) location: Edmonton, AB, Seal Identification: TPS Devices designed by: Farris Engineering (TFO) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 57024 A 3800 VIII Div. 1 Pilot Operated Pressure Relief Valve Jan 4, 2024 57035 A 3800FP VIII Div. 1 Jan 4, 2024 Pilot Operated Pressure Relief Valve 2600 & 2600S A 57057 VIII Div. 1 Jan 4, 2024 Safety Relief Valve A 57068 2600L (Liquids) Relief Valve VIII Div. 1 Jan 4, 2024 57215 3800L, PCL, PCM pilots A Mar 6, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 2700, 2700S, 3700, 3700S 57237 A Safety Relief Valve Jan 4, 2024 VIII Div. 1 57248 A 2700L, 3700L (Liquids) VIII Div. 1 Jan 4, 2024 Relief Valve Page 115 of 812 Effective Date: 2019-05-31

117 Table of Contents TVI, Inc (TVC) location: Calvert City, KY, UNITED STATES Acceptable Abbrev.: TVI - KY Devices designed by: Farris Engineering (TFO) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification 1850, 1850H, 1851, 1852, 1855, 1856M, 2850, 2852, 2856, 2850H 57002 A Sep 22, 2020 VIII Div. 1 Safety Relief Valve 57057 2600 & 2600S A Safety Relief Valve Sep 22, 2020 VIII Div. 1 2600L (Liquids) 57068 A VIII Div. 1 Relief Valve Sep 22, 2020 57237 A 2700, 2700S, 3700, 3700S Jun 15, 2023 VIII Div. 1 Safety Relief Valve A 57248 2700L, 3700L (Liquids) Jun 17, 2023 Relief Valve VIII Div. 1 2600L (Air & Steam) 57260 A Safety Relief Valve VIII Div. 1 Apr 29, 2020 4200 / 4400 57282 A Safety Valve Apr 29, 2020 I TVI, Inc. (TRA) location: El Dorado, AR, UNITED STATES Acceptable Abbrev.: TVI-AR Devices designed by: Farris Engineering (TFO) Cert Cat Device Type Expiration Date Code Section Type Classification NB Cert # A 2600 & 2600S 57057 Jul 25, 2023 Safety Relief Valve VIII Div. 1 57068 2600L (Liquids) A Relief Valve Jul 25, 2023 VIII Div. 1 57237 A 2700, 2700S, 3700, 3700S Safety Relief Valve VIII Div. 1 Jul 25, 2023 57248 2700L, 3700L (Liquids) A Jul 25, 2023 VIII Div. 1 Relief Valve TVI, Inc. (TVI) location: Memphis, TN, UNITED STATES Acceptable Abbrev.: TVI - TN Devices designed by: Farris Engineering (TFO) Device Type NB Cert # Cert Cat Code Section Type Classification Expiration Date 1890, 1892, 1895, 1896 A 57013 VIII Div. 1 Safety Relief Valve Apr 28, 2020 57057 2600 & 2600S A Safety Relief Valve VIII Div. 1 Mar 23, 2023 A 57068 2600L (Liquids) Relief Valve VIII Div. 1 Nov 2, 2023 2700, 2700S, 3700, 3700S 57237 A Safety Relief Valve VIII Div. 1 Mar 23, 2023 57248 2700L, 3700L (Liquids) A Apr 28, 2020 VIII Div. 1 Relief Valve A 4200 / 4400 57282 I & VIII Div. 1 Mar 23, 2023 Safety Valve Devices designed by: Spence Engineering Company, Incorporated (SEC) Type Classification Cert Cat Expiration Date Device Type Code Section NB Cert # Fig 31, 41, 41A 65045 A Safety Valve I & VIII Div. 1 Mar 23, 2023 Unified Valve Group Ltd (UNI) location: Calgary, Acceptable Abbrev.: UVGL Devices designed by: LESER GmbH & Company KG (LES) Device Type NB Cert # Type Classification Expiration Date Code Section Cert Cat 37101 459/462 liquids A Relief Valve Sep 28, 2024 VIII Div. 1 459/462 37112 A Safety Relief Valve VIII Div. 1 Sep 28, 2024 A 526 37224 VIII Div. 1 Sep 28, 2024 Safety Relief Valve 37246 526D A Safety Relief Valve Sep 28, 2024 VIII Div. 1 Page 116 of 812 Effective Date: 2019-05-31

118 Table of Contents V TEX Corporation (VTX) location: Hitachinaka-City, Ibaraki, JAPAN Acceptable Abbrev.: VTEX Devices designed by: V TEX Corporation (VTX) Expiration Date Cert Cat Device Type Type Classification Code Section NB Cert # M FB Series 00471 VIII Div. 1 Rupture Disk Device Dec 2, 2020 M 01584 FMB Series Jan 26, 2024 VIII Div. 1 Rupture Disk Device Valserve, LLC (VLS) location: Evanston, WY, UNITED STATES Devices designed by: Farris Engineering (TFO) Cert Cat Type Classification Device Type NB Cert # Code Section Expiration Date A 3800 57024 Feb 25, 2022 Pilot Operated Pressure Relief Valve VIII Div. 1 3800FP 57035 A VIII Div. 1 Feb 25, 2022 Pilot Operated Pressure Relief Valve A 2600 & 2600S 57057 VIII Div. 1 Feb 25, 2022 Safety Relief Valve 57068 2600L (Liquids) A Relief Valve Feb 25, 2022 VIII Div. 1 3800L, PCL, PCM pilots 57215 A VIII Div. 1 Pilot Operated Pressure Relief Valve Feb 25, 2022 A 57237 2700, 2700S, 3700, 3700S Feb 25, 2022 VIII Div. 1 Safety Relief Valve 57248 2700L, 3700L (Liquids) A Relief Valve VIII Div. 1 Feb 25, 2022 57260 A 2600L (Air & Steam) Safety Relief Valve VIII Div. 1 Feb 25, 2022 ValvTechnologies, Incorporated (VLC) location: Houston, TX, UNITED STATES Devices designed by: ValvTechnologies, Incorporated (VLC) Expiration Date Cert Cat Code Section Type Classification Device Type NB Cert # 59015 E*L114 M Power Actuated Relief Valve I Jan 6, 2020 M 59026 E*L111 Power Actuated Relief Valve I Jan 6, 2020 ERV 3 1/16" Bore 59037 M Power Actuated Relief Valve I Jun 9, 2024 59059 M Z***-05********-*****-*** Feb 23, 2024 I Power Actuated Relief Valve 59060 E*9121 M Power Actuated Relief Valve Jun 16, 2024 I 59082 M EOL121NRA*P1-MK1H I Aug 1, 2019 Power Actuated Relief Valve Z***-105***8* M 59105 Power Actuated Relief Valve Oct 9, 2021 I Z***1135R55P1 (1.06" Bore) 59127 M Power Actuated Relief Valve I May 9, 2020 Valvulas Nacional S. A. (VNS) location: Rubi (Barcelona), SPAIN Devices designed by: Valvulas Nacional S. A. (VNS) Cert Cat Type Classification NB Cert # Device Type Expiration Date Code Section 96016 M 6400 VIII Div. 1 Mar 5, 2020 Safety Relief Valve 96027 M 6400 (Liquid) VIII Div. 1 Mar 5, 2020 Safety Relief Valve Vaptec Inc. Equipement de Vapeur Industrielle (VEV) location: St. Laurent, CANADA Acceptable Abbrev.: Vaptec Inc. Devices designed by: Spence Engineering Company, Incorporated (SEC) Expiration Date NB Cert # Cert Cat Type Classification Device Type Code Section Fig 31, 41, 41A 65045 A Safety Valve I & VIII Div. 1 Jan 5, 2023 Page 117 of 812 Effective Date: 2019-05-31

119 Table of Contents Vinson Process Controls, LP (VIN) location: Carrollton, TX, Acceptable Abbrev.: VPCCO Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Expiration Date Cert Cat Device Type Type Classification Code Section NB Cert # JOS-E-RL/JBS-E-RL (Restricted Lift version of cert 15208) 01045 A Safety Relief Valve Oct 23, 2024 VIII Div. 1 81, 81P, 83, 86 A 01089 Safety Relief Valve Oct 24, 2024 VIII Div. 1 81P (Liquids) 01102 A Oct 24, 2024 Relief Valve VIII Div. 1 243/249/443/449/546/843/849/943/5046/5049/8043/8049 A 01292 Pilot Operated Pressure Relief Valve VIII Div. 1 Oct 24, 2024 253/259/453/459/853/859/953/959/5059/8053/8059 01304 A Pilot Operated Pressure Relief Valve Oct 24, 2024 VIII Div. 1 263/269/463/469/566/863/869/963/969/5066/5069 A 01315 Pilot Operated Pressure Relief Valve VIII Div. 1 Oct 24, 2024 453/459/853/859/953/959/5059 (Liquids) A 01326 VIII Div. 1 Pilot Operated Pressure Relief Valve Oct 24, 2024 A 01337 443/449/546/843/849/943/949/5046/5049(Liquids) Oct 24, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 463/469/566/863/869/963/969/5066/5069 (Liquids) 01348 A VIII Div. 1 Oct 24, 2024 Pilot Operated Pressure Relief Valve A JLT (Liquids) 15095 VIII Div. 1 Oct 24, 2024 Safety Relief Valve 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB A Oct 24, 2024 Safety Relief Valve VIII Div. 1 900 Series, 7700, SNC 15411 A Oct 24, 2024 Safety Relief Valve VIII Div. 1 900 Series (Liquid), 7700, SNC A 15499 Relief Valve VIII Div. 1 Oct 24, 2024 VRC Protx , LLC. (Evanston) (VRR) location: Evanston, WY, UNITED STATES Acceptable Abbrev.: VRC Protx Evanston, Wyoming Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) NB Cert # Code Section Type Classification Expiration Date Device Type Cert Cat A 81, 81P, 83, 86 01089 VIII Div. 1 Jun 19, 2021 Safety Relief Valve 01102 A 81P (Liquids) Relief Valve VIII Div. 1 Jun 20, 2021 01292 243/249/443/449/546/843/849/943/5046/5049/8043/8049 A Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 3, 2021 253/259/453/459/853/859/953/959/5059/8053/8059 01304 A VIII Div. 1 Pilot Operated Pressure Relief Valve Jun 19, 2021 263/269/463/469/566/863/869/963/969/5066/5069 A 01315 VIII Div. 1 Pilot Operated Pressure Relief Valve Jun 19, 2021 01326 A 453/459/853/859/953/959/5059 (Liquids) Feb 3, 2021 VIII Div. 1 Pilot Operated Pressure Relief Valve A 01337 443/449/546/843/849/943/949/5046/5049(Liquids) Jun 20, 2021 Pilot Operated Pressure Relief Valve VIII Div. 1 463/469/566/863/869/963/969/5066/5069 (Liquids) 01348 A May 5, 2021 VIII Div. 1 Pilot Operated Pressure Relief Valve A 15095 JLT (Liquids) Feb 3, 2021 Safety Relief Valve VIII Div. 1 JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 A Safety Relief Valve Jun 8, 2021 VIII Div. 1 15411 A 900 Series, 7700, SNC VIII Div. 1 Safety Relief Valve Jun 13, 2021 15499 A 900 Series (Liquid), 7700, SNC Relief Valve VIII Div. 1 Jun 8, 2021 JLT-JOS, JLT-JBS, 8500, ACL/ABL 15512 A Safety Relief Valve Feb 3, 2021 VIII Div. 1 Devices designed by: Farris Engineering (TFO) NB Cert # Cert Cat Expiration Date Device Type Code Section Type Classification 3800 57024 A Pilot Operated Pressure Relief Valve VIII Div. 1 Jan 30, 2024 57035 A 3800FP VIII Div. 1 Pilot Operated Pressure Relief Valve Jan 29, 2024 57046 A 6400/6600 (previously 2500 & 4600) Safety Valve I & VIII Div. 1 Jan 29, 2024 2600 & 2600S 57057 A Safety Relief Valve Jan 29, 2024 VIII Div. 1 2600L (Liquids) 57068 A VIII Div. 1 Jan 29, 2024 Relief Valve A 57215 3800L, PCL, PCM pilots Pilot Operated Pressure Relief Valve VIII Div. 1 Jan 29, 2024 57237 A 2700, 2700S, 3700, 3700S Safety Relief Valve VIII Div. 1 Jan 29, 2024 2700L, 3700L (Liquids) A 57248 Relief Valve Jan 29, 2024 VIII Div. 1 2600L (Air & Steam) 57260 A Safety Relief Valve Jan 29, 2024 VIII Div. 1 4200 / 4400 57282 A Safety Valve Jan 29, 2024 I & VIII Div. 1 Page 118 of 812 Effective Date: 2019-05-31

120 Table of Contents VRC Protx , LLC. (Evanston) (VRR) location: (continued) Evanston, WY, UNITED STATES Acceptable Abbrev.: VRC Protx Evanston, Wyoming Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) Expiration Date Cert Cat Type Classification Device Type Code Section NB Cert # 81, 81P, 83, 86 A 01089 Safety Relief Valve Jun 19, 2021 VIII Div. 1 81P (Liquids) 01102 A VIII Div. 1 Relief Valve Jun 20, 2021 A 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 Pilot Operated Pressure Relief Valve Feb 3, 2021 VIII Div. 1 253/259/453/459/853/859/953/959/5059/8053/8059 01304 A Jun 19, 2021 VIII Div. 1 Pilot Operated Pressure Relief Valve 263/269/463/469/566/863/869/963/969/5066/5069 A 01315 VIII Div. 1 Jun 19, 2021 Pilot Operated Pressure Relief Valve A 01326 453/459/853/859/953/959/5059 (Liquids) Feb 3, 2021 Pilot Operated Pressure Relief Valve VIII Div. 1 443/449/546/843/849/943/949/5046/5049(Liquids) 01337 A Jun 20, 2021 VIII Div. 1 Pilot Operated Pressure Relief Valve A 01348 463/469/566/863/869/963/969/5066/5069 (Liquids) May 5, 2021 Pilot Operated Pressure Relief Valve VIII Div. 1 JLT (Liquids) 15095 A VIII Div. 1 Feb 3, 2021 Safety Relief Valve A JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 VIII Div. 1 Jun 8, 2021 Safety Relief Valve 15411 A 900 Series, 7700, SNC Jun 13, 2021 VIII Div. 1 Safety Relief Valve A 15499 900 Series (Liquid), 7700, SNC Jun 8, 2021 Relief Valve VIII Div. 1 JLT-JOS, JLT-JBS, 8500, ACL/ABL 15512 A Safety Relief Valve VIII Div. 1 Feb 3, 2021 Devices designed by: Farris Engineering (TFO) Device Type Cert Cat Expiration Date Code Section Type Classification NB Cert # 3800 57024 A Pilot Operated Pressure Relief Valve Jan 30, 2024 VIII Div. 1 57035 A 3800FP VIII Div. 1 Jan 29, 2024 Pilot Operated Pressure Relief Valve 57046 6400/6600 (previously 2500 & 4600) A Safety Valve I & VIII Div. 1 Jan 29, 2024 57057 A 2600 & 2600S Jan 29, 2024 VIII Div. 1 Safety Relief Valve 2600L (Liquids) 57068 A Relief Valve Jan 29, 2024 VIII Div. 1 3800L, PCL, PCM pilots A 57215 VIII Div. 1 Pilot Operated Pressure Relief Valve Jan 29, 2024 57237 2700, 2700S, 3700, 3700S A Jan 29, 2024 VIII Div. 1 Safety Relief Valve 2700L, 3700L (Liquids) 57248 A Jan 29, 2024 Relief Valve VIII Div. 1 2600L (Air & Steam) A 57260 VIII Div. 1 Safety Relief Valve Jan 29, 2024 4200 / 4400 57282 A Jan 29, 2024 Safety Valve I & VIII Div. 1 VRC Protx, LLC (RIL) location: New Berlin, WI, UNITED STATES Devices designed by: Emerson Automation Solutions Final Control, US LP (KBM) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # A 910 to 919 36100 VIII Div. 1 Jan 29, 2025 Safety Relief Valve 36111 A 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) Relief Valve VIII Div. 1 Oct 30, 2024 Devices designed by: Farris Engineering (TFO) Code Section Cert Cat Type Classification Expiration Date Device Type NB Cert # 3800 57024 A Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 20, 2024 57035 A 3800FP VIII Div. 1 Pilot Operated Pressure Relief Valve Feb 20, 2024 57046 A 6400/6600 (previously 2500 & 4600) Safety Valve I & VIII Div. 1 Feb 20, 2024 2600 & 2600S 57057 A Safety Relief Valve Feb 20, 2024 VIII Div. 1 2600L (Liquids) 57068 A VIII Div. 1 Feb 20, 2024 Relief Valve A 57215 3800L, PCL, PCM pilots Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 20, 2024 57237 A 2700, 2700S, 3700, 3700S Safety Relief Valve VIII Div. 1 Feb 20, 2024 2700L, 3700L (Liquids) A 57248 Relief Valve Feb 20, 2024 VIII Div. 1 2600L (Air & Steam) 57260 A Safety Relief Valve Feb 20, 2024 VIII Div. 1 4200 / 4400 57282 A Safety Valve Feb 20, 2024 I & VIII Div. 1 Page 119 of 812 Effective Date: 2019-05-31

121 Table of Contents Watts Regulator Company (WWF) location: Franklin, NH, UNITED STATES Acceptable Abbrev.: Watts Webster Valve Division Devices designed by: Watts Regulator Company (WWF) Device Type Expiration Date NB Cert # Type Classification Code Section Cert Cat 3L, 10L, (F, SL, L, LL, LLL, RL) 100XL Mod. M7 (LF prefix also) M 63009 Temperature and Pressure Relief Valve Jan 26, 2023 IV 3/4" 40L, (LL, LLL) 40XL, 140S, 140X, (Z2) Mod. M15 (LF prefix 63021 M Temperature and Pressure Relief Valve Jan 26, 2023 IV M 63032 1" 40L (LL) 40XL (Z2) , Mod 15 (LF prefix also) Temperature and Pressure Relief Valve Jan 26, 2023 IV 1" 140S, 140X (Mod. M15) (LF prefix also) M 63043 Temperature and Pressure Relief Valve IV Jan 26, 2023 M 174A M3, 474A M2, M474-M2 (3/4")(also LF prefix) 63054 Jan 25, 2023 Safety Relief Valve IV 174A Model M1 (1")(also LF prefix) 63065 M Jan 25, 2023 IV Safety Relief Valve M 63076 174A, LF174A M1 (1-1/4") Jan 5, 2023 Safety Relief Valve IV 174A, LF174A Model M (1-1/2") M 63087 Safety Relief Valve IV Oct 11, 2021 63098 M 174A, LF174A Model M (2") Oct 31, 2021 IV Safety Relief Valve M 63100 1" N240X(-6,-9),1-1/4 N241X(-5,-8) Mod. M15 (LF prefix also) Nov 2, 2023 Temperature and Pressure Relief Valve IV 340-3, 340X-8 M15, 342-3, 342X-8 M15 (T & P) (LF prefix also) 63122 M IV Temperature and Pressure Relief Valve Nov 2, 2023 M 63144 374A & M374 Model M & TACO Inc. 333-1(also LF prefix) Apr 9, 2021 Safety Relief Valve IV 740 Model M1 (3/4") M 63177 Safety Relief Valve IV Mar 6, 2021 63188 M 740 Model M (1") Safety Relief Valve IV Mar 6, 2021 63199 740 Model M (1 1/4") M Safety Relief Valve IV Mar 16, 2021 740 Model M (1 1/2") 63201 M IV Nov 2, 2023 Safety Relief Valve 740 Model M (2") 63212 M Safety Relief Valve IV Mar 6, 2021 63223 M (L) 315 Mod. M1 and M2 Aug 29, 2023 IV Safety Valve M 63245 415 M1 (3/4") Jan 25, 2023 Safety Valve IV (LF, M) 335 Mod. M1 & M2 63256 M IV Safety Relief Valve Jan 25, 2023 M 63267 330-M1 & M330-M1 Aug 24, 2023 Safety Relief Valve IV 415 Model M (1 1/4") 63278 M Safety Valve Feb 23, 2021 IV 63289 M 415 Model M (1 1/2") Safety Valve IV Feb 23, 2021 63302 375-M1 & M375-M1 M Safety Relief Valve IV Jan 26, 2023 63324 415-M1 (1") M Safety Valve Jan 25, 2023 IV 4L, LF4L, M7 (3/4") 63335 M Safety Relief Valve Feb 9, 2024 IV 63403 M 3/4" (M)354A IV Safety Relief Valve Nov 2, 2023 Watts Water Technologies (Canada) Inc. (WBC) location: Burlington, CANADA Acceptable Abbrev.: Watts, Burlington, Ontario Canada Devices designed by: Spence Engineering Company, Incorporated (SEC) NB Cert # Device Type Expiration Date Type Classification Code Section Cert Cat A Fig 31, 41, 41A 65045 I & VIII Div. 1 Jul 1, 2020 Safety Valve Weir BDK Valves (WIN) location: Hubli, Karnataka, INDIA Devices designed by: Weir Power & Industrial - France (SAR) NB Cert # Cert Cat Type Classification Device Type Code Section Expiration Date 9 Series (Liquids) 44020 M Safety Relief Valve Jan 9, 2021 VIII Div. 1 92012 M P3, P4 (liquids) VIII Div. 1 Dec 15, 2023 Relief Valve Page 120 of 812 Effective Date: 2019-05-31

122 Table of Contents Weir Group Energy Equipment (Suzhou) Co., Ltd. (WSZ) location: Suzhou, Jiangsu, PEOPLES REP/CHINA Acceptable Abbrev.: WVCS Devices designed by: Weir Power & Industrial - France (SAR) Device Type Expiration Date NB Cert # Code Section Type Classification Cert Cat P3, P4, P5 M 92001 Safety Relief Valve Jan 17, 2024 VIII Div. 1 M 92012 P3, P4 (liquids) Relief Valve Apr 16, 2024 VIII Div. 1 Weir Power & Industrial - France (SAR) location: Vendin-le-Vieil, FRANCE Sarasin-RSBD Devices designed by: Weir Power & Industrial - France (SAR) Device Type Type Classification Cert Cat Code Section Expiration Date NB Cert # M 44019 9 Series Jun 30, 2020 VIII Div. 1 Safety Relief Valve 44020 M 9 Series (Liquids) Safety Relief Valve I & VIII Div. 1 Nov 17, 2020 44031 76 Series Steam & Liquid (Water K=0.850) M Pilot Operated Pressure Relief Valve Dec 3, 2021 I 44042 M 76 Series VIII Div. 1 Jun 29, 2020 Pilot Operated Pressure Relief Valve 44053 M 78 (Pilot Operated) VIII Div. 1 Apr 17, 2024 Pilot Operated Pressure Relief Valve M 44064 78 (Pilot Operated, Liquid) Apr 17, 2024 Pilot Operated Pressure Relief Valve I & VIII Div. 1 74 Series 44097 M Pilot Operated Pressure Relief Valve VIII Div. 1 Aug 4, 2022 78LP Series 44109 M Pilot Operated Pressure Relief Valve VIII Div. 1 Feb 28, 2023 44110 STARFLOW-V M Safety Valve I & VIII Div. 1 Dec 20, 2023 44121 STARFLOW-V (Restricted Lift) M Safety Valve I & VIII Div. 1 Dec 20, 2023 92001 P3, P4, P5 M Safety Relief Valve Dec 20, 2024 VIII Div. 1 P3, P4 (liquids) 92012 M Relief Valve I & VIII Div. 1 Apr 17, 2024 Starsteam V Series M 92034 I & VIII Div. 1 Safety Relief Valve Jan 24, 2025 92045 Starsteam V Series (Res. Lift) M Safety Valve Jan 24, 2025 I & VIII Div. 1 76 Series (Liquid) 92056 M Mar 19, 2020 Pilot Operated Pressure Relief Valve I & VIII Div. 1 Westech Industrial Ltd. (YCO) location: Burlington, CANADA Acceptable Abbrev.: YCO Devices designed by: Emerson Automation Solutions Final Control US LP (AGC) NB Cert # Cert Cat Code Section Type Classification Expiration Date Device Type 01089 81, 81P, 83, 86 A Safety Relief Valve May 2, 2023 VIII Div. 1 01102 A 81P (Liquids) VIII Div. 1 May 2, 2023 Relief Valve 243/249/443/449/546/843/849/943/5046/5049/8043/8049 A 01292 Pilot Operated Pressure Relief Valve May 2, 2023 VIII Div. 1 253/259/453/459/853/859/953/959/5059/8053/8059 01304 A Pilot Operated Pressure Relief Valve VIII Div. 1 May 2, 2023 01315 A 263/269/463/469/566/863/869/963/969/5066/5069 VIII Div. 1 Pilot Operated Pressure Relief Valve May 2, 2023 01326 A 453/459/853/859/953/959/5059 (Liquids) VIII Div. 1 May 2, 2023 Pilot Operated Pressure Relief Valve 443/449/546/843/849/943/949/5046/5049(Liquids) A 01337 VIII Div. 1 May 2, 2023 Pilot Operated Pressure Relief Valve A 01348 463/469/566/863/869/963/969/5066/5069 (Liquids) Pilot Operated Pressure Relief Valve VIII Div. 1 May 2, 2023 15208 JOS-E/JBS-E/JOS-H-E 8400 AC/AB A May 2, 2023 Safety Relief Valve VIII Div. 1 900 Series, 7700, SNC 15411 A Safety Relief Valve May 2, 2023 VIII Div. 1 15499 A 900 Series (Liquid), 7700, SNC VIII Div. 1 May 2, 2023 Relief Valve Page 121 of 812 Effective Date: 2019-05-31

123 Table of Contents Westech Industrial Ltd. (YCO) location: (continued) Burlington, CANADA Acceptable Abbrev.: YCO Devices designed by: LESER GmbH & Company KG (LES) Expiration Date Cert Cat Type Classification Device Type Code Section NB Cert # 459/462 liquids A 37101 Relief Valve Mar 20, 2024 VIII Div. 1 459/462 37112 A VIII Div. 1 Safety Relief Valve Mar 20, 2024 A 437 (Liquids) 37189 Relief Valve Mar 20, 2024 VIII Div. 1 438 Sub Types 481, 439 37190 A Safety Relief Valve VIII Div. 1 Mar 20, 2024 37202 438 Sub Types 481, 439, Liquids A Sep 21, 2024 VIII Div. 1 Safety Relief Valve A 37213 437 Safety Relief Valve VIII Div. 1 Mar 20, 2024 526 37224 A Safety Relief Valve VIII Div. 1 Mar 20, 2024 37235 526 (Liquids) A VIII Div. 1 Relief Valve Mar 20, 2024 A 526D 37246 VIII Div. 1 Mar 20, 2024 Safety Relief Valve 37257 A 526D Liquids Mar 20, 2024 VIII Div. 1 Relief Valve A 37268 820 (liquid) (821) Mar 20, 2024 Pilot Operated Pressure Relief Valve VIII Div. 1 810/820 (811/821) 37280 A VIII Div. 1 Mar 20, 2024 Pilot Operated Pressure Relief Valve Xuzhou Bafang Safety Device Co., Ltd (XBA) location: Xuzhou City, Jiangsu Province, PEOPLES REP/CHINA Devices designed by: Xuzhou Bafang Safety Device Co., Ltd (XBA) Expiration Date Cert Cat Device Type NB Cert # Code Section Type Classification 00684 M FCD VIII Div. 1 Rupture Disk Device Oct 13, 2022 00954 M RCD Series Rupture Disc Rupture Disk Device VIII Div. 1 Oct 13, 2022 9100 Series Buckling Pin Relief Valve 00965 M Buckling Pin Non-reclosing Device VIII Div. 1 Oct 13, 2022 YONGYI VALVE GROUP CO., LTD. (YOY) location: Oubei Town, Yongjia, Zhejiang, PEOPLES REP/CHINA Acceptable Abbrev.: YOY Devices designed by: YONGYI VALVE GROUP CO., LTD. (YOY) Cert Cat Code Section Expiration Date Device Type NB Cert # Type Classification M YFA42C-300aC 1-1/2G3 04116 Aug 3, 2023 VIII Div. 1 Safety Relief Valve 04127 M YFA42C-150C 2J3 Aug 3, 2023 VIII Div. 1 Safety Relief Valve Yusuf Bin Ahmed Kanoo Co. Limited (YAK) location: Dammam, SAUDI ARABIA Acceptable Abbrev.: YBA Kanoo - Oil & Gas Div., Kanoo Flow Control Devices designed by: Farris Engineering (TFO) NB Cert # Cert Cat Code Section Expiration Date Device Type Type Classification 57024 A 3800 Pilot Operated Pressure Relief Valve VIII Div. 1 Jun 3, 2020 57035 A 3800FP VIII Div. 1 Pilot Operated Pressure Relief Valve Jun 3, 2020 2600 & 2600S 57057 A Safety Relief Valve Apr 27, 2021 VIII Div. 1 57068 A 2600L (Liquids) VIII Div. 1 Relief Valve Jun 3, 2020 57215 A 3800L, PCL, PCM pilots Pilot Operated Pressure Relief Valve VIII Div. 1 Jul 28, 2019 2700, 2700S, 3700, 3700S 57237 A Safety Relief Valve Jul 28, 2019 VIII Div. 1 2700L, 3700L (Liquids) 57248 A VIII Div. 1 Jul 28, 2019 Relief Valve Zeeco, Inc. (ZCO) location: Broken Arrow, OK, UNITED STATES Devices designed by: Zeeco, Inc. (ZCO) NB Cert # Cert Cat Type Classification Device Type Code Section Expiration Date PO-BPV 03306 M Buckling Pin Non-reclosing Device Jun 25, 2024 VIII Div. 1 03317 M DA-BPV VIII Div. 1 Nov 22, 2023 Buckling Pin Non-reclosing Device Page 122 of 812 Effective Date: 2019-05-31

124 Table of Contents Zhejiang Chaochao Safety Valve Manufacturing Co., Ltd. (CXI) location: Cixi City, Zhejiang Province, 315321, PEOPLES REP/CHINA Acceptable Abbrev.: CHAOCHAO Devices designed by: Zhejiang Chaochao Safety Valve Manufacturing Co., Ltd. (CXI) Expiration Date Cert Cat Code Section Device Type Type Classification NB Cert # AX2.II 12755 M Safety Relief Valve May 3, 2023 VIII Div. 1 CAXL4-2.5 M 12812 Safety Valve Feb 11, 2022 VIII Div. 1 CAX3.11-2.5 12823 M Feb 11, 2022 Safety Valve VIII Div. 1 CAXL6-2.5 12834 M VIII Div. 1 Feb 11, 2022 Safety Valve CAXL8-2.5 12845 M VIII Div. 1 Feb 11, 2022 Safety Valve CAXL8.II - 2.5 12856 M Safety Valve VIII Div. 1 Feb 11, 2022 M 12867 CAGU24 Apr 12, 2023 Safety Valve VIII Div. 1 ZOOK Canada Inc. (PEL) location: Burlington, CANADA Acceptable Abbrev.: ZOOK Devices designed by: ZOOK Canada Inc. (PEL) Cert Cat Code Section Device Type Type Classification NB Cert # Expiration Date M 82000 RL-PB-LVR Series Jan 26, 2020 VIII Div. 1 Rupture Disk Device 82011 M R-PB-R Dec 21, 2020 VIII Div. 1 Rupture Disk Device R-D-R Series 82022 M VIII Div. 1 Jan 26, 2020 Rupture Disk Device M R-D-VR Series 82033 VIII Div. 1 Jan 26, 2020 Rupture Disk Device 82044 M SFAL & SFA-II-L Series Rupture Disk Device VIII Div. 1 Jan 27, 2020 82055 SB90-L Series M Rupture Disk Device VIII Div. 1 Jan 27, 2020 URA-L, URA 82066 M Rupture Disk Device VIII Div. 1 Feb 17, 2021 82077 M RA4, RLP VIII Div. 1 Rupture Disk Device Jun 25, 2019 82101 M SRA, SRA-L, SRA-C, SRA-LC, SRA-X, RAX VIII Div. 1 Oct 27, 2022 Rupture Disk Device M 82112 RA6 (Liquid) Jul 23, 2025 Rupture Disk Device VIII Div. 1 RA6 (Air/Gas) 82123 M Rupture Disk Device VIII Div. 1 Oct 1, 2024 RA8 (Liquid) 82134 M Rupture Disk Device VIII Div. 1 Jul 23, 2025 82145 M RA8 (Gas) Rupture Disk Device VIII Div. 1 Oct 1, 2024 82156 RAUS (Liquid) M Rupture Disk Device VIII Div. 1 Apr 17, 2020 RAUS (Air/Gas) 82167 M VIII Div. 1 Jul 23, 2025 Rupture Disk Device 82178 Throwaway (TA), Screw Type (ST) Assemblies M Rupture Disk Device VIII Div. 1 Sep 30, 2021 82189 M FAX-L,SFAZ-L and SFA-II-L and SFA-L Series Rupture Disks Sep 30, 2021 VIII Div. 1 Rupture Disk Device Zook Enterprises, LLC (ZOE) location: Chagrin Falls, OH, UNITED STATES Acceptable Abbrev.: Zook Devices designed by: Zook Enterprises, LLC (ZOE) NB Cert # Cert Cat Type Classification Code Section Device Type Expiration Date 76025 Mono Style W/Plate Vac. Support M Rupture Disk Device Mar 24, 2020 VIII Div. 1 M Mono Style W/Cross Vac. Support 76036 VIII Div. 1 Mar 24, 2020 Rupture Disk Device M 76047 Mono W/Ring Vac. Support Rupture Disk Device May 27, 2025 VIII Div. 1 Mono Style W/Bar Vacuum Support 76058 M Rupture Disk Device Feb 25, 2020 VIII Div. 1 Page 123 of 812 Effective Date: 2019-05-31

125 Table of Contents LISTING OF CERTIFIED DEVICE TYPES This publication includes certification tables for each design type presently certified. These tables are listed in alphabetical order according to the manufacturer. The following is an example and brief description of the listings and certification tables. 1 The National Board capacity certification number given solely to this valve type. 2 The design series or catalog number is the commercial designation specified by the manufacturer. The Classification of the pressure relief device type as defined in ASME PTC 25. 3 4 This indicates the requirements of the Construction Code used during the initial certification testing. Also listed, the National Board accepted testing laboratory where the testing was performed. In some cases, the device may be certified for additional Code Section as noted in the tables. 5 There are several methods of establishing a certified value used to determine capacity: · the valve average capacity method is used when a manufacturer has only one size and one set pressure to be certified (Flow Capacity, 1 or 3 Valve Method). · the slope (flow factor for liquid) method is used when a manufacturer has one valve design of one size to be certified for a range of set pressures (Flow Capacity, Flow Factor or Flow Capacity, Slope). · the coefficient of discharge method is used when a manufacturer has one design type and wishes to have it certified for a range of sizes and set pressures (Flow Capacity, K). · ). the flow resistance method is used to certify non-reclosing devices such as rupture disk devices (Resistance Factor, K r The quantitative value and applicable unit used to determine device relieving capacity. 6 7 Special provisions of rules, such as Code Cases, and special applications that apply to the device. 8 The test medium listed is the medium that was used during the initial testing. Either air, gas, steam or water could be indicated as the test medium. The certified mediums are the mediums for which the device may be used in service. 9 Set pressure is the valve of increasing inlet static pressure at which a pressure relief device displays an operational characteristic. These 10 characteristics are defined in ASME PTC-25. 11 Blowdown is the difference between actual popping pressure of a pressure relief valve and actual reseating pressure expressed as a percentage of set pressure or in pressure units. This indicates whether the valve has a fixed or adjustable blowdown construction. The NPS (DN) and outlet size or range of sizes of a pressure relief device. 12 For pressure relief valves, flow area is the measured minimum flow area through the valve. For non-reclosing pressure relief devices (e.g. 13 rupture disk devices), flow area is the minimum net flow area to be marked on the device. 14 The orifice diameter is the minimum diameter of the nozzle. 15 The minimum lift is the lift that the valve is expected to have to meet its rated capacity. This column indicates the minimum and maximum set pressures valid for the size, Code Section and medium. 16 This column lists the medium of the certified capacity and is associated with the minimum and maximum set pressures in column 16. 17 18 This column lists the Code Section associated with the minimum and maximum set pressures in column 16. Page 124 of 812 Effective Date: 2019-05-31

126 Table of Contents Ademco 1 GmbH (HAG) 90009 NB#: Hardhofweg 40, Mosbach 74821 Germany location: Acceptable Abbrev.: Ademco 1 GmbH Ademco 1 GmbH (HAG) location: Hardhofweg 40, Mosbach 74821 Germany Acceptable Abbrev.: Ademco 1 GmbH Certification Design Series S245 90009 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Leser Gmbh on December 06, 1996 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .863 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Inlet Size Code Section Outlet Size Flow Area Set Pressure Range Media VIII Air 0.157 in 40 - 435 psi 0.5 NPS 0.122 sq in 0.394 in Side VIII Air 0.591 in 0.236 in 40 - 435 psi 0.75 NPS Side 0.274 sq in VIII Air Side 0.487 sq in 0.787 in 0.346 in 40 - 435 psi 1 NPS VIII Air 0.76 sq in 40 - 435 psi 1.25 NPS Side 0.984 in 0.398 in VIII Air 1.5 NPS 1.246 sq in 1.26 in 0.504 in Side 40 - 435 psi VIII Air 1.575 in 0.693 in 40 - 435 psi 2 NPS Side 1.947 sq in Page 125 of 812 Effective Date: 2019-05-31

127 Table of Contents Albert Handtmann Armaturenfabrik GmbH & Co. KG (AHA) 00639 NB#: Arthur-Handtmann-Str. 11, Biberach/Riss 88400 Germany location: Albert Handtmann Armaturenfabrik GmbH & Co. KG (AHA) location: Arthur-Handtmann-Str. 11, Biberach/Riss 88400 Germany Design Series Certification 33551 and 33651 00639 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on October 02, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.640 Unitless Certified Value: Air Test Medium: Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Media Set Pressure Range Lift Flow Area Outlet Size VIII Div. 1 Air 1 - 10 bar 1.5 NPS 0.2323 in 0.8268 in 0.5369 sq in 2.5 NPS VIII Div. 1 Air 15 - 145 psi VIII Div. 1 Air 0.3543 in 2 NPS 3 NPS 1.3662 sq in 1.3189 in 1 - 10 bar VIII Div. 1 Air 15 - 145 psi VIII Div. 1 Air 0.5039 in 1.811 in 2.5759 sq in 3.5 NPS 1 - 10 bar 2.5 NPS VIII Div. 1 Air 15 - 145 psi VIII Div. 1 Air 1 - 10 bar 0.5827 in 4 NPS 3 NPS 2.3228 in 4.2377 sq in VIII Div. 1 Air 15 - 145 psi VIII Div. 1 Air 3.5 NPS 5 NPS 6.1367 sq in 0.7559 in 1 - 10 bar 2.7953 in VIII Div. 1 Air 15 - 145 psi Certification Design Series 33551 and 33651 (Liquid) 00640 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 31, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.436 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Lift Set Pressure Range Media Code Section Flow Area VIII Div. 1 Water 0.8268 in 1.5 NPS 2.5 NPS 0.5369 in 0.2323 in 1 - 10 bar VIII Div. 1 Water 15 - 145 psi VIII Div. 1 Water 1 - 10 bar 0.3543 in 1.3189 in 1.3662 in 3 NPS 2 NPS VIII Div. 1 Water 15 - 145 psi VIII Div. 1 Water 1 - 10 bar 3.5 NPS 2.5 NPS 2.5759 in 1.811 in 0.5039 in VIII Div. 1 Water 15 - 145 psi VIII Div. 1 Water 2.3228 in 0.5827 in 4.2377 in 1 - 10 bar 3 NPS 4 NPS VIII Div. 1 Water 15 - 145 psi VIII Div. 1 Water 6.1367 in 2.7953 in 0.7559 in 1 - 10 bar 3.5 NPS 5 NPS VIII Div. 1 Water 15 - 145 psi Page 126 of 812 Effective Date: 2019-05-31

128 Table of Contents Apparecchi Di Sicurezza e Tenuta S.p.A. (ADS) 07108 NB#: Via Merendi 40, Cornaredo (Milano) 20010 Italy location: Acceptable Abbrev.: A.S.T. S.p.A. Apparecchi Di Sicurezza e Tenuta S.p.A. (ADS) location: Via Merendi 40, Cornaredo (Milano) 20010 Italy Acceptable Abbrev.: A.S.T. S.p.A. Certification Design Series SVP-7200 Restrict Lift (Liquid) 07108 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 14, 2013 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .765 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Outlet Size Inlet Size Set Pressure Range Lift Flow Area VIII Div. 1 Water 0.079 in 15 - 15000 psi 1 - 1.8125 NPS 2, 3 NPS 0.3945 sq in [D] 0.709 in VIII Div. 1 Water [E] 0.709 in 0.154 in 15 - 15000 psi VIII Div. 1 Water [G1] 1.083 in 15 - 15000 psi 1.5 - 1.8125 NPS 3 NPS 0.9207 sq in 0.326 in VIII Div. 1 Water 1.4913 sq in 3 NPS 1.8125 - 2.0625 NPS [G1] 1.378 in 15 - 15000 psi 0.28 in VIII Div. 1 Water [H1] 1.378 in 0.425 in 15 - 15000 psi VIII Div. 1 Water [J1] 2.047 in 0.445 in 15 - 10000 psi 2.5625 - 4 NPS 4, 6 NPS 3.2917 sq in VIII Div. 1 Water 15 - 10000 psi 0.61 in [K1] 2.047 in VIII Div. 1 Water 15 - 10000 psi 0.772 in [K2] 2.047 in VIII Div. 1 Water 4 NPS 6 NPS 7.5977 sq in [L1] 3.11 in 15 - 3775 psi 0.61 in VIII Div. 1 Water [M1] 3.11 in 15 - 3775 psi 0.732 in VIII Div. 1 Water 15 - 3775 psi 0.898 in [N1] 3.11 in VIII Div. 1 Water 6 NPS 8 NPS 18.4176 sq in [P2] 4.843 in 1.138 in 15 - 2264 psi VIII Div. 1 Water 15 - 2264 psi [Q1] 4.843 in 1.402 in VIII Div. 1 Water 15 - 2264 psi 1.705 in [Q2] 4.843 in VIII Div. 1 Water [R2] 6.22 in 2.047 in 15 - 2264 psi 8 NPS 10, 12 NPS 30.3905 sq in Page 127 of 812 Effective Date: 2019-05-31

129 Table of Contents Apparecchi Di Sicurezza e Tenuta S.p.A. (ADS) 07119 NB#: Via Merendi 40, Cornaredo (Milano) 20010 Italy location: Acceptable Abbrev.: A.S.T. S.p.A. Design Series Certification SVP-7200 Restrict Lift 07119 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 15, 2013 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .876 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Outlet Size Lift Set Pressure Range Media Code Section Inlet Size VIII Div. 1 Air 2, 3 NPS 0.3945 sq in [D] 0.709 in 1 - 1.8125 NPS 15 - 15000 psi 0.079 in VIII Div. 1 Steam 15 - 6000 psi VIII Div. 1 Air [E] 0.709 in 0.154 in 15 - 15000 psi VIII Div. 1 Steam 15 - 6000 psi VIII Div. 1 Air 1.5 - 1.8125 NPS [G1] 1.083 in 0.326 in 15 - 15000 psi 3 NPS 0.9207 sq in VIII Div. 1 Steam 15 - 6000 psi VIII Div. 1 Air 0.28 in 1.8125 - 2.0625 NPS 3 NPS 1.4913 sq in [G1] 1.378 in 15 - 15000 psi VIII Div. 1 Steam 15 - 6000 psi VIII Div. 1 Air 0.425 in [H1] 1.378 in 15 - 15000 psi 3 NPS 1.8125 - 2.0626 NPS 1.4913 sq in VIII Div. 1 Steam 15 - 6000 psi VIII Div. 1 Air 15 - 10000 psi 0.445 in [J1] 2.047 in 3.2917 sq in 4,6 NPS 2.5625 - 4 NPS VIII Div. 1 Steam 15 - 3697 psi VIII Div. 1 Air 15 - 10000 psi 0.61 in [K1] 2.047 in 3.2917 sq in 4, 6 NPS VIII Div. 1 Steam 15 - 3697 psi VIII Div. 1 Air [K2] 2.047 in 15 - 10000 psi 0.772 in VIII Div. 1 Steam 15 - 3697 psi VIII Div. 1 Air 0.61 in 15 - 3775 psi 4 NPS 6 NPS 7.5977 sq in [L1] 3.11 in VIII Div. 1 Steam VIII Div. 1 Air 0.732 in 15 - 3775 psi [M1] 3.11 in VIII Div. 1 Steam VIII Div. 1 Air [N1] 3.11 in 15 - 3775 psi 0.898 in VIII Div. 1 Steam VIII Div. 1 Air [P2] 4.843 in 1.138 in 15 - 2264 psi 6 NPS 8 NPS 18.4176 sq in VIII Div. 1 Steam VIII Div. 1 Air [Q1] 4.843 in 1.402 in 15 - 2264 psi VIII Div. 1 Steam VIII Div. 1 Air [Q2] 4.843 in 15 - 2264 psi 1.705 in VIII Div. 1 Steam VIII Div. 1 Air [R2] 6.22 in 2.047 in 15 - 2264 psi 8 NPS 10, 12 NPS 30.3905 sq in VIII Div. 1 Steam Page 128 of 812 Effective Date: 2019-05-31

130 Table of Contents Apparecchi Di Sicurezza e Tenuta S.p.A. (ADS) 07120 NB#: Via Merendi 40, Cornaredo (Milano) 20010 Italy location: Acceptable Abbrev.: A.S.T. S.p.A. Certification Design Series SVP-7200 (Full Lift) (Liquid) 07120 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 14, 2013 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .765 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Flow Area Media Code Section Outlet Size Lift Inlet Size VIII Div. 1 Water 0.3945 sq in 1 - 1.8125 NPS 15 - 15000 psi 0.25 in [F] 0.709 in 2, 3 NPS VIII Div. 1 Water 1.5 - 1.8125 NPS 0.9207 sq in 0.512 in 3 NPS 15 - 15000 psi [H] 1.083 in VIII Div. 1 Water 0.709 in 15 - 15000 psi 1.8125 - 2.0625 NPS 3 NPS 1.4913 sq in [J] 1.378 in VIII Div. 1 Water 4, 6 NPS 2.5625 - 4 NPS 3.2917 sq in [L] 2.047 in 0.984 in 15 - 10000 psi VIII Div. 1 Water 15 - 3775 psi 4 NPS 7.5977 sq in [P] 3.11 in 1.409 in 6 NPS VIII Div. 1 Water 8 NPS 2.122 in 6 NPS 15 - 2264 psi 18.4176 sq in [R] 4.843 in VIII Div. 1 Water 8 NPS [T] 6.22 in 2.713 in 10, 12 NPS 15 - 2264 psi 30.3905 sq in Certification Design Series SVP-7200 (Full Lift) 07131 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 15, 2013 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .876 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Code Section Outlet Size Inlet Size Lift Set Pressure Range VIII Div. 1 Air 1 - 1.8125 NPS 0.25 in 15 - 15000 psi 2, 3 NPS [F] 0.709 in 0.3945 sq in VIII Div. 1 Steam 15 - 6000 psi VIII Div. 1 Air 0.512 in 1.5 - 1.8125 NPS 3 NPS 0.9207 sq in [H] 1.083 in 15 - 15000 psi VIII Div. 1 Steam 15 - 6000 psi VIII Div. 1 Air 1.8125 - 2.0625 NPS 15 - 15000 psi 3 NPS 1.4913 sq in [J] 1.378 in 0.709 in VIII Div. 1 Steam 15 - 6000 psi VIII Div. 1 Air [L] 2.047 in 0.984 in 15 - 10000 psi 2.5625 - 4 NPS 4, 6 NPS 3.2917 sq in VIII Div. 1 Steam 15 - 6000 psi VIII Div. 1 Air 7.5977 sq in [P] 3.11 in 1.409 in 4 NPS 15 - 3775 psi 6 NPS VIII Div. 1 Steam VIII Div. 1 Air 2.122 in 15 - 2264 psi 18.4176 sq in 8 NPS 6 NPS [R] 4.843 in VIII Div. 1 Steam VIII Div. 1 Air [T] 6.22 in 2.713 in 15 - 2264 psi 8 NPS 10, 12 NPS 30.3905 sq in VIII Div. 1 Steam Page 129 of 812 Effective Date: 2019-05-31

131 Table of Contents Apparecchi Di Sicurezza e Tenuta S.p.A. (ADS) 07175 NB#: Via Merendi 40, Cornaredo (Milano) 20010 Italy location: Acceptable Abbrev.: A.S.T. S.p.A. Certification Design Series SMG-7000 07175 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 13, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.869 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Inlet Size Code Section Outlet Size Set Pressure Range Media VIII Div. 1 Steam 15 - 6000 psi 1 - 1.5 NPS 2-3 NPS 0.335 sq in [F] 0.654 in 0.213 in VIII Div. 1 Air 15 - 6291 psi VIII Div. 1 Steam 0.217 in 0.547 sq in 2.5, 3 NPS 1.5 - 2 NPS 15 - 6000 psi [G] 0.835 in VIII Div. 1 Air 15 - 6291 psi VIII Div. 1 Air [H] 1.043 in 3 NPS 0.855 sq in 0.299 in 15 - 3775 psi VIII Div. 1 Steam VIII Div. 1 Air 2 - 3 NPS 15 - 3775 psi 0.35 in 3, 4 NPS [J] 1.339 in 1.407 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 3775 psi 3 NPS 2.007 sq in [K] 1.598 in 4, 6 NPS 0.419 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 3775 psi [K2] 1.811 in 2.576 sq in 0.472 in VIII Div. 1 Steam VIII Div. 1 Air [L] 1.992 in 0.52 in 15 - 3775 psi 3 - 4 NPS 4, 6 NPS 3.117 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 2264 psi 4 NPS 0.583 in [M] 2.236 in 3.928 sq in 6 NPS VIII Div. 1 Steam VIII Div. 1 Air 15 - 2264 psi 0.643 in [N] 2.457 in 4.74 sq in VIII Div. 1 Steam VIII Div. 1 Air 6.976 sq in 15 - 2264 psi 0.778 in [P] 2.98 in VIII Div. 1 Steam VIII Div. 1 Air 0.923 in 15 - 3775 psi 6 NPS 8, 10 NPS 9.861 sq in [P2] 3.543 in VIII Div. 1 Steam VIII Div. 1 Air 1.024 in [Q] 3.921 in 12.077 sq in 8 NPS 15 - 1509 psi VIII Div. 1 Steam VIII Div. 1 Air 15 - 3775 psi 8, 10 NPS 14.784 sq in [Q2] 4.339 in 1.134 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 1509 psi 17.472 sq in [R] 4.717 in 1.228 in VIII Div. 1 Steam VIII Div. 1 Air 8 NPS 10 NPS 22.949 sq in 15 - 754 psi 1.411 in [R2] 5.406 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 754 psi 10, 12 NPS 28.423 sq in [T] 6.016 in 1.569 VIII Div. 1 Steam Page 130 of 812 Effective Date: 2019-05-31

132 Table of Contents Apparecchi Di Sicurezza e Tenuta S.p.A. (ADS) 07186 NB#: Via Merendi 40, Cornaredo (Milano) 20010 Italy location: Acceptable Abbrev.: A.S.T. S.p.A. Certification Design Series SML-7000 (Liquid) 07186 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 13, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.699 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Media Code Section Inlet Size Lift Set Pressure Range VIII Div. 1 Water 0.121 sq in 1 - 1.5 NPS 2-3 NPS 15 - 10000 psi 0.15 in [D] 0.394 in VIII Div. 1 Water [E] 0.524 in 15 - 6291 psi 0.196 in 0.215 sq in VIII Div. 1 Water 0.24 in 15 - 6291 psi 0.335 sq in [F] 0.654 in VIII Div. 1 Water 1 - 2 NPS 2-3 NPS 0.547 sq in [G] 0.835 in 0.265 in 15 - 6291 psi VIII Div. 1 Water 15 - 3775 psi 1.5 - 2 NPS 0.855 sq in [H] 1.043 in 0.299 in 3 NPS VIII Div. 1 Water 2 - 3 NPS 3, 4 NPS 1.407 sq in [J] 1.339 in 15 - 3775 psi 0.425 in VIII Div. 1 Water 3 NPS 4, 6 NPS 2.007 sq in [K] 1.598 in 0.501 in 15 - 3775 psi VIII Div. 1 Water [K2] 1.811 in 0.576 in 15 - 3775 psi 2.576 sq in VIII Div. 1 Water 3 - 4 NPS 4, 6 NPS 3.117 sq in [L] 1.992 in 0.633 in 15 - 3775 psi VIII Div. 1 Water 3.928 sq in 4 NPS 15 - 2264 psi [M] 2.236 in 6 NPS 0.712 in VIII Div. 1 Water 4.74 sq in [N] 2.547 in 15 - 2264 psi 0.781 in VIII Div. 1 Water 0.948 in [P] 2.98 in 6.976 sq in 15 - 2264 psi VIII Div. 1 Water 15 - 3775 psi 8, 10 NPS 9.861 sq in 6 NPS 1.124 in [P2] 3.543 in VIII Div. 1 Water 15 - 1509 psi 1.244 in [Q] 3.921 in 12.077 sq in 8 NPS VIII Div. 1 Water 15 - 3775 psi 8, 10 NPS 14.784 sq in [Q2] 4.339 in 1.38 in VIII Div. 1 Water 17.472 sq in [R] 4.717 in 15 - 1509 psi 1.502 in VIII Div. 1 Water [R2] 5.406 in 8 NPS 10 NPS 1.732 in 22.949 sq in 15 - 754 psi VIII Div. 1 Water 15 - 754 psi 10, 12 NPS 28.423 sq in [T] 6.016 in 1.937 in Page 131 of 812 Effective Date: 2019-05-31

133 Table of Contents Apparecchi Di Sicurezza e Tenuta S.p.A. (ADS) 07197 NB#: Via Merendi 40, Cornaredo (Milano) 20010 Italy location: Acceptable Abbrev.: A.S.T. S.p.A. Certification Design Series SMG-7000 (Restricted Lift) 07197 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 13, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.869 Unitless Certified Value: N/A Certified Value (alternate medium): Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Inlet Size Flow Area Outlet Size Code Section Media Set Pressure Range VIII Div. 1 Steam 0.087 in 1 - 1.5 NPS 15 - 6000 psi [D1] 0.654 in 0.335 sq in 2-3 NPS VIII Div. 1 Air 15 - 6291 psi VIII Div. 1 Steam [D2] 0.654 in 0.118 in 15 - 6000 psi VIII Div. 1 Air 15 - 6291 psi VIII Div. 1 Steam 15 - 6000 psi 0.138 in [E] 0.654 in VIII Div. 1 Air 15 - 6291 psi VIII Div. 1 Air 1.5 - 2 NPS 0.244 in 3 NPS 0.855 sq in [G2] 1.043 in 15 - 3775 psi VIII Div. 1 Steam VIII Div. 1 Air [G3] 1.043 in 0.264 in 15 - 3775 psi VIII Div. 1 Steam VIII Div. 1 Air 0.28 in [G4] 1.043 in 15 - 3775 psi VIII Div. 1 Steam VIII Div. 1 Air [H1] 1.339 in 0.236 in 15 - 3775 psi 2 - 3 NPS 3, 4 NPS 1.407 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 3775 psi 0.268 in [H3] 1.339 in VIII Div. 1 Steam VIII Div. 1 Air [H4] 1.339 in 0.299 in 15 - 3775 psi VIII Div. 1 Steam VIII Div. 1 Air 6 NPS 15 - 2264 psi 4 NPS 0.346 in 6.976 sq in [L] 2.98 in VIII Div. 1 Steam VIII Div. 1 Air 0.437 in 15 - 2264 psi [M] 2.98 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 2264 psi 0.528 in [N] 2.98 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 2264 psi 0.622 in [N2] 2.98 in VIII Div. 1 Steam VIII Div. 1 Air 6 NPS 8, 10 NPS 17.472 sq in 15 - 1509 psi [P2] 4.717 in 0.693 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 1509 psi 0.846 in [Q] 4.717 in VIII Div. 1 Steam VIII Div. 1 Air [Q2] 4.717 in 1.039 in 15 - 1509 psi VIII Div. 1 Steam Page 132 of 812 Effective Date: 2019-05-31

134 Table of Contents Apparecchi Di Sicurezza e Tenuta S.p.A. (ADS) 07209 NB#: Via Merendi 40, Cornaredo (Milano) 20010 Italy location: Acceptable Abbrev.: A.S.T. S.p.A. Certification Design Series SML-7000 (Liquid) (Restricted Lift) 07209 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 13, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.699 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Water 1 - 1.5 NPS 2-3 NPS 0.335 sq in [D1] 0.654 in 0.098 in 15 - 6291 psi VIII Div. 1 Water [D2] 0.654 in 0.134 in 15 - 6291 psi VIII Div. 1 Water [E] 0.654 in 0.154 in 15 - 6291 psi VIII Div. 1 Water 15 - 3775 psi 0.855 sq in 0.244 in [G2] 1.043 in 3 NPS 1.5 - 2 NPS VIII Div. 1 Water 0.264 in 15 - 3775 psi [G3] 1.043 in VIII Div. 1 Water 0.28 in [G4] 1.043 in 15 - 3775 psi VIII Div. 1 Water [H1] 1.339 in 0.287 in 15 - 3775 psi 2 - 3 NPS 3, 4 NPS 1.407 sq in VIII Div. 1 Water 15 - 3775 psi 0.327 in [H3] 1.339 in VIII Div. 1 Water 15 - 3775 psi [H4] 1.339 in 0.362 in VIII Div. 1 Water 4 NPS 15 - 2264 psi 0.425 in [L] 2.98 in 6.976 sq in 6 NPS VIII Div. 1 Water 15 - 2264 psi 0.535 in [M] 2.98 in VIII Div. 1 Water 0.646 in 15 - 2264 psi [N] 2.98 in VIII Div. 1 Water 0.76 in [N2] 2.98 in 15 - 2264 psi VIII Div. 1 Water [P2] 4.717 in 0.846 in 15 - 1509 psi 6 NPS 8, 10 NPS 17.472 sq in VIII Div. 1 Water 15 - 1509 psi 1.039 in [Q] 4.717 in VIII Div. 1 Water [Q2] 4.717 in 15 - 1509 psi 1.272 in Page 133 of 812 Effective Date: 2019-05-31

135 Table of Contents Apparecchi Di Sicurezza e Tenuta S.p.A. (ADS) 07210 NB#: Via Merendi 40, Cornaredo (Milano) 20010 Italy location: Acceptable Abbrev.: A.S.T. S.p.A. Certification Design Series SML-7000 (Steam & Air/Gas) 07210 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 14, 2016 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.869 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Inlet Size Code Section Set Pressure Range Media Outlet Size VIII Div. 1 Air 15 - 10000 psi 1 - 1.5 NPS 2-3 NPS 0.121 sq in [D] 0.394 in 0.15 in VIII Div. 1 Steam 15 - 6000 psi VIII Div. 1 Steam 15 - 6000 psi 0.196 in [E] 0.524 in 0.215 sq in VIII Div. 1 Air 15 - 6291 psi VIII Div. 1 Steam 0.335 sq in [F] 0.654 in 0.24 in 15 - 6000 psi VIII Div. 1 Air 15 - 6291 psi VIII Div. 1 Steam 2-3 NPS [G] 0.835 in 0.265 in 15 - 6000 psi 1 - 2 NPS 0.547 sq in VIII Div. 1 Air 15 - 6291 psi VIII Div. 1 Air 15 - 3775 psi 1.5 - 2 NPS 0.855 sq in 3 NPS 0.299 in [H] 1.043 in VIII Div. 1 Steam VIII Div. 1 Air 0.425 in 15 - 3775 psi 2 - 3 NPS 3, 4 NPS 1.407 sq in [J] 1.339 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 3775 psi 3 NPS 4, 6 NPS 2.007 sq in [K] 1.598 in 0.501 in VIII Div. 1 Steam VIII Div. 1 Air [K2] 1.811 in 0.576 in 15 - 3775 psi 2.576 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 3775 psi 4, 6 NPS 3 - 4 NPS 0.633 in [L] 1.992 in 3.117 sq in VIII Div. 1 Steam VIII Div. 1 Air 6 NPS 4 NPS 0.712 in [M] 2.236 in 3.928 sq in 15 - 2264 psi VIII Div. 1 Steam VIII Div. 1 Air 15 - 2264 psi 0.781 in [N] 2.547 in 4.74 sq in VIII Div. 1 Steam VIII Div. 1 Air 0.948 in 15 - 2264 psi 6.976 sq in [P] 2.98 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 3775 psi 1.124 in 9.861 sq in 8, 10 NPS 6 NPS [P2] 3.543 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 1509 psi 1.244 in [Q] 3.921 in 12.077 sq in 8 NPS VIII Div. 1 Steam VIII Div. 1 Air 8, 10 NPS [Q2] 4.339 in 1.38 in 15 - 3775 psi 14.784 sq in VIII Div. 1 Steam VIII Div. 1 Air [R] 4.717 in 1.502 in 17.472 sq in 15 - 1509 psi VIII Div. 1 Steam VIII Div. 1 Air [R2] 5.406 in 1.732 in 15 - 754 psi 8 NPS 10 NPS 22.949 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 754 psi 1.937 in [T] 6.016 in 28.423 sq in 10, 12 NPS VIII Div. 1 Steam Page 134 of 812 Effective Date: 2019-05-31

136 Table of Contents Apparecchi Di Sicurezza e Tenuta S.p.A. (ADS) 07221 NB#: Via Merendi 40, Cornaredo (Milano) 20010 Italy location: Acceptable Abbrev.: A.S.T. S.p.A. Certification Design Series SML-7000 (Steam & Air/Gas) (Restricted Lift) 07221 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 14, 2016 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.869 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Outlet Size Lift Set Pressure Range Media Code Section Inlet Size VIII Div. 1 Steam 2-3 NPS 0.335 sq in [D1] 0.654 in 1 - 1.5 NPS 15 - 6000 psi 0.098 in VIII Div. 1 Air 15 - 6291 psi VIII Div. 1 Steam [D2] 0.654 in 0.134 in 15 - 6000 psi VIII Div. 1 Air 15 - 6291 psi VIII Div. 1 Steam [E] 0.654 in 0.154 in 15 - 6000 psi VIII Div. 1 Air 15 - 6291 psi VIII Div. 1 Air [G2] 1.043 in 0.855 sq in 15 - 3775 psi 3 NPS 1.5 - 2 NPS 0.244 in VIII Div. 1 Steam VIII Div. 1 Air [G3] 1.043 in 0.264 in 15 - 3775 psi VIII Div. 1 Steam VIII Div. 1 Air 15 - 3775 psi 0.28 in [G4] 1.043 in VIII Div. 1 Steam VIII Div. 1 Air [H1] 1.339 in 0.287 in 15 - 3775 psi 2 - 3 NPS 3, 4 NPS 1.407 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 3775 psi 0.327 in [H3] 1.339 in VIII Div. 1 Steam VIII Div. 1 Air [H4] 1.339 in 0.362 in 15 - 3775 psi VIII Div. 1 Steam VIII Div. 1 Air 6 NPS 15 - 2264 psi 4 NPS 0.425 in 6.976 sq in [L] 2.98 in VIII Div. 1 Steam VIII Div. 1 Air 0.535 in 15 - 2264 psi [M] 2.98 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 2264 psi 0.646 in [N] 2.98 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 2264 psi 0.76 in [N2] 2.98 in VIII Div. 1 Steam VIII Div. 1 Air 6 NPS 8, 10 NPS 17.472 sq in 15 - 1509 psi [P2] 4.717 in 0.846 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 1509 psi 1.039 in [Q] 4.717 in VIII Div. 1 Steam VIII Div. 1 Air [Q2] 4.717 in 1.272 in 15 - 1509 psi VIII Div. 1 Steam Page 135 of 812 Effective Date: 2019-05-31

137 Table of Contents Apparecchi Di Sicurezza e Tenuta S.p.A. (ADS) 07232 NB#: Via Merendi 40, Cornaredo (Milano) 20010 Italy location: Acceptable Abbrev.: A.S.T. S.p.A. Certification Design Series SHL-7000 / SUL-7000 07232 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 07, 2017 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.901 SCFM/PSIA Certified Value: 5.340 PPH/PSIA Certified Value (alternate medium): Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size Media VIII Div. 1 Air 0.75 - 1 NPS 1-1.5 NPS 0.121 sq in [D] 0.394 in 15 - 10000 psi 0.102 in VIII Div. 1 Steam 15 - 6000 psi Design Series Certification SHL-7000 / SUL-7000 (Liquid) 07243 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 07, 2017 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 3.166 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section VIII Div. 1 Water 15 - 10000 psi 0.102 in [D] 0.394 in 0.121 sq in 1-1.5 NPS 0.75 - 1 NPS Page 136 of 812 Effective Date: 2019-05-31

138 Table of Contents Aquatrol, Incorporated (AQT) 02002 NB#: 600 E North Street, Elburn, IL 60119-8012 United States location: Aquatrol, Incorporated (AQT) 600 E North Street, Elburn, IL 60119-8012 United States location: Certification Design Series 88A, 89A 02002 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on October 15, 1980 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .644 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Set Pressure Range Media Code Section Lift VIII Div. 1 Air 0.5 in 0.5 NPS .75 NPS 0.036 in 15 - 250 psi VIII Div. 1 Steam Design Series Certification 88B, 89B 02013 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on October 15, 1980 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .930 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Lift Set Pressure Range Media Inlet Size Code Section VIII Div. 1 Air 1 NPS 15 - 250 psi 0.04 in 0.75 in 0.75 NPS VIII Div. 1 Steam Certification Design Series 88C, 89C 02024 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on October 14, 1980 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.274 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Flow Area Outlet Size Inlet Size Code Section Lift Media VIII Div. 1 Air 15 - 250 psi 0.075 in 1 in 1.25 NPS 1 NPS VIII Div. 1 Steam Page 137 of 812 Effective Date: 2019-05-31

139 Table of Contents Aquatrol, Incorporated (AQT) 02035 NB#: 600 E North Street, Elburn, IL 60119-8012 United States location: Certification Design Series 88D, 89D 02035 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on October 14, 1980 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.504 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size VIII Div. 1 Air 15 - 250 psi 1.25 NPS 1.5 NPS 1.25 in 0.086 in Design Series Certification 88E, 89E 02046 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on October 14, 1980 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 4.900 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size VIII Div. 1 Air 1.5 NPS 2 NPS 15 - 250 psi 1.5 in 0.1 in VIII Div. 1 Steam Certification Design Series 88F, 89F 02057 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on October 14, 1981 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 7.404 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Outlet Size Flow Area Code Section VIII Div. 1 Air 2 NPS 15 - 250 psi 0.12 in 2 in 2.5 NPS VIII Div. 1 Steam Page 138 of 812 Effective Date: 2019-05-31

140 Table of Contents Aquatrol, Incorporated (AQT) 02068 NB#: 600 E North Street, Elburn, IL 60119-8012 United States location: Certification Design Series 120, 121, 125, 126 02068 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on February 03, 1982 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.037 SCFM/PSIA Certified Value: 2.91 PPH/PSIA Certified Value (alternate medium): Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Lift Outlet Size Inlet Size Code Section Set Pressure Range Flow Area VIII Div. 1 Air .75, top NPS 0.5 - 1 NPS 0.75 in 0.045 in 15 - 200 psi VIII Div. 1 Steam Certification Design Series 130, 132, 133, 135 02079 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on October 15, 1980 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .403 SCFM/PSIA Certified Value: 1.13 PPH/PSIA Certified Value (alternate medium): Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Inlet Size Outlet Size Flow Area Lift Set Pressure Range Code Section VIII Div. 1 Air 0.25 - 0.5 NPS .5, Top NPS 0.5 in 0.024 in 15 - 200 psi VIII Div. 1 Steam Certification Design Series 560, 570 02080 Number: or catalog number Safety Valve Type Classification: Sec. I at National Board T L (Worthington) on November 10, 2005 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.856 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Dual Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Outlet Size Inlet Size Media Set Pressure Range Code Section I & VIII Div. 1 Steam 0.5 - 0.75 NPS .75 NPS 0.125 sq in [D] 0.4 in 0.1 in 15 - 250 psi VIII Div. 1 Air 15 - 300 psi I & VIII Div. 1 Steam 15 - 250 psi 0.132 in [E] 0.53 in 0.221 sq in 1 NPS 0.75 - 1 NPS VIII Div. 1 Air 15 - 300 psi I & VIII Div. 1 Steam 15 - 250 psi 0.167 in [F] 0.67 in 0.352 sq in 1.25 NPS 1 - 1.25 NPS VIII Div. 1 Air 15 - 300 psi I & VIII Div. 1 Steam 15 - 250 psi [G] 0.85 in 0.567 sq in 1.5 NPS 1.25 - 1.5 NPS 0.212 in VIII Div. 1 Air 15 - 300 psi I & VIII Div. 1 Steam 1.5 - 2 NPS 2 NPS 0.899 sq in [H] 1.07 in 0.267 in 15 - 250 psi VIII Div. 1 Air 15 - 300 psi I & VIII Div. 1 Steam [J] 1.365 in 2 - 2.5 NPS 2.5 NPS 15 - 250 psi 0.41 in 1.463 sq in VIII Div. 1 Air 15 - 300 psi Page 139 of 812 Effective Date: 2019-05-31

141 Table of Contents Aquatrol, Incorporated (AQT) 02091 NB#: 600 E North Street, Elburn, IL 60119-8012 United States location: Certification Design Series Series 740 02091 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on November 21, 2012 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Lift Inlet Size Code Section Outlet Size Set Pressure Range VIII Div. 1 Air 0.5 - 1 NPS 0.75, 1 NPS 0.125 sq in [D] 0.4 in 0.105 in 15 - 1500 psi VIII Div. 1 Steam 15 - 300 psi VIII Div. 1 Air 15 - 1500 psi 0.75 - 1 NPS 0.135 in [E] 0.53 in 0.221 sq in 1, 1.25 NPS VIII Div. 1 Steam 15 - 300 psi VIII Div. 1 Air 15 - 1500 psi 0.75 - 1.5 in 1, 1.25 NPS 0.221 sq in 0.135 in [E] 0.53 in VIII Div. 1 Steam 15 - 300 psi VIII Div. 1 Steam 1.5 NPS 0.17 in 15 - 300 psi 0.353 sq in 1 - 1.5 NPS [F] 0.67 in VIII Div. 1 Air 15 - 750 psi VIII Div. 1 Steam 1.25 - 2 NPS 0.215 in [G] 0.84 in 0.554 sq in 15 - 300 psi 2 NPS VIII Div. 1 Air 15 - 700 psi VIII Div. 1 Steam [H] 1.084 in 0.28 in 15 - 300 psi 1.5 - 2.5 NPS 2.5 NPS 0.923 sq in VIII Div. 1 Air 15 - 600 psi VIII Div. 1 Steam 1.421 sq in [J] 1.345 in 0.34 in 15 - 300 psi 2 - 3 NPS 3 NPS VIII Div. 1 Air 15 - 600 psi Design Series Certification Series 740 (Liquid) 02103 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on November 20, 2012 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .791 Unitless Certified Value: Liquid Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size VIII Div. 1 Water [D] 0.4 in 0.5 - 1 NPS 15 - 1500 psi 0.105 in 0.125 sq in 0.75, 1 NPS VIII Div. 1 Water 0.221 sq in 0.135 in 15 - 1500 psi 1, 1.25 NPS [E] 0.53 in 0.75 - 1 NPS VIII Div. 1 Water 0.221 sq in [E] 0.53 in 0.135 in 15 - 1500 psi 0.75 - 1.5 in 1, 1.25 NPS VIII Div. 1 Water 1 - 1.5 NPS 15 - 750 psi 0.17 in [F] 0.67 in 0.353 sq in 1.5 NPS VIII Div. 1 Water 0.554 sq in 1.25 - 2 NPS 15 - 700 psi 0.215 in [G] 0.84 in 2 NPS VIII Div. 1 Water 1.5 - 2.5 NPS 2.5 NPS 0.923 sq in [H] 1.084 in 0.28 in 15 - 600 psi VIII Div. 1 Water 2 - 3 NPS 15 - 600 psi 0.34 in [J] 1.345 in 1.421 sq in 3 NPS Page 140 of 812 Effective Date: 2019-05-31

142 Table of Contents Aquatrol, Incorporated (AQT) 02114 NB#: 600 E North Street, Elburn, IL 60119-8012 United States location: Certification Design Series 140-A 02114 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on August 20, 2018 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 0.924 SCFM/PSIA Certified Value: Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Set Pressure Range Lift Flow Area Outlet Size Inlet Size VIII Div. 1 Air Side 15 - 450 psi 0.09 in 0.281 in 0.0604 sq in 0.25 - 0.5 NPS Certification Design Series 140-B 02125 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on August 20, 2018 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.487 SCFM/PSIA Certified Value: Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Media Set Pressure Range Lift Flow Area Outlet Size VIII Div. 1 Air 0.375 - 0.75 NPS 15 - 450 psi 0.12 in 0.39 in 0.0837 sq in Side Page 141 of 812 Effective Date: 2019-05-31

143 Table of Contents ARI - Armaturen USA, LP (TAR) 73000 NB#: 125 Magellan Circle, Webster, TX 77598 United States location: ARI - Armaturen USA, LP (TAR) 125 Magellan Circle, Webster, TX 77598 United States location: Certification Design Series Reyco R, RB & RO (Fig. 971, 973, 974) 73000 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 19, 1997 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .86 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Outlet Size Media Set Pressure Range Inlet Size VIII Div. 1 Steam 15 - 2900 psi [D] 0.394 in 0.122 sq in 2 - 3 NPS 1 - 1.5 NPS 0.12 in VIII Div. 1 Air 15 - 6250 psi VIII Div. 1 Steam [E] 0.526 in 0.217 sq in 0.16 in 15 - 2900 psi VIII Div. 1 Air 15 - 6250 psi VIII Div. 1 Steam [F] 0.658 in 15 - 2900 psi 0.34 sq in 1.5 NPS 2 - 3 NPS 0.2 in VIII Div. 1 Air 15 - 6250 psi VIII Div. 1 Steam 15 - 2900 psi 0.26 in 1.5 - 2 NPS [G] 0.843 in 0.558 sq in 2.5, 3 NPS VIII Div. 1 Air 15 - 4905 psi VIII Div. 1 Steam 3 NPS 0.869 sq in [H] 1.052 in 0.32 in 15 - 2900 psi VIII Div. 1 Air 15 - 3300 psi VIII Div. 1 Steam 1.427 sq in [J] 1.348 in 0.41 in 15 - 2900 psi 2 - 3 NPS 3, 4 NPS VIII Div. 1 Air 15 - 3300 psi VIII Div. 1 Steam [K] 1.61 in 3 NPS 2.036 sq in 4, 6 NPS 0.49 in 15 - 2900 psi VIII Div. 1 Air 15 - 3300 psi VIII Div. 1 Air 0.61 in 3.16 sq in 4, 6 NPS 3 - 4 NPS [L] 2.006 in 15 - 2900 psi VIII Div. 1 Steam VIII Div. 1 Air [M] 2.253 in 0.69 in 15 - 1600 psi 4 NPS 6 NPS 3.987 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 1600 psi 4.807 sq in [N] 2.474 in 0.75 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 1600 psi 0.92 in [P] 3 in 7.07 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 925 psi 6 NPS [Q] 3.948 in 12.24 sq in 8 NPS 1.2 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 350 psi 1.45 in 17.72 sq in 8, 10 NPS [R] 4.75 in VIII Div. 1 Steam VIII Div. 1 Air [T] 6.155 in 8 NPS 1.84 in 15 - 325 psi 29.75 sq in 10 NPS VIII Div. 1 Steam Page 142 of 812 Effective Date: 2019-05-31

144 Table of Contents ARI - Armaturen USA, LP (TAR) 73011 NB#: 125 Magellan Circle, Webster, TX 77598 United States location: Certification Design Series Reyco R, RB, RO, RBO (Fig. 971, 973, 974) (liquid) 73011 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 27, 2001 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .724 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Lift Inlet Size Code Section Outlet Size Set Pressure Range VIII Div. 1 Water 15 - 6250 psi 2, 2.5, 3 NPS 0.122 sq in [D] 0.394 in 1 - 1.5 NPS 0.12 in VIII Div. 1 Water 15 - 6250 psi 0.16 in [E] 0.526 in 0.217 sq in VIII Div. 1 Water [F] 0.658 in 0.2 in 15 - 6250 psi 1.5 NPS 2 - 3 NPS 0.34 sq in VIII Div. 1 Water 1.5 - 2 NPS 0.558 sq in [G] 0.843 in 0.26 in 15 - 4905 psi 2.5, 3 NPS VIII Div. 1 Water 3 NPS 0.869 sq in [H] 1.052 in 0.32 in 15 - 3300 psi VIII Div. 1 Water 15 - 3300 psi 3, 4 NPS 2 - 3 NPS [J] 1.348 in 0.41 in 1.427 sq in VIII Div. 1 Water [K] 1.61 in 0.49 in 15 - 3300 psi 3 NPS 4, 6 NPS 2.036 sq in VIII Div. 1 Water 15 - 2900 psi 0.61 in [L] 2.006 in 3.16 sq in 4, 6 NPS 3 - 4 NPS VIII Div. 1 Water 3.987 sq in [M] 2.253 in 0.69 in 15 - 1600 psi 4 NPS 6 NPS VIII Div. 1 Water 15 - 1600 psi 0.75 in [N] 2.474 in 4.807 sq in VIII Div. 1 Water [P] 3 in 15 - 1600 psi 7.07 sq in 0.92 in VIII Div. 1 Water 1.2 in [Q] 3.948 in 12.24 sq in 8 NPS 6 NPS 15 - 925 psi VIII Div. 1 Water 17.72 sq in 8, 10 NPS 15 - 350 psi 1.45 in [R] 4.75 in VIII Div. 1 Water [T] 6.155 in 1.84 in 15 - 325 psi 8 NPS 10 NPS 29.75 sq in Certification Design Series RL-14 & RLO-14 73044 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 08, 2010 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.23 SCFM/PSIA Certified Value: 3.46 PPH/PSIA Certified Value (alternate medium): Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Set Pressure Range Lift Inlet Size Flow Area Outlet Size VIII Div. 1 0.315 in 0.5 - 1 NPS 1 NPS 15 - 2900 psi 0.078 in 0.078 sq in VIII Div. 1 Air 15 - 5000 psi Page 143 of 812 Effective Date: 2019-05-31

145 Table of Contents ARI - Armaturen USA, LP (TAR) 73055 NB#: 125 Magellan Circle, Webster, TX 77598 United States location: Certification Design Series RL-14 & RLO-14 (Liquids) 73055 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 04, 2010 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 1.88 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Div. 1 Water 0.315 in 0.5 - 1 NPS 1 NPS 0.078 sq in 0.078 in 15 - 5000 psi Certification Design Series RL40, RLO40, RL41, RLO41 73145 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 10, 2010 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.86 SCFM/PSIA Certified Value: 5.23 PPH/PSIA Certified Value (alternate medium): Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Set Pressure Range Outlet Size Inlet Size Media Flow Area VIII Div. 1 15 - 2900 psi 0.44 in 0.152 sq in 1-2 NPS 0.75 - 1 NPS 0.365 in VIII Div. 1 Air 15 - 5000 psi Certification Design Series RL40, RLO40, RL41, RLO41 (Liquids) 73156 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 26, 2010 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 2.684 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Set Pressure Range Inlet Size Outlet Size Lift Flow Area VIII Div. 1 Water 0.44 in 15 - 5000 psi 0.75 - 1 NPS 1-2 NPS 0.152 sq in Page 144 of 812 Effective Date: 2019-05-31

146 Table of Contents ARI - Armaturen USA, LP (TAR) 73167 NB#: 125 Magellan Circle, Webster, TX 77598 United States location: Certification Design Series RL40, RL040 (0.847 in. orif.) 73167 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on November 03, 2010 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 8.86 SCFM/PSIA Certified Value: 24.89 PPH/PSIA Certified Value (alternate medium): Air Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Set Pressure Range Media Code Section Lift VIII Div. 1 Air 2 NPS 1.5 - 2 NPS 0.563 sq in 0.847 in 15 - 1500 psi VIII Div. 1 Steam Design Series Certification RL40, RL040 (0.847 in. orif.)(liquid) 73178 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on November 03, 2010 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 13.05 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Set Pressure Range Outlet Size Inlet Size Flow Area Media VIII Div. 1 Water 15 - 1500 psi 0.847 in 0.563 sq in 1.5 - 2 NPS 2 NPS Certification Design Series RL14 & RLO14 (0.394 in.) 73202 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 30, 2014 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.637 SCFM/PSIA Certified Value: 4.60 PPH/PSIA Certified Value (alternate medium): Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Outlet Size Flow Area Lift Set Pressure Range Code Section VIII Div. 1 Steam 0.122 sq in 0.394 in 0.0985 in 15 - 2900 psi 0.5 - 1 NPS 1 NPS VIII Div. 1 Air 15 - 5000 psi Page 145 of 812 Effective Date: 2019-05-31

147 Table of Contents ARI - Armaturen USA, LP (TAR) 73213 NB#: 125 Magellan Circle, Webster, TX 77598 United States location: Certification Design Series RL14 & RLO14 (0.394 in.) (Liquid) 73213 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 30, 2014 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 3.021 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size VIII Div. 1 Water 0.394 in 0.0985 in 15 - 5000 psi 0.5 - 1 NPS 1 NPS 0.122 sq in Design Series Certification RL40, RLO40, RL41, RLO41 (0.547 in orifice), Design Rev. A 73224 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 04, 2014 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.76 SCFM/PSIA Certified Value: 10.53 PPH/PSIA Certified Value (alternate medium): Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size VIII Div. 1 Steam 0.137 in 0.547 in 0.235 sq in 1-2 NPS 15 - 2900 psi 1 - 1.5 NPS VIII Div. 1 Air 15 - 3000 psi Certification Design Series RL40, RLO40, RL41, RLO41 (0.547 in. orifice) (Liquid), Design Rev. A 73235 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 04, 2014 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 5.635 GPM/SQ.RT. PSID Certified Value: Liquid Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Inlet Size Outlet Size Media Set Pressure Range Lift Flow Area VIII Div. 1 Water 15 - 3000 psi 0.137 in 0.547 in 0.235 sq in 1-2 NPS 1 - 1.5 NPS Page 146 of 812 Effective Date: 2019-05-31

148 Table of Contents ARI-Armaturen Albert Richter GmbH & Co. KG (ARI) 08008 NB#: Mergelheide 56-60, D-33758 Schloss Holte-Stukenbrock Germany location: Acceptable Abbrev.: ARI ARI-Armaturen Albert Richter GmbH & Co. KG (ARI) location: Mergelheide 56-60, D-33758 Schloss Holte-Stukenbrock Germany Acceptable Abbrev.: ARI Certification Design Series 901/902/911/912 08008 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on November 09, 2001 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .817 Unitless Certified Value: Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Outlet Size Inlet Size Media Code Section Lift Flow Area VIII Div. 1 Air 0.617 sq in 1 NPS 1.5, 2.0 NPS 0.886 in 0.22 in 30 - 493 psi VIII Div. 1 Steam VIII Div. 1 Air 1.024 sq in 1.142 in 1.25 NPS 0.29 in 2.0 NPS 30 - 493 psi VIII Div. 1 Steam VIII Div. 1 Air 0.29 in 30 - 493 psi 1.5 NPS 2, 2.5 NPS 1.024 sq in 1.142 in VIII Div. 1 Steam VIII Div. 1 Air 30 - 493 psi 0.37 in 1.417 in 1.578 sq in 2.5, 3.0 NPS VIII Div. 1 Steam VIII Div. 1 Air 1.772 in 0.45 in 30 - 493 psi 3 NPS 2 NPS 2.465 sq in VIII Div. 1 Steam VIII Div. 1 Air 0.61 in 4.166 sq in 4 NPS 2.5 - 3 NPS 30 - 406 psi 2.303 in VIII Div. 1 Steam VIII Div. 1 Air 30 - 276 psi 6 NPS 9.861 sq in 4 NPS 0.98 in 3.543 in VIII Div. 1 Steam VIII Div. 1 Air 30 - 392 psi 8 NPS 5 - 6 NPS 1.34 in 4.173 in 13.678 sq in VIII Div. 1 Steam VIII Div. 1 Air 4.921 in 19.022 sq in 10 NPS 6 NPS 30 - 305 psi 1.46 in VIII Div. 1 Steam Design Series Certification 901/902/911/912 (Liquids) 08019 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on October 15, 2001 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .545 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: Opening Pressure Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size Media VIII Div. 1 Water 1.25 NPS 2 NPS 15 - 493 psi 0.29 in 1.142 in 1.024 sq in VIII Div. 1 Water 0.29 in 15 - 493 psi 1.5 NPS 1.024 sq in 1.142 in 2, 2.5 NPS VIII Div. 1 Water 15 - 493 psi 2.5, 3 NPS 1.578 sq in 1.417 in 0.37 in VIII Div. 1 Water 1.772 in 2 NPS 3 NPS 2.465 sq in 0.45 in 15 - 493 psi VIII Div. 1 Water 0.61 in 15 - 406 psi 4 NPS 2.303 in 2.5 - 3 NPS 4.166 sq in VIII Div. 1 Water 0.98 in 3.543 in 9.861 sq in 6 NPS 4 NPS 15 - 276 psi VIII Div. 1 Water 4.173 in 1.34 in 15 - 392 psi 5 - 6 NPS 8 NPS 13.678 sq in VIII Div. 1 Water 15 - 305 psi 1.46 in 4.921 in 19.022 sq in 10 NPS 6 NPS Page 147 of 812 Effective Date: 2019-05-31

149 Table of Contents ARI-Armaturen Albert Richter GmbH & Co. KG (ARI) 08020 NB#: Mergelheide 56-60, D-33758 Schloss Holte-Stukenbrock Germany location: Acceptable Abbrev.: ARI Certification Design Series 901/902/911/912 (1" liquid) 08020 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on August 24, 2001 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 14.41 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: Opening Pressure Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Outlet Size Flow Area Inlet Size Lift Code Section Media VIII Div. 1 Water 0.617 sq in 1 NPS 1.5, 2.0 NPS 0.886 in 15 - 493 psi 0.22 in Design Series Certification 901/902/911/912 {15-30} 08031 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 09, 2007 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .769 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Inlet Size Lift Set Pressure Range Media Code Section Flow Area VIII Div. 1 Air 15 - 30 psi 1.5, 2.0 NPS 0.394 sq in 0.709 in 1 NPS 0.205 in VIII Div. 1 Steam VIII Div. 1 Air 1.142 in 0.29 in 15 - 30 psi 1.25 NPS 2.0 NPS 1.024 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 30 psi 1.5 NPS 0.29 in 1.142 in 1.024 sq in 2, 2.5 NPS VIII Div. 1 Steam VIII Div. 1 Air 15 - 30 psi 0.37 in 2.5, 3.0 NPS 1.578 sq in 1.417 in VIII Div. 1 Steam VIII Div. 1 Air 2 NPS 0.45 in 15 - 30 psi 2.465 sq in 1.772 in 3 NPS VIII Div. 1 Steam VIII Div. 1 Air 15 - 30 psi 2.5 - 3 NPS 4 NPS 2.303 in 4.166 sq in 0.61 in VIII Div. 1 Steam VIII Div. 1 Air 3.543 in 0.98 in 15 - 30 psi 4 NPS 6 NPS 9.861 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 30 psi 1.34 in 4.173 in 8 NPS 13.678 sq in 5 - 6 NPS VIII Div. 1 Steam VIII Div. 1 Air 4.921 in 15 - 30 psi 1.46 in 19.022 sq in 10 NPS 6 NPS VIII Div. 1 Steam Page 148 of 812 Effective Date: 2019-05-31

150 Table of Contents Baird Manufacturing (BRD) 04004 NB#: 3105 Charles Page Boulevard, Tulsa, OK 74127 United States location: Baird Manufacturing (BRD) 3105 Charles Page Boulevard, Tulsa, OK 74127 United States location: Certification Design Series 731-1-GS 04004 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on October 10, 1984 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .963 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media Code Section VIII Div. 1 Air 0.5 - 1 NPS 25 - 2500 psi 1 NPS 0.066 sq in 0.456 in 0.125 in Design Series Certification 831 04037 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on March 12, 1986 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.128 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Lift Outlet Size Inlet Size Flow Area Set Pressure Range VIII Div. 1 Air 25 - 300 psi 0.375 in 0.02449 sq in 1 NPS 1 NPS Certification Design Series 7100-2 G 04048 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Louisiana State University on December 04, 1971 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.97 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Outlet Size Flow Area Lift Set Pressure Range Code Section VIII Div. 1 Air 0.442 sq in 0.75 in 0.218 in 20 - 600 psi 2 NPS 2 NPS Page 149 of 812 Effective Date: 2019-05-31

151 Table of Contents Baird Manufacturing (BRD) 04059 NB#: 3105 Charles Page Boulevard, Tulsa, OK 74127 United States location: Certification Design Series 7100-2 GHP 04059 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Louisiana State University on December 04, 1971 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.45 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size VIII Div. 1 Air 20 - 2500 psi 0.156 in 0.5 in 0.196 sq in 2 NPS 2 NPS Page 150 of 812 Effective Date: 2019-05-31

152 Table of Contents Beaumont Manufacturing and Distribution Company, LLC (MPV) 00910 NB#: 1009 Laurel Street, Beaumont, TX 77701 United States location: Acceptable Abbrev.: BMD Beaumont Manufacturing and Distribution Company, LLC (MPV) location: 1009 Laurel Street, Beaumont, TX 77701 United States Acceptable Abbrev.: BMD Design Series Certification RV10 00910 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 06, 2016 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .756 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Outlet Size Media Set Pressure Range Inlet Size VIII Div. 1 Air 15 - 3000 psi 0.75 - 2 NPS .75-2 NPS 0.13 sq in [D] 0.407 in 0.2 in VIII Div. 1 Air 0.23 in 0.22 sq in 15 - 2400 psi [E] 0.529 in VIII Div. 1 Air 15 - 2400 psi 0.31 in [F] 0.674 in 0.357 sq in 1.5-2.5 NPS 1.5 - 2 NPS VIII Div. 1 Air 15 - 2000 psi 1.5- 2.5 NPS 0.35 in 0.478 sq in [G] 0.78 in VIII Div. 1 Air 2 NPS [H] 1.078 in 2, 2.5 NPS 0.913 sq in 15 - 2000 psi 0.44 in VIII Div. 1 Air 2 - 3 NPS 1.44 sq in [J] 1.354 in 0.61 in 3, 4 NPS 15 - 1800 psi VIII Div. 1 Air [K] 1.635 in 0.72 in 15 - 1500 psi 3 NPS 3, 4 NPS 2.1 sq in VIII Div. 1 Air 15 - 1250 psi 0.895 in [L] 2.05 in 3.3 sq in 4, 6 NPS 3 - 4 NPS VIII Div. 1 Air 4.1 sq in 1.01 in 15 - 1000 psi 6 NPS [M] 2.285 in 4 NPS Page 151 of 812 Effective Date: 2019-05-31

153 Table of Contents Beijing Aerospace Petrochemical Technology & Equipment Engineering Corporation Limited (BAP) 12407 NB#: No. 11, Yuncheng Street, location: Acceptable Abbrev.: BAPC Beijing Aerospace Petrochemical Technology & Equipment Engineering Corporation Limited (BAP) location: No. 11, Yuncheng Street, Acceptable Abbrev.: BAPC Certification Design Series HT Series 12407 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on August 20, 2010 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .872 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Inlet Size Outlet Size Flow Area Lift Set Pressure Range Code Section VIII Div. 1 Air 0.134 sq in 1 - 1.5 NPS 2, 3 NPS [D] 0.4134 in 0.124 in 15 - 6000 psi VIII Div. 1 Air 0.165 in 0.239 sq in 15 - 6000 psi [E] 0.5512 in VIII Div. 1 Air 15 - 5000 psi 0.201 in [F] 0.6693 in 0.352 sq in 2, 3 NPS 1.5 NPS VIII Div. 1 Air 0.26 in 15 - 3705 psi 1.5 - 2 NPS 2.5, 3 NPS 0.589 sq in [G] 0.866 in VIII Div. 1 Air 0.887 sq in 3 NPS [H] 1.063 in 0.319 in 15 - 2750 psi VIII Div. 1 Air 3, 4 NPS [J] 1.358 in 0.407 in 15 - 2700 psi 2 - 3 NPS 1.448 sq in VIII Div. 1 Air 15 - 2220 psi 3 NPS 4, 6 NPS 2.097 sq in [K] 1.634 in 0.19 in VIII Div. 1 Air 3 - 4 NPS [L] 2.028 in 0.608 in 4, 6 NPS 15 - 1500 psi 3.23 sq in VIII Div. 1 Air 0.685 in 15 - 1100 psi 4 NPS 6 NPS 4.097 sq in [M] 2.284 in VIII Div. 1 Air 15 - 1000 psi 4.988 sq in [N] 2.52 in 0.756 in VIII Div. 1 Air 0.909 in [P] 3.032 in 15 - 1000 psi 7.22 sq in VIII Div. 1 Air [Q] 4.016 in 1.206 in 15 - 600 psi 6 NPS 8 NPS 12.667 sq in VIII Div. 1 Air 15 - 300 psi 1.441 in [R] 4.803 in 18.118 sq in 8, 10 NPS VIII Div. 1 Air 8 NPS [T] 6.142 in 1.843 in 15 - 300 psi 10 NPS 29.628 sq in VIII Div. 1 Air 15 - 285 psi 2.244 in [V] 7.48 in 43.943 sq in 14 NPS 10 NPS VIII Div. 1 Air [W] 8.858 in 5.658 in 15 - 285 psi 61.626 sq in 16 NPS 12 NPS VIII Div. 1 Air 15 - 145 psi 3.071 in [Y] 10.236 in 82.291 sq in 18 NPS 14 NPS VIII Div. 1 Air 3.307 in 15 - 145 psi 16 NPS 18 NPS 95.448 sq in [Z] 11.024 in VIII Div. 1 Air 20 NPS 109.563 sq in 15 - 145 psi 3.543 in [Z1] 11.811 in VIII Div. 1 Air 4.016 in 15 - 145 psi 24 NPS [AA] 13.386 in 18 NPS 140.732 sq in VIII Div. 1 Air [BB] 14.567 in 4.37 in 15 - 145 psi 20 NPS 24 NPS 166.66 sq in Design Series Certification HTXO Series (Liquid) 12418 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 20, 2014 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 3.30 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 15 - 6000 psi 0.118 in 0.394 in 0.122 sq in .5-1.0 NPS 0.5 - 1 NPS Page 152 of 812 Effective Date: 2019-05-31

154 Table of Contents Beijing Aerospace Petrochemical Technology & Equipment Engineering Corporation Limited (BAP) 12429 NB#: No. 11, Yuncheng Street, location: Acceptable Abbrev.: BAPC Design Series Certification HT Series (Liquid) 12429 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 20, 2014 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.751 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Media Code Section Inlet Size Lift Set Pressure Range VIII Div. 1 Water 0.134 sq in 1 - 1.5 2-3 NPS 15 - 6000 psi 0.124 in [D] 0.4134 in VIII Div. 1 Water [E] 0.5512 in 15 - 6000 psi 0.165 in 0.239 sq in VIII Div. 1 Water 0.201 in 15 - 5000 psi 1.5 2-3 NPS 0.352 sq in [F] 0.6693 in VIII Div. 1 Water 0.589 sq in 1.5 - 2 2.5-3 NPS [G] 0.8661 in 0.26 in 15 - 3705 psi VIII Div. 1 Water [H] 1.063 in 0.319 in 15 - 2750 psi 3 NPS 0.887 sq in VIII Div. 1 Water 15 - 2700 psi 0.407 in 2 - 3 3-4 NPS 1.448 sq in [J] 1.358 in VIII Div. 1 Water 3 [K] 1.634 in 4-6 NPS 0.49 in 15 - 2220 psi 2.097 sq in VIII Div. 1 Water 15 - 1500 psi [L] 2.028 in 3.23 sq in 4-6 NPS 3 - 4 0.608 in VIII Div. 1 Water 15 - 1100 psi 0.685 in [M] 2.284 in 4.097 sq in 6 NPS 4 VIII Div. 1 Water 4.988 sq in 15 - 1000 psi [N] 2.52 in 0.756 in VIII Div. 1 Water 0.909 in 7.22 sq in [P] 3.032 in 15 - 1000 psi VIII Div. 1 Water 12.667 sq in 15 - 600 psi 1.206 in 8 NPS 6 [Q] 4.016 in VIII Div. 1 Water 8-10 NPS 18.118 sq in [R] 4.803 in 1.441 in 15 - 300 psi VIII Div. 1 Water 10 NPS 29.628 sq in 1.843 in [T] 6.142 in 15 - 300 psi 8 VIII Div. 1 Water 2.244 in [V] 7.48 in 43.943 sq in 14 NPS 10 15 - 285 psi VIII Div. 1 Water 15 - 285 psi 2.658 in [W] 8.858 in 61.626 sq in 16 NPS 12 VIII Div. 1 Water 18 NPS 15 - 145 psi 14 3.071 in 82.291 sq in [Y] 10.236 in VIII Div. 1 Water 16 18 NPS 95.448 sq in [Z] 11.024 in 15 - 145 psi 3.307 in VIII Div. 1 Water 20 NPS 3.543 in 15 - 145 psi 109.563 sq in [Z1] 11.811 in VIII Div. 1 Water [AA] 13.386 in 4.016 in 15 - 145 psi 18 24 NPS 140.732 sq in VIII Div. 1 Water 15 - 145 psi 4.37 in [BB] 14.567 in 166.66 sq in 24 NPS 20 Page 153 of 812 Effective Date: 2019-05-31

155 Table of Contents Beijing Aerospace Petrochemical Technology & Equipment Engineering Corporation Limited (BAP) 12430 NB#: No. 11, Yuncheng Street, location: Acceptable Abbrev.: BAPC Certification Design Series HTXD Series (Liquid) 12430 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 21, 2014 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .763 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Inlet Size Code Section Set Pressure Range Outlet Size Media VIII Div. 1 Water 30 - 6170 psi 1 - 1.5 NPS 2 NPS 0.134 sq in [D] 0.4134 in 0.165 in VIII Div. 1 Water 0.239 sq in 0.22 in 30 - 6170 psi [E] 0.5512 in VIII Div. 1 Water 0.373 sq in [F] 0.689 in 0.276 in 30 - 6170 psi VIII Div. 1 Water 0.616 sq in 1.5 - 2 NPS 3 NPS [G] 0.8858 in 0.355 in 30 - 6170 psi VIII Div. 1 Water [H] 1.102 in 30 - 6170 psi 0.954 sq in 0.441 in VIII Div. 1 Water 30 - 4620 psi 2 - 3 NPS 3, 4 NPS 1.578 sq in [J] 1.4173 in 0.567 in VIII Div. 1 Water 3 NPS 4 NPS [K] 1.693 in 0.677 in 30 - 3705 psi 2.251 sq in VIII Div. 1 Water 0.843 in 30 - 3705 psi 3 - 4 NPS 4, 6 NPS 3.484 sq in [L] 2.1063 in VIII Div. 1 Water 30 - 3705 psi 0.945 in [M] 2.3622 in 4.383 sq in 4 NPS 6 NPS VIII Div. 1 Water [N] 2.5984 in 1.04 in 30 - 3705 psi 5.303 sq in VIII Div. 1 Water 30 - 3705 psi 1.26 in [P] 3.1496 in 7.791 sq in VIII Div. 1 Water 8 NPS 30 - 1480 psi 6 NPS 1.653 in 13.421 sq in [Q] 4.1339 in VIII Div. 1 Water 19.327 sq in [R] 4.961 in 1.984 in 30 - 1020 psi VIII Div. 1 Water 2.488 in 10 NPS [T] 6.2205 in 30.39 sq in 30 - 985 psi 8 NPS VIII Div. 1 Water 2.992 in 30 - 765 psi 10 NPS 14 NPS 43.943 sq in [V] 7.48 in VIII Div. 1 Water 30 - 765 psi 3.543 in [W] 8.858 in 16 NPS 12 NPS 61.626 sq in VIII Div. 1 Water [Y] 10.236 in 4.095 in 30 - 765 psi 14 NPS 18 NPS 82.291 sq in VIII Div. 1 Water 18 NPS 95.448 sq in [Z] 11.024 in 4.409 in 30 - 765 psi 16 NPS VIII Div. 1 Water 109.563 sq in 20 NPS [Z1] 11.811 in 30 - 765 psi 4.724 in VIII Div. 1 Water 24 NPS 18 NPS 5.355 in 30 - 765 psi 140.732 sq in [AA] 13.386 in VIII Div. 1 Water [BB] 14.567 in 5.827 in 30 - 765 psi 20 NPS 24 NPS 166.66 sq in Page 154 of 812 Effective Date: 2019-05-31

156 Table of Contents Beijing Aerospace Petrochemical Technology & Equipment Engineering Corporation Limited (BAP) 12441 NB#: No. 11, Yuncheng Street, location: Acceptable Abbrev.: BAPC Certification Design Series HTXD Series 12441 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 30, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .853 Unitless Certified Value: Gas Test Medium: Air/Gas Certified Medium: None Special Service: 1.Pop 3.Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Media Code Section Set Pressure Range Lift Inlet Size Outlet Size VIII Div. 1 Air 30 - 6170 psi 0.165 in 0.134 sq in 2 NPS 1 - 1.5 NPS [D] 0.4134 in VIII Div. 1 Air 0.239 sq in [E] 0.5512 in 0.22 in 30 - 6170 psi VIII Div. 1 Air [F] 0.689 in 30 - 6170 psi 0.373 sq in 0.276 in VIII Div. 1 Air 0.355 in [G] 0.8858 in 0.616 sq in 3 NPS 1.5 - 2 NPS 30 - 6170 psi VIII Div. 1 Air 0.441 in 30 - 6170 psi 0.954 sq in [H] 1.1024 in VIII Div. 1 Air 1.578 sq in 2 - 3 NPS 3, 4 NPS [J] 1.4173 in 0.567 in 30 - 4620 psi VIII Div. 1 Air 30 - 3705 psi 3 NPS 2.251 sq in [K] 1.6929 in 0.677 in 4 NPS VIII Div. 1 Air 30 - 3705 psi 3 - 4 NPS 4, 6 NPS 3.484 sq in [L] 2.1063 in 0.843 in VIII Div. 1 Air 4 NPS [M] 2.3622 in 0.945 in 30 - 3705 psi 4.383 sq in 6 NPS VIII Div. 1 Air 1.04 in 30 - 3705 psi 5.303 sq in [N] 2.5984 in VIII Div. 1 Air 7.791 sq in 30 - 3705 psi 1.26 in [P] 3.1496 in VIII Div. 1 Air [Q] 4.1339 in 6 NPS 13.421 sq in 1.653 in 8 NPS 30 - 1480 psi VIII Div. 1 Air [R] 4.9606 in 1.984 in 30 - 1020 psi 19.327 sq in VIII Div. 1 Air 8 NPS 10 NPS 30.39 sq in [T] 6.2205 in 2.488 in 30 - 985 psi VIII Div. 1 Air 43.943 sq in 10 NPS 30 - 765 psi [V] 7.48 in 14 NPS 2.992 in VIII Div. 1 Air 12 NPS 16 NPS 61.626 sq in [W] 8.858 in 30 - 765 psi 3.543 in VIII Div. 1 Air 18 NPS 14 NPS 4.095 in 30 - 765 psi 82.291 sq in [Y] 10.236 in VIII Div. 1 Air 16 NPS 18 NPS 95.448 sq in [Z] 11.024 in 4.409 in 30 - 765 psi VIII Div. 1 Air 20 NPS 30 - 765 psi 4.724 in [Z1] 11.811 in 109.563 sq in VIII Div. 1 Air 5.355 in 30 - 765 psi 18 NPS 140.732 sq in [AA] 13.386 in 24 NPS VIII Div. 1 Air [BB] 14.567 in 5.827 in 30 - 765 psi 20 NPS 24 NPS 166.66 sq in Design Series Certification HTXO Series 12452 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 30, 2015 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.823 SCFM/PSIA Certified Value: Gas Test Medium: Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 15 - 6000 psi 0.118 in 0.394 in 0.122 sq in .5-1 NPS 0.5 - 1 NPS Page 155 of 812 Effective Date: 2019-05-31

157 Table of Contents Beijing Aerospace Petrochemical Technology & Equipment Engineering Corporation Limited (BAP) 12463 NB#: No. 11, Yuncheng Street, location: Acceptable Abbrev.: BAPC Certification Design Series HTBPO 12463 or catalog number Number: Buckling Pin Non-reclosing Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on November 01, 2016 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.790 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Buckling Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Inlet Size Outlet Size Flow Area Lift Set Pressure Range VIII Div. 1 Air 50 - 1480 psi 1 NPS 2 NPS 0.77 sq in 0.99 in 0.81 in VIII Div. 1 Air 15 - 1480 psi 0.98 in 1.55 in 1.89 sq in 2, 3 NPS 1.5 NPS VIII Div. 1 Air 2.92 sq in 2 NPS 3 NPS 1.93 in 1.09 in 15 - 1480 psi VIII Div. 1 Air 4 NPS 3.12 in 1.45 in 15 - 1480 psi 3 NPS 7.63 sq in VIII Div. 1 Air 15 - 1480 psi 1.67 in 4 NPS 6 NPS 11.74 sq in 3.87 in VIII Div. 1 Air 6 NPS 5.87 in 2.27 in 8 NPS 15 - 1480 psi 27.03 sq in VIII Div. 1 Air 2.8 in 7.61 in 45.52 sq in 10 NPS 8 NPS 15 - 1480 psi VIII Div. 1 Air 9.61 in 3.4 in 15 - 1480 psi 10 NPS 12 NPS 72.58 sq in VIII Div. 1 Air 12 NPS 14 NPS 101.42 sq in 11.36 in 3.92 in 15 - 1480 psi VIII Div. 1 Air 140.26 sq in 14 NPS 13.36 in 4.52 in 16 NPS 15 - 740 psi VIII Div. 1 Air 15 - 740 psi 5.12 in 15.36 in 185.38 sq in 18 NPS 16 NPS VIII Div. 1 Air 15 - 740 psi 18 NPS 5.75 in 17.46 in 239.55 sq in 20 NPS VIII Div. 1 Air 19.46 in 20 NPS 297.55 sq in 6.35 in 24 NPS 15 - 285 psi VIII Div. 1 Air 23.44 in 7.55 in 15 - 285 psi 24 NPS 30 NPS 431.87 sq in VIII Div. 1 Air 32 NPS 508.68 sq in 25.44 in 8.15 in 15 - 285 psi 26 NPS VIII Div. 1 Air 28 NPS 34 NPS 15 - 285 psi 8.48 in 26.57 in 554.34 sq in VIII Div. 1 Air 28.41 in 9.03 in 15 - 285 psi 30 NPS 36 NPS 633.72 sq in Page 156 of 812 Effective Date: 2019-05-31

158 Table of Contents Beijing Aerospace Petrochemical Technology & Equipment Engineering Corporation Limited (BAP) 12474 NB#: No. 11, Yuncheng Street, location: Acceptable Abbrev.: BAPC Certification Design Series HTBPX 12474 or catalog number Number: Buckling Pin Non-reclosing Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on November 01, 2016 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.86 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Buckling Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Inlet Size Outlet Size Flow Area Lift Set Pressure Range Code Section VIII Div. 1 Air 4 NPS 4 NPS 11.74 sq in 3.87 in 2.87 in 15 - 720 psi VIII Div. 1 Air 27.03 sq in 4.06 in 5.87 in 6 NPS 5 - 720 psi 6 NPS VIII Div. 1 Air 5.24 in 7.61 in 45.52 sq in 8 NPS 8 NPS 5 - 720 psi VIII Div. 1 Air 72.58 sq in 10 NPS 10 NPS 9.61 in 6.42 in 5 - 720 psi VIII Div. 1 Air 12 NPS 11.36 in 7.6 in 5 - 720 psi 12 NPS 101.42 sq in VIII Div. 1 Air 5 - 720 psi 14 NPS 14 NPS 140.26 sq in 13.36 in 8.78 in VIII Div. 1 Air 16 NPS 16 NPS 15.36 in 9.96 in 5 - 720 psi 185.38 sq in VIII Div. 1 Air 11.14 in 5 - 720 psi 18 NPS 18 NPS 239.55 sq in 17.46 in VIII Div. 1 Air 5 - 720 psi 12.32 in 19.46 in 297.55 sq in 20 NPS 20 NPS VIII Div. 1 Air 23.44 in 14.69 in 5 - 720 psi 24 NPS 24 NPS 431.87 sq in VIII Div. 1 Air 26 NPS 26 NPS 508.65 sq in 25.44 in 15.87 in 5 - 720 psi VIII Div. 1 Air 554.34 sq in 28 NPS 26.57 in 28 NPS 5 - 720 psi 17.05 in VIII Div. 1 Air 5 - 145 psi 18.23 in 28.35 in 631.08 sq in 30 NPS 30 NPS VIII Div. 1 Air 32 NPS 30.33 in 19.41 in 32 NPS 5 - 145 psi 722.53 sq in VIII Div. 1 Air 5 - 145 psi 34 NPS 34 NPS 813.97 sq in 32.19 in 20.59 in VIII Div. 1 Air 21.77 in 5 - 145 psi 912.55 sq in 36 NPS 34.09 in 36 NPS VIII Div. 1 Air 5 - 145 psi 22.95 in 35.94 in 1014.65 sq in 38 NPS 38 NPS VIII Div. 1 Air 37.87 in 24.13 in 5 - 145 psi 40 NPS 40 NPS 1126.61 sq in VIII Div. 1 Air 42 NPS 1249.84 sq in 39.89 in 25.31 in 5 - 145 psi 42 NPS VIII Div. 1 Air 1366.03 sq in 5 - 145 psi 44 NPS 44 NPS 41.7 in 26.5 in VIII Div. 1 Air 46 NPS 1469.14 sq in 43.65 in 27.68 in 46 NPS 5 - 145 psi VIII Div. 1 Air 45.59 in 28.86 in 5 - 145 psi 48 NPS 48 NPS 1632.45 sq in Page 157 of 812 Effective Date: 2019-05-31

159 Table of Contents Beijing Aerospace Petrochemical Technology & Equipment Engineering Corporation Limited (BAP) 12485 NB#: No. 11, Yuncheng Street, location: Acceptable Abbrev.: BAPC Certification Design Series HTGS 12485 or catalog number Number: Safety Valve Type Classification: Sec. I & VIII Div. 1 at National Board T L (Worthington) on January 25, 2018 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.869 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Dual Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Lift Media Code Section Flow Area Outlet Size Set Pressure Range I & VIII Div. 1 Steam 145 - 6525 psi 1.5 NPS 2-3 NPS 0.352 sq in [F] 0.669 in 0.167 in I & VIII Div. 1 Steam 2.5, 3 NPS [G] 0.866 in 0.217 in 145 - 6525 psi 0.589 sq in I & VIII Div. 1 Steam 0.266 in 3, 4 NPS 0.887 sq in 145 - 6525 psi [H] 1.063 in I & VIII Div. 1 Steam 1.024 sq in [H2] 1.142 in 0.285 in 145 - 6525 psi I & VIII Div. 1 Steam 0.34 in [J] 1.358 in 2 NPS 3-6 NPS 1.449 sq in 145 - 6525 psi I & VIII Div. 1 Steam 145 - 6525 psi 0.354 in [J2] 1.417 in 1.578 sq in I & VIII Div. 1 Steam 4, 6 NPS 2.097 sq in [K] 1.634 in 0.408 in 145 - 6525 psi 2.5 - 3 NPS I & VIII Div. 1 Steam 145 - 6525 psi 0.463 in [K2] 1.85 in 2.689 sq in I & VIII Div. 1 Steam 0.507 in 145 - 6525 psi 3 NPS 4, 6 NPS 3.229 sq in [L] 2.028 in I & VIII Div. 1 Steam [L2] 2.126 in 3.55 sq in 0.531 in 145 - 6525 psi I & VIII Div. 1 Steam 0.571 in [M] 2.283 in 145 - 6525 psi 4.095 sq in I & VIII Div. 1 Steam [N] 2.52 in 0.63 in 145 - 6525 psi 4 NPS 6 NPS 4.986 sq in I & VIII Div. 1 Steam 145 - 6525 psi 0.758 in [P] 3.031 in 7.218 sq in 6,8 NPS I & VIII Div. 1 Steam 0.778 in 7.598 sq in 145 - 6525 psi 6, 8 NPS [P2] 3.11 in I & VIII Div. 1 Steam 8 NPS 6 NPS 12.666 sq in [Q] 4.016 in 1.004 in 145 - 2000 psi I & VIII Div. 1 Steam 145 - 2000 psi [R] 4.803 in 8, 10 NPS 1.201 in 18.119 sq in I & VIII Div. 1 Steam 19.945 sq in [R2] 5.039 in 1.26 in 145 - 2000 psi I & VIII Div. 1 Steam [T] 6.142 in 145 - 2000 psi 29.626 sq in 8 NPS 1.535 in 10, 12 NPS I & VIII Div. 1 Steam 145 - 500 psi 1.929 in [V] 7.717 in 46.766 sq in 14 NPS 10 NPS I & VIII Div. 1 Steam 145 - 500 psi 2.313 in [W] 9.252 in 67.229 sq in 16 NPS 12 NPS I & VIII Div. 1 Steam 18 NPS 145 - 500 psi 14 NPS 2.697 in 91.395 sq in [Y] 10.787 in I & VIII Div. 1 Steam 16 NPS 18 NPS 100.974 sq in [Z] 11.339 in 145 - 500 psi 2.835 in I & VIII Div. 1 Steam 20 NPS 3.1 in 145 - 500 psi 120.793 sq in [ZZ] 12.402 in I & VIII Div. 1 Steam [AA] 13.898 in 3.474 in 145 - 500 psi 18 NPS 24 NPS 151.695 sq in I & VIII Div. 1 Steam 145 - 500 psi 3.858 in [BB] 15.433 in 187.066 sq in 24 NPS 20 NPS Page 158 of 812 Effective Date: 2019-05-31

160 Table of Contents Berstscheiben Schlesinger GmbH (BER) 43029 NB#: Gewerbering 20, Schalksmühle D-58579 Germany location: Berstscheiben Schlesinger GmbH (BER) Gewerbering 20, Schalksmühle D-58579 Germany location: Certification Design Series BK 43029 Number: or catalog number H Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 12, 2017 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 2.98 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Inlet Size Lift Flow Area Certification Design Series C 43030 Number: or catalog number H Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on November 15, 2016 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size VIII Div. 1 0.351 sq in 20 DN 4.35 - 580 psi VIII Div. 1 4.35 - 580 psi 0.589 sq in 25 DN VIII Div. 1 4.35 - 580 psi 0.954 sq in 32 DN VIII Div. 1 4.35 - 580 psi 1.407 sq in 40 DN VIII Div. 1 50 DN 1.45 - 580 psi 2.25 sq in VIII Div. 1 1.45 - 580 psi 3.682 sq in 65 DN VIII Div. 1 80 DN 1.16 - 580 psi 5.964 sq in VIII Div. 1 100 DN .73 - 362.5 psi 9.86 sq in VIII Div. 1 125 DN 14.729 sq in .73 - 362.5 psi VIII Div. 1 .36 - 290 psi 150 DN 23.86 sq in VIII Div. 1 35.181 sq in 200 DN .29 - 290 psi VIII Div. 1 .29 - 290 psi 64.396 sq in 250 DN VIII Div. 1 300 DN .73 - 290 psi 88.743 sq in VIII Div. 1 124.65 sq in .73 - 217.5 psi 350 DN VIII Div. 1 .36 - 217.5 psi 157.64 sq in 400 DN VIII Div. 1 .36 - 145 psi 268.91 sq in 500 DN VIII Div. 1 600 DN .36 - 145 psi 368.13 sq in VIII Div. 1 .36 - 145 psi 514.29 sq in 700 DN VIII Div. 1 800 DN 684.79 sq in .36 - 145 psi VIII Div. 1 879.47 sq in .36 - 145 psi 900 DN VIII Div. 1 .36 - 145 psi 1098.64 sq in 1000 DN Page 159 of 812 Effective Date: 2019-05-31

161 Table of Contents 72009 Bopp & Reuther Valves GmbH (BOP) NB#: location: Carl Reuther Strasse 1, Mannheim D-68305 Germany Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Bopp & Reuther Valves GmbH (BOP) location: Carl Reuther Strasse 1, Mannheim D-68305 Germany Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Page 160 of 812 Effective Date: 2019-05-31

162 Table of Contents Bopp & Reuther Valves GmbH (BOP) NB#: 72009 location: Carl Reuther Strasse 1, Mannheim D-68305 Germany Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Certification Design Series Si 81/83/84 72009 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 19, 1995 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .860 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Outlet Size Set Pressure Range Lift Media Flow Area III Steam 0.185 in 1 - 1.5 NPS 2, 3 NPS 0.2252 sq in [E] 0.535 in 15 - 2900 psi VIII Div. 1 III Air 15 - 6000 psi VIII Div. 1 III Steam 2, 2.5, 3 NPS 1.5 NPS 0.236 in [F] 0.669 in 0.3518 sq in 15 - 2900 psi VIII Div. 1 III Air 15 - 5000 psi VIII Div. 1 Air 15 - 5500 psi III Steam 1.5 - 2 NPS 15 - 2900 psi 2.5, 3 NPS 0.5785 sq in [G] 0.858 in 0.295 in VIII Div. 1 III Air 15 - 3705 psi VIII Div. 1 III Air 0.374 in 15 - 2750 psi 3 NPS 0.9007 sq in [H] 1.071 in III Steam VIII Div. 1 VIII Div. 1 Air 15 - 5080 psi III Steam 1.4743 sq in 0.472 in 15 psi 3, 4 NPS 2 - 3 NPS [J] 1.37 in III Air 15 - 2700 psi VIII Div. 1 VIII Div. 1 Steam III Air 0.571 in 15 - 2220 psi 4, 6 NPS 2.1067 sq in 3 NPS [K] 1.638 in VIII Div. 1 III Steam VIII Div. 1 III Air 4, 6 NPS 3.2665 sq in 3 - 4 NPS 0.709 in 15 - 1500 psi [L] 2.039 in VIII Div. 1 III Steam VIII Div. 1 III Air 0.787 in 15 - 1100 psi 4.1235 sq in 4 NPS [M] 2.291 in 6 NPS VIII Div. 1 III Steam VIII Div. 1 III Air 15 - 1000 psi [N] 2.516 in 0.866 in 4.9708 sq in VIII Div. 1 III Steam VIII Div. 1 III Air 15 - 1000 psi 7.3118 sq in [P] 3.051 in 1.063 in VIII Div. 1 III Steam VIII Div. 1 Page 161 of 812 Effective Date: 2019-05-31

163 Table of Contents Bopp & Reuther Valves GmbH (BOP) 72009 NB#: Carl Reuther Strasse 1, Mannheim D-68305 Germany location: Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther ...Continued Orifice [designator] diameter Inlet Size Outlet Size Code Section Flow Area Lift Set Pressure Range Media III Air 8 NPS [Q] 4.016 in 1.417 in 15 - 600 psi 6 NPS 12.6655 sq in VIII Div. 1 III Steam VIII Div. 1 III Air 15 - 300 psi 8, 10 NPS 18.3279 sq in [R] 4.831 in 1.693 in VIII Div. 1 III Steam VIII Div. 1 III Air 8 NPS 2.165 in 15 - 300 psi 10 NPS [T] 6.157 in 29.778 sq in VIII Div. 1 III Steam VIII Div. 1 VIII Div. 1 Air [V] 204.5 mm 10 NPS 14 NPS 49087 sq mm 72 mm 15 - 300 psi VIII Div. 1 Air 15 - 300 psi 12 NPS 125664 sq mm [W] 245 mm 86 mm 16 NPS Design Series Certification Si/83/84/81 (RL) 72010 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 19, 1995 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.20 SCFM/PSIA Certified Value: 6.18 PPH/PSIA Certified Value (alternate medium): Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Lift Inlet Size Set Pressure Range Media Code Section III Steam 15 - 2900 psi 1 - 1.5 NPS 0.087 in [D] 0.402 in 0.1267 sq in 2, 3 NPS VIII Div. 1 III Air 15 - 6000 psi VIII Div. 1 Design Series Certification Si 81/83/84 (Liquids) (RL) 72021 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 14, 1995 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 3.51 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Lift Inlet Size Code Section Outlet Size Set Pressure Range III Water [D] 0.402 in 0.087 in 15 - 6000 psi 1 - 1.5 NPS 2, 3 NPS 0.1267 sq in VIII Div. 1 Page 162 of 812 Effective Date: 2019-05-31

164 Table of Contents Bopp & Reuther Valves GmbH (BOP) 72032 NB#: Carl Reuther Strasse 1, Mannheim D-68305 Germany location: Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Certification Design Series SiZ 2507 72032 or catalog number Number: Safety Valve Type Classification: Sec. III at National Board T L (Worthington) on January 31, 2000 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size III Steam 24.2 sq in 200 mm 300 mm 141 mm 51 mm 726 - 745 psi Certification Design Series SiC 11/13/14 72043 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 19, 2000 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Outlet Size Inlet Size Code Section Set Pressure Range Lift III Air 0.5 - 0.75 NPS 1 NPS 0.107 in 15 - 2900 psi 0.099 sq in 0.355 in VIII Div. 1 III Steam VIII Div. 1 III Air 0.481 in 0.146 in 15 - 1500 psi 0.181 sq in 1 NPS 0.75 - 1 NPS VIII Div. 1 III Steam VIII Div. 1 III Air 15 - 750 psi 0.352 sq in 1.5 NPS 1 - 1.5 NPS 0.201 in 0.67 in VIII Div. 1 III Steam VIII Div. 1 Page 163 of 812 Effective Date: 2019-05-31

165 Table of Contents Bopp & Reuther Valves GmbH (BOP) 72054 NB#: Carl Reuther Strasse 1, Mannheim D-68305 Germany location: Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Certification Design Series SiC 11/13/14 (Liquids) 72054 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 19, 2000 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .647 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Inlet Size Media Outlet Size Set Pressure Range III Water 0.355 in 0.107 in 15 - 2900 psi 0.5 - 0.75 NPS 1 NPS 0.099 sq in VIII Div. 1 III Water 0.75 - 1 NPS 1 NPS 0.181 sq in 0.481 in 0.146 in 15 - 1500 psi VIII Div. 1 III Water 15 - 750 psi 0.201 in 0.67 in 0.352 sq in 1.5 NPS 1 NPS VIII Div. 1 Page 164 of 812 Effective Date: 2019-05-31

166 Table of Contents Bopp & Reuther Valves GmbH (BOP) 72065 NB#: Carl Reuther Strasse 1, Mannheim D-68305 Germany location: Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Design Series Certification Si 83/84/81 (Liquids) 72065 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 13, 1995 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .675 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Outlet Size Flow Area Code Section Inlet Size Media Set Pressure Range III Water 15 - 6000 psi 0.185 in 0.2252 sq in 2, 3 NPS 1 - 1.5 NPS [E] 0.535 in VIII Div. 1 III Water 2, 2.5, 3 NPS 0.3518 sq in [F] 0.669 in 0.236 in 15 - 5000 psi VIII Div. 1 III Water 0.295 in 15 - 3705 psi 0.5785 sq in 1.5 - 2 NPS 2.5, 3 NPS [G] 0.858 in VIII Div. 1 III Water 0.9007 sq in 15 - 2750 psi 3 NPS 0.374 in [H] 1.071 in VIII Div. 1 III Water 0.472 in 15 - 2700 psi 3, 4 NPS 1.4743 sq in 2 - 3 NPS [J] 1.37 in VIII Div. 1 III Water 15 - 2220 psi 0.571 in [K] 1.638 in 2.1067 sq in 4, 6 NPS 3 NPS VIII Div. 1 III Water 3 - 4 NPS 15 - 1500 psi 0.709 in [L] 2.039 in 3.2665 sq in 4, 6 NPS VIII Div. 1 III Water 4.1235 sq in [M] 2.291 in 6 NPS 0.787 in 4 NPS 15 - 1100 psi VIII Div. 1 III Water [N] 2.516 in 15 - 1000 psi 0.866 in 4.9708 sq in VIII Div. 1 III Water 7.3118 sq in [P] 3.051 in 1.063 in 15 - 1000 psi VIII Div. 1 III Water 15 - 600 psi 1.417 in 8 NPS 6 NPS [Q] 4.016 in 12.6655 sq in VIII Div. 1 III Water 15 - 300 psi 8, 10 NPS 18.3279 sq in [R] 4.831 in 1.693 in VIII Div. 1 III Water 8 NPS 15 - 300 psi 2.165 in [T] 6.157 in 29.778 sq in 10 NPS VIII Div. 1 VIII Div. 1 Water 72 mm 15 - 300 psi 10 NPS 49087 sq mm [V] 204.5 mm 14 NPS VIII Div. 1 Air [W] 245 mm 86 mm 15 - 300 psi 12 NPS 16 NPS 125664 sq mm Page 165 of 812 Effective Date: 2019-05-31

167 Table of Contents Bopp & Reuther Valves GmbH (BOP) NB#: 72076 location: Carl Reuther Strasse 1, Mannheim D-68305 Germany Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Certification Design Series Si 91/95, SiZ 2507 RL 72076 or catalog number Number: Safety Valve Type Classification: Sec. I at National Board T L (Worthington) on April 07, 2005 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .826 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: Force Flow Steam Generator or High Temperature Water Boilers Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Outlet Size Flow Area Code Section Inlet Size Media Set Pressure Range I Steam 0.487 sq in 44 - 4351 psi 1.5 NPS 0.236 in 2.5, 3 NPS 0.787 in III VIII I Steam 0.761 sq in 0.295 in 44 - 4351 psi 0.984 in III VIII I Steam 44 - 4351 psi 0.378 in 1.247 sq in 1.26 in III VIII I Steam 2 NPS 3 NPS 1.417 in 0.425 in 44 - 3626 psi 1.578 sq in III VIII I Steam 1.948 sq in 44 - 3626 psi 1.575 in 0.472 in III VIII I Steam 44 - 4786 psi 2.5 NPS 1.772 in 2.465 sq in 3, 4 NPS 0.531 in III VIII I Steam 3.292 sq in 2.047 in 0.614 in 44 - 4786 psi III VIII I Steam 2.283 in 44 - 3916 psi 3 NPS 6 NPS 0.685 in 4.095 sq in III VIII I Steam 44 - 3916 psi 4.832 sq in 2.48 in 0.744 in III VIII I Steam 0.803 in 44 - 3626 psi 6 NPS 2.677 in 5.629 sq in 4 NPS III VIII I Steam 44 - 3626 psi 2.874 in 0.862 in 6.487 sq in III VIII I Steam 44 - 3626 psi 7.598 sq in 3.11 in 0.933 in III VIII Page 166 of 812 Effective Date: 2019-05-31

168 Table of Contents Bopp & Reuther Valves GmbH (BOP) 72076 NB#: Carl Reuther Strasse 1, Mannheim D-68305 Germany location: Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther ...Continued Orifice [designator] diameter Media Lift Code Section Inlet Size Set Pressure Range Outlet Size Flow Area I Steam 6 NPS 1.016 in 44 - 2611 psi 8, 8 Dual NPS 3.386 in 9.004 sq in III VIII I Steam 10.99 sq in 3.74 in 1.122 in 44 - 2611 psi III VIII I Steam 44 - 2611 psi 1.24 in 4.134 in 13.42 sq in III VIII I Steam 10, 10 Dual NPS 15.27 sq in 4.409 in 1.323 in 44 - 2176 psi III VIII I Steam 17.53 sq in 44 - 2176 psi 4.724 in 1.417 in III VIII I Steam 44 - 1870 psi 1.559 in 8 NPS 5.197 in 21.21 sq in 10, 12, 14, 10 Dual, 12 Dual, 14 Dual NPS III VIII I Steam 12, 14, 12 Dual, 14 Dual NPS 21.86 sq in 5.276 in 1.583 in 44 - 1814 psi III VIII I Steam 44 - 1549 psi 12, 12 Dual NPS 24.271 sq in 5.559 in 1.668 in III VIII I Steam 25.6 sq in 10 Dual, 12, 14, 12 Dual, 14 Dual NPS 44 - 1549 psi 1.713 in 5.709 in III VIII I Steam 30.39 sq in 6.22 in 1.866 in 44 - 1450 psi III VIII I Steam 35.18 sq in 2.008 in 10 NPS 6.693 in 44 - 1450 psi 16, 16 Dual NPS III VIII I Steam 40.77 sq in 44 - 1450 psi 7.205 in 2.161 in III VIII I Steam 7.756 in 2.327 in 44 - 1450 psi 47.25 sq in III VIII I Steam 57.85 sq in 8.583 in 2.575 in 44 - 609 psi 12 NPS 20, 20 Dual NPS III VIII I Steam 44 - 609 psi 2.776 in 9.252 in 67.23 sq in III VIII Page 167 of 812 Effective Date: 2019-05-31

169 Table of Contents Bopp & Reuther Valves GmbH (BOP) 72087 NB#: Carl Reuther Strasse 1, Mannheim D-68305 Germany location: Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Certification Design Series Si 91/95 01-07 Type L + H (restricted lift) 72087 Number: or catalog number Safety Valve Type Classification: Sec. I at National Board T L (Worthington) on August 03, 2010 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.826 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Lift Flow Area Outlet Size Inlet Size Set Pressure Range Page 168 of 812 Effective Date: 2019-05-31

170 Table of Contents Bopp & Reuther Valves GmbH (BOP) 72098 NB#: Carl Reuther Strasse 1, Mannheim D-68305 Germany location: Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Certification Design Series Si 41/43/44 02-05 72098 Number: or catalog number Safety Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 18, 2010 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.848 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Media Code Section Set Pressure Range Lift Inlet Size Outlet Size VIII Div. 1 Air 15 - 4351 psi 0.22 in 0.351 sq in 1.25 NPS 0.75 - 1 NPS 0.669 in VIII Div. 1 Steam VIII Div. 1 Air 1 NPS 2 NPS 0.486 sq in 0.26 in 15 - 4351 psi 0.787 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 4351 psi 0.287 in 0.866 in 0.588 sq in 1.5 NPS VIII Div. 1 Steam VIII Div. 1 Air 0.358 in 15 - 3626 psi 1.25 - 1.5 NPS 2 NPS 0.92 sq in 1.083 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 3191 psi 0.457 in 1.378 in 1.49 sq in 3 NPS 1.5 - 2 NPS VIII Div. 1 Steam VIII Div. 1 Air 2 NPS 1.575 in 0.52 in 1.947 sq in 3 NPS 15 - 2321 psi VIII Div. 1 Steam VIII Div. 1 Air 0.547 in 1.654 in 2.147 sq in 15 - 2321 psi VIII Div. 1 Steam VIII Div. 1 Air 0.677 in 2.5 - 3 NPS 4 NPS 3.289 sq in 2.047 in 15 - 2321 psi VIII Div. 1 Steam VIII Div. 1 Air 3 NPS 3.816 sq in 2.205 in 0.728 in 4 NPS 15 - 1668 psi VIII Div. 1 Steam VIII Div. 1 Air 15 - 1668 psi 5,6 NPS 5.14 sq in 2.559 in 0.846 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 1160 psi 4 NPS 0.909 in 2.756 in 5.962 sq in 6 NPS VIII Div. 1 Steam VIII Div. 1 Air 15 - 1160 psi 1.028 in 3.11 in 7.592 sq in VIII Div. 1 Steam VIII Div. 1 Air 8,9,10 NPS 10.521 sq in 5 - 6 NPS 3.661 in 1.209 in 15 - 943 psi VIII Div. 1 Steam VIII Div. 1 Air 6 NPS 15 - 943 psi 1.457 in 15.259 sq in 10 NPS 4.409 in VIII Div. 1 Steam VIII Div. 1 Air 4.921 in 8 NPS 10 NPS 19.009 sq in 1.626 in 15 - 435 psi VIII Div. 1 Steam VIII Div. 1 Air 15 - 435 psi 12 NPS 29.61 sq in 2.028 in 6.142 in VIII Div. 1 Steam VIII Div. 1 Air 7.087 in 2.339 in 15 - 290 psi 10 - 12 NPS 14, 16 NPS 39.42 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 290 psi 16 NPS 12 NPS 2.22 in 8.661 in 58.88 sq in VIII Div. 1 Steam VIII Div. 1 Air 3.055 in 9.252 in 15 - 290 psi 20 NPS 14 NPS 67.19 sq in VIII Div. 1 Steam VIII Div. 1 Air 16 NPS 20 NPS 79.11 sq in 10.039 in 3.315 in 15 - 290 psi VIII Div. 1 Steam VIII Div. 1 Air 95.39 sq in 15 - 290 psi 3.638 in 11.024 in VIII Div. 1 Steam Page 169 of 812 Effective Date: 2019-05-31

171 Table of Contents Bopp & Reuther Valves GmbH (BOP) 72100 NB#: Carl Reuther Strasse 1, Mannheim D-68305 Germany location: Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Design Series Certification Si 41/43/44 02-05 (Liquids) 72100 Number: or catalog number Safety Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 17, 2010 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .575 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Code Section Media Set Pressure Range Lift Inlet Size Outlet Size VIII Div. 1 Water 15 - 4351 psi 0.22 in 0.352 sq in 1.25, 1.50 NPS 0.75 - 1 NPS 0.669 in VIII Div. 1 Water 2 NPS 1 NPS 0.486 sq in 0.787 in 0.26 in 15 - 4351 psi VIII Div. 1 Water 0.287 in 1.5 NPS 0.589 sq in 15 - 4351 psi 0.866 in VIII Div. 1 Water 15 - 3626 psi 0.358 in 1.083 in 0.921 sq in 2 NPS 1.25 - 1.5 NPS VIII Div. 1 Water 2 NPS 1.5 - 2 NPS 1.491 sq in 1.378 in 0.457 in 15 - 3626 psi VIII Div. 1 Water 0.52 in 15 - 2321 psi 1.948 sq in 2 NPS 3 NPS 1.575 in VIII Div. 1 Water 15 - 2321 psi 547 in 1.654 in 2.149 sq in VIII Div. 1 Water 3.291 sq in 2.5 - 3 NPS 15 - 2321 psi 2.047 in 0.677 in 4 NPS VIII Div. 1 Water 15 - 1668 psi 0.728 in 2.205 in 3.819 sq in 4 NPS 3 NPS VIII Div. 1 Water 5,6 NPS 5.143 sq in 2.559 in 0.846 in 15 - 1668 psi VIII Div. 1 Water 6 NPS 5.966 sq in 2.756 in 0.909 in 4 NPS 15 - 1160 psi VIII Div. 1 Water 3.11 in 15 - 1160 psi 1.028 in 7.596 sq in VIII Div. 1 Water 15 - 943 psi 1.209 in 3.661 in 10.53 sq in 8, 10 NPS 5 - 6 NPS VIII Div. 1 Water 6 NPS 4.409 in 10 NPS 1.457 in 15 - 943 psi 15.27 sq in VIII Div. 1 Water 15 - 435 psi 1.626 in 4.921 in 19.02 sq in 10 NPS 8 NPS VIII Div. 1 Water 15 - 435 psi 12 NPS 6.142 in 29.63 sq in 2.028 in VIII Div. 1 Water 15 - 290 psi 2.339 in 7.087 in 39.45 sq in 16 NPS 10 - 12 NPS VIII Div. 1 Water 2.858 in 15 - 290 psi 12 NPS 16 NPS 58.92 sq in 8.661 in VIII Div. 1 Water 3.055 in 14 NPS 20 NPS 67.23 sq in 9.252 in 15 - 290 psi VIII Div. 1 Water 15 - 290 psi 16 NPS 20 NPS 95.44 sq in 11.024 in 3.638 in Design Series Certification Si 11, Si 13, Si 14 (B, C, D, E orif.) 72122 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 07, 2013 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .841 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Lift Set Pressure Range Code Section Inlet Size Media Flow Area VIII Div. 1 0.091 in 15 - 5800 psi 1/2 NPS 0.063 sq in 0.375 - 0.5 NPS [B] 0.283 in VIII Div. 1 VIII Div. 1 0.099 sq in [C] 0.354 in 0.114 in 15 - 5800 psi 0.375 - 0.75 NPS 1/2, 3/4, 1 NPS VIII Div. 1 VIII Div. 1 15 - 5800 psi 0.5 - 1 NPS 3/4, 1 NPS 0.139 sq in [D] 0.421 in 0.138 in VIII Div. 1 VIII Div. 1 0.245 sq in 1 - 1.5 NPS 15 - 2900 psi 0.181 in [E] 0.559 in 1.5, 2 NPS VIII Div. 1 Page 170 of 812 Effective Date: 2019-05-31

172 Table of Contents Bopp & Reuther Valves GmbH (BOP) 72133 NB#: Carl Reuther Strasse 1, Mannheim D-68305 Germany location: Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Certification Design Series Si 11, Si 13, Si 14 (F orif.) 72133 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 06, 2013 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 6.41 SCFM/PSIA Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Code Section Outlet Size Inlet Size Media Set Pressure Range VIII Div. 1 15 - 1450 psi 0.252 in [F] 0.768 in 2 NPS 1.5 - 2 NPS 0.463 sq in VIII Div. 1 Certification Design Series Si 11, Si 13, Si 14 (B, C, D, E orif., Liquid) 72144 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 05, 2013 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .620 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: (none) Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media Code Section VIII Div. 1 0.063 sq in [B] 0.283 in 0.091 in 15 - 5800 psi 0.375 - 0.5 NPS 1/2 NPS VIII Div. 1 15 - 5800 psi 0.114 in [C] 0.354 in 0.099 sq in 1/2, 3/4, 1 NPS 0.375 - 0.75 NPS VIII Div. 1 15 - 5800 psi 0.5 - 1 NPS 3/4, 1 NPS [D] 0.421 in 0.138 in 0.139 sq in VIII Div. 1 2 NPS 0.181 in [E] 0.559 in 15 - 1450 psi 0.245 sq in 1 NPS VIII Div. 1 [E] 0.559 in 1 - 1.5 NPS 0.245 sq in 15 - 2900 psi 0.181 in 1.5 NPS Design Series Certification Si 11, Si 13, Si 14 (F orif. , Liquid) 72155 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 05, 2013 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 9.16 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Flow Area Lift Set Pressure Range Media Code Section Outlet Size VIII Div. 1 0.463 sq in [F] 0.768 in 0.252 in 15 - 1450 psi 1.5 - 2 NPS 2 NPS Page 171 of 812 Effective Date: 2019-05-31

173 Table of Contents Bopp & Reuther Valves GmbH (BOP) 72166 NB#: Carl Reuther Strasse 1, Mannheim D-68305 Germany location: Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Certification Design Series Si 63 (High Press.) 72166 Number: or catalog number Safety Relief Valve Type Classification: Sec. III NC at National Board T L (Worthington) on December 06, 2012 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .819 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Code Section Outlet Size Set Pressure Range Lift Inlet Size Media III NC 0.175 sq in 0.472 in 0.75 NPS .75, 1.5 NPS 15 - 4350 psi 0.158 in III NC 0.217 in 15 - 4350 psi 0.75 - 1 NPS 1, 1.25 NPS 0.312 sq in 0.63 in III NC 0.312 sq in 1 NPS 1, 1.5, 2 NPS 0.63 in 0.217 in 15 - 4350 psi III NC 15 - 3625 psi 0.787 in 0.276 in 0.487 sq in 1.5, 2 NPS III NC 15 - 3625 psi 0.276 in 0.787 in 0.487 sq in 1.25, 2 NPS 1.25 - 1.5 NPS III NC 15 - 3625 psi 1.5, 2 NPS 0.761 sq in 0.984 in 0.335 in III NC 1.5 NPS 2.5, 3 NPS 1.247 sq in 1.26 in 0.434 in 15 - 3190 psi III NC 15 - 3190 psi 2 NPS 1.26 in 0.434 in 2 NPS 1.247 sq in III NC 15 - 2900 psi 0.552 in 1.575 in 1.948 sq in 3, 4 NPS 2 - 2.5 NPS III NC 0.67 in 15 - 2320 psi 4 NPS 1.969 in 2.5 - 3 NPS 3.043 sq in III NC 15 - 1740 psi 0.847 in 2.48 in 4.832 sq in 5 NPS 3 NPS III NC 2.48 in 0.847 in 15 - 1740 psi 4 NPS 6 NPS 4.832 sq in III NC 7.218 sq in 15 - 1305 psi 1.044 in 3.031 in III NC 1.26 in 15 - 870 psi 3.661 in 10.529 sq in 8 NPS 5 - 6 NPS Design Series Certification Si 63 (Low Press.) 72177 Number: or catalog number Safety Relief Valve Type Classification: Sec. III NC at National Board T L (Worthington) on December 04, 2012 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .701 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Lift Outlet Size Code Section Inlet Size Set Pressure Range Media III NC 0.158 in 6 - 15 psi 0.75 NPS .75, 1.5 NPS 0.175 sq in 0.472 in III NC 6 - 15 psi 0.217 in 0.312 sq in 1, 1.25 NPS 0.63 in III NC 1 NPS 6 - 15 psi 1, 1.5, 2 NPS 0.312 sq in 0.63 in 0.217 in III NC 1.5, 2 NPS 0.487 sq in 0.787 in 0.276 in 6 - 15 psi III NC 6 - 15 psi 1.25, 2 NPS 0.487 sq in 0.787 in 1.25 - 1.5 NPS 0.276 in III NC 0.335 in 0.984 in 0.761 sq in 1.5, 2 NPS 6 - 15 psi III NC 1.247 sq in 1.26 in 0.434 in 6 - 15 psi 1.5 NPS 2.5, 3 NPS III NC 6 - 15 psi 0.434 in 1.26 in 1.247 sq in 2 NPS 2 NPS III NC 6 - 15 psi 2 - 2.5 NPS 1.575 in 0.552 in 3 NPS 1.948 sq in III NC 6 - 15 psi 0.67 in 1.969 in 3.043 sq in 4 NPS 2.5 - 3 NPS III NC 3 NPS 6 - 15 psi 5 NPS 2.48 in 4.832 sq in 0.847 in III NC 4.832 sq in 2.48 in 0.847 in 6 - 15 psi 4 NPS 6 NPS III NC 6 - 15 psi 1.044 in 3.031 in 7.218 sq in III NC 5 - 6 NPS 3.661 in 1.26 in 6 - 15 psi 10.529 sq in 8 NPS Page 172 of 812 Effective Date: 2019-05-31

174 Table of Contents Bopp & Reuther Valves GmbH (BOP) 72188 NB#: Carl Reuther Strasse 1, Mannheim D-68305 Germany location: Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Certification Design Series Si 25/ Si 63RL (Low Press., Restricted lift) 72188 Number: or catalog number Safety Relief Valve Type Classification: Sec. III NC at National Board T L (Worthington) on December 06, 2012 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .701 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Code Section Outlet Size Set Pressure Range Lift Inlet Size Media III NC 0.175 sq in 0.472 in 0.75 NPS .75, 1.5 NPS 6 - 15 psi 0.08 in III NC 1, 1.25 NPS 0.312 sq in 0.63 in 0.08 in 6 - 15 psi III NC 0.63 in 1 NPS 1, 1.5, 2 NPS 0.312 sq in 0.08 in 6 - 15 psi III NC 6 - 15 psi 0.787 in 0.083 in 0.487 sq in 1.5, 2 NPS III NC 6 - 15 psi 0.083 in 0.787 in 0.487 sq in 1.25, 2 NPS 1.25 - 1.5 NPS III NC 6 - 15 psi 1.5, 2 NPS 0.761 sq in 0.984 in 0.1 in III NC 2.5, 3 NPS 1.5 NPS 1.247 sq in 1.26 in 0.13 in 6 - 15 psi III NC 6 - 15 psi 2 NPS 1.26 in 0.13 in 2 NPS 1.247 sq in III NC 6 - 15 psi 0.165 in 1.575 in 1.948 sq in 3, 4 NPS 2 - 2.5 NPS III NC 0.201 in 65 - 15 psi 4 NPS 1.969 in 2.5 - 3 NPS 3.043 sq in III NC 6 - 15 psi 0.254 in 2.48 in 4.832 sq in 5 NPS 3 NPS III NC 2.48 in 0.254 in 6 - 15 psi 4 NPS 6 NPS 4.832 sq in III NC 7.218 sq in 6 - 15 psi 0.313 in 3.031 in III NC 0.378 in 6 - 15 psi 3.661 in 10.529 sq in 8 NPS 5 - 6 NPS Design Series Certification Si 25/ Si 63RL (High Press., Restricted lift) 72199 Number: or catalog number Safety Relief Valve Type Classification: Sec. III NC at National Board T L (Worthington) on December 06, 2012 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.819 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Lift Outlet Size Code Section Inlet Size Set Pressure Range Media III NC 0.08 in 15 - 4350 psi 0.75 NPS .75, 1.5 NPS 0.175 sq in 0.472 in III NC 15 - 4350 psi 0.08 in 0.312 sq in 1, 1.25 NPS 0.63 in III NC 1 NPS 15 - 4350 psi 1, 1.5, 2 NPS 0.312 sq in 0.63 in 0.08 in III NC 1.5, 2 NPS 0.487 sq in 0.787 in 0.083 in 15 - 3625 psi III NC 15 - 3625 psi 1.25, 2 NPS 0.487 sq in 0.787 in 1.25 - 1.5 NPS 0.083 in III NC 0.1 in 0.984 in 0.761 sq in 1.5, 2 NPS 15 - 3625 psi III NC 1.247 sq in 1.26 in 0.13 in 15 - 3190 psi 1.5 NPS 2.5, 3 NPS III NC 15 - 3190 psi 0.13 in 1.26 in 1.247 sq in 2 NPS 2 NPS III NC 15 - 2900 psi 2 - 2.5 NPS 1.575 in 0.165 in 3, 4 NPS 1.948 sq in III NC 15 - 2320 psi 0.201 in 1.969 in 3.043 sq in 4 NPS 2.5 - 3 NPS III NC 3 NPS 15 - 1740 psi 5 NPS 2.48 in 4.832 sq in 0.254 in III NC 4.832 sq in 2.48 in 0.254 in 15 - 1740 psi 4 NPS 6 NPS III NC 15 - 1305 psi 0.313 in 3.031 in 7.218 sq in III NC 5 - 6 NPS 3.661 in 0.378 in 15 - 870 psi 10.529 sq in 8 NPS Page 173 of 812 Effective Date: 2019-05-31

175 Table of Contents Bopp & Reuther Valves GmbH (BOP) 72201 NB#: Carl Reuther Strasse 1, Mannheim D-68305 Germany location: Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Certification Design Series Si 91 / 95, SiZ 2507 72201 Number: or catalog number Safety Valve Type Classification: Sec. III NC at National Board T L (Worthington) on January 27, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .843 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Set Pressure Range Media Inlet Size Code Section Lift III NC, ND 44 - 4785 psi 1.5 NPS 2.5, 3 NPS 0.486 sq in 0.787 in 0.236 in III NC, ND 0.295 in 44 - 4785 psi 0.76 sq in 0.984 in III NC, ND 1.26 in 1.247 sq in 0.378 in 44 - 4785 psi III NC, ND 0.425 in 2 NPS 1.417 in 44 - 4785 psi 3 NPS 1.577 sq in III NC, ND 44 - 4785 psi 0.472 in 1.575 in 1.948 sq in III NC, ND 0.531 in 2.5 - 3 NPS 4 NPS 2.466 sq in 1.772 in 44 - 4785 psi III NC, ND 3.291 sq in 2.047 in 0.614 in 44 - 4785 psi III NC, ND 4.094 sq in 0.685 in 44 - 3915 psi 3 NPS 6 NPS 2.283 in III NC, ND 44 - 3915 psi 0.744 in 4.831 sq in 2.48 in III NC, ND 2.677 in 6 NPS 5.628 sq in 44 - 3625 psi 4 NPS 0.803 in III NC, ND 44 - 3625 psi 0.862 in 2.874 in 6.487 sq in III NC, ND 3.11 in 0.933 in 44 - 3625 psi 7.596 sq in III NC, ND 3.386 in 6 NPS 8, 8 (Dual) NPS 9.005 sq in 1.016 in 44 - 2610 psi III NC, ND 1.122 in 10.986 sq in 44 - 2610 psi 3.74 in III NB, NC 13.422 sq in 4.134 in 1.24 in 44 - 2610 psi III NC, ND 44 - 2175 psi 1.323 in 4.409 in 15.268 sq in 10, 10 (Dual) NPS III NC, ND 4.724 in 17.527 sq in 1.417 in 44 - 2175 psi III NC, ND 44 - 1885 psi 1.559 in 5.197 in 21.213 sq in 10-14, 10-14 (Dual) NPS 8 NPS III NC, ND 44 - 1885 psi 5.276 in 21.862 sq in 12-14, 12-14 (Dual) NPS 1.583 in III NC, ND 44 - 1595 psi 12, 12 (Dual) NPS 1.665 in 5.551 in 24.201 sq in III NC, ND 24.271 sq in 5.559 in 44 - 1595 psi 1.669 in III NC, ND 44 - 1595 psi 10-14, 10-14 (Dual) NPS 25.598 sq in 5.709 in 1.713 in III NC, ND 6.22 in 30.386 sq in 1.866 in 44 - 1595 psi III NC, ND 44 - 1305 psi 6.693 in 2.008 in 35.183 sq in 16, 16 (Dual) NPS 10 NPS III NC, ND 44 - 1305 psi 2.161 in 7.205 in 40.772 sq in III NC, ND 44 - 870 psi 2.327 in 7.756 in 47.246 sq in III NC, ND 8.583 in 20, 20 (Dual) NPS 12 NPS 2.575 in 44 - 870 psi 57.859 sq in III NC, ND 9.252 in 67.23 sq in 44 - 870 psi 2.776 in Certification Design Series Si 91 / 95, SiZ 2507 (Restricted Lift) 72212 Number: or catalog number Safety Valve Type Classification: Sec. III NC at National Board T L (Worthington) on January 27, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .843 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Outlet Size Flow Area Lift Set Pressure Range Media Page 174 of 812 Effective Date: 2019-05-31

176 Table of Contents Bopp & Reuther Valves GmbH (BOP) 72223 NB#: Carl Reuther Strasse 1, Mannheim D-68305 Germany location: Acceptable Abbrev.: IMI B&R Valves, IMI B&R, IMI BuR, IMI Bopp & Reuther Certification Design Series SiZ 2507 72223 Number: or catalog number Safety Relief Valve Type Classification: Sec. III at National Board T L (Worthington) on November 28, 2018 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.831 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Code Section Outlet Size Inlet Size Set Pressure Range Media III & VIII Div.1 Steam 160 mm 57.6 mm 15 - 1450 psi 200 mm 250 mm 20106 sq mm III & VIII Div.1 Steam 350 mm 45239 sq mm 240 mm 86.4 mm 15 - 1450 psi 300 mm III & VIII Div.1 Steam 400 mm 500 mm 15 - 1450 psi 115.2 mm 320 mm 80425 sq mm III & VIII Div.1 Steam 400 mm 144 mm 15 - 1450 psi 500 mm 600 mm 125664 sq mm Page 175 of 812 Effective Date: 2019-05-31

177 Table of Contents Broady Flow Control Limited (BVL) 93002 NB#: English Street, Kingston-Upon-Hull, East Yorkshire HU3 2DU United Kingdom location: Acceptable Abbrev.: Broady - Valvitalia Broady Flow Control Limited (BVL) location: English Street, Kingston-Upon-Hull, East Yorkshire HU3 2DU United Kingdom Acceptable Abbrev.: Broady - Valvitalia Certification Design Series 3500 93002 Number: or catalog number Design Comments: 6R10 added 8/11/17 Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 01, 2001 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .861 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Set Pressure Range Inlet Size Outlet Size Flow Area Lift VIII Div. 1 Steam 1 - 1.5 NPS 15 - 2900 psi 0.121 sq in 2.5 mm [D] 10 mm 2, 3 NPS VIII Div. 1 Air 15 - 6400 psi VIII Div. 1 Steam 0.215 sq in [E] 13.3 mm 3.32 mm 15 - 2900 psi VIII Div. 1 Air 15 - 6200 psi VIII Div. 1 Steam 2, 3 NPS [F] 16.6 mm 4.15 mm 15 - 2900 psi 1.5 NPS 0.335 sq in VIII Div. 1 Air 15 - 5100 psi VIII Div. 1 Air 5.3 mm 1.5 - 2 NPS 3 NPS 0.547 sq in [G] 21.2 mm 15 - 2800 psi VIII Div. 1 Steam VIII Div. 1 Air 15 - 2800 psi 0.855 sq in 6.63 mm [H] 26.5 mm VIII Div. 1 Steam VIII Div. 1 Air [J] 34 mm 8.5 mm 15 - 2850 psi 2 - 3 NPS 3, 4 NPS 1.405 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 2160 psi 3 NPS 10.2 mm [K] 40.6 mm 2.003 sq in 4, 6 NPS VIII Div. 1 Steam VIII Div. 1 Air 3.115 sq in 4, 6 NPS 3 - 4 NPS [L] 50.6 mm 15 - 1560 psi 12.7 mm VIII Div. 1 VIII Div. 1 Air 15 - 1140 psi 14.2 mm [M] 56.8 in 3.927 sq in 6 NPS 4 NPS VIII Div. 1 Steam VIII Div. 1 Air 4.73 sq in [N] 62.4 mm 15.7 mm 15 - 1050 psi VIII Div. 1 Steam VIII Div. 1 Air 6.97 sq in 15 - 1020 psi 19 mm [P] 75.7 mm VIII Div. 1 Steam VIII Div. 1 Air [Q] 99.6 mm 25 mm 15 - 630 psi 6 NPS 8 NPS 12.06 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 630 psi 8, 10 NPS 17.42 sq in 30 mm [R] 119.8 mm VIII Div. 1 Steam VIII Div. 1 Air [T] 152.8 mm 38.5 mm 15 - 300 psi 8 NPS 10 NPS 28.4 sq in VIII Div. 1 Steam Page 176 of 812 Effective Date: 2019-05-31

178 Table of Contents Broady Flow Control Limited (BVL) 93013 NB#: English Street, Kingston-Upon-Hull, East Yorkshire HU3 2DU United Kingdom location: Acceptable Abbrev.: Broady - Valvitalia Certification Design Series 3500 (Liquid) 93013 Number: or catalog number Design Comments: 6R10 added 8/11/17 Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 11, 2011 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .635 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Flow Area Code Section Lift Set Pressure Range Outlet Size Media VIII Div. 1 Water 2,3 NPS 0.121 sq in [D] 10 mm 2.5 mm 1 - 1.5 NPS 15 - 6400 psi VIII Div. 1 Water 15 - 6200 psi 3.32 mm [E] 13.3 mm 0.215 sq in VIII Div. 1 Water 4.15 mm 15 - 5100 psi 1.5 NPS 2,3 NPS 0.335 sq in [F] 16.6 mm VIII Div. 1 Water 1.5 - 2 NPS 3 NPS 0.547 sq in [G] 21.2 mm 5.3 mm 15 - 2800 psi VIII Div. 1 Water 0.855 sq in 6.63 mm 15 - 2800 psi [H] 26.5 mm VIII Div. 1 Water 2 - 3 NPS 3,4 NPS 1.405 sq in [J] 34 mm 8.5 mm 15 - 2850 psi VIII Div. 1 Water 15 - 2160 psi 3 NPS 2.003 sq in 4,6 NPS [K] 40.6 mm 10.2 mm VIII Div. 1 Water 12.7 mm [L] 50.6 mm 3.115 sq in 4,6 NPS 3 - 4 NPS 15 - 1560 psi VIII Div. 1 Water [M] 56.8 mm 14.2 mm 15 - 1140 psi 4 NPS 6 NPS 3.927 sq in VIII Div. 1 Water 15 - 1050 psi 15.7 mm [N] 62.4 mm 4.73 sq in VIII Div. 1 Water [P] 75.7 mm 6.97 sq in 19 mm 15 - 1020 psi VIII Div. 1 Water 15 - 630 psi 6 NPS 8 NPS 12.06 sq in [Q] 99.6 in 25 mm VIII Div. 1 Water 15 - 630 psi 17.42 sq in 8, 10 NPS [R] 119.8 mm 30 mm VIII Div. 1 Water 38.5 mm 15 - 300 psi 8 NPS 10 NPS 28.4 sq in [T] 152.8 mm Design Series Certification 3600 93024 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 01, 2010 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.97 SCFM/PSIA Certified Value: 5.54 PPH/PSIA Certified Value (alternate medium): Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Inlet Size Outlet Size Lift Set Pressure Range Media Flow Area VIII Div. 1 Steam 10.4 mm 2.5 mm 15 - 2900 psi 0.5 - 1 NPS 1 NPS 84.9 sq mm VIII Div. 1 Air 15 - 3625 psi Page 177 of 812 Effective Date: 2019-05-31

179 Table of Contents Broady Flow Control Limited (BVL) 93035 NB#: English Street, Kingston-Upon-Hull, East Yorkshire HU3 2DU United Kingdom location: Acceptable Abbrev.: Broady - Valvitalia Certification Design Series 3600 (Liquid) 93035 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 25, 2011 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 2.69 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Water 2.4 mm 1 - 250 bar 0.5 - 1 NPS 1 NPS 70.9 sq mm 9.5 mm Design Series Certification 4000 (Full Bore, Modulating & Snap Acting Pilot, Air/gas)) 93046 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on April 15, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.729 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air [G1] 25.45 mm 508.7 sq mm 50 DN 25 DN 10 mm 29 - 6400 psi VIII Div. 1 Air 29 - 6170 psi 1256.6 sq mm 40 DN [J1] 40 mm 15 mm 80 DN VIII Div. 1 Air 29 - 6170 psi 19 mm [L1] 50.85 mm 2030.8 sq mm 80 DN 50 DN VIII Div. 1 Air 29 - 3705 psi 100 DN 80 DN [P1] 80.05 mm 29 mm 5032.8 sq mm VIII Div. 1 Air [Q1] 101.7 mm 37 mm 29 - 3705 psi 100 DN 150 DN 8123.3 sq mm VIII Div. 1 Air 29 - 1480 psi 53 mm [R1] 150.1 mm 17695 sq mm 200 DN 150 DN VIII Div. 1 Air 32445.24 sq mm 71 mm 29 - 985 psi 250 DN [T1] 203.25 mm 200 DN Page 178 of 812 Effective Date: 2019-05-31

180 Table of Contents Broady Flow Control Limited (BVL) 93068 NB#: English Street, Kingston-Upon-Hull, East Yorkshire HU3 2DU United Kingdom location: Acceptable Abbrev.: Broady - Valvitalia Certification Design Series 4000 (API Nozzle -Modulating & Snap Acting Pilot, Air/gas) 93068 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on April 15, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.821 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Media Set Pressure Range Code Section Lift Inlet Size Outlet Size VIII Div. 1 Air 29 - 6400 psi 10 mm 78.54 sq mm 50 DN 25 - 40 DN [D] 10 mm VIII Div. 1 Air 136.85 sq mm [E] 13.25 mm 10 mm 29 - 6400 psi VIII Div. 1 Air 216.42 sq mm [F] 16.6 mm 29 - 6170 psi 10 mm VIII Div. 1 Air [G] 21.25 mm 15 mm 50, 80 DN 40 - 50 DN 354.66 sq mm 29 - 6170 psi VIII Div. 1 Air 551.55 sq mm 15 mm [H] 26.5 mm 29 - 6170 psi 80 DN VIII Div. 1 Air 19 mm 29 - 4620 psi 50 - 80 DN 80, 100 DN 913.27 sq mm [J] 34.1 mm VIII Div. 1 Air 80 DN 100 DN 1294.62 sq mm [K] 40.6 mm 29 mm 29 - 3705 psi VIII Div. 1 Air 29 - 3705 psi 80 - 100 DN 2010.9 sq mm [L] 50.6 mm 29 mm 100, 150 DN VIII Div. 1 Air 29 - 3705 psi 37 mm [M] 56.7 mm 2524.97 sq mm 150 DN 100 DN VIII Div. 1 Air 29 - 3705 psi 37 mm 3058.15 sq mm [N] 62.4 mm VIII Div. 1 Air 29 - 3705 psi 37 mm [P] 75 mm 4417.86 sq mm VIII Div. 1 Air 53 mm 29 - 1480 psi 150 DN 200 DN 7791.28 sq mm [Q] 99.6 mm VIII Div. 1 Air [R] 119 mm 29 - 1020 psi 53 mm 11122.02 sq mm VIII Div. 1 Air 29 - 985 psi 18337.35 sq mm 71 mm 250 DN [T] 152.8 mm 200 DN Design Series Certification 4000 (API Nozzle -Modulating & Snap Acting Pilot, Liquid) 93079 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on October 13, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.724 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Outlet Size Inlet Size Media Set Pressure Range Flow Area VIII Div. 1 Water 50 DN 78.54 sq mm [D] 10 mm 10 mm 25 - 40 DN 29 - 6400 psi VIII Div. 1 Water [E] 13.25 mm 135.85 sq mm 10 mm 29 - 6400 psi VIII Div. 1 Water 216.42 sq mm [F] 16.6 mm 10 mm 29 - 6170 psi VIII Div. 1 Water 29 - 6170 psi 15 mm [G] 21.25 mm 354.66 sq mm 50, 80 DN 40 - 50 DN VIII Div. 1 Water 15 mm 551.55 sq mm 29 - 6170 psi 80 DN [H] 26.5 mm VIII Div. 1 Water 29 - 4620 psi 19 mm [J] 34.1 mm 913.27 sq mm 80, 100 DN 50 - 80 DN VIII Div. 1 Water 80 DN [K] 40.6 mm 29 mm 29 - 3705 psi 100 DN 1294.62 sq mm VIII Div. 1 Water 100, 150 DN 29 mm 80 - 100 DN 29 - 3705 psi 2010.9 sq mm [L] 50.6 mm VIII Div. 1 Water 100 DN [M] 56.7 mm 150 DN 37 mm 29 - 3705 psi 2524.97 sq mm VIII Div. 1 Water 29 - 3705 psi 37 mm [N] 62.4 mm 3058.15 sq mm VIII Div. 1 Water [P] 75 mm 37 mm 29 - 3705 psi 4417.86 sq mm VIII Div. 1 Water 200 DN 7791.28 sq mm [Q] 99.6 mm 53 mm 29 - 1480 psi 150 DN VIII Div. 1 Water [R] 119 mm 11122.02 sq mm 29 - 1020 psi 53 mm VIII Div. 1 Water [T] 152.8 mm 71 mm 29 - 985 psi 200 DN 250 DN 18337.35 sq mm Page 179 of 812 Effective Date: 2019-05-31

181 Table of Contents BS & B Premco Latinoamerica S.A. De C.V. (PLS) 13004 NB#: Av. San Sebastian No. 392, Colonia La Comedia, Guadalupe, Nuevo Leon 67180 Mexico location: BS & B Premco Latinoamerica S.A. De C.V. (PLS) Av. San Sebastian No. 392, Colonia La Comedia, Guadalupe, Nuevo Leon 67180 Mexico location: Certification Design Series REL 13004 or catalog number Number: REL-7R, REL-7F Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on August 28, 2001 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: .16 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Media Inlet Size Outlet Size VIII Div. 1 1 NPS 0.864 sq in 10 - 435 psi VIII Div. 1 1.5 NPS 2.036 sq in 7 - 290 psi VIII Div. 1 3 - 217 psi 3.36 sq in 2 NPS VIII Div. 1 3 - 174 psi 4.78 sq in 2.5 NPS VIII Div. 1 7.39 sq in 2.2 - 145 psi 3 NPS VIII Div. 1 2.2 - 116 psi 12.73 sq in 4 NPS VIII Div. 1 1.5 - 87 psi 5 NPS 20.01 sq in VIII Div. 1 28.89 sq in 1 - 72 psi 6 NPS VIII Div. 1 1 - 58 psi 8 NPS 50.03 sq in VIII Div. 1 78.85 sq in 10 NPS 1 - 43 psi VIII Div. 1 1 - 36 psi 12 NPS 113.1 sq in VIII Div. 1 1 - 29 psi 14 NPS 137.9 sq in VIII Div. 1 182.7 sq in 1 - 21 psi 16 NPS VIII Div. 1 18 NPS 233.7 sq in 1 - 21 psi VIII Div. 1 20 NPS 291.4 sq in 1 - 17 psi VIII Div. 1 1 - 17 psi 424.6 sq in 24 NPS Page 180 of 812 Effective Date: 2019-05-31

182 Table of Contents BS & B Premco Latinoamerica S.A. De C.V. (PLS) 13015 NB#: Av. San Sebastian No. 392, Colonia La Comedia, Guadalupe, Nuevo Leon 67180 Mexico location: Certification Design Series REV 13015 Number: or catalog number REV-7R Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on August 21, 2001 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 3.15 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Inlet Size Lift Media Code Section Flow Area Outlet Size VIII Div. 1 10 - 435 psi 0.691 sq in 1 NPS VIII Div. 1 1.5 NPS 1.767 sq in 7 - 290 psi VIII Div. 1 2 NPS 3.092 sq in 3 - 217 psi VIII Div. 1 3 - 174 psi 4.79 sq in 2.5 NPS VIII Div. 1 2.2 - 145 psi 6.29 sq in 3 NPS VIII Div. 1 2.2 - 116 psi 4 NPS 10.27 sq in VIII Div. 1 5 NPS 14.71 sq in 1.5 - 87 psi VIII Div. 1 1 - 72 psi 20.95 sq in 6 NPS VIII Div. 1 8 NPS 1 - 58 psi 37.12 sq in VIII Div. 1 56.54 sq in 1 - 43 psi 10 NPS VIII Div. 1 1 - 36 psi 77.6 sq in 12 NPS VIII Div. 1 99.2 sq in 14 NPS 1 - 29 psi VIII Div. 1 16 NPS 125.3 sq in 1 - 21 psi VIII Div. 1 158.7 sq in 1 - 21 psi 18 NPS VIII Div. 1 20 NPS 1 - 17 psi 190 sq in VIII Div. 1 1 - 17 psi 269.4 sq in 24 NPS Certification Design Series RE 13026 Number: or catalog number RETR, RETF Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on August 23, 2001 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: .15 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Flow Area Set Pressure Range Inlet Size Lift Outlet Size VIII Div. 1 0.864 sq in 1 NPS 10 - 435 psi VIII Div. 1 1.5 NPS 2.036 sq in 7 - 290 psi VIII Div. 1 2 NPS 3.36 sq in 3 - 217 psi VIII Div. 1 3 - 174 psi 2.5 NPS 4.79 sq in VIII Div. 1 2.2 - 145 psi 7.39 sq in 3 NPS VIII Div. 1 12.73 sq in 4 NPS 2.2 - 116 psi VIII Div. 1 20.01 sq in 1.5 - 87 psi 5 NPS VIII Div. 1 1 - 72 psi 28.89 sq in 6 NPS VIII Div. 1 1 - 58 psi 8 NPS 50.03 sq in VIII Div. 1 78.85 sq in 1 - 43 psi 10 NPS VIII Div. 1 12 NPS 113.1 sq in 1 - 36 psi VIII Div. 1 14 NPS 1 - 29 psi 137.9 sq in VIII Div. 1 1 - 21 psi 182.6 sq in 16 NPS VIII Div. 1 233.7 sq in 1 - 21 psi 18 NPS VIII Div. 1 1 - 17 psi 291 sq in 20 NPS VIII Div. 1 1 - 17 psi 424.6 sq in 24 NPS Page 181 of 812 Effective Date: 2019-05-31

183 Table of Contents BS & B Premco Latinoamerica S.A. De C.V. (PLS) 13037 NB#: Av. San Sebastian No. 392, Colonia La Comedia, Guadalupe, Nuevo Leon 67180 Mexico location: Certification Design Series AMBV & MBV W/Bar Type Vacuum Support 13037 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on August 10, 2001 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.9 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Inlet Size Lift Set Pressure Range Media Code Section Flow Area VIII Div. 1 0.63 sq in 10 - 150 psi 1 NPS VIII Div. 1 1.5 NPS 1.66 sq in 10 - 150 psi VIII Div. 1 2 NPS 2.693 sq in 10 - 150 psi VIII Div. 1 10 - 150 psi 2.5 NPS 4.33 sq in VIII Div. 1 5.923 sq in 10 - 150 psi 3 NPS VIII Div. 1 10 - 150 psi 4 NPS 10.41 sq in VIII Div. 1 16.15 sq in 5 NPS 10 - 150 psi I, IV & VIII (limited per NB-514, 4.0) 10 - 150 psi 23.15 sq in 6 NPS VIII Div. 1 8 NPS 10 - 150 psi 40.92 sq in VIII Div. 1 63.73 sq in 10 - 125 psi 10 NPS VIII Div. 1 10 - 125 psi 91.55 sq in 12 NPS VIII Div. 1 110.3 sq in 14 NPS 10 - 100 psi VIII Div. 1 16 NPS 146.1 sq in 10 - 100 psi VIII Div. 1 187 sq in 10 - 100 psi 18 NPS VIII Div. 1 20 NPS 10 - 50 psi 232.9 sq in VIII Div. 1 10 - 50 psi 339.7 sq in 24 NPS Certification Design Series IMB, AIMB, IMBL, AIMBL, FSM, AFSM 13048 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on August 10, 2001 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: .31 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Inlet Size Lift Media Flow Area Code Section Outlet Size VIII Div. 1 10 - 1000 psi 0.864 sq in 1 NPS VIII Div. 1 7 - 1000 psi 1.5 NPS 2.036 sq in VIII Div. 1 2 NPS 3.36 sq in 3 - 500 psi VIII Div. 1 4.79 sq in 2 - 500 psi 2.5 NPS VIII Div. 1 7.39 sq in 3 NPS 2 - 500 psi VIII Div. 1 12.73 sq in 1.5 - 500 psi 4 NPS VIII Div. 1 20.01 sq in 1 - 450 psi 5 NPS VIII Div. 1 1 - 450 psi 28.89 sq in 6 NPS VIII Div. 1 .5 - 450 psi 8 NPS 50.03 sq in VIII Div. 1 78.85 sq in .25 - 150 psi 10 NPS VIII Div. 1 12 NPS 113.1 sq in .25 - 150 psi VIII Div. 1 14 NPS .25 - 150 psi 137.9 sq in VIII Div. 1 .25 - 150 psi 182.7 sq in 16 NPS VIII Div. 1 233.7 sq in .25 - 150 psi 18 NPS VIII Div. 1 .25 - 150 psi 291 sq in 20 NPS VIII Div. 1 .25 - 150 psi 424.6 sq in 24 NPS Page 182 of 812 Effective Date: 2019-05-31

184 Table of Contents BS & B Premco Latinoamerica S.A. De C.V. (PLS) 13059 NB#: Av. San Sebastian No. 392, Colonia La Comedia, Guadalupe, Nuevo Leon 67180 Mexico location: Certification Design Series MB & AMB 13059 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on August 10, 2001 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: .193 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Set Pressure Range Media Lift Inlet Size Outlet Size Code Section VIII Div. 1 0.864 sq in 1 NPS 10 - 150 psi VIII Div. 1 1.5 NPS 2.035 sq in 7 - 150 psi VIII Div. 1 3.36 sq in 2 NPS 2 - 150 psi VIII Div. 1 2 - 150 psi 4.79 sq in 2.5 NPS VIII Div. 1 7.39 sq in 1 - 150 psi 3 NPS VIII Div. 1 4 NPS 12.73 sq in 1 - 150 psi VIII Div. 1 5 NPS 20 sq in 1 - 150 psi VIII Div. 1 1 - 150 psi 6 NPS 28.89 sq in VIII Div. 1 8 NPS .5 - 150 psi 50.03 sq in VIII Div. 1 78.85 sq in 10 NPS .25 - 125 psi VIII Div. 1 12 NPS .25 - 125 psi 113.1 sq in VIII Div. 1 .25 - 100 psi 14 NPS 137.9 sq in VIII Div. 1 16 NPS 182.7 sq in .25 - 100 psi VIII Div. 1 18 NPS 233.7 sq in .25 - 100 psi VIII Div. 1 20 NPS 291 sq in .25 - 50 psi VIII Div. 1 .25 - 50 psi 424.6 sq in 24 NPS Certification Design Series MBV, AMBV w. Dial Vac. Support 13060 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 21, 2001 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 5.4 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Flow Area Inlet Size Lift Set Pressure Range VIII Div. 1 7 - 150 psi 1.5 NPS 1.02 sq in VIII Div. 1 2 NPS 1.75 sq in 2 - 150 psi VIII Div. 1 2 - 150 psi 2.5 NPS 3.05 sq in VIII Div. 1 1 - 150 psi 3 NPS 4.2 sq in VIII Div. 1 1 - 150 psi 7.61 sq in 4 NPS VIII Div. 1 11.61 sq in 5 NPS 1 - 150 psi VIII Div. 1 15.82 sq in 1 - 150 psi 6 NPS VIII Div. 1 .5 - 150 psi 25.87 sq in 8 NPS VIII Div. 1 .25 - 125 psi 10 NPS 41.1 sq in VIII Div. 1 12 NPS 59.1 sq in .25 - 125 psi VIII Div. 1 .25 - 100 psi 88.4 sq in 14 NPS VIII Div. 1 16 NPS .25 - 100 psi 95.7 sq in VIII Div. 1 18 NPS 124.3 sq in .25 - 100 psi VIII Div. 1 153.9 sq in .25 - 50 psi 20 NPS VIII Div. 1 24 NPS .25 - 50 psi 226.1 sq in Page 183 of 812 Effective Date: 2019-05-31

185 Table of Contents BS & B Premco LLC (PRL) 77813 NB#: 7422 - B E 46th Place, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB BS & B Premco LLC (PRL) location: 7422 - B E 46th Place, Tulsa, OK 74145 United States Acceptable Abbrev.: BSB Certification Design Series BPRV, BPIV 77813 Number: or catalog number Buckling Pin Non-reclosing Device Type Classification: Sec. VIII Div. 1 at BS & B on April 12, 2004 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.22 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Buckling Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Outlet Size Inlet Size Lift Set Pressure Range Media Code Section VIII Div. 1 2 NPS 2.75 sq in 15 - 3700 psi VIII Div. 1 3 NPS 6 sq in 15 - 3700 psi VIII Div. 1 4 NPS 15 - 2250 psi 10 sq in VIII Div. 1 1 - 2250 psi 23.5 sq in 6 NPS VIII Div. 1 1 - 2250 psi 39.65 sq in 8 NPS VIII Div. 1 10 NPS 62.48 sq in 1 - 2250 psi VIII Div. 1 12 NPS 90.5 sq in 1 - 2250 psi VIII Div. 1 14 NPS 109 sq in 1 - 1440 psi VIII Div. 1 16 NPS 1 - 1440 psi 149 sq in VIII Div. 1 1 - 1440 psi 18 NPS 196.2 sq in VIII Div. 1 1 - 720 psi 239.1 sq in 20 NPS VIII Div. 1 24 NPS 1 - 720 psi 367.6 sq in VIII Div. 1 1 - 720 psi 400.6 sq in 26 NPS VIII Div. 1 28 NPS 466.8 sq in 1 - 720 psi VIII Div. 1 601 sq in 30 NPS 1 - 720 psi VIII Div. 1 1 - 720 psi 614 sq in 32 NPS VIII Div. 1 1 - 720 psi 34 NPS 695 sq in VIII Div. 1 1 - 720 psi 781 sq in 36 NPS VIII Div. 1 872 sq in 38 NPS 1 - 720 psi VIII Div. 1 40 NPS 1 - 720 psi 968 sq in VIII Div. 1 1 - 720 psi 1069 sq in 42 NPS VIII Div. 1 1175 sq in 44 NPS 1 - 720 psi VIII Div. 1 46 NPS 1 - 160 psi 1286 sq in VIII Div. 1 1403 sq in 1 - 160 psi 48 NPS VIII Div. 1 50 NPS 1 - 160 psi 1524 sq in VIII Div. 1 52 NPS 1650 sq in 1 - 160 psi VIII Div. 1 1 - 160 psi 54 NPS 1784 sq in VIII Div. 1 1918 sq in 1 - 160 psi 56 NPS VIII Div. 1 58 NPS 1 - 160 psi 2059.4 sq in VIII Div. 1 1 - 160 psi 60 NPS 2206 sq in VIII Div. 1 1 - 160 psi 62 NPS 2357 sq in VIII Div. 1 1 - 160 psi 2514 sq in 64 NPS VIII Div. 1 2675 sq in 1 - 160 psi 66 NPS VIII Div. 1 68 NPS 2842 sq in 1 - 160 psi VIII Div. 1 70 NPS 3013 sq in 1 - 160 psi VIII Div. 1 1 - 160 psi 72 NPS 3190 sq in VIII Div. 1 1 - 160 psi 3371 sq in 74 NPS VIII Div. 1 1 - 160 psi 76 NPS 3558 sq in VIII Div. 1 1 - 160 psi 3750 sq in 78 NPS Page 184 of 812 Effective Date: 2019-05-31

186 Table of Contents BS & B Premco LLC (PRL) 77970 NB#: 7422 - B E 46th Place, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series BPAV (Liquid) 77970 Number: or catalog number Buckling Pin Non-reclosing Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 03, 2012 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.686 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: Buckling Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Media Inlet Size Code Section Lift Set Pressure Range VIII Div. 1 Water 1.5 NPS 1 NPS 0.72 sq in 0.957 in 2100 - 3500 psi VIII Div. 1 Water 1.046 in 50 - 2100 psi 0.86 sq in VIII Div. 1 Water 1.5 NPS 2 NPS 2.04 sq in 1.612 in 15 - 1440 psi VIII Div. 1 Water 3 NPS 2 NPS 3.36 sq in 2.067 in 15 - 720 psi VIII Div. 1 Water 15 - 720 psi 4 NPS 3.067 in 3 NPS 7.39 sq in VIII Div. 1 Water 4 NPS 6 NPS 12.73 sq in 4.026 in 15 - 720 psi VIII Div. 1 Water 8 NPS 28.89 sq in 15 - 275 psi 6.065 in 6 NPS VIII Div. 1 Water 7.981 in 50.03 sq in 10 NPS 8 NPS 15 - 275 psi Design Series Certification BPAV (air/gas) 77981 Number: or catalog number Buckling Pin Non-reclosing Device Type Classification: Sec. VIII Div. 1 at BS & B on October 27, 2011 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .80 Unitless Certified Value: Air Test Medium: Air/Gas Certified Medium: None Special Service: Buckling Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Lift Media Set Pressure Range Code Section Flow Area Inlet Size VIII Div. 1 Air 1 NPS 1.5 NPS 0.72 sq in 0.957 in 2100 - 3500 psi VIII Div. 1 Air 0.86 sq in 1.046 in 15 - 2100 psi VIII Div. 1 Air 15 - 1440 psi 1.5 NPS 1.612 in 2.04 sq in 2 NPS VIII Div. 1 Air 15 - 720 psi 2 NPS 3 NPS 3.36 sq in 2.067 in VIII Div. 1 Air 3 NPS 4 NPS 7.39 sq in 3.067 in 15 - 720 psi VIII Div. 1 Air 15 - 720 psi 4 NPS 12.73 sq in 4.026 in 6 NPS VIII Div. 1 Air 15 - 275 psi 6.065 in 28.89 sq in 8 NPS 6 NPS VIII Div. 1 Air 15 - 275 psi 8 NPS 10 NPS 50.03 sq in 7.981 in Page 185 of 812 Effective Date: 2019-05-31

187 Table of Contents BS & B Premco LLC (PRL) 77992 NB#: 7422 - B E 46th Place, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Design Series Certification BPPV 77992 Number: or catalog number Buckling Pin Non-reclosing Device Type Classification: Sec. VIII Div. 1 at BS & B on December 20, 2011 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 2.2 Unitless Certified Value: per CC 2397 Certification Provisions: Air or gases (Krg) Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Buckling Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Outlet Size Flow Area Code Section Inlet Size Media Set Pressure Range VIII Div. 1 Air 15 - 275 psi 3 in 28.27 sq in 6 NPS 6 NPS 6 in VIII Div. 1 Air 8 NPS 8 NPS 49.02 sq in 7.9 in 3.95 in 15 - 275 psi VIII Div. 1 Air 10 NPS 10 NPS 15 - 275 psi 4.96 in 9.92 in 77.91 sq in VIII Div. 1 Air 15 - 275 psi 12 NPS 5.94 in 12 NPS 110.85 sq in 11.88 in VIII Div. 1 Air 14 NPS 14 NPS 135.2 sq in 13.12 in 6.56 in 15 - 275 psi VIII Div. 1 Air 15 - 275 psi 7.55 in 15.1 in 179.08 sq in 16 NPS 16 NPS VIII Div. 1 Air 18 NPS 15 - 275 psi 229.12 sq in 18 NPS 8.54 in 17.08 in VIII Div. 1 Air 15 - 275 psi 9.53 in 19.06 in 285.32 sq in 20 NPS 20 NPS VIII Div. 1 Air 416.2 sq in 15 - 275 psi 11.51 in 23.02 in 24 NPS 24 NPS VIII Div. 1 Air 30 NPS 30 NPS 658.7 sq in 28.96 in 14.48 in 15 - 275 psi Certification Design Series EORV 78218 or catalog number Number: Buckling Pin Non-reclosing Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 04, 2018 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 1.164 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: Buckling Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Inlet Size Outlet Size Set Pressure Range Media Flow Area VIII Div. 1 Water 0.25 in 0.9 in 5000 - 20000 psi 0.8125 in .8125 in 0.049 sq in Page 186 of 812 Effective Date: 2019-05-31

188 Table of Contents BS & B Premco LLC (PRL) 78386 NB#: 7422 - B E 46th Place, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series BPCV (Air/Gas) 78386 or catalog number Number: Buckling Pin Non-reclosing Device Type Classification: Sec. VIII Div. 1 at BS & B on October 12, 2017 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.706 Unitless Certified Value: Air Test Medium: Air/Gas Certified Medium: Buckling Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Inlet Size Outlet Size Flow Area VIII Div. 1 Air 0.371 in 1 NPS 2101 - 3500 psi 0.72 sq in 0.957 in 1 NPS VIII Div. 1 Air 15 - 2100 psi 0.86 sq in 1.05 in 0.371 in VIII Div. 1 Air 1.5 NPS 2.04 sq in 1.61 in 0.547 in 15 - 1440 psi 1.5 NPS VIII Div. 1 Air 3.36 sq in 2 NPS 15 - 720 psi 0.703 in 2.07 in 2 NPS VIII Div. 1 Air 7.39 sq in 3 NPS 3 NPS 3.07 in 1.016 in 15 - 720 psi VIII Div. 1 Air 4 NPS 4.03 in 1.328 in 15 - 720 psi 4 NPS 12.73 sq in VIII Div. 1 Air 15 - 275 psi 6 NPS 6 NPS 28.89 sq in 6.07 in 1.953 in VIII Div. 1 Air 8 NPS 7.981 in 2.656 in 15 - 275 psi 8 NPS 50.03 sq in VIII Div. 1 Air 3.281 in 15 - 275 psi 10 NPS 10 NPS 78.81 sq in 10.02 in VIII Div. 1 Air 12 NPS 12 NPS 113.04 sq in 12 in 15 - 275 psi 3.906 in VIII Div. 1 Air 14 NPS 15 - 275 psi 4.297 in 13.25 in 137.81 sq in 14 NPS Design Series Certification BPCV (Liquid) 78397 Number: or catalog number Buckling Pin Non-reclosing Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 04, 2018 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.617 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: Buckling Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Inlet Size Flow Area Set Pressure Range Outlet Size Code Section Lift VIII Div. 1 Water 2101 - 3500 psi 0.371 in 0.72 sq in 1 NPS 1 NPS 0.957 in VIII Div. 1 Water 1.05 in 0.86 sq in 0.371 in 15 - 2100 psi VIII Div. 1 Water 1.61 in 15 - 1440 psi 1.5 NPS 0.547 in 1.5 NPS 2.04 sq in VIII Div. 1 Water 0.703 in 2.07 in 3.36 sq in 2 NPS 2 NPS 15 - 720 psi VIII Div. 1 Water 15 - 720 psi 1.016 in 3.07 in 7.39 sq in 3 NPS 3 NPS VIII Div. 1 Water 4 NPS 4.03 in 1.328 in 15 - 720 psi 4 NPS 12.73 sq in VIII Div. 1 Water 6 NPS 6 NPS 28.89 sq in 6.07 in 15 - 275 psi 1.953 in VIII Div. 1 Water 8 NPS 8 NPS 50.03 sq in 7.981 in 2.656 in 15 - 275 psi VIII Div. 1 Water 10.02 in 3.281 in 15 - 275 psi 10 NPS 10 NPS 78.81 sq in VIII Div. 1 Water 15 - 275 psi 3.906 in 12 in 113.04 sq in 12 NPS 12 NPS VIII Div. 1 Water 137.81 sq in 4.297 in 15 - 275 psi 14 NPS 13.25 in 14 NPS Page 187 of 812 Effective Date: 2019-05-31

189 Table of Contents BS & B Premco LLC (PRL) 78409 NB#: 7422 - B E 46th Place, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series IDV 78409 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at BS & B on August 31, 2017 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.700 Unitless Certified Value: Air Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Air 1 NPS 1 NPS 0.66 sq in 15 - 500 psi VIII Div. 1 Air 1.5 NPS 1.5 NPS 1.59 sq in 15 - 500 psi VIII Div. 1 Air 2 NPS 2 NPS 2.69 sq in 15 - 500 psi VIII Div. 1 Air 3 NPS 3 NPS 15 - 500 psi 5.95 sq in VIII Div. 1 Air 15 - 500 psi 10.4 sq in 4 NPS 4 NPS VIII Div. 1 Air 6 NPS 23.52 sq in 15 - 500 psi 6 NPS VIII Div. 1 Air 15 - 500 psi 41.27 sq in 8 NPS 8 NPS VIII Div. 1 Air 10 NPS 64.78 sq in 10 NPS 15 - 500 psi Design Series Certification RDV-HP 79017 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 20, 2014 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 3261 SCFM Certified Value: Air Test Medium: Air Certified Medium: Bubble Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Inlet Size Code Section Media Set Pressure Range Lift Outlet Size VIII Div. 1 50 - 50 psi 0.384 in 2.352 in 4.345 sq in 3 NPS 3 NPS Page 188 of 812 Effective Date: 2019-05-31

190 Table of Contents BS & B Safety Systems, LLC (BSB) 77004 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB BS & B Safety Systems, LLC (BSB) location: 7455 East 46th Street, Tulsa, OK 74145 United States Acceptable Abbrev.: BSB Certification Design Series CSR 77004 Number: or catalog number CSR-7RS, CSR-7FS, CSI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 13, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.00 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Outlet Size Flow Area Code Section Inlet Size Media Set Pressure Range N/A 120 - 800 psi 1 NPS 0.86 sq in VIII Div. 1 50 - 800 psi 1.5 NPS 2.03 sq in VIII Div. 1 50 - 800 psi 2 NPS 3.35 sq in VIII Div. 1 3 NPS 7.39 sq in 50 - 800 psi VIII Div. 1 12.73 sq in 4 NPS 50 - 800 psi VIII Div. 1 6 NPS 28.89 sq in 30 - 800 psi VIII Div. 1 8 NPS 50 - 800 psi 50.03 sq in Design Series Certification JRS 77015 Number: or catalog number SRB-7RS, SRB-7RS-TR, SRB-7FS, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 10, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .31 Unitless Certified Value: Air or gases (Krg) Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 22 - 180 psi 0.86 sq in 1 NPS VIII Div. 1 1.89 sq in 1.5 NPS 20 - 150 psi VIII Div. 1 2 NPS 18 - 120 psi 3.35 sq in VIII Div. 1 16 - 80 psi 6.53 sq in 3 NPS VIII Div. 1 11.86 sq in 14 - 70 psi 4 NPS VIII Div. 1 12 - 50 psi 25.08 sq in 6 NPS VIII Div. 1 12 - 42 psi 42.07 sq in 8 NPS VIII Div. 1 10 NPS 68.65 sq in 12 - 36 psi VIII Div. 1 12 - 33 psi 12 NPS 102.28 sq in VIII Div. 1 9 - 30 psi 14 NPS 121.86 sq in VIII Div. 1 156 sq in 7 - 28 psi 16 NPS VIII Div. 1 6 - 26 psi 18 NPS 198 sq in VIII Div. 1 20 NPS 246 sq in 5 - 24 psi VIII Div. 1 5 - 22 psi 24 NPS 357 sq in VIII Div. 1 30 NPS 592 sq in 5 - 14 psi VIII Div. 1 5 - 14 psi 32 NPS 706.9 sq in VIII Div. 1 36 NPS 868 sq in 5 - 14 psi VIII Div. 1 5 - 14 psi 42 NPS 1111 sq in Page 189 of 812 Effective Date: 2019-05-31

191 Table of Contents BS & B Safety Systems, LLC (BSB) 77026 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series BV, BRV, BSV, BRSV 77026 Number: or catalog number FA-7R, FA-7,FA-1,2,3,4,5,6,7,8,9,UA-2,3,5,6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 13, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .80 Unitless Certified Value: Air or gases (Krg) Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Air 0.57 sq in 145 - 12000 psi 1 NPS VIII Div. 1 Air 1.44 sq in 1.5 NPS 95 - 6000 psi VIII Div. 1 Air 2.24 sq in 55 - 6000 psi 2 NPS VIII Div. 1 3 NPS 5.41 sq in 41 - 6000 psi VIII Div. 1 31 - 6000 psi 4 NPS 9.62 sq in VIII Div. 1 6 NPS 23.76 sq in 23 - 3600 psi VIII Div. 1 18 - 3600 psi 8 NPS 44.18 sq in VIII Div. 1 14 - 1400 psi 70.88 sq in 10 NPS VIII Div. 1 101.5 sq in 12 NPS 12 - 1000 psi VIII Div. 1 14 NPS 130.3 sq in 11 - 750 psi VIII Div. 1 9 - 500 psi 176.7 sq in 16 NPS VIII Div. 1 202.4 sq in 18 NPS 8 - 475 psi VIII Div. 1 8 - 450 psi 280 sq in 20 NPS VIII Div. 1 24 NPS 380.1 sq in 37 - 230 psi VIII Div. 1 20 - 184 psi 615.7 sq in 30 NPS VIII Div. 1 31 - 181 psi 32 NPS 728 sq in VIII Div. 1 36 NPS 927 sq in 28 - 160 psi VIII Div. 1 25 - 145 psi 40 NPS 1149 sq in VIII Div. 1 42 NPS 24 - 138 psi 1269 sq in VIII Div. 1 23 - 132 psi 1395 sq in 44 NPS Page 190 of 812 Effective Date: 2019-05-31

192 Table of Contents BS & B Safety Systems, LLC (BSB) 77037 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series B, BR, BRR 77037 or catalog number Number: FA-7R, FA1,2,3,4,5,6,7,8,9,UA-2,3,5,6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 15, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .71 Unitless Certified Value: Air or gases (Krg) Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 0.5 NPS 0.189 sq in 80 - 30000 psi VIII Div. 1 1 NPS 0.801 sq in 40 - 12000 psi VIII Div. 1 Air 1.76 sq in 1.5 NPS 26 - 6000 psi VIII Div. 1 2 NPS 3.33 sq in 16 - 6000 psi VIII Div. 1 12 - 6000 psi 3 NPS 6.514 sq in VIII Div. 1 4 NPS 11.82 sq in 9 - 6000 psi VIII Div. 1 7 - 3600 psi 28.84 sq in 6 NPS VIII Div. 1 5 - 3600 psi 8 NPS 49.9 sq in VIII Div. 1 4 - 1400 psi 78.85 sq in 10 NPS VIII Div. 1 112.5 sq in 12 NPS 4 - 1000 psi VIII Div. 1 14 NPS 137.9 sq in 3 - 750 psi VIII Div. 1 3 - 500 psi 182.7 sq in 16 NPS VIII Div. 1 233.7 sq in 18 NPS 3 - 475 psi VIII Div. 1 2 - 450 psi 291 sq in 20 NPS VIII Div. 1 24 NPS 424.6 sq in 2 - 230 psi VIII Div. 1 2 - 184 psi 672 sq in 30 NPS VIII Div. 1 2 - 181 psi 32 NPS 767 sq in VIII Div. 1 36 NPS 976 sq in 6 - 160 psi VIII Div. 1 6 - 145 psi 40 NPS 1210 sq in VIII Div. 1 42 NPS 6 - 138 psi 1336 sq in VIII Div. 1 6 - 132 psi 1469 sq in 44 NPS Page 191 of 812 Effective Date: 2019-05-31

193 Table of Contents BS & B Safety Systems, LLC (BSB) 77048 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series DV, D, DR, DRR, DRV 77048 or catalog number Number: FA-7R, FA-1F - 9F, UA-2,3,5,6, FF-* Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 15, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.19 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 1 NPS 0.69 sq in 44 - 2000 psi VIII Div. 1 1.5 NPS 1.62 sq in 31 - 1400 psi VIII Div. 1 2.95 sq in 2 NPS 15 - 1100 psi VIII Div. 1 3 NPS 6.49 sq in 11 - 900 psi VIII Div. 1 8 - 830 psi 4 NPS 11 sq in VIII Div. 1 25.9 sq in 6 - 640 psi 6 NPS VIII Div. 1 5 - 590 psi 47.1 sq in 8 NPS VIII Div. 1 4 - 480 psi 10 NPS 74.6 sq in VIII Div. 1 3 - 400 psi 106 sq in 12 NPS VIII Div. 1 135 sq in 14 NPS 3 - 350 psi VIII Div. 1 176 sq in 3 - 300 psi 16 NPS VIII Div. 1 223 sq in 3 - 270 psi 18 NPS VIII Div. 1 277 sq in 3 - 240 psi 20 NPS VIII Div. 1 24 NPS 397 sq in 3 - 200 psi VIII Div. 1 3 - 170 psi NPS 28 NPS 584 sq in VIII Div. 1 30 NPS 661 sq in 3 - 170 psi VIII Div. 1 36 NPS 907 sq in 3 - 170 psi VIII Div. 1 3 - 170 psi 40 NPS 1120 sq in VIII Div. 1 3 - 170 psi 1234 sq in 42 NPS VIII Div. 1 3 - 170 psi 44 NPS 1355 sq in Page 192 of 812 Effective Date: 2019-05-31

194 Table of Contents BS & B Safety Systems, LLC (BSB) 77059 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series RLS, RLS Welded Assemly 77059 Number: or catalog number SRB-7RS, SRB-7RS-TR, S90-7R, SRB-7FS, SMR-7R, SRI-7RS, SRB-7RS Special Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on August 12, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.14 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Outlet Size Media Flow Area Code Section Lift Inlet Size VIII Div. 1 0.5 sq in 300 - 2000 psi 0.75 NPS VIII Div. 1 125 - 2000 psi 1 NPS 0.84 sq in VIII Div. 1 85 - 1800 psi 1.5 NPS 1.77 sq in VIII Div. 1 70 - 1800 psi 2 NPS 3.23 sq in VIII Div. 1 3 NPS 6.44 sq in 55 - 1600 psi VIII Div. 1 45 - 1500 psi 4 NPS 11.54 sq in VIII Div. 1 6 NPS 26.4 sq in 35 - 650 psi VIII Div. 1 8 NPS 35 - 400 psi 47 sq in VIII Div. 1 10 NPS 73.9 sq in 35 - 250 psi VIII Div. 1 12 NPS 99 sq in 35 - 150 psi VIII Div. 1 14 NPS 35 - 130 psi 131 sq in VIII Div. 1 16 NPS 172 sq in 25 - 110 psi VIII Div. 1 25 - 90 psi 219 sq in 18 NPS VIII Div. 1 20 NPS 20 - 90 psi 270 sq in Design Series Certification GFN, GFA 77060 Number: or catalog number NF-7RS, NF-7R Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on December 18, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .55 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Inlet Size Lift Set Pressure Range Media Code Section Flow Area VIII Div. 1 0.86 sq in 113 - 1800 psi 1 NPS VIII Div. 1 1.5 NPS 2.03 sq in 81 - 1800 psi VIII Div. 1 2 NPS 3.36 sq in 68 - 1800 psi VIII Div. 1 54 - 1600 psi 3 NPS 7.39 sq in VIII Div. 1 12.7 sq in 45 - 1400 psi 4 NPS VIII Div. 1 36 - 1400 psi 6 NPS 28.9 sq in VIII Div. 1 53 - 1300 psi 50 sq in 8 NPS VIII Div. 1 78.8 sq in 45 - 1300 psi 10 NPS VIII Div. 1 12 NPS 111.9 sq in 41 - 1100 psi VIII Div. 1 14 NPS 137.9 sq in 37 - 750 psi VIII Div. 1 35 - 270 psi 16 NPS 176.7 sq in VIII Div. 1 33 - 240 psi 223.3 sq in 18 NPS VIII Div. 1 32 - 213 psi 20 NPS 277.9 sq in VIII Div. 1 30 - 177 psi 402 sq in 24 NPS Page 193 of 812 Effective Date: 2019-05-31

195 Table of Contents BS & B Safety Systems, LLC (BSB) 77071 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series ECR 77071 Number: or catalog number EC-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 02, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .58 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Flow Area Set Pressure Range Lift Inlet Size Media VIII Div. 1 0.864 sq in 1 NPS 2 - 180 psi VIII Div. 1 2.03 sq in 2 - 80 psi 1.5 NPS VIII Div. 1 3.36 sq in 2 NPS 2 - 80 psi VIII Div. 1 1 - 50 psi 3 NPS 7.3 sq in VIII Div. 1 1 - 50 psi 4 NPS 12.1 sq in VIII Div. 1 6 NPS 25.4 sq in 1 - 50 psi VIII Div. 1 1 - 15 psi 8 NPS 43.6 sq in VIII Div. 1 10 NPS 66.3 sq in 1 - 15 psi VIII Div. 1 12 NPS 1 - 15 psi 94.7 sq in VIII Div. 1 14 NPS 118 sq in 1 - 15 psi VIII Div. 1 154 sq in 1 - 15 psi 16 NPS VIII Div. 1 195 sq in 18 NPS 1 - 15 psi VIII Div. 1 1 - 15 psi 241 sq in 20 NPS VIII Div. 1 24 NPS 348 sq in 1 - 15 psi Certification Design Series S90, S90 Welded Assembly 77082 Number: or catalog number SRB-7RS, SRB-7RS-TR, S90-7R, SMR-7R, SRB-7FS, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 27, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.13 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Outlet Size Media Set Pressure Range Inlet Size Lift Code Section VIII Div. 1 75 - 1000 psi 0.86 sq in 1 NPS VIII Div. 1 54 - 1000 psi 1.5 NPS 2.03 sq in VIII Div. 1 2 NPS 3.36 sq in 45 - 1000 psi VIII Div. 1 36 - 1000 psi 3 NPS 7.39 sq in VIII Div. 1 12.7 sq in 30 - 800 psi 4 NPS VIII Div. 1 6 NPS 24 - 800 psi 28.8 sq in VIII Div. 1 8 NPS 35 - 700 psi 50 sq in VIII Div. 1 30 - 700 psi 78.8 sq in 10 NPS VIII Div. 1 27 - 600 psi 111 sq in 12 NPS VIII Div. 1 14 NPS 135 sq in 25 - 500 psi VIII Div. 1 16 NPS 176 sq in 23 - 475 psi VIII Div. 1 22 - 475 psi 18 NPS 223 sq in VIII Div. 1 277 sq in 20 - 250 psi 20 NPS VIII Div. 1 20 - 250 psi 402 sq in 24 NPS VIII Div. 1 20 - 250 psi 28 NPS 583 sq in VIII Div. 1 20 - 250 psi 672 sq in 30 NPS VIII Div. 1 20 - 250 psi 1195 sq in NPS 40 NPS Page 194 of 812 Effective Date: 2019-05-31

196 Table of Contents BS & B Safety Systems, LLC (BSB) 77093 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series CSR (liquid) 77093 Number: or catalog number CSR-7RS, CRS-7FS, CSI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 15, 1998 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 3.19 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Code Section Outlet Size Inlet Size Media Set Pressure Range VIII Div. 1 120 - 800 psi 1 NPS 0.86 sq in VIII Div. 1 1.5 NPS 2.03 sq in 50 - 800 psi VIII Div. 1 2 NPS 3.35 sq in 50 - 800 psi VIII Div. 1 3 NPS 7.39 sq in 50 - 800 psi VIII Div. 1 4 NPS 50 - 800 psi 12.73 sq in VIII Div. 1 28.89 sq in 30 - 800 psi 6 NPS VIII Div. 1 50 - 800 psi 50.03 sq in 8 NPS Design Series Certification GFR-S, -SM, -SE, -SS, -SMS, -SES (1") 77105 or catalog number Number: GRC Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on December 19, 1998 Capacity Tests: Resistance Factor, 1 Size, Krgl Method of Establishing Relieving Capacity: 19.14 Unitless Certified Value: Air/Gas Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Set Pressure Range Outlet Size Flow Area Lift Media Code Section VIII Div. 1 1 NPS 0.2 sq in 45 - 175 psi Certification Design Series GFR-S, -SM, -SE, -SS, -SMS, -SES (1.5") 77116 Number: or catalog number GRC Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on December 18, 1998 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 9.92 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section VIII Div. 1 13.5 - 100 psi 0.79 sq in 1.5 NPS Page 195 of 812 Effective Date: 2019-05-31

197 Table of Contents BS & B Safety Systems, LLC (BSB) 77127 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series GFR-S, -SM, -SE, -SS, -SMS, -SES (2") 77127 Number: or catalog number GRC-C, FM-C, FT-C Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on December 19, 1998 Capacity Tests: Resistance Factor, 1 Size, Krgl Method of Establishing Relieving Capacity: 4.76 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Code Section Lift Flow Area Outlet Size Set Pressure Range VIII Div. 1 1.77 sq in 11.5 - 105 psi 2 NPS Certification Design Series RB-90 77138 Number: or catalog number RB-7R, RB-7F, RB-7FF, RB-7FS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 19, 1999 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 3.47 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Inlet Size Outlet Size Flow Area Lift Set Pressure Range VIII Div. 1 1 NPS 0.831 sq in 30 - 1800 psi VIII Div. 1 25 - 1700 psi 1.805 sq in 1.5 NPS VIII Div. 1 22 - 1600 psi 2 NPS 3.153 sq in VIII Div. 1 21 - 1500 psi 6.849 sq in 3 NPS VIII Div. 1 11.84 sq in 4 NPS 20 - 1500 psi VIII Div. 1 6 NPS 20 - 850 psi 25.45 sq in VIII Div. 1 15 - 800 psi 47.68 sq in 8 NPS VIII Div. 1 67.62 sq in 15 - 800 psi 10 NPS VIII Div. 1 15 - 800 psi 101.8 sq in 12 NPS VIII Div. 1 15 - 800 psi 121.7 sq in 14 NPS VIII Div. 1 16 NPS 162.8 sq in 15 - 800 psi VIII Div. 1 13 - 700 psi 209.99 sq in 18 NPS VIII Div. 1 13 - 700 psi 262.9 sq in 20 NPS VIII Div. 1 10 - 700 psi 24 NPS 386.9 sq in VIII Div. 1 26 NPS 465 sq in 10 - 700 psi VIII Div. 1 10 - 700 psi 28 NPS 530.7 sq in VIII Div. 1 30 NPS 617.7 sq in 10 - 700 psi VIII Div. 1 10 - 700 psi 32 NPS 698.4 sq in VIII Div. 1 34 NPS 790.1 sq in 10 - 700 psi VIII Div. 1 10 - 700 psi 36 NPS 872.8 sq in Page 196 of 812 Effective Date: 2019-05-31

198 Table of Contents BS & B Safety Systems, LLC (BSB) 77194 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series GFR-S, -SM, -SE, -SS, -SMS, -SES (Combined) 77194 or catalog number Number: GRC Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on December 19, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 23.47 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Inlet Size Code Section Set Pressure Range Flow Area Media Lift VIII Div. 1 4.91 sq in 11.5 - 75 psi 3 NPS Certification Design Series S-90 (Inconel) 77206 Number: or catalog number S90-7R, SRB-7RS, SRB-7RS-TR, SMR-7R, SRB-7FS, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on April 24, 1999 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .23 Unitless Certified Value: Air or gases (Krg) Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Inlet Size Set Pressure Range Flow Area Outlet Size Lift Code Section VIII Div. 1 170 - 1000 psi 0.864 sq in 1 NPS VIII Div. 1 1.5 NPS 2.03 sq in 128 - 1000 psi VIII Div. 1 96 - 1000 psi 2 NPS 3.36 sq in VIII Div. 1 72 - 1000 psi 7.39 sq in 3 NPS VIII Div. 1 60 - 800 psi 4 NPS 12.7 sq in VIII Div. 1 48 - 800 psi 28.9 sq in 6 NPS VIII Div. 1 50 sq in 8 NPS 42 - 700 psi VIII Div. 1 10 NPS 78.8 sq in 36 - 700 psi VIII Div. 1 33 - 600 psi 111 sq in 12 NPS VIII Div. 1 135 sq in 14 NPS 30 - 500 psi VIII Div. 1 16 NPS 176 sq in 28 - 200 psi VIII Div. 1 26 - 160 psi 18 NPS 223 sq in VIII Div. 1 24 - 142 psi 20 NPS 277 sq in VIII Div. 1 22 - 118 psi 402 sq in 24 NPS VIII Div. 1 30 NPS 672 sq in 20 - 80 psi Design Series Certification 1/2" FRB A-6 M x F & M x M Stakul 77217 or catalog number Number: A-6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on June 08, 1999 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 2.19 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Lift Flow Area Inlet Size VIII Div. 1 35 - 600 psi 0.196 sq in 0.5 NPS 0.5 NPS Page 197 of 812 Effective Date: 2019-05-31

199 Table of Contents BS & B Safety Systems, LLC (BSB) 77228 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series 3/4" B assembly 77228 Number: or catalog number Single use Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on February 18, 2000 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 3.85 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Lift Inlet Size Flow Area VIII Div. 1 0.44 sq in 108 - 1000 psi 0.75 NPS Certification Design Series GFR-S, -SM, -SE, -SS, -SMS, -SES 1 1/2" Liquid 77239 Number: or catalog number GR-C Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on April 26, 1999 Capacity Tests: Resistance Factor, 1 Size, Krl Method of Establishing Relieving Capacity: 11.5 Unitless Certified Value: Air/Gas Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Inlet Size Outlet Size Lift Set Pressure Range Media Code Section VIII Div. 1 1.5 NPS 0.79 sq in 13.5 - 150 psi Page 198 of 812 Effective Date: 2019-05-31

200 Table of Contents BS & B Safety Systems, LLC (BSB) 77273 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series BV,BRV,BSV,BRSV (liquid) 77273 Number: or catalog number FA-7R, FA-1 - FA-9,UA-,3,5,6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on July 01, 1999 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 2.45 Unitless Certified Value: Liquid (Krl) Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Outlet Size Media Flow Area Code Section Lift Inlet Size VIII Div. 1 0.57 sq in 145 - 12000 psi 1 NPS VIII Div. 1 95 - 6000 psi 1.44 sq in 1.5 NPS VIII Div. 1 55 - 6000 psi 2.24 sq in 2 NPS VIII Div. 1 3 NPS 5.41 sq in 41 - 6000 psi VIII Div. 1 9.62 sq in 4 NPS 31 - 6000 psi VIII Div. 1 6 NPS 23.76 sq in 23 - 3600 psi VIII Div. 1 8 NPS 18 - 3600 psi 44.18 sq in VIII Div. 1 70.88 sq in 10 NPS 14 - 1400 psi VIII Div. 1 12 NPS 12 - 1000 psi 101.5 sq in VIII Div. 1 130.3 sq in 11 - 750 psi 14 NPS VIII Div. 1 16 NPS 176.7 sq in 9 - 500 psi VIII Div. 1 202.4 sq in 18 NPS 8 - 475 psi VIII Div. 1 8 - 450 psi 20 NPS 280 sq in VIII Div. 1 37 - 230 psi 380.1 sq in 24 NPS VIII Div. 1 615.8 sq in 30 NPS 20 - 184 psi VIII Div. 1 32 NPS 728 sq in 31 - 181 psi VIII Div. 1 28 - 160 psi 927 sq in 36 NPS VIII Div. 1 40 NPS 25 - 145 psi 1149 sq in VIII Div. 1 24 - 138 psi 1269 sq in 42 NPS VIII Div. 1 23 - 132 psi 1395 sq in 44 NPS Certification Design Series FRS 77284 Number: or catalog number SRB-7RS, SRB-7RS-TR, SRB-7FS, S90-7R, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on June 23, 1999 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.80 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Outlet Size Inlet Size Flow Area Lift Set Pressure Range Media VIII Div. 1 1 NPS 0.86 sq in 13.5 - 150 psi VIII Div. 1 11.5 - 70 psi 1.5 NPS 1.94 sq in VIII Div. 1 11.5 - 50 psi 3.36 sq in 2 NPS Page 199 of 812 Effective Date: 2019-05-31

201 Table of Contents BS & B Safety Systems, LLC (BSB) 77307 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series RLS, RLS Welded Assembly (liquid) 77307 Number: or catalog number SRB-7RS, SRB-7RS-TR, SRB-7FS, S90-7R, SMR-7R, SRI-7RS, SRB-7RS Special Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on July 16, 1999 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 5.83 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size VIII Div. 1 0.75 NPS 0.5 sq in 300 - 6000 psi VIII Div. 1 1 NPS 125 - 6000 psi 0.84 sq in VIII Div. 1 1.5 NPS 85 - 5400 psi 1.77 sq in VIII Div. 1 70 - 4800 psi 3.23 sq in 2 NPS VIII Div. 1 55 - 3800 psi 6.44 sq in 3 NPS VIII Div. 1 4 NPS 11.54 sq in 45 - 2800 psi VIII Div. 1 6 NPS 26.4 sq in 35 - 2000 psi VIII Div. 1 35 - 1600 psi 8 NPS 47 sq in VIII Div. 1 73.9 sq in 35 - 1200 psi 10 NPS VIII Div. 1 35 - 900 psi 99 sq in 12 NPS VIII Div. 1 35 - 650 psi 14 NPS 131 sq in VIII Div. 1 16 NPS 172 sq in 25 - 550 psi VIII Div. 1 25 - 450 psi 219 sq in 18 NPS VIII Div. 1 20 NPS 20 - 350 psi 270 sq in Page 200 of 812 Effective Date: 2019-05-31

202 Table of Contents BS & B Safety Systems, LLC (BSB) 77318 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series B, BR, BRR (liquid) 77318 or catalog number Number: FA-7R, FA-1 - FA9, UA-2,3,5,6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on July 12, 1999 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 1.47 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 0.5 NPS 0.189 sq in 80 - 30000 psi VIII Div. 1 1 NPS 0.801 sq in 40 - 12000 psi VIII Div. 1 1.76 sq in 1.5 NPS 26 - 6000 psi VIII Div. 1 2 NPS 3.33 sq in 16 - 6000 psi VIII Div. 1 12 - 6000 psi 3 NPS 6.514 sq in VIII Div. 1 11.82 sq in 9 - 6000 psi 4 NPS VIII Div. 1 7 - 3600 psi 28.84 sq in 6 NPS VIII Div. 1 5 - 3600 psi 8 NPS 49.89 sq in VIII Div. 1 4 - 1400 psi 78.85 sq in 10 NPS VIII Div. 1 112.5 sq in 12 NPS 4 - 1000 psi VIII Div. 1 14 NPS 137.9 sq in 3 - 750 psi VIII Div. 1 3 - 500 psi 182.7 sq in 16 NPS VIII Div. 1 233.7 sq in 18 NPS 3 - 475 psi VIII Div. 1 2 - 450 psi 291 sq in 20 NPS VIII Div. 1 24 NPS 424.6 sq in 2 - 230 psi VIII Div. 1 2 - 184 psi 672 sq in 30 NPS VIII Div. 1 2 - 181 psi 32 NPS 767 sq in VIII Div. 1 36 NPS 976 sq in 6 - 160 psi VIII Div. 1 6 - 145 psi 40 NPS 1210 sq in VIII Div. 1 42 NPS 3 - 138 psi 1336 sq in VIII Div. 1 6 - 132 psi 1469 sq in 44 NPS Page 201 of 812 Effective Date: 2019-05-31

203 Table of Contents BS & B Safety Systems, LLC (BSB) 77341 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series AV 77341 Number: or catalog number AV7R, AV-1, -2, -3, -4, -5, -6, -7, -8, -9 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on November 04, 1999 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 4.35 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Set Pressure Range Flow Area Media Code Section Lift VIII Div. 1 0.864 sq in 10 - 150 psi 1 NPS VIII Div. 1 8 - 150 psi 1.25 NPS 1.4 sq in VIII Div. 1 7 - 150 psi 2.036 sq in 1.5 NPS VIII Div. 1 2 NPS 3.356 sq in 5 - 150 psi VIII Div. 1 5 - 150 psi 2.5 NPS 4.787 sq in VIII Div. 1 3 NPS 7.392 sq in 4 - 150 psi VIII Div. 1 4 NPS 2 - 150 psi 12.73 sq in VIII Div. 1 20 sq in 5 NPS 2 - 100 psi VIII Div. 1 6 NPS 1 - 100 psi 28.89 sq in VIII Div. 1 50.02 sq in 1 - 100 psi 8 NPS VIII Div. 1 10 NPS 78.85 sq in .6 - 60 psi VIII Div. 1 113.1 sq in 12 NPS .6 - 60 psi VIII Div. 1 0.6 - 60 psi 14 NPS 137.9 sq in VIII Div. 1 .6 - 60 psi 182.7 sq in 16 NPS VIII Div. 1 233.7 sq in 18 NPS .5 - 60 psi VIII Div. 1 20 NPS .5 - 60 psi 291 sq in VIII Div. 1 .5 - 60 psi 354.7 sq in 22 NPS VIII Div. 1 424.6 sq in .5 - 60 psi 24 NPS VIII Div. 1 .5 - 40 psi 500.7 sq in 26 NPS VIII Div. 1 .5 - 40 psi 583.2 sq in 28 NPS VIII Div. 1 30 NPS 672 sq in .5 - 40 psi VIII Div. 1 .35 - 40 psi 767 sq in 32 NPS VIII Div. 1 .35 - 40 psi 868.3 sq in 34 NPS VIII Div. 1 .25 - 40 psi 36 NPS 975.9 sq in VIII Div. 1 38 NPS 1090 sq in .25 - 40 psi VIII Div. 1 .25 - 40 psi 40 NPS 1210 sq in VIII Div. 1 42 NPS 1336 sq in .25 - 40 psi VIII Div. 1 .25 - 40 psi 44 NPS 1469 sq in VIII Div. 1 46 NPS 1608 sq in .25 - 40 psi VIII Div. 1 .25 - 40 psi 48 NPS 1753 sq in Page 202 of 812 Effective Date: 2019-05-31

204 Table of Contents BS & B Safety Systems, LLC (BSB) 77352 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series D Series (liquid) DR, DRR 77352 Number: or catalog number FA-7R, FA-1 - FA-9,UA-2,3,5,6, FF-* Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on October 28, 1999 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 1.3 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Set Pressure Range Flow Area Media Code Section Lift VIII Div. 1 0.801 sq in 44 - 2000 psi 1 NPS VIII Div. 1 31 - 1400 psi 1.5 NPS 1.76 sq in VIII Div. 1 15 - 1100 psi 3.33 sq in 2 NPS VIII Div. 1 3 NPS 6.51 sq in 11 - 900 psi VIII Div. 1 8 - 830 psi 4 NPS 11.8 sq in VIII Div. 1 6 NPS 28.84 sq in 6 - 640 psi VIII Div. 1 8 NPS 5 - 590 psi 49.9 sq in VIII Div. 1 78.8 sq in 10 NPS 4 - 480 psi VIII Div. 1 12 NPS 3 - 1000 psi 112.5 sq in VIII Div. 1 137.9 sq in 3 - 350 psi 14 NPS VIII Div. 1 16 NPS 182.7 sq in 3 - 300 psi VIII Div. 1 233.7 sq in 18 NPS 3 - 270 psi VIII Div. 1 3 - 240 psi 20 NPS 291 sq in VIII Div. 1 3 - 200 psi 424.6 sq in 24 NPS VIII Div. 1 584 sq in 28 NPS 3 - 170 psi VIII Div. 1 30 NPS 3 - 170 psi 672 sq in VIII Div. 1 3 - 170 psi 767 sq in 32 NPS VIII Div. 1 36 NPS 3 - 170 psi 976 sq in VIII Div. 1 3 - 170 psi 1210 sq in 40 NPS VIII Div. 1 3 - 170 psi 1336 sq in 42 NPS VIII Div. 1 44 NPS 1465 sq in 3 - 170 psi Design Series Certification GCR-S,SE,SM,SS,SES,SMS, SW, N, NS (2") 77420 Number: or catalog number GR-C, FM-C , not req'd for -SM Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on January 10, 2000 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 1.25 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section VIII Div. 1 Air 10 - 300 psi 2.7 sq in 2 NPS Page 203 of 812 Effective Date: 2019-05-31

205 Table of Contents BS & B Safety Systems, LLC (BSB) 77442 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series 1/2" Welded FRB with 3/4" Sanitary Clamp Connection (A/G/L) 77442 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on April 11, 2000 Capacity Tests: Resistance Factor, 1 Size, Krgl Method of Establishing Relieving Capacity: 12.0 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media VIII Div. 1 100 - 300 psi 0.75 NPS 0.75 NPS 0.22 sq in 0.62 in Design Series Certification 2" BV 77486 or catalog number Number: FA-7R, FA-1F - 9F, UA-2,3,5,6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on August 11, 1998 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: .55 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Lift Inlet Size Flow Area Outlet Size Set Pressure Range VIII Div. 1 2.24 sq in 16 - 6000 psi 2 NPS Certification Design Series 2" B 77497 or catalog number Number: FA-7R, 1F - 9F, UA-2,3,5,6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on August 11, 1998 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: .23 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Inlet Size Lift Flow Area Set Pressure Range Code Section Media VIII Div. 1 16 - 6000 psi 3.33 sq in 2 NPS Page 204 of 812 Effective Date: 2019-05-31

206 Table of Contents BS & B Safety Systems, LLC (BSB) 77565 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series CSI 77565 Number: or catalog number CSR-7RS, CSR-7FS, CSI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on August 30, 2000 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.62 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Inlet Size Flow Area Outlet Size Code Section Media Set Pressure Range VIII Div. 1 70 - 800 psi 0.86 sq in 1 NPS 1 NPS VIII Div. 1 50 - 800 psi 1.89 sq in 1.5 NPS 1.5 NPS VIII Div. 1 Air 2 NPS 2 NPS 3.36 sq in 50 - 800 psi VIII Div. 1 3 NPS 3 NPS 7.29 sq in 45 - 800 psi VIII Div. 1 4 NPS 4 NPS 11.2 sq in 45 - 800 psi VIII Div. 1 30 - 800 psi 22.65 sq in 6 NPS 6 NPS VIII Div. 1 8 NPS 8 NPS 42.72 sq in 30 - 800 psi Certification Design Series A-10 SK 1" SCD B 77587 Number: or catalog number Integral Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 06, 2000 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: .415 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Media Outlet Size Inlet Size Lift Set Pressure Range VIII Div. 1 1 NPS 0.785 sq in 150 - 900 psi 1 NPS Certification Design Series A-2 SK 0.5 FRB 77598 Number: or catalog number Integral Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 01, 2000 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 2.2 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Flow Area Lift Set Pressure Range Media Code Section Outlet Size VIII Div. 1 0.5 NPS 0.5 NPS 0.196 sq in 50 - 650 psi Page 205 of 812 Effective Date: 2019-05-31

207 Table of Contents BS & B Safety Systems, LLC (BSB) 77600 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series 0.5" FRB WFT 77600 Number: or catalog number Single use assembly Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 07, 2000 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 35.7 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Inlet Size Flow Area Outlet Size Code Section Media Set Pressure Range VIII Div. 1 Air 0.216 sq in 1 NPS 1 NPS 85 - 450 psi Design Series Certification GCR-S, SE, SM, SS, SES, SMS, SW, N, NS 77611 or catalog number Number: GR-C, FM-C, not req'd for -SM Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on November 22, 2000 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.95 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Div. 1 Air 1.5 NPS 1.5 sq in 10 - 300 psi VIII Div. 1 10 - 175 psi 5.29 sq in 3 NPS VIII Div. 1 9.78 sq in 4 NPS 10 - 150 psi VIII Div. 1 6 NPS 22.5 sq in 10 - 75 psi Certification Design Series GCR-S, SE, SM, SS, SES, SMS, SW, N, NS (liquids) 77622 or catalog number Number: GR-C, FM-C (not req'd for SM) Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on November 29, 2000 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 4.95 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 1.5 NPS 1.5 sq in 10 - 300 psi VIII Div. 1 10 - 175 psi 3 NPS 5.29 sq in VIII Div. 1 4 NPS 10 - 150 psi 9.78 sq in VIII Div. 1 10 - 75 psi 22.5 sq in 6 NPS Page 206 of 812 Effective Date: 2019-05-31

208 Table of Contents BS & B Safety Systems, LLC (BSB) 77633 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series A-6 with B Disk 77633 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on April 25, 2001 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 6.44 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Inlet Size Lift Set Pressure Range Media Code Section Outlet Size VIII Div. 1 0.19 sq in 600 - 1500 psi 0.5 NPS .5 NPS Certification Design Series A19 with Scored B Disk 77644 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on April 30, 2001 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: .503 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Outlet Size Inlet Size Flow Area Media Lift Set Pressure Range VIII Div. 1 108 - 1000 psi 0.44 sq in .75 NPS 0.75 NPS Design Series Certification RLS DD (liquid) 77688 Number: or catalog number SRB-7RS DD, SRB-7RS-TR DD, SRB-7FS DD Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on October 24, 2002 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 5.83 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Media Set Pressure Range Inlet Size Code Section Flow Area Lift VIII Div. 1 0.842 sq in 125 - 3900 psi 1 NPS VIII Div. 1 1.5 NPS 1.77 sq in 85 - 1800 psi VIII Div. 1 2 NPS 70 - 1800 psi 3.23 sq in VIII Div. 1 6.44 sq in 55 - 1600 psi 3 NPS VIII Div. 1 45 - 1050 psi 11.54 sq in 4 NPS VIII Div. 1 35 - 650 psi 26.44 sq in 6 NPS VIII Div. 1 47.07 sq in 35 - 400 psi 8 NPS VIII Div. 1 10 NPS 73.94 sq in 35 - 250 psi VIII Div. 1 12 NPS 35 - 150 psi 99.06 sq in VIII Div. 1 131.5 sq in 35 - 130 psi 14 NPS VIII Div. 1 16 NPS 25 - 110 psi 172.1 sq in VIII Div. 1 25 - 90 psi 18 NPS 219.5 sq in VIII Div. 1 20 - 90 psi 270 sq in 20 NPS Page 207 of 812 Effective Date: 2019-05-31

209 Table of Contents BS & B Safety Systems, LLC (BSB) 77699 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series RLS DD 77699 Number: or catalog number SRB-7RS DD, SRB-7RS-TR DD, SRB-7FS DD Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on October 16, 2002 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.9 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Outlet Size Media Flow Area Code Section Lift Inlet Size VIII Div. 1 0.842 sq in 125 - 2000 psi 1 NPS VIII Div. 1 85 - 1800 psi 1.5 NPS 1.77 sq in VIII Div. 1 70 - 1800 psi 2 NPS 3.23 sq in VIII Div. 1 70 - 1600 psi 3 NPS 6.44 sq in VIII Div. 1 4 NPS 11.54 sq in 45 - 1050 psi VIII Div. 1 35 - 650 psi 6 NPS 26.44 sq in VIII Div. 1 8 NPS 47.07 sq in 35 - 400 psi VIII Div. 1 10 NPS 35 - 250 psi 73.94 sq in VIII Div. 1 35 - 150 psi 12 NPS 99.06 sq in VIII Div. 1 131.5 sq in 35 - 130 psi 14 NPS VIII Div. 1 16 NPS 25 - 110 psi 172.1 sq in VIII Div. 1 25 - 90 psi 219.5 sq in 18 NPS VIII Div. 1 20 NPS 270 sq in 20 - 90 psi Certification Design Series JRS DD 77701 Number: or catalog number SRB-7RS DD, SRB-7RS-TR DD, SRB-7FS DD Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on June 27, 2002 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.68 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Code Section Inlet Size Outlet Size Lift Set Pressure Range Media VIII Div. 1 0.86 sq in 1 NPS 22 - 180 psi VIII Div. 1 1.5 NPS 1.89 sq in 20 - 150 psi VIII Div. 1 2 NPS 3.35 sq in 18 - 120 psi VIII Div. 1 6.53 sq in 16 - 80 psi 3 NPS VIII Div. 1 14 - 70 psi 11.8 sq in 4 NPS VIII Div. 1 25 sq in 6 NPS 12 - 50 psi VIII Div. 1 12 - 42 psi 42 sq in 8 NPS VIII Div. 1 12 - 36 psi 68.6 sq in 10 NPS VIII Div. 1 12 NPS 102 sq in 12 - 33 psi VIII Div. 1 14 NPS 121 sq in 9 - 30 psi VIII Div. 1 7 - 28 psi 16 NPS 156 sq in VIII Div. 1 198 sq in 6 - 26 psi 18 NPS VIII Div. 1 5 - 24 psi 246 sq in 20 NPS VIII Div. 1 5 - 22 psi 24 NPS 357 sq in VIII Div. 1 5 - 14 psi 592 sq in 30 NPS VIII Div. 1 5 - 14 psi 868 sq in 36 NPS Page 208 of 812 Effective Date: 2019-05-31

210 Table of Contents BS & B Safety Systems, LLC (BSB) 77712 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series S90 DD 77712 Number: or catalog number S90-7R DD, SRB-7RS DD, SRB-7RS-TR DD,SRB-7FS DD Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on October 14, 2002 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.13 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Outlet Size Media Flow Area Code Section Lift Inlet Size VIII Div. 1 0.86 sq in 75 - 1000 psi 1 NPS VIII Div. 1 54 - 1000 psi 2.03 sq in 1.5 NPS VIII Div. 1 45 - 1000 psi 3.35 sq in 2 NPS VIII Div. 1 3 NPS 7.39 sq in 36 - 1000 psi VIII Div. 1 12.7 sq in 4 NPS 30 - 800 psi VIII Div. 1 6 NPS 28.8 sq in 24 - 800 psi VIII Div. 1 8 NPS 35 - 700 psi 50 sq in VIII Div. 1 79.8 sq in 10 NPS 30 - 700 psi VIII Div. 1 12 NPS 27 - 600 psi 111 sq in VIII Div. 1 135 sq in 25 - 500 psi 14 NPS VIII Div. 1 16 NPS 176 sq in 23 - 200 psi VIII Div. 1 223 sq in 18 NPS 22 - 160 psi VIII Div. 1 20 - 142 psi 20 NPS 277 sq in VIII Div. 1 20 - 118 psi 402 sq in 24 NPS VIII Div. 1 672 sq in 30 NPS 20 - 80 psi Certification Design Series SVI Assembly 77723 Number: or catalog number SVI Assembly Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on June 10, 2002 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 11.35 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Lift Media Code Section Inlet Size Outlet Size Set Pressure Range VIII Div. 1 125 - 1000 psi 1.5 NPS 1.37 sq in VIII Div. 1 2 NPS 2.26 sq in 90 - 1000 psi VIII Div. 1 75 - 1000 psi 3 NPS 5.11 sq in VIII Div. 1 4 NPS 8.66 sq in 60 - 800 psi VIII Div. 1 50 - 700 psi 6 NPS 20.92 sq in VIII Div. 1 8 NPS 37 sq in 40 - 700 psi VIII Div. 1 35 - 700 psi 10 NPS 61 sq in Page 209 of 812 Effective Date: 2019-05-31

211 Table of Contents BS & B Safety Systems, LLC (BSB) 77734 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series DV, DRV, DSV, DRSV (liquids) 77734 Number: or catalog number FA-7R,FA-1F - FA-9F, UA-2,3,5,6, FF-* Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on June 11, 2002 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 2.6 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Outlet Size Flow Area Code Section Inlet Size Media Set Pressure Range VIII Div. 1 0.57 sq in 1 NPS 44 - 2000 psi VIII Div. 1 31 - 1400 psi 1.44 sq in 1.5 NPS VIII Div. 1 2 NPS 2.24 sq in 15 - 1100 psi VIII Div. 1 11 - 900 psi 3 NPS 5.41 sq in VIII Div. 1 4 NPS 9.62 sq in 8 - 830 psi VIII Div. 1 6 NPS 6 - 640 psi 23.76 sq in VIII Div. 1 44.18 sq in 5 - 590 psi 8 NPS VIII Div. 1 4 - 480 psi 70.88 sq in 10 NPS VIII Div. 1 3 - 1000 psi 101.5 sq in 12 NPS VIII Div. 1 14 NPS 130.3 sq in 3 - 350 psi VIII Div. 1 176.7 sq in 16 NPS 3 - 300 psi VIII Div. 1 3 - 270 psi 202.3 sq in 18 NPS VIII Div. 1 3 - 240 psi 280 sq in 20 NPS VIII Div. 1 24 NPS 380.1 sq in 3 - 200 psi VIII Div. 1 3 - 170 psi 584 sq in 28 NPS VIII Div. 1 615.7 sq in 3 - 170 psi 30 NPS VIII Div. 1 728 sq in 32 NPS 3 - 170 psi VIII Div. 1 36 NPS 3 - 170 psi 927 sq in VIII Div. 1 1149 sq in 3 - 170 psi 40 NPS VIII Div. 1 42 NPS 3 - 170 psi 1269 sq in VIII Div. 1 44 NPS 1395 sq in 3 - 170 psi Certification Design Series Welded 1" FRB, w. 1/2" VCR connections 77778 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 04, 2002 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 16.95 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Lift Flow Area Inlet Size VIII Div. 1 15 - 150 psi 0.126 sq in .5 NPS 0.5 NPS Page 210 of 812 Effective Date: 2019-05-31

212 Table of Contents BS & B Safety Systems, LLC (BSB) 77789 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series 1/2" Welded FRB w. 3/4" Sanitary Connection (air/gas) 77789 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on January 13, 2003 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 5.9 Unitless Certified Value: Air or gases (Krg) Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Inlet Size Code Section Set Pressure Range Flow Area Media Lift VIII Div. 1 0.22 sq in 40 - 500 psi 0.75 NPS Design Series Certification MRB 77824 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on May 05, 2004 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 5.3 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media Code Section VIII Div. 1 0.046 sq in 4300 - 55000 psi 0.29 in VIII Div. 1 4300 - 55000 psi 0.05 sq in 0.3 in VIII Div. 1 4300 - 55000 psi 0.08 sq in 0.375 NPS VIII Div. 1 0.5 NPS 0.14 sq in 3800 - 54000 psi VIII Div. 1 3500 - 52000 psi 0.22 sq in 0.625 NPS VIII Div. 1 2900 - 49000 psi 0.31 sq in 0.75 NPS VIII Div. 1 2900 - 49000 psi 0.875 in 0.52 sq in VIII Div. 1 2500 - 43000 psi 0.55 sq in 1 NPS VIII Div. 1 0.69 sq in 1.125 in 2500 - 43000 psi VIII Div. 1 1.25 NPS 0.86 sq in 2500 - 43000 psi VIII Div. 1 1900 - 35000 psi 1.24 sq in 1.5 NPS VIII Div. 1 2.2 sq in 1800 - 29000 psi 2 NPS VIII Div. 1 1500 - 21000 psi 4.5 sq in 3 NPS VIII Div. 1 1500 - 21000 psi 5.2 sq in 3.25 in VIII Div. 1 4 NPS 8.8 sq in 1500 - 16000 psi VIII Div. 1 6 NPS 19.8 sq in 1000 - 14000 psi VIII Div. 1 35.2 sq in 600 - 14000 psi 8 NPS VIII Div. 1 400 - 12000 psi 55 sq in 10 NPS Design Series Certification FRB (welded cassette) 77835 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on February 26, 2004 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 6.8 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size VIII Div. 1 60 - 400 psi 0.09 sq in 0.375 NPS Page 211 of 812 Effective Date: 2019-05-31

213 Table of Contents BS & B Safety Systems, LLC (BSB) 77846 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series SKA 77846 Number: or catalog number Integral one piece design Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on October 13, 2004 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.878 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Outlet Size Media Set Pressure Range Inlet Size VIII Div. 1 Air 50 - 750 psi 0.25 in 0.046 sq in 0.25 NPS VIII Div. 1 0.375 NPS 50 - 750 psi 0.375 in 0.085 sq in VIII Div. 1 35 - 700 psi 0.5 in 0.182 sq in 0.5 NPS Design Series Certification X 90 Welded 77868 or catalog number Number: Integral Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on June 09, 2005 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 6.0 Unitless Certified Value: Air Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 500 - 4000 psi 0.34 sq in .75 NPS 0.75 NPS Page 212 of 812 Effective Date: 2019-05-31

214 Table of Contents BS & B Safety Systems, LLC (BSB) 77879 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series B, BR, BRR-LTF 77879 or catalog number Number: Lo-to-Flo Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 14, 2005 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 8.0 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 0.5 NPS 0.189 sq in 80 - 30000 psi VIII Div. 1 1 NPS 0.801 sq in 40 - 12000 psi VIII Div. 1 1.76 sq in 1.5 NPS 26 - 6000 psi VIII Div. 1 2 NPS 3.33 sq in 16 - 6000 psi VIII Div. 1 12 - 6000 psi 3 NPS 6.514 sq in VIII Div. 1 11.82 sq in 9 - 6000 psi 4 NPS VIII Div. 1 7 - 3600 psi 28.84 sq in 6 NPS VIII Div. 1 5 - 3600 psi 8 NPS 49.89 sq in VIII Div. 1 4 - 1400 psi 78.85 sq in 10 NPS VIII Div. 1 112.5 sq in 12 NPS 4 - 1000 psi VIII Div. 1 14 NPS 137.9 sq in 3 - 750 psi VIII Div. 1 3 - 500 psi 182.7 sq in 16 NPS VIII Div. 1 233.7 sq in 18 NPS 3 - 475 psi VIII Div. 1 2 - 450 psi 291 sq in 20 NPS VIII Div. 1 24 NPS 424.6 sq in 2 - 230 psi VIII Div. 1 2 - 184 psi 672 sq in 30 NPS VIII Div. 1 2 - 181 psi 32 NPS 767 sq in VIII Div. 1 36 NPS 975.9 sq in 6 - 160 psi VIII Div. 1 6 - 145 psi 40 NPS 1210 sq in VIII Div. 1 42 NPS 6 - 138 psi 1336 sq in VIII Div. 1 6 - 132 psi 1469 sq in 44 NPS Page 213 of 812 Effective Date: 2019-05-31

215 Table of Contents BS & B Safety Systems, LLC (BSB) 77880 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series BV, BRV, BSV, BRSV-LTF 77880 or catalog number Number: Lo-to-Flo Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 14, 2005 Capacity Tests: Resistance Factor, 1 Size, Krgl Method of Establishing Relieving Capacity: 2.47 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 1 NPS 0.57 sq in 40 - 12000 psi VIII Div. 1 1.5 NPS 1.44 sq in 26 - 6000 psi VIII Div. 1 2.24 sq in 2 NPS 16 - 6000 psi VIII Div. 1 3 NPS 5.41 sq in 12 - 6000 psi VIII Div. 1 9 - 6000 psi 4 NPS 9.62 sq in VIII Div. 1 23.76 sq in 7 - 3600 psi 6 NPS VIII Div. 1 5 - 3600 psi 44.18 sq in 8 NPS VIII Div. 1 4 - 1400 psi 10 NPS 70.88 sq in VIII Div. 1 4 - 1000 psi 101.5 sq in 12 NPS VIII Div. 1 130.3 sq in 14 NPS 3 - 750 psi VIII Div. 1 16 NPS 176.7 sq in 3 - 500 psi VIII Div. 1 3 - 475 psi 202.4 sq in 18 NPS VIII Div. 1 280 sq in 20 NPS 2 - 450 psi VIII Div. 1 2 - 230 psi 380.1 sq in 24 NPS VIII Div. 1 30 NPS 615.8 sq in 2 - 184 psi VIII Div. 1 6 - 181 psi 728 sq in 32 NPS VIII Div. 1 6 - 160 psi 36 NPS 927 sq in VIII Div. 1 40 NPS 1149 sq in 6 - 145 psi VIII Div. 1 6 - 138 psi 1269 sq in 42 NPS VIII Div. 1 44 NPS 6 - 132 psi 1395 sq in Page 214 of 812 Effective Date: 2019-05-31

216 Table of Contents BS & B Safety Systems, LLC (BSB) 77891 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series D, DR, DRR-LTF 77891 Number: or catalog number Lo-to-Flo Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 13, 2005 Capacity Tests: Resistance Factor, 1 Size, Krgl Method of Establishing Relieving Capacity: 2.3 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Media Code Section Inlet Size Lift Set Pressure Range VIII Div. 1 1 NPS 0.801 sq in 44 - 2000 psi VIII Div. 1 1.5 NPS 1.76 sq in 31 - 1400 psi VIII Div. 1 3.33 sq in 15 - 1100 psi 2 NPS VIII Div. 1 11 - 900 psi 6.514 sq in 3 NPS VIII Div. 1 4 NPS 11.82 sq in 8 - 830 psi VIII Div. 1 6 - 640 psi 6 NPS 28.84 sq in VIII Div. 1 8 NPS 48.89 sq in 5 - 590 psi VIII Div. 1 10 NPS 4 - 480 psi 78.85 sq in VIII Div. 1 112.5 sq in 12 NPS 3 - 400 psi VIII Div. 1 137.9 sq in 3 - 350 psi 14 NPS VIII Div. 1 3 - 300 psi 182.7 sq in 16 NPS VIII Div. 1 18 NPS 233.7 sq in 3 - 270 psi VIII 3 - 240 psi 291 sq in 20 NPS VIII Div. 1 3 - 200 psi 424.6 sq in 24 NPS VIII Div. 1 3 - 170 psi 30 NPS 672 sq in VIII Div. 1 3 - 170 psi 767 sq in 32 NPS VIII Div. 1 975.9 sq in 36 NPS 3 - 170 psi VIII Div. 1 40 NPS 3 - 170 psi 1210 sq in VIII Div. 1 3 - 170 psi 1336 sq in 42 NPS Certification Design Series FVA 77925 or catalog number Number: FVA Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on October 07, 2008 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .840 Unitless Certified Value: Code Case 2395 Certification Provisions: Air/Gas Test Medium: Air/Gas Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size VIII Div. 1 Air 115 - 1800 psi 0.049 sq in 0.25 NPS VIII Div. 1 Air 115 - 1800 psi 0.375 NPS 0.11 sq in VIII Div. 1 Air 0.5 NPS 0.196 sq in 115 - 1800 psi VIII Div. 1 Air 0.75 NPS 0.442 sq in 100 - 1000 psi VIII Div. 1 Air 90 - 1000 psi 0.785 sq in 1 NPS VIII Div. 1 Air 85 - 1000 psi 1.77 sq in 1.5 NPS Page 215 of 812 Effective Date: 2019-05-31

217 Table of Contents BS & B Safety Systems, LLC (BSB) 77936 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series Welded FRB w/ 3/4" VCR Connections 77936 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on March 16, 2011 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 5.0 Unitless Certified Value: Air or gases (Krg) Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Media Outlet Size Inlet Size Set Pressure Range Lift VIII Div. 1 0.2 sq in 0.75 NPS 15 - 150 psi Certification Design Series Scored B -LTF, Scd B-LTF, XB-LTF 78151 Number: or catalog number Lo-To-Flo Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on October 18, 2014 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 4.77 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size VIII Div. 1 250 - 6000 psi 0.8 sq in 1 NPS VIII Div. 1 1.76 sq in 1.5 NPS 200 - 4000 psi VIII Div. 1 2 NPS 3.33 sq in 175 - 3500 psi VIII Div. 1 150 - 3000 psi 6.51 sq in 3 NPS VIII Div. 1 4 NPS 135 - 2500 psi 11.82 sq in VIII Div. 1 125 - 2000 psi 28.8 sq in 6 NPS VIII Div. 1 8 NPS 49.9 sq in 110 - 1750 psi VIII Div. 1 78.9 sq in 10 NPS 100 - 1500 psi VIII Div. 1 90 - 1250 psi 112.5 sq in 12 NPS VIII Div. 1 80 - 1000 psi 14 NPS 137.9 sq in VIII Div. 1 16 NPS 182.7 sq in 75 - 800 psi VIII Div. 1 70 - 600 psi 18 NPS 233.7 sq in VIII Div. 1 20 NPS 65 - 500 psi 291 sq in VIII Div. 1 60 - 250 psi 424.6 sq in 24 NPS Page 216 of 812 Effective Date: 2019-05-31

218 Table of Contents BS & B Safety Systems, LLC (BSB) 78162 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series CSI (liquid) 78162 or catalog number Number: CSR-7RS, CSR-7FS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on June 23, 2015 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 3.09 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Set Pressure Range Media Code Section Flow Area Lift VIII Div. 1 0.86 sq in 70 - 800 psi 1 NPS 1 NPS VIII Div. 1 50 - 800 psi 1.89 sq in 1.5 NPS 1.5 NPS VIII Div. 1 50 - 800 psi 3.36 sq in 2 NPS 2 NPS VIII Div. 1 3 NPS 3 NPS 7.29 sq in 45 - 800 psi VIII Div. 1 45 - 800 psi 4 NPS 4 NPS 11.2 sq in VIII Div. 1 30 - 800 psi 6 NPS 6 NPS 22.65 sq in VIII Div. 1 30 - 800 psi 8 NPS 8 NPS 42.72 sq in Certification Design Series PLD 78173 Number: or catalog number FA-*, FF-*, UA-2, 3, 4, 5, 6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on August 20, 2015 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 4.2 Unitless Certified Value: Air/Gas Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: (none) Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 44 - 2000 psi 0.69 1 NPS VIII Div. 1 1.62 1.5 NPS 31 - 1400 psi VIII Div. 1 2 NPS 15 - 1100 psi 2.95 VIII Div. 1 11 - 900 psi 6.49 3 NPS VIII Div. 1 11 4 NPS 8 - 830 psi VIII Div. 1 6 NPS 6 - 640 psi 25.9 VIII Div. 1 47.1 5 - 590 psi 8 NPS VIII Div. 1 10 NPS 4 - 480 psi 74.6 VIII Div. 1 12 NPS 106 3 - 400 psi VIII Div. 1 14 NPS 135 3 - 350 psi VIII Div. 1 3 - 300 psi 16 NPS 176 VIII Div. 1 223 3 - 270 psi 18 NPS VIII Div. 1 3 - 240 psi 20 NPS 277 VIII Div. 1 3 - 200 psi 397 24 NPS VIII Div. 1 584 3 - 180 psi 28 NPS VIII Div. 1 661 30 NPS 3 - 170 psi VIII Div. 1 3 - 170 psi 907 36 NPS VIII Div. 1 40 NPS 1120 3 - 170 psi VIII Div. 1 3 - 170 psi 42 NPS 1234 VIII Div. 1 3 - 170 psi 1355 44 NPS Page 217 of 812 Effective Date: 2019-05-31

219 Table of Contents BS & B Safety Systems, LLC (BSB) 78184 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series PLDV 78184 or catalog number Number: FA-*, FF-*, UA-2, -3, -5, -6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on August 20, 2015 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 6.0 Unitless Certified Value: Air/Gas Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: (none) Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Code Section Outlet Size Inlet Size Media Set Pressure Range VIII Div. 1 0.57 sq in 1 NPS 230 - 1000 psi VIII Div. 1 105 - 700 psi 1.44 sq in 1.5 NPS VIII Div. 1 2 NPS 2.24 sq in 75 - 555 psi VIII Div. 1 3 NPS 5.41 sq in 45 - 450 psi VIII Div. 1 9.62 sq in 4 NPS 35 - 415 psi VIII Div. 1 45 - 320 psi 6 NPS 23.76 sq in VIII Div. 1 55 - 295 psi 44.18 sq in 8 NPS VIII Div. 1 10 NPS 35 - 240 psi 70.88 sq in VIII Div. 1 30 - 200 psi 101.5 sq in 12 NPS VIII Div. 1 14 NPS 130.3 sq in 30 - 170 psi VIII Div. 1 176.7 sq in 16 NPS 25 - 150 psi VIII Div. 1 25 - 150 psi 202.3 sq in 18 NPS VIII Div. 1 25 - 150 psi 270 sq in 20 NPS VIII Div. 1 25 - 150 psi 375 sq in 24 NPS VIII Div. 1 28 NPS 575 sq in 15 - 150 psi VIII Div. 1 650 sq in 30 NPS 15 - 150 psi VIII Div. 1 15 - 150 psi 900 sq in 36 NPS VIII Div. 1 40 NPS 15 - 150 psi 1100 sq in VIII Div. 1 15 - 150 psi 1200 sq in 42 NPS VIII Div. 1 44 NPS 1300 sq in 15 - 150 psi Certification Design Series GCR-S, SE, SM, SS, SES, SMS, SW, N, NS (liquids) 78195 or catalog number Number: GR-C, FM-C (not req'd for SM) Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on October 05, 2015 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 2.75 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Set Pressure Range Lift Outlet Size Inlet Size Media Code Section VIII Div. 1 10 - 300 psi 1.5 NPS 1.5 sq in VIII Div. 1 10 - 175 psi 5.29 sq in 3 NPS VIII Div. 1 9.78 sq in 10 - 150 psi 4 NPS VIII Div. 1 6 NPS 22.5 sq in 10 - 75 psi Page 218 of 812 Effective Date: 2019-05-31

220 Table of Contents BS & B Safety Systems, LLC (BSB) 78207 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series GCR-S,SE,SM,SS,SES,SMS, SW, N, NS (2" liquids) 78207 Number: or catalog number GR-C, FM-C, not req'd for -SM Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on June 25, 2015 Capacity Tests: Resistance Factor, 1 Size, Krl Method of Establishing Relieving Capacity: 1.42 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Water 2.7 sq in 10 - 300 psi 2 NPS Design Series Certification ECV 78274 or catalog number Number: EC-7RS, EC-7FS, EC-7R Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on May 19, 2016 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 4.18 Unitless Certified Value: Air Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size VIII Div. 1 8 - 15 psi 0.735 sq in 1 NPS VIII Div. 1 1.24 sq in 1.5 NPS 5 - 15 psi VIII Div. 1 2 NPS 2.21 sq in 3 - 15 psi VIII Div. 1 2 - 15 psi 4.76 sq in 3 NPS VIII Div. 1 4 NPS 1 - 15 psi 7.9 sq in VIII Div. 1 1 - 15 psi 18.1 sq in 6 NPS VIII Div. 1 8 NPS 31.4 sq in 1 - 15 psi VIII Div. 1 48.8 sq in 10 NPS 1 - 15 psi VIII Div. 1 1 - 15 psi 69.4 sq in 12 NPS VIII Div. 1 1 - 15 psi 14 NPS 88 sq in VIII Div. 1 16 NPS 115 sq in 1 - 15 psi VIII Div. 1 1 - 15 psi 18 NPS 146 sq in VIII Div. 1 20 NPS 1 - 15 psi 180 sq in VIII Div. 1 1 - 15 psi 261 sq in 24 NPS Page 219 of 812 Effective Date: 2019-05-31

221 Table of Contents BS & B Safety Systems, LLC (BSB) 78285 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series AV-E, AV-EL 78285 Number: or catalog number AV7R, AV-1, -2, -3, -4, -5, -6, -7, -8, -9 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on December 02, 2016 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.2 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Set Pressure Range Flow Area Media Code Section Lift VIII Div. 1 0.864 sq in 18 - 150 psi 1 NPS VIII Div. 1 15 - 150 psi 1.25 NPS 1.4 sq in VIII Div. 1 15 - 150 psi 2.036 sq in 1.5 NPS VIII Div. 1 2 NPS 3.356 sq in 12 - 150 psi VIII Div. 1 10 - 150 psi 2.5 NPS 4.787 sq in VIII Div. 1 3 NPS 7.392 sq in 8 - 150 psi VIII Div. 1 4 NPS 4 - 150 psi 12.73 sq in VIII Div. 1 20 sq in 5 NPS 3 - 100 psi VIII Div. 1 6 NPS 2 - 100 psi 28.89 sq in VIII Div. 1 50.02 sq in 2 - 100 psi 8 NPS VIII Div. 1 10 NPS 78.85 sq in 1 - 60 psi VIII Div. 1 113.1 sq in 12 NPS 1 - 60 psi VIII Div. 1 1 - 60 psi 14 NPS 137.9 sq in VIII Div. 1 1 - 60 psi 182.7 sq in 16 NPS VIII Div. 1 233.7 sq in 18 NPS .8 - 60 psi VIII Div. 1 20 NPS .6 - 60 psi 291 sq in VIII Div. 1 .5 - 60 psi 354.7 sq in 22 NPS VIII Div. 1 424.6 sq in .5 - 60 psi 24 NPS VIII Div. 1 .5 - 40 psi 500.7 sq in 26 NPS VIII Div. 1 .5 - 40 psi 583.2 sq in 28 NPS VIII Div. 1 30 NPS 672 sq in .5 - 40 psi VIII Div. 1 .35 - 40 psi 767 sq in 32 NPS VIII Div. 1 .35 - 40 psi 868.3 sq in 34 NPS VIII Div. 1 .25 - 40 psi 36 NPS 975.9 sq in VIII Div. 1 38 NPS 1090 sq in .25 - 40 psi VIII Div. 1 .25 - 40 psi 40 NPS 1210 sq in VIII Div. 1 42 NPS 1336 sq in .25 - 40 psi VIII Div. 1 .25 - 40 psi 44 NPS 1469 sq in VIII Div. 1 46 NPS 1608 sq in .25 - 40 psi VIII Div. 1 .25 - 40 psi 48 NPS 1753 sq in Page 220 of 812 Effective Date: 2019-05-31

222 Table of Contents BS & B Safety Systems, LLC (BSB) 78364 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series AVV 78364 Number: or catalog number AV-75 (optional) Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on March 17, 2017 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 10.5 Unitless Certified Value: Steam, Air/Gas & Liquid Test Medium: Steam, Air/Gas & Liquid Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: (none) Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Inlet Size Flow Area Outlet Size Code Section Media Set Pressure Range VIII Div. 1 1 in 0.4 sq in 10 - 150 psi VIII Div. 1 7 - 150 psi 1.5 in 0.95 sq in VIII Div. 1 5 - 150 psi 2 in 1.6 sq in VIII Div. 1 3 in 4 sq in 4 - 150 psi VIII Div. 1 2 - 150 psi 4 in 8 sq in VIII Div. 1 6 in 16.5 sq in 1 - 100 psi VIII Div. 1 8 in 1 - 100 psi 35.75 sq in VIII Div. 1 45.5 sq in 10 in 0.6 - 60 psi VIII Div. 1 62.75 sq in 0.6 - 60 psi 12 in VIII Div. 1 0.6 - 60 psi 74.5 sq in 14 in VIII Div. 1 16 in 111 sq in 0.6 - 60 psi VIII Div. 1 0.5 - 60 psi 158 sq in 18 in VIII Div. 1 0.5 - 60 psi 195 sq in 20 in VIII Div. 1 0.5 - 60 psi 24 in 280 sq in VIII Div. 1 0.5 - 60 psi 382 sq in 28 in VIII Div. 1 425 sq in 30 in 0.5 - 60 psi VIII Div. 1 0.35 - 40 psi 32 in 500 sq in VIII Div. 1 36 in 630 sq in 0.25 - 40 psi VIII Div. 1 40 in 780 sq in 0.25 - 40 psi VIII Div. 1 945 sq in 44 in 0.25 - 40 psi VIII Div. 1 48 in 1125 sq in 0.25 - 40 psi Certification Design Series Welded QRB 78375 or catalog number Number: Integral Holder Designation: Rupture Disk Device Type Classification: Control Script failed for control txtCoc , Source= Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.85 Unitless Certified Value: Air Test Medium: Air/Gas Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Inlet Size Set Pressure Range Lift Media VIII Div. 1 800 - 16000 psi 0.049 sq in 0.25 NPS VIII Div. 1 800 - 14000 psi 0.375 NPS 0.11 sq in VIII Div. 1 500 - 10500 psi 0.5 NPS 0.19 sq in VIII Div. 1 350 - 3000 psi 0.44 sq in 0.75 NPS Page 221 of 812 Effective Date: 2019-05-31

223 Table of Contents BS & B Safety Systems, LLC (BSB) 84046 NB#: 7455 East 46th Street, Tulsa, OK 74145 United States location: Acceptable Abbrev.: BSB Certification Design Series Scored B, SCD B, XB 84046 Number: or catalog number NF-7R, NF-7RS, NF-7FS, FF-*, FA-* Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on February 13, 2013 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 0.40 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section Media VIII Div. 1 1 NPS 1 NPS 0.86 sq in 250 - 6000 psi VIII Div. 1 1.5 NPS 1.5 NPS 2.04 sq in 200 - 6000 psi VIII Div. 1 2 NPS 175 - 6000 psi 3.35 sq in 2 NPS VIII Div. 1 7.4 sq in 3 NPS 3 NPS 150 - 6000 psi VIII Div. 1 4 NPS 4 NPS 12.73 sq in 135 - 6000 psi VIII Div. 1 125 - 6000 psi 28.99 sq in 6 NPS 6 NPS VIII Div. 1 50 sq in 8 NPS 110 - 4000 psi 8 NPS VIII Div. 1 78.9 sq in 10 NPS 10 NPS 100 - 3200 psi VIII Div. 1 90 - 1250 psi 113.1 sq in 12 NPS 12 NPS VIII Div. 1 14 NPS 137.9 sq in 80 - 1000 psi 14 NPS VIII Div. 1 182.6 sq in 16 NPS 16 NPS 75 - 800 psi VIII Div. 1 18 NPS 18 NPS 233.7 sq in 70 - 600 psi VIII Div. 1 65 - 500 psi 291.1 sq in 20 NPS 20 NPS VIII Div. 1 60 - 250 psi 24 NPS 24 NPS 424.6 sq in Page 222 of 812 Effective Date: 2019-05-31

224 Table of Contents BS & B Safety Systems, Ltd. (BSI) 77149 NB#: Raheen Business Park, Limerick Ireland location: BS & B Safety Systems, Ltd. (BSI) Raheen Business Park, Limerick Ireland location: Certification Design Series XT 77149 Number: or catalog number NX-7R, NF-7R, NF-7RS, TL-7R, TLP-7R Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on August 01, 2006 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.5 Unitless Certified Value: Air Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Lift Inlet Size Flow Area VIII Div. 1 0.86 sq in 1 in 80 - 1450 psi in VIII Div. 1 1.5 in in 2.03 sq in 55 - 1450 psi VIII Div. 1 2 in in 3.36 sq in 45 - 1450 psi VIII Div. 1 45 - 1300 psi 7.39 sq in in 3 in VIII Div. 1 in 12.7 sq in 40 - 1150 psi 4 in VIII Div. 1 40 - 1040 psi 28.8 sq in in 6 in VIII Div. 1 40 - 960 psi 50 sq in in 8 in VIII Div. 1 60 - 840 psi 78.8 sq in in 10 in VIII Div. 1 60 - 720 psi 111 sq in in 12 in Design Series Certification SKR, SKR Welded Assembly 77161 Number: or catalog number SRB-7RS, SRB-7RS-TR, S90-7R, SRB-7FS, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on April 24, 1999 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .37 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Media Inlet Size Outlet Size VIII Div. 1 55 - 500 psi 0.59 sq in 0.75 NPS VIII Div. 1 55 - 500 psi 0.86 sq in 1 NPS VIII Div. 1 2.04 sq in 40 - 500 psi 1.5 NPS VIII Div. 1 25 - 500 psi 3.36 sq in 2 NPS VIII Div. 1 20 - 500 psi 7.39 sq in 3 NPS VIII Div. 1 4 NPS 16 - 500 psi 12.74 sq in VIII Div. 1 15 - 261 psi 28.89 sq in 6 NPS VIII Div. 1 8 NPS 50 sq in 15 - 200 psi VIII Div. 1 78.86 sq in 15 - 150 psi 10 NPS VIII Div. 1 9 - 110 psi 111.87 sq in 12 NPS Page 223 of 812 Effective Date: 2019-05-31

225 Table of Contents BS & B Safety Systems, Ltd. (BSI) 77183 NB#: Raheen Business Park, Limerick Ireland location: Certification Design Series CL 77183 Number: or catalog number NX7R, NXV7R Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on July 21, 2006 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.75 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Inlet Size Code Section Media Set Pressure Range Lift Flow Area VIII Div. 1 Water 0.86 sq in 1 in 14 - 188 psi in VIII Div. 1 1.5 in in 2.03 sq in 12 - 135 psi VIII Div. 1 2 in in 3.35 sq in 7 - 113 psi VIII Div. 1 7.39 sq in 3 in in 5 - 90 psi VIII Div. 1 5 - 75 psi 4 in in 12.7 sq in VIII Div. 1 in 28.8 sq in 6 in 3 - 60 psi VIII Div. 1 8 in in 50 sq in 3 - 53 psi Certification Design Series SKR, SKR Welded Assemly (Liquids) 77329 or catalog number Number: S90-7R, SRB-7RS, SRB-7RS-TR, SRB-7FS, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on April 30, 1999 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 1.9 Unitless Certified Value: Air/Gas Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Flow Area Code Section Outlet Size Inlet Size Lift Media VIII Div. 1 0.75 NPS 0.59 sq in 55 - 500 psi VIII Div. 1 55 - 500 psi 1 NPS 0.86 sq in VIII Div. 1 2.04 sq in 40 - 500 psi 1.5 NPS VIII Div. 1 3.36 sq in 25 - 500 psi 2 NPS VIII Div. 1 20 - 500 psi 7.39 sq in 3 NPS VIII Div. 1 16 - 500 psi 4 NPS 12.74 sq in VIII Div. 1 6 NPS 15 - 261 psi 28.89 sq in VIII Div. 1 15 - 200 psi 50 sq in 8 NPS VIII Div. 1 15 - 150 psi 78.86 sq in 10 NPS VIII Div. 1 9 - 110 psi 99.1 sq in 12 NPS Page 224 of 812 Effective Date: 2019-05-31

226 Table of Contents BS & B Safety Systems, Ltd. (BSI) 77464 NB#: Raheen Business Park, Limerick Ireland location: Certification Design Series SIGMA, SIGMA EXL, UBR 77464 or catalog number Number: SRB-7RS, SRB-7RS-TR, SRB-7FS, SR-7R, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on July 28, 2000 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.38 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Outlet Size Media Code Section Inlet Size Set Pressure Range VIII Div. 1 1 NPS 0.86 sq in 30 - 500 psi 1 NPS VIII Air 1.5 NPS 1.5 NPS 25 - 450 psi 1.93 sq in VIII Air 25 - 400 psi 2 NPS 2 NPS 3.36 sq in VIII Air 3 NPS 3 NPS 7.39 sq in 20 - 400 psi VIII Air 12.74 sq in 4 NPS 4 NPS 16 - 400 psi VIII Air 15 - 225 psi 28.89 sq in 6 NPS 6 NPS VIII Air 8 NPS 8 NPS 15 - 125 psi 50 sq in VIII Div. 1 Air 15 - 100 psi 78.86 sq in 10 NPS 10 Design Series Certification SIGMA, SIGMA EXL, UBR (liquid) 77475 or catalog number Number: SRB-7RS, SRB-7RS-TR, SRB-7FS, SRB-7R, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on July 28, 2000 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 1.25 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Set Pressure Range Outlet Size Inlet Size Media Flow Area VIII Div. 1 30 - 500 psi 0.86 sq in 1 NPS 1 NPS VIII Water 1.76 sq in 25 - 750 psi 1.5 NPS 1.5 NPS VIII Water 25 - 400 psi 3.36 sq in 2 NPS 2 NPS VIII Water 3 NPS 20 - 400 psi 3 NPS 6.33 sq in VIII Water 4 NPS 4 NPS 10.81 sq in 16 - 400 psi VIII Water 20.89 sq in 6 NPS 15 - 225 psi 6 NPS VIII Water 15 - 125 psi 50 sq in 8 NPS 8 NPS VIII Div. 1 Water 10 NPS 10 NPS 78.86 sq in 15 - 100 psi Design Series Certification Skr-U 1/2" 77509 Number: or catalog number UR-2, UR-6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 15, 2000 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 0.85 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size VIII Div. 1 55 - 500 psi 0.304 sq in .5 NPS 0.5 NPS Page 225 of 812 Effective Date: 2019-05-31

227 Table of Contents BS & B Safety Systems, Ltd. (BSI) 77510 NB#: Raheen Business Park, Limerick Ireland location: Certification Design Series SKr-U 3/4" 77510 Number: or catalog number UR-2, UR-6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on July 26, 2000 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 0.73 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size Media VIII Div. 1 55 - 500 psi 0.533 sq in 0.75 NPS .75 NPS Design Series Certification SKr-U 1" 77521 or catalog number Number: UR-2, UR-6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on July 24, 2000 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 1.25 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Outlet Size Media Inlet Size VIII Div. 1 55 - 500 psi 0.608 sq in 1 NPS Certification Design Series SKr-U 3/4" Liquid 77543 Number: or catalog number UR-2, UR-6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on July 26, 2000 Capacity Tests: Resistance Factor, 1 Size, Krl Method of Establishing Relieving Capacity: 1.10 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size VIII Div. 1 .75 NPS 55 - 500 psi 0.533 sq in 0.75 NPS Certification Design Series SKr-U 1" Liquid 77554 Number: or catalog number UR-2, UR-6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on July 24, 2000 Capacity Tests: Resistance Factor, 1 Size, Krl Method of Establishing Relieving Capacity: 2.20 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Flow Area Code Section Outlet Size VIII Div. 1 55 - 500 psi 0.608 sq in 1 NPS Page 226 of 812 Effective Date: 2019-05-31

228 Table of Contents BS & B Safety Systems, Ltd. (BSI) 77655 NB#: Raheen Business Park, Limerick Ireland location: Certification Design Series MVB Cassette 77655 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on July 11, 2001 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: .232 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size VIII Div. 1 Air 3 NPS 7.39 sq in 80 - 400 psi Certification Design Series LPS, LPS Welded Assembly 77745 or catalog number Number: SRB-7RS, SRB-7FS, SR-7R, SMR-7R, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on August 20, 2002 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.79 Unitless Certified Value: Air or gases (Krg) Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Lift Inlet Size Set Pressure Range Media Code Section VIII Div. 1 0.59 sq in 15 - 70 psi 0.75 NPS VIII Div. 1 15 - 70 psi 0.86 sq in 1 NPS VIII Div. 1 1.93 sq in 1.5 NPS 6 - 55 psi VIII Div. 1 5 - 40 psi 2 NPS 3.36 sq in VIII Div. 1 5 - 50 psi 3 NPS 7.39 sq in VIII Div. 1 4 NPS 12.74 sq in 5 - 30 psi VIII Div. 1 5 - 25 psi 28.89 sq in 6 NPS VIII Div. 1 8 NPS 50 sq in 5 - 25 psi VIII Div. 1 10 NPS 78.86 sq in 5 - 25 psi VIII Div. 1 Air 5 - 25 psi 12 NPS 111.87 sq in Page 227 of 812 Effective Date: 2019-05-31

229 Table of Contents BS & B Safety Systems, Ltd. (BSI) 77756 NB#: Raheen Business Park, Limerick Ireland location: Certification Design Series LPS, LPS Welded Assembly (liquid) 77756 Number: or catalog number SRB-7RS, SRB-7FS, SR-7R, SMR-7R, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on August 20, 2002 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 0.86 Unitless Certified Value: Liquid (Krl) Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size Media VIII Div. 1 Water 15 - 70 psi 0.59 sq in 0.75 NPS 0.75 NPS VIII Div. 1 15 - 70 psi 1 NPS 0.86 sq in VIII Div. 1 6 - 55 psi 1.5 NPS 1.93 sq in VIII Div. 1 3.36 sq in 2 NPS 5 - 40 psi VIII Div. 1 5 - 50 psi 3 NPS 7.39 sq in VIII Div. 1 5 - 30 psi 12.74 sq in 4 NPS VIII Div. 1 5 - 25 psi 28.89 sq in 6 NPS VIII Div. 1 5 - 25 psi 8 NPS 50 sq in VIII Div. 1 5 - 25 psi 78.86 sq in 10 NPS VIII Div. 1 Water 5 - 25 psi 12 NPS 111.87 sq in Design Series Certification SRC 77767 Number: or catalog number None Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on August 26, 2002 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.1 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Set Pressure Range Lift Flow Area Inlet Size Media VIII Div. 1 75 - 400 psi 3.35 sq in 2 NPS VIII Div. 1 7.39 sq in 60 - 400 psi 3 NPS VIII Div. 1 4 NPS 12.7 sq in 50 - 400 psi VIII Div. 1 5 NPS 20 sq in 50 - 350 psi VIII Div. 1 6 N/A 92 - 350 psi [SPL] 141.5 mm 22.85 sq in VIII Div. 1 50 - 350 psi 28.8 sq in 6 NPS VIII Div. 1 50 sq in 50 - 350 psi 8 NPS Page 228 of 812 Effective Date: 2019-05-31

230 Table of Contents BS & B Safety Systems, Ltd. (BSI) 77790 NB#: Raheen Business Park, Limerick Ireland location: Certification Design Series GLP-S 77790 Number: or catalog number LP-C Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on July 30, 2003 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 10. Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Code Section Media VIII Div. 1 15 - 70 psi 1.5 NPS 0.86 sq in VIII Div. 1 1.93 sq in 2 NPS 6 - 55 psi VIII Div. 1 5 - 40 psi 3 NPS 3.36 sq in VIII Div. 1 7.39 sq in 5 - 35 psi 4 NPS Certification Design Series SSR (liquid) 77958 Number: or catalog number SRB-7RS, SRB-7RS-TR, SMR-7R, SPR-7R, S90-7R, SRB-7FS, SR-7R, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on March 28, 2006 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 0.52 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Outlet Size Inlet Size Code Section Flow Area Set Pressure Range Media VIII Div. 1 1 NPS 0.86 sq in 55 - 350 psi VIII Div. 1 1.93 sq in 40 - 350 psi 1.5 NPS VIII Div. 1 3.36 sq in 25 - 300 psi 2 NPS VIII Div. 1 7.39 sq in 20 - 250 psi 3 NPS VIII Div. 1 12.74 sq in 16 - 250 psi 4 NPS VIII Div. 1 28.89 sq in 6 NPS 15 - 250 psi VIII Div. 1 15 - 200 psi 8 NPS 50 sq in VIII Div. 1 15 - 150 psi 78.8 sq in 10 NPS Page 229 of 812 Effective Date: 2019-05-31

231 Table of Contents BS & B Safety Systems, Ltd. (BSI) 77969 NB#: Raheen Business Park, Limerick Ireland location: Certification Design Series SSR 77969 or catalog number Number: SRB-7RS, SRB-7RS-TR, SPR-7R, SMR-7R, S90-7R, SRB-7FS, SR-7R, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on March 28, 2006 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.52 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size Media VIII Div. 1 0.86 sq in 1 NPS 55 - 350 psi VIII Div. 1 40 - 350 psi 1.93 sq in 1.5 NPS VIII Div. 1 2 NPS 3.36 sq in 25 - 300 psi VIII Div. 1 3 NPS 7.39 sq in 20 - 250 psi VIII Div. 1 16 - 250 psi 4 NPS 12.74 sq in VIII Div. 1 15 - 250 psi 28.89 sq in 6 NPS VIII Div. 1 8 NPS 50 sq in 15 - 200 psi VIII Div. 1 78.8 sq in 10 NPS 15 - 150 psi Certification Design Series XT (Liquid) 78094 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on February 13, 2013 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 0.5 Unitless Certified Value: Liquid (Krl) Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Lift Set Pressure Range Media Outlet Size Code Section Inlet Size VIII Div. 1 Water 1 NPS 250 - 1450 psi 0.88 sq in 1 VIII Div. 1 Water 1.5 NPS 1.5 2.03 sq in 150 - 1450 psi VIII Div. 1 Water 2 NPS 2 3.36 sq in 150 - 1450 psi VIII Div. 1 Water 150 - 1300 psi 7.39 sq in 3 3 NPS VIII Div. 1 Water 4 NPS 4 12.7 sq in 80 - 1150 psi VIII Div. 1 Water 6 NPS 6 28.8 sq in 70 - 1040 psi VIII Div. 1 Water 60 - 960 psi 8 NPS 50 sq in 8 VIII Div. 1 Water 60 - 840 psi 78.8 sq in 10 10 NPS VIII Div. 1 Water 12 NPS 12 111 sq in 60 - 720 psi Page 230 of 812 Effective Date: 2019-05-31

232 Table of Contents BS & B Safety Systems, Ltd. (BSI) 78106 NB#: Raheen Business Park, Limerick Ireland location: Certification Design Series SKr DD 78106 Number: or catalog number S90-7R DD, SRB-7RS DD, SRB-7RS-TR DD, SRB-7FS DD Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 26, 2013 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .63 Unitless Certified Value: Air Test Medium: Air/Gas Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: (none) Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size Media VIII Div. 1 Air 0.59 sq in 0.75 NPS 55 - 500 psi VIII Div. 1 Air 0.86 sq in 55 - 500 psi 1 NPS VIII Div. 1 Air 1.5 NPS 2.04 sq in 40 - 500 psi VIII Div. 1 Air 2 NPS 3.36 sq in 25 - 500 psi VIII Div. 1 Air 3 NPS 7.39 sq in 20 - 500 psi VIII Div. 1 Air 4 NPS 12.74 sq in 16 - 500 psi VIII Div. 1 Air 15 - 261 psi 28.89 sq in 6 NPS VIII Div. 1 Air 8 NPS 50 sq in 15 - 200 psi VIII Div. 1 Air 15 - 150 psi 10 NPS 78.86 sq in Design Series Certification SKr DD (Liquid) 78117 or catalog number Number: S90-7R DD, SRB-7RS DD, SRB-7RS-TR DD, SRB-7FS DD Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 26, 2013 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 1.6 Unitless Certified Value: Liquid Test Medium: Liquid Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Inlet Size Flow Area Media Code Section Lift Set Pressure Range VIII Div. 1 Water 0.75 NPS 0.59 sq in 55 - 500 psi VIII Div. 1 Water 1 NPS 0.86 sq in 55 - 500 psi VIII Div. 1 Water 2.04 sq in 40 - 500 psi 1.5 NPS VIII Div. 1 Water 25 - 500 psi 2 NPS 3.36 sq in VIII Div. 1 Water 20 - 500 psi 3 NPS 7.39 sq in VIII Div. 1 Water 12.74 sq in 16 - 500 psi 4 NPS VIII Div. 1 Water 15 - 261 psi 28.89 sq in 6 NPS VIII Div. 1 Water 15 - 200 psi 50 sq in 8 NPS VIII Div. 1 Water 78.86 sq in 10 NPS 15 - 150 psi Page 231 of 812 Effective Date: 2019-05-31

233 Table of Contents BS & B Safety Systems, Ltd. (BSI) 78128 NB#: Raheen Business Park, Limerick Ireland location: Certification Design Series 1.5" SLP-S, SLP-SE, SLP-SM, SLP-N, SLP-SS, SLP-SES, SLP-SMS, SLP-NS 78128 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 12, 2014 Capacity Tests: Resistance Factor, 1 Size, Krgl Method of Establishing Relieving Capacity: 6.7 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Div. 1 15 - 70 psi 1.5 NPS 1.08 sq in Design Series Certification 2" SLP-S, SLP-SE, SLP-SM, SLP-N, SLP-SS, SLP-SES, SLP-SMS, SLP-NS 78139 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 12, 2014 Capacity Tests: Resistance Factor, 1 Size, Krgl Method of Establishing Relieving Capacity: 4.9 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Set Pressure Range Outlet Size Inlet Size Flow Area Media VIII Div. 1 2 NPS 2.04 sq in 6 - 55 psi Design Series Certification 3" SLP-S, SLP-SE, SLP-SM, SLP-N, SLP-SS, SLP-SES, SLP-SMS, SLP-NS 78140 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on September 12, 2014 Capacity Tests: Resistance Factor, 1 Size, Krgl Method of Establishing Relieving Capacity: 9.9 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size Media VIII Div. 1 3.55 sq in 5 - 40 psi 3 NPS Page 232 of 812 Effective Date: 2019-05-31

234 Table of Contents BS & B Safety Systems, Ltd. (BSI) 78229 NB#: Raheen Business Park, Limerick Ireland location: Certification Design Series SRD & CCS 78229 Number: or catalog number SRB-7RS, SRB-7RS-TR, SRB-7FS, SMR-7R, SR-7R, SPR-7R, S90-7R, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on May 19, 2016 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .59 Unitless Certified Value: Air Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Code Section Media VIII Div. 1 481 - 750 psi 1 NPS 0.84 sq in VIII Div. 1 1.77 sq in 1.5 NPS 421 - 600 psi VIII Div. 1 421 - 500 psi 3.23 sq in 2 NPS VIII Div. 1 281 - 500 psi 3 NPS 6.44 sq in VIII Div. 1 271 - 500 psi 11.54 sq in 4 NPS VIII Div. 1 101 - 200 psi 26.44 sq in 6 NPS VIII Div. 1 76 - 150 psi 8 NPS 47.07 sq in Certification Design Series SRD & CCS (Liquid) 78230 Number: or catalog number SRB-7RS, SRB-7RS-TR, SRB-7FS, SMR-7R, SR-7R, SPR-7R, S90-7R, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on May 19, 2016 Capacity Tests: Resistance Factor, 1 Size, Krl Method of Establishing Relieving Capacity: 4.0 Unitless Certified Value: Air Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Media Code Section Set Pressure Range Inlet Size Lift Flow Area VIII Div. 1 0.84 sq in 481 - 750 psi 1 NPS VIII Div. 1 1.77 sq in 421 - 600 psi 1.5 NPS VIII Div. 1 2 NPS 3.23 sq in 421 - 500 psi VIII Div. 1 3 NPS 6.44 sq in 281 - 500 psi VIII Div. 1 4 NPS 271 - 500 psi 11.54 sq in VIII Div. 1 101 - 200 psi 26.44 sq in 6 NPS VIII Div. 1 47.07 sq in 76 - 150 psi 8 NPS Page 233 of 812 Effective Date: 2019-05-31

235 Table of Contents BS & B Safety Systems, Ltd. (BSI) 78241 NB#: Raheen Business Park, Limerick Ireland location: Certification Design Series SRD-L & CCS-L 78241 Number: or catalog number SRB-7RS, SRB-7RS-TR, SRB-7FS, SMR-7R, SR-7R, SPR-7R, S90-7R, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on May 19, 2016 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 3.4 Unitless Certified Value: Air Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section Media VIII Div. 1 75 - 480 psi 1 NPS 0.84 sq in VIII Div. 1 75 - 420 psi 1.5 NPS 1.77 sq in VIII Div. 1 3.23 sq in 75 - 420 psi 2 NPS VIII Div. 1 45 - 280 psi 3 NPS 6.44 sq in VIII Div. 1 4 NPS 11.54 sq in 20 - 270 psi VIII Div. 1 26.44 sq in 6 NPS 20 - 100 psi VIII Div. 1 15 - 75 psi 8 NPS 47.07 sq in Certification Design Series SRD-L & CCS-L (Liquid) 78252 or catalog number Number: SRB-7RS, SRB-7RS-TR, SRB-7FS, SMR-7R, SR-7R, SPR-7R, S90-7R, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on May 19, 2016 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 4.5 Unitless Certified Value: Air Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Set Pressure Range Outlet Size Inlet Size Media Flow Area VIII Div. 1 1 NPS 75 - 480 psi 0.84 sq in VIII Div. 1 1.77 sq in 1.5 NPS 75 - 420 psi VIII Div. 1 2 NPS 75 - 420 psi 3.23 sq in VIII Div. 1 45 - 280 psi 3 NPS 6.44 sq in VIII Div. 1 4 NPS 11.54 sq in 20 - 270 psi VIII Div. 1 6 NPS 26.44 sq in 20 - 100 psi VIII Div. 1 15 - 75 psi 47.07 sq in 8 NPS Certification Design Series LPS-U 0.5" 78308 or catalog number Number: UR-2, UR-6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on February 27, 2017 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 1.06 Unitless Certified Value: Air Test Medium: Air/Gas Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Flow Area Code Section Outlet Size VIII Div. 1 Air 15 - 70 psi 0.304 sq in 0.500 in 0.5 in Page 234 of 812 Effective Date: 2019-05-31

236 Table of Contents BS & B Safety Systems, Ltd. (BSI) 78319 NB#: Raheen Business Park, Limerick Ireland location: Certification Design Series LPS-U 0.5" (Liquid) 78319 Number: or catalog number UR-2, UR-6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on February 27, 2017 Capacity Tests: Resistance Factor, 1 Size, Krl Method of Establishing Relieving Capacity: 1.22 Unitless Certified Value: Air Test Medium: Liquid Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media Code Section VIII Div. 1 Water 0.500 in 0.5 in 0.304 sq in 15 - 70 psi Certification Design Series LPS-U 0.75" 78320 Number: or catalog number UR-2, UR-6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on February 27, 2017 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 0.89 Unitless Certified Value: Air Test Medium: Air Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Lift Outlet Size Inlet Size Flow Area Set Pressure Range VIII Div. 1 Air 0.75 in 0.75 in 0.533 sq in 15 - 70 psi Certification Design Series LPS-U 0.75" 78331 or catalog number Number: UR-2, UR-6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on February 27, 2017 Capacity Tests: Resistance Factor, 1 Size, Krl Method of Establishing Relieving Capacity: 0.93 Unitless Certified Value: Air Test Medium: Liquid Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Code Section Media Outlet Size Lift Set Pressure Range Inlet Size VIII Div. 1 Water 0.75 in 0.750 in 0.533 sq in 15 - 70 psi Page 235 of 812 Effective Date: 2019-05-31

237 Table of Contents BS & B Safety Systems, Ltd. (BSI) 78342 NB#: Raheen Business Park, Limerick Ireland location: Certification Design Series LPS-U 1.0" 78342 or catalog number Number: UR-2, UR-6 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on February 27, 2017 Capacity Tests: Resistance Factor, 1 Size, Krgl Method of Establishing Relieving Capacity: 1.70 Unitless Certified Value: Air Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Lift Outlet Size Inlet Size Code Section Set Pressure Range Flow Area VIII Div. 1 Air 1.0 in 1 in 0.608 sq in 15 - 70 psi Design Series Certification SKI 78410 or catalog number Number: SRB-7RS, SRB-7RS-TR, SRB-7FS, SRB-7FS-TR, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on June 04, 2018 Capacity Tests: Resistance Factor, 1 Size, Krg Method of Establishing Relieving Capacity: 0.47 Unitless Certified Value: Air Test Medium: Air/Gas Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Set Pressure Range Inlet Size Lift Media VIII Div. 1 Air 60 - 500 psi 0.86 sq in 1.0 in 1 in VIII Div. 1 Air 1.5 in 1.93 sq in 45 - 500 psi 1.5 in VIII Div. 1 Air 2 in 2.0 in 30 - 500 psi 3.36 sq in VIII Div. 1 Air 25 - 500 psi 3 in 3.0 in 7.39 sq in VIII Div. 1 Air 4 in 4.0 in 12.74 sq in 20 - 500 psi VIII Div. 1 Air 20 - 261 psi 28.89 sq in 6.0 in 6 in VIII Div. 1 Air 8.0 in 8 in 20 - 200 psi 50 sq in Certification Design Series SKI (Liquid) 78421 Number: or catalog number SRB-7RS, SRB-7RS-TR, SRB-7FS, SRB-7FS-TR, SRI-7RS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at BS & B on June 04, 2018 Capacity Tests: Resistance Factor, 1 Size, Krl Method of Establishing Relieving Capacity: 1.03 Unitless Certified Value: Liquid Test Medium: Liquid Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Inlet Size Lift Set Pressure Range Media Code Section Outlet Size VIII Div. 1 Water 60 - 500 psi 0.86 sq in 1.0 in 1 in VIII Div. 1 Water 1.5 in 1.5 in 1.93 sq in 45 - 500 psi VIII Div. 1 Water 30 - 500 psi 3.36 sq in 2.0 in 2 in VIII Div. 1 Water 3.0 in 3 in 25 - 500 psi 7.39 sq in VIII Div. 1 Water 4 in 4.0 in 12.74 sq in 20 - 500 psi VIII Div. 1 Water 28.89 sq in 6 in 20 - 261 psi 6.0 in VIII Div. 1 Water 20 - 200 psi 50 sq in 8.0 in 8 in Page 236 of 812 Effective Date: 2019-05-31

238 Table of Contents Burns Pressure Systems Enterprises, Incorporated (BPS) 05005 NB#: 304 North Walnut Ave., Broken Arrow, OK 74012 United States location: Acceptable Abbrev.: BPS, INC. Page 237 of 812 Effective Date: 2019-05-31

239 Table of Contents Burns Pressure Systems Enterprises, Incorporated (BPS) 05005 NB#: 304 North Walnut Ave., Broken Arrow, OK 74012 United States location: Acceptable Abbrev.: BPS, INC. Burns Pressure Systems Enterprises, Incorporated (BPS) 304 North Walnut Ave., Broken Arrow, OK 74012 United States location: Acceptable Abbrev.: BPS, INC. Certification Design Series 2MBF 05005 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Kunkle (Fort Wayne, IN) on November 14, 1990 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 11.46 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Inlet Size Code Section Flow Area Outlet Size Set Pressure Range Lift VIII Div. 1 Air Top 2 NPS 1.1 in 50 - 500 psi Design Series Certification 3MBF/ MBP-2 05016 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Kunkle (Fort Wayne, IN) on November 14, 1990 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 29.7 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 100 - 500 psi 1.85 in Top 2 NPS VIII Div. 1 Air Top 3 NPS 1.85 in 15 - 500 psi Design Series Certification 4 MBF/4 MRB/ 4 MBF-A 05027 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 12, 1992 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 49.1 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Media Code Section Set Pressure Range VIII Div. 1 Air 15 - 500 psi 2.7 in Top 4 NPS Page 238 of 812 Effective Date: 2019-05-31

240 Table of Contents Burns Pressure Systems Enterprises, Incorporated (BPS) 05050 NB#: 304 North Walnut Ave., Broken Arrow, OK 74012 United States location: Acceptable Abbrev.: BPS, INC. Certification Design Series 1 1/4" MBP 05050 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 11, 2000 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 13.508 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Lift Code Section Media Outlet Size Inlet Size Set Pressure Range VIII Div. 1 Air 100 - 325 psi 1.25 in Top 1.25 NPS Design Series Certification MBP-1 (revised) 05061 Number: or catalog number NLG (20% OP) PRV Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 29, 2000 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 9.99 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 75 - 375 psi 1 in Top 1 NPS Page 239 of 812 Effective Date: 2019-05-31

241 Table of Contents Carraro s.r.l. (CAO) 95408 NB#: Via Enrico Fermi 22, Segrate (MI) 20090 Italy location: Carraro s.r.l. (CAO) Via Enrico Fermi 22, Segrate (MI) 20090 Italy location: Certification Design Series CS 35 / G 95408 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on April 10, 2014 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 22.25 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Media Set Pressure Range Lift Flow Area Outlet Size VIII Div. 1 1.5 NPS 1 - 29 bar 11.5 mm [G] 30 mm 706.5 sq mm 2 NPS Certification Design Series CS 35 / J 95419 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on April 10, 2014 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 42.03 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Flow Area Code Section Outlet Size VIII Div. 1 Water 1 - 30 bar 17 mm [J] 40 mm 1256 sq mm 3 NPS 2 NPS Page 240 of 812 Effective Date: 2019-05-31

242 Table of Contents Cash Acme (Part of Reliance Worldwide Corporation) (CSH) 09009 NB#: 2400 7th Avenue S.W., Cullman, AL 35055 United States location: Cash Acme (Part of Reliance Worldwide Corporation) (CSH) 2400 7th Avenue S.W., Cullman, AL 35055 United States location: Certification Design Series F-30 (3/4") 09009 or catalog number Number: Safety Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on July 18, 1983 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 510 PPH Certified Value: Steam Test Medium: Saturated Water Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section IV Steam 0.75 NPS .75 NPS 0.307 sq in 0.156 in 30 - 30 psi 0.625 in Certification Design Series F-82, P3000BR (3/4") 09010 Number: or catalog number Safety Relief Valve Type Classification: Sec. IV at Ohio State University (Robinson Laboratory) on August 06, 1972 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 15.05 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Outlet Size Set Pressure Range Inlet Size Code Section Lift IV Steam 0.75 NPS .75 NPS 0.3 in 0.75 in 30 - 150 psi 0.442 sq in Design Series Certification F-82, P3000BR (1") 09021 Number: or catalog number Safety Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on May 16, 1980 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 21.49 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Code Section Media Outlet Size Lift Set Pressure Range Inlet Size IV Steam 0.785 sq in 1 in 0.3 in 30 - 150 psi 1 NPS 1 NPS Page 241 of 812 Effective Date: 2019-05-31

243 Table of Contents Cash Acme (Part of Reliance Worldwide Corporation) (CSH) 09032 NB#: 2400 7th Avenue S.W., Cullman, AL 35055 United States location: Certification Design Series F-82, P3000BR (1-1/4") 09032 Number: or catalog number Safety Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on November 19, 1981 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 35.72 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size IV Steam 1.25 in 0.4 in 30 - 150 psi 1.25 NPS 1.25 NPS 1.23 sq in Design Series Certification F-82, P3000BR (1-1/2") 09043 or catalog number Number: Safety Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on November 11, 1981 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 43.74 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size IV Steam 0.421 in 1.5 in 1.77 sq in 30 - 150 psi 1.5 NPS 1.5 NPS Certification Design Series F-82, P3000BR (2") 09054 or catalog number Number: Safety Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on November 19, 1981 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 81.8 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Outlet Size Flow Area Set Pressure Range Media Code Section Inlet Size IV Steam 3.142 sq in 2 in 0.562 in 30 - 150 psi 2 NPS 2 NPS Page 242 of 812 Effective Date: 2019-05-31

244 Table of Contents Cash Acme (Part of Reliance Worldwide Corporation) (CSH) 09098 NB#: 2400 7th Avenue S.W., Cullman, AL 35055 United States location: Certification Design Series (1-1/2")FVX-4 (2") FVMX-3 (T&P) 09098 or catalog number Number: Temperature and Pressure Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on November 19, 1981 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 33.69 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: 40 CC Method Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size Media IV Steam 75 - 150 psi 0.4 in 1.25 in 1.5 NPS 1.5 - 2 NPS 1.23 sq in Design Series Certification 1 FVX-5L/Series 15, 1-1/4 FVMX4L, FVX-8L 09100 or catalog number Number: Temperature and Pressure Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on April 04, 1979 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 20.17 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: 40 CC Method Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Media Set Pressure Range Lift Flow Area Outlet Size IV Steam 1 NPS 75 - 150 psi 0.3 in 1 in 0.785 sq in 1 - 1.25 NPS Certification Design Series FVX, FVMX-1-3-5-8, FVMX-5LS-SST Ser. 4 (3/4") 09111 Number: or catalog number Temperature and Pressure Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on June 20, 1984 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 10.64 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: 40 CC Method Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section IV Steam 75 - 150 psi 0.442 sq in 0.75 NPS .75 NPS 0.75 in 0.17 in Certification Design Series 1 FVX, FVMX3-5C, 3LS-6LS Ser. 4 (T&P) 09122 or catalog number Number: Temperature and Pressure Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on May 29, 1980 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 11.99 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: 40 CC Method Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Outlet Size Flow Area Code Section IV Steam 75 - 150 psi 0.148 in 0.843 in 0.558 sq in 1 NPS 1 NPS Page 243 of 812 Effective Date: 2019-05-31

245 Table of Contents Cash Acme (Part of Reliance Worldwide Corporation) (CSH) 09155 NB#: 2400 7th Avenue S.W., Cullman, AL 35055 United States location: Certification Design Series NCLX-1, -5, -8; NCLX-5L, -5LX, -5S, -LS, -A;S-14 and FWL-2 ,-6,A4,4,A2 09155 or catalog number Number: Temperature and Pressure Relief Valve Type Classification: Sec. IV at National Board T L (Worthington) on November 01, 1994 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.6 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: 40 CC Method Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size IV Steam 0.173 sq in 0.75 NPS .75 NPS 0.469 in 0.08 in 75 - 150 psi Certification Design Series F-95, P3000CI 09199 or catalog number Number: Safety Relief Valve Type Classification: Sec. IV at National Board T L (Worthington) on November 08, 1995 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .694 Unitless Certified Value: Steam Test Medium: Saturated Water Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Media Flow Area Outlet Size Inlet Size Lift Code Section IV Steam 0.75 NPS 30 - 75 psi 1 NPS 0.559 sq in 0.844 in 0.323 in IV Steam 1 NPS 30 - 75 psi 0.294 in 1 in 1.25 NPS 0.785 sq in IV Steam 1.227 sq in 1.25 in 0.383 in 30 - 75 psi 1.25 NPS 1.5 NPS IV Steam 1.5 NPS 2 NPS 1.767 sq in 1.5 in 0.437 in 30 - 75 psi IV Steam 30 - 75 psi 0.59 in 2 in 3.142 sq in 2.5 NPS 2 NPS Page 244 of 812 Effective Date: 2019-05-31

246 Table of Contents Cavagna Group S.p.A. - OMECA Division (CAV) 69083 NB#: Via Statale, 11/13--Casella Postale 11, Ponte San Marco, Brescia 25011 Italy location: Acceptable Abbrev.: OMECA Cavagna Group S.p.A. - OMECA Division (CAV) location: Via Statale, 11/13--Casella Postale 11, Ponte San Marco, Brescia 25011 Italy Acceptable Abbrev.: OMECA Certification Design Series 700073 69083 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 12, 2001 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 1808 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Outlet Size Inlet Size Set Pressure Range Media Code Section Lift VIII Div. 1 Air 250 - psi Top 283.4 sq mm 19 mm 0.75 NPS 9 mm Design Series Certification 1139 69117 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 01, 2002 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 262 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Media Code Section Flow Area Outlet Size Inlet Size Lift VIII Div. 1 Air 5 mm 7.4 mm 43 sq mm 250 - psi Top 0.25 NPS Design Series Certification 1128 69128 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 12, 2002 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 1790 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Lift Code Section Flow Area Outlet Size Inlet Size Set Pressure Range VIII Div. 1 Air 0.787 in 10 mm 250 - psi 0.75 NPS Top 268.2 sq mm Page 245 of 812 Effective Date: 2019-05-31

247 Table of Contents Cavagna Group S.p.A. - OMECA Division (CAV) 69139 NB#: Via Statale, 11/13--Casella Postale 11, Ponte San Marco, Brescia 25011 Italy location: Acceptable Abbrev.: OMECA Certification Design Series 1129 69139 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 25, 2002 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 2396 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Air 12 mm 250 - psi 1 NPS Top 483.6 sq mm 1 in Design Series Certification 1130 69140 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 25, 2002 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 3934 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Flow Area Outlet Size Lift Set Pressure Range Media Code Section VIII Div. 1 Air 716.3 sq mm 250 - psi 10 mm 1.25 NPS 1.224 in Top Certification Design Series 1135 69151 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 25, 2002 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 967 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Inlet Size Code Section Media Lift Set Pressure Range VIII Div. 1 Air 250 - psi 10 mm 14.7 mm 157 sq mm Top 1 NPS Page 246 of 812 Effective Date: 2019-05-31

248 Table of Contents Cavagna Group S.p.A. - OMECA Division (CAV) 69173 NB#: Via Statale, 11/13--Casella Postale 11, Ponte San Marco, Brescia 25011 Italy location: Acceptable Abbrev.: OMECA Certification Design Series 1335 69173 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 19, 2015 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 1278 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Bubble Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Outlet Size Inlet Size Set Pressure Range Lift Flow Area VIII Div. 1 Air 126.3 sq mm 1 in Top 13.3 mm 7 mm 375 psi Certification Design Series 1361 69184 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on November 03, 2015 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 954 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Bubble Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Lift Flow Area Inlet Size Outlet Size Set Pressure Range VIII Div. 1 Air 250 - 250 psi 8 mm 14.7 mm 1 NPS Top 157.1 sq mm Certification Design Series PV60 69195 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 28, 2016 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 11433 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Bubble Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Outlet Size Code Section Inlet Size Lift Flow Area VIII Div. 1 Air 45 mm 20 mm 250 psi 2 NPS Top 1590.4 sq mm Page 247 of 812 Effective Date: 2019-05-31

249 Table of Contents Cavagna Group S.p.A. - OMECA Division (CAV) 69218 NB#: Via Statale, 11/13--Casella Postale 11, Ponte San Marco, Brescia 25011 Italy location: Acceptable Abbrev.: OMECA Certification Design Series 1162A 69218 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 13, 2007 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 657 SCFM Certified Value: Air Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Media Inlet Size Set Pressure Range Lift Outlet Size VIII Div. 1 Air 0.75 NPS Top 312 - 312 psi Certification Design Series PV29 (700217) 69229 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 01, 2012 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 4656 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air Top 1.25 NPS 683.5 sq mm 1.16 in 12 mm 250 psi Design Series Certification PV19 (700214) 69230 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 29, 2011 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 2051 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Lift Outlet Size Media Set Pressure Range Flow Area Code Section VIII Div. 1 Air 250 psi 10 mm 0.748 in 283.4 sq mm Top 0.75 NPS Page 248 of 812 Effective Date: 2019-05-31

250 Table of Contents Cavagna Group S.p.A. - OMECA Division (CAV) 69241 NB#: Via Statale, 11/13--Casella Postale 11, Ponte San Marco, Brescia 25011 Italy location: Acceptable Abbrev.: OMECA Certification Design Series PV24 (700216) 69241 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 29, 2011 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 3158 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Lift Outlet Size Media Set Pressure Range Flow Area Code Section VIII Div. 1 Air 250 psi 10 mm 0.965 in 471.2 sq mm Top 1 NPS Page 249 of 812 Effective Date: 2019-05-31

251 Table of Contents Circor Aerospace, Inc. (CSC) 10001 NB#: 2301 Wardlow Circle, Corona, CA 92880 United States location: Acceptable Abbrev.: Circle Seal Circor Aerospace, Inc. (CSC) location: 2301 Wardlow Circle, Corona, CA 92880 United States Acceptable Abbrev.: Circle Seal Certification Design Series D-500-2M 10001 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Phillips Petroleum on November 16, 1966 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .359 SCFM/PSIA Certified Value: Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Outlet Size Inlet Size Set Pressure Range Lift Flow Area VIII Air 0.275 in 0.069 in 0.25 NPS 0.059 sq in 15 - 150 psi Design Series Certification M5100-1M 10012 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Phillips Petroleum on November 06, 1966 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .286 SCFM/PSIA Certified Value: Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Lift Flow Area Inlet Size Outlet Size Set Pressure Range VIII Air 100 - 1200 psi 0.06 in 0.25 in 0.125 NPS 0.049 sq in Certification Design Series M5100-2M & 3M 10023 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Phillips Petroleum on November 16, 1966 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .667 SCFM/PSIA Certified Value: Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size Media VIII Air 15 - 1200 psi 0.25 - 0.375 NPS 0.1 sq in 0.358 in 0.08 in Page 250 of 812 Effective Date: 2019-05-31

252 Table of Contents Circor Aerospace, Inc. (CSC) 10034 NB#: 2301 Wardlow Circle, Corona, CA 92880 United States location: Acceptable Abbrev.: Circle Seal Certification Design Series M5100-4M 10034 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Phillips Petroleum on November 16, 1966 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.310 SCFM/PSIA Certified Value: Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Air 15 - 1200 psi 0.1 in 0.516 in 0.209 sq in 0.5 NPS Design Series Certification M5100-6M & 8M 100 - 1200 10056 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Phillips Petroleum on November 16, 1966 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.453 SCFM/PSIA Certified Value: Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Inlet Size Flow Area Lift Set Pressure Range Media Code Section VIII Air 100 - 1200 psi 0.75 - 1 NPS 0.738 in 0.25 in 0.428 sq in Page 251 of 812 Effective Date: 2019-05-31

253 Table of Contents Circor Energy Products (HDS) 30003 NB#: 1500 SE 89th St, Oklahoma City, OK 73149 United States location: Acceptable Abbrev.: Hydroseal Circor Energy Products (HDS) location: 1500 SE 89th St, Oklahoma City, OK 73149 United States Acceptable Abbrev.: Hydroseal Certification Design Series 1-BV thru 3-BV, 1EV thru 4EV, FL 30003 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Louisiana State University on April 08, 1972 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .68 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Outlet Size Inlet Size Set Pressure Range Lift Flow Area VIII Div. 1 Air 0.375 in 0.094 in 0.5 - 0.75 NPS .75, 1 NPS 15 - 6000 psi Design Series Certification 5-BV thru 7-BV, FL-5-FV thru FL 30014 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Louisiana State University on September 30, 1972 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.22 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Lift Flow Area Inlet Size Outlet Size Set Pressure Range VIII Div. 1 Air 15 - 3000 psi 0.218 in 0.75 in 1.25 - 3 NPS 2, 2.5, 3, 4 NPS Certification Design Series 1-CRV thru 3-CRV, 1-FRV thru 4-F 30025 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on January 17, 1983 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.11 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size Media VIII Div. 1 Air 21 - 3500 psi 0.5 - 2 NPS .75, 1, 2 NPS 0.196 sq in 0.5 in Page 252 of 812 Effective Date: 2019-05-31

254 Table of Contents Circor Energy Products (HDS) 30036 NB#: 1500 SE 89th St, Oklahoma City, OK 73149 United States location: Acceptable Abbrev.: Hydroseal Certification Design Series 5-CRV, thru 8-CRV, FL-5-CRV 30036 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on January 17, 1983 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.09 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Inlet Size Flow Area Outlet Size Code Section Media Set Pressure Range VIII Div. 1 Air 18 - 2000 psi 0.939 in 2 NPS 1 - 2 NPS Certification Design Series 5, 6, 7, 8 CV, FL 30047 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on September 30, 1976 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.13 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size Media VIII Div. 1 Air 15 - 2000 psi 0.188 in 1.5, - 4 NPS 1 - 3 NPS 1 in Design Series Certification CXV, FXV, AXV, FL-XV 30058 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on August 22, 1977 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.15 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section Media VIII Div. 1 Air 0.5 - 2 NPS .75, 1, 2 NPS 0.5625 in 15 - 3500 psi 0.07 in Certification Design Series 3FT, 4FT, 5FT, FT flanged series 30069 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on July 25, 1988 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 4.88 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size VIII Div. 1 Air 20 - 4000 psi 0.625 in 1.5 - 3 NPS 0.75 - 2 NPS Page 253 of 812 Effective Date: 2019-05-31

255 Table of Contents Circor Energy Products (HDS) 30081 NB#: 1500 SE 89th St, Oklahoma City, OK 73149 United States location: Acceptable Abbrev.: Hydroseal Certification Design Series 5HC, 6HC & 7HC 30081 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on July 21, 1986 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 12.62 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Media Flow Area Inlet Size Code Section Lift Set Pressure Range VIII Div. 1 Air 0.785 sq in 1.25 - 4 NPS 2 - 4 NPS 1 in 15 - 2500 psi Design Series Certification 2500 (Liquids) 30115 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 08, 1994 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .673 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Outlet Size Inlet Size Lift Media Set Pressure Range Code Section VIII Div. 1 Water 0.121 in 15 - 7200 psi 0.75 - 1.5 NPS 2, 2.5 NPS 0.1213 sq in [D] 0.393 in VIII Div. 1 Water 15 - 7200 psi 0.161 in [E] 0.522 in 2 - 3 NPS 1 - 1.5 NPS 0.214 sq in VIII Div. 1 Water [F] 0.635 in 0.195 in 15 - 5000 psi 1.5 - 2 NPS 2 - 3 NPS 0.3167 sq in VIII Div. 1 Water 15 - 3705 psi 0.262 in [G] 0.85 in 0.5675 sq in 2.5, 3 NPS VIII Div. 1 Water 15 - 2750 psi 3 NPS 0.331 in 0.911 sq in [H] 1.077 in VIII Div. 1 Water 15 - 2700 psi 2 - 3 NPS 3, 4 NPS 1.4569 sq in [J] 1.362 in 0.419 in VIII Div. 1 Water 3 NPS 4, 6 NPS [K] 1.645 in 0.506 in 15 - 2220 psi 2.1253 sq in VIII Div. 1 Water 0.629 in 15 - 1500 psi 3 - 4 NPS 4, 6 NPS 3.2813 sq in [L] 2.044 in VIII Div. 1 Water 15 - 1100 psi 0.698 in [M] 2.27 in 4.0471 sq in 4 NPS 6 NPS VIII Div. 1 Water [N] 2.52 in 0.775 in 15 - 1000 psi 4.988 sq in VIII Div. 1 Water 7.33 sq in [P] 3.055 in 0.939 in 15 - 1000 psi VIII Div. 1 Water 1.236 in 15 - 600 psi 8 NPS [Q] 4.021 in 6 NPS 12.7 sq in VIII Div. 1 Water 15 - 300 psi 1.488 in [R] 4.838 in 18.38 sq in 8, 10 NPS VIII Div. 1 Water [T] 6 in 1.845 in 15 - 300 psi 8 NPS 10, 12 NPS 28.27 sq in Page 254 of 812 Effective Date: 2019-05-31

256 Table of Contents Circor Energy Products (HDS) 30126 NB#: 1500 SE 89th St, Oklahoma City, OK 73149 United States location: Acceptable Abbrev.: Hydroseal Certification Design Series Series 1500 30126 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on October 02, 1998 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .870 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Outlet Size Lift Set Pressure Range Media Code Section Inlet Size VIII Div. 1 Steam .75 - 1.5 NPS 0.058 sq in [C] 0.272 in 0.091 in 0.375 - 1 NPS 15 - 2000 psi VIII Div. 1 Air 15 - 8000 psi VIII Div. 1 Steam 0.135 in 15 - 2000 psi 0.5 - 1 NPS 1, 1.5 NPS 0.129 sq in [D] 0.405 in VIII Div. 1 Air 15 - 8000 psi VIII Div. 1 Steam 0.75 - 2 NPS 1.5, 2 NPS 0.23 sq in [E] 0.541 in 0.18 in 15 - 2000 psi VIII Div. 1 Air 15 - 8000 psi VIII Div. 1 Steam 0.366 sq in 0.228 in 15 - 2000 psi 1.5, 2 NPS 1 - 2 NPS [F] 0.683 in VIII Div. 1 Air 15 - 6400 psi VIII Div. 1 Air 15 - 1500 psi 0.289 in [G] 0.867 in 0.59 sq in 1.5 - 2 NPS 2 - 3 NPS VIII Div. 1 Steam VIII Div. 1 Air 15 - 1500 psi 0.343 in [H] 1.028 in 0.83 sq in VIII Div. 1 Steam Design Series Certification Series 1500 (Liquids) 30137 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on October 01, 1999 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .672 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size VIII Div. 1 Water 15 - 8000 psi [C] 0.272 in 0.058 sq in .75 - 1.5 NPS 0.5 - 1 NPS 0.091 in VIII Div. 1 Water 15 - 8000 psi 1, 1.5 NPS 0.129 sq in [D] 0.405 in 0.135 in VIII Div. 1 Water 0.75 - 2 NPS 15 - 8000 psi 0.18 in [E] 0.541 in 0.23 sq in 1.5, 2 NPS VIII Div. 1 Water 1.5, 2 NPS 15 - 6400 psi 0.228 in [F] 0.683 in 0.366 sq in 1 - 2 NPS VIII Div. 1 Water 15 - 1500 psi 0.289 in [G] 0.867 in 0.59 sq in 2 - 3 NPS 1.5 - 2 NPS VIII Div. 1 Water 0.343 in 15 - 1500 psi [H] 1.028 in 0.83 sq in Page 255 of 812 Effective Date: 2019-05-31

257 Table of Contents Circor Energy Products (HDS) 30182 NB#: 1500 SE 89th St, Oklahoma City, OK 73149 United States location: Acceptable Abbrev.: Hydroseal Certification Design Series 2500 Series ER (25MR, 25SER, B25ER) 30182 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 28, 2001 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.645 SCFM/PSIA Certified Value: 10.256 PPH/PSIA Certified Value (alternate medium): Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Steam 0.11 in 15 - 2500 psi 1 - 1.5 NPS 1.5 - 3 NPS 0.23 sq in [E] 0.635 in VIII Div. 1 Air 15 - 6200 psi Design Series Certification 5HD thru 7HD, HD Flanged Series 30205 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 21, 2002 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 17.62 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Lift Inlet Size Flow Area Outlet Size Set Pressure Range VIII Div. 1 Water 0.25 in 1 in 0.785 sq in 15 - 2500 psi 0.75 - 2 NPS 1.5 - 3 NPS Certification Design Series 1200B 30250 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 15, 2008 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 7.74 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Lift Code Section Flow Area Outlet Size Inlet Size Set Pressure Range VIII Div. 1 Air 15 - 2000 psi 1.5 - 2 NPS 2 NPS 0.478 sq in [G] 0.78 in Page 256 of 812 Effective Date: 2019-05-31

258 Table of Contents Circor Energy Products (HDS) 30261 NB#: 1500 SE 89th St, Oklahoma City, OK 73149 United States location: Acceptable Abbrev.: Hydroseal Certification Design Series 1200B (liquid) 30261 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 15, 2008 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 14.19 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Water 1.5 - 2 NPS 2 NPS 0.478 sq in [G] 0.78 in 15 - 2000 psi Design Series Certification 1400B 30272 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 25, 2009 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.46 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 15 - 2300 psi 0.5 - 1 NPS 1 NPS 0.211 sq in [E] 0.52 in 0.23 in Design Series Certification 1400B (Liquid) 30283 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 25, 2009 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 6.29 GPM/SQ.RT. PSID Certified Value: Liquid Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Lift Inlet Size Flow Area VIII Div. 1 Water 0.5 - 1 NPS 15 - 2300 psi 0.23 in [E] 0.52 in 0.211 sq in 1 NPS Page 257 of 812 Effective Date: 2019-05-31

259 Table of Contents Circor Energy Products (HDS) 30294 NB#: 1500 SE 89th St, Oklahoma City, OK 73149 United States location: Acceptable Abbrev.: Hydroseal Certification Design Series 3500 w/ Modulating & Snap Pilots 30294 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 16, 2009 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: 1.Pop 2.Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Air 1 - 1.5 NPS 2 NPS 0.15 sq in [D] 0.437 in 0.35 in 15 - 6170 psi VIII Div. 1 Air 0.35 in 15 - 6170 psi 0.246 sq in [E] 0.56 in VIII Div. 1 Air 0.372 sq in [F] 0.688 in 0.35 in 15 - 6170 psi VIII Div. 1 Air 0.596 sq in 3 NPS 0.57 in [G] 0.871 in 1.5 - 2 NPS 15 - 6170 psi VIII Div. 1 Air 15 - 6170 psi 0.57 in [H] 1.125 in 0.994 sq in VIII Div. 1 Air [J] 1.382 in 0.57 in 15 - 6170 psi 2 - 3 NPS 3, 4 NPS 1.5 sq in VIII Div. 1 Air 3 NPS 4 NPS 2.146 sq in [K] 1.653 in 1.05 in 15 - 3705 psi VIII Div. 1 Air 3.343 sq in 4, 6 NPS 15 - 3705 psi 1.05 in 3 - 4 NPS [L] 2.063 in VIII Div. 1 Air 15 - 3705 psi 1.59 in [M] 4.13 in 4.206 sq in 6 NPS 4 NPS VIII Div. 1 Air 15 - 3705 psi 5.054 sq in [N] 2.537 in 1.59 in VIII Div. 1 Air 1.59 in 7.67 sq in 15 - 3705 psi [P] 3.125 in VIII Div. 1 Air [Q] 4.06 in 2.48 in 15 - 1480 psi 6 NPS 8 NPS 12.946 sq in VIII Div. 1 Air 15 - 1480 psi 2.48 in [R] 4.882 in 18.719 sq in VIII Div. 1 Air 30.748 sq in 3.18 in 15 - 900 psi 10 NPS [T] 6.257 in 8 NPS Page 258 of 812 Effective Date: 2019-05-31

260 Table of Contents Conbraco Industries, Incorporated (CNB) 11002 NB#: 1418 S. Pearl St, Pageland, SC 29728 United States location: Conbraco Industries, Incorporated (CNB) 1418 S. Pearl St, Pageland, SC 29728 United States location: Certification Design Series 10-102/104 (RVW10) 11002 or catalog number Number: Safety Relief Valve Type Classification: Sec. IV at Ohio State University (Robinson Laboratory) on February 28, 1970 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 14.85 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media Code Section IV Steam 0.75 NPS 20 - 60 psi 1 NPS 0.442 sq in 0.75 in 0.3 in Design Series Certification 10-301/303 (RVW30) 11024 Number: or catalog number Safety Relief Valve Type Classification: Sec. IV at Ohio State University (Robinson Laboratory) on October 12, 1962 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 11.5 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Lift Outlet Size Inlet Size Flow Area Set Pressure Range IV Steam 0.19 in 0.75 in 20 - 60 psi 0.442 sq in .75 NPS 0.75 NPS Certification Design Series 10-321 (RVW32) 11035 or catalog number Number: Safety Relief Valve Type Classification: Sec. IV at Ohio State University (Robinson Laboratory) on May 08, 1975 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 8.90 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size IV Steam 0.442 sq in 0.75 in 0.14 in 20 - 60 psi 0.75 NPS .75 NPS Page 259 of 812 Effective Date: 2019-05-31

261 Table of Contents Conbraco Industries, Incorporated (CNB) 11046 NB#: 1418 S. Pearl St, Pageland, SC 29728 United States location: Certification Design Series 10-322 (RVS32) 11046 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on May 08, 1975 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 9.0 PPH/PSIA Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size VIII Div. 1 Steam 0.75 in 0.14 in 20 - 60 psi 0.75 NPS .75 NPS 0.442 sq in Design Series Certification 10-407 & 10-408 (30 psig) 11057 or catalog number Number: Safety Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on September 28, 1983 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 535 PPH Certified Value: Steam Test Medium: Saturated Water Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size IV Steam 0.26 in 0.625 in 0.307 sq in .75 NPS 0.75 NPS 30 - 30 psi Certification Design Series 10-512 (RVS52) 11080 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on March 23, 1981 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 4.867 PPH/PSIA Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Lift Flow Area Inlet Size VIII Div. 1 Steam 15 - 60 psi 0.1 in 0.437 in 0.15 sq in .5 NPS 0.5 NPS Page 260 of 812 Effective Date: 2019-05-31

262 Table of Contents Conbraco Industries, Incorporated (CNB) 11091 NB#: 1418 S. Pearl St, Pageland, SC 29728 United States location: Certification Design Series 10-600 (RVW60) 11091 or catalog number Number: Safety Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on June 18, 1987 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .63 Unitless Certified Value: Steam Test Medium: Saturated Water Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Lift Inlet Size Code Section Outlet Size Set Pressure Range IV Steam 15 - 160 psi .75 NPS 0.535 sq in 0.825 in 0.75 NPS 0.336 in IV Steam 15 - 160 psi 0.429 in 1.05 in 0.866 sq in 1 NPS 1 NPS IV Steam 1.498 sq in 1.25 NPS 1.25 NPS 1.381 in 0.554 in 15 - 160 psi IV Steam 15 - 160 psi 1.5 NPS 1.611 in 0.659 in 2.038 sq in 1.5 NPS IV Steam 0.89 in 2.068 in 3.359 sq in 2 NPS 15 - 160 psi 2 NPS Design Series Certification 10-610 (RVW61) 11103 Number: or catalog number Safety Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on June 03, 1987 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .739 Unitless Certified Value: Steam Test Medium: Saturated Water Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Set Pressure Range Outlet Size Inlet Size Media Flow Area IV Steam 0.336 in 0.825 in 0.535 sq in 1 NPS 0.75 NPS 15 - 160 psi IV Steam 1.25 NPS 15 - 160 psi 0.429 in 1 NPS 1.05 in 0.866 sq in IV Steam 1.381 in 0.554 in 15 - 160 psi 1.25 NPS 1.5 NPS 1.498 sq in IV Steam 1.5 NPS 2 NPS 2.038 sq in 0.659 in 15 - 160 psi 1.611 in IV Steam 2 NPS 15 - 160 psi 0.89 in 2.068 in 3.359 sq in 2.5 NPS Certification Design Series 12-205 (RVS12) 11114 Number: or catalog number Safety Valve Type Classification: Sec. IV at Ohio State University (Robinson Laboratory) on April 26, 1964 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 2500 PPH Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Media Set Pressure Range Lift Flow Area Outlet Size IV Steam 2 NPS 15 - 15 psi 0.64 in 1.875 in 2.761 sq in 2 NPS Page 261 of 812 Effective Date: 2019-05-31

263 Table of Contents Conbraco Industries, Incorporated (CNB) 11125 NB#: 1418 S. Pearl St, Pageland, SC 29728 United States location: Certification Design Series 12-206 (RVS12) 11125 or catalog number Number: Safety Valve Type Classification: Sec. IV at Ohio State University (Robinson Laboratory) on September 08, 1963 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 3529 PPH Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size Media IV Steam 15 - 15 psi 0.56 in 2.25 in 2.5 NPS 2.5 NPS 3.976 sq in Design Series Certification 12-208 (RVS12) 11136 or catalog number Number: Safety Valve Type Classification: Sec. IV at National Board T L (Picaway) on September 05, 1979 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 4100 PPH Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Media Set Pressure Range Lift Flow Area Outlet Size IV Steam 3 NPS 15 - 15 psi 0.42 in 2.89 in 6.56 sq in 3 NPS Certification Design Series 13-101 (RVS13T) 11147 Number: or catalog number Safety Valve Type Classification: Sec. IV at Ohio State University (Robinson Laboratory) on August 27, 1961 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 410 PPH Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section IV Steam 15 - 15 psi 0.442 sq in 0.75 NPS open 0.75 in 0.21 in Certification Design Series 13-202 (RVS13) 11169 or catalog number Number: Safety Valve Type Classification: Sec. IV at Ohio State University (Robinson Laboratory) on June 19, 1962 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 643 PPH Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Outlet Size Flow Area Code Section IV Steam 15 - 15 psi 0.37 in 0.75 in 0.442 sq in 1 NPS 1 NPS Page 262 of 812 Effective Date: 2019-05-31

264 Table of Contents Conbraco Industries, Incorporated (CNB) 11170 NB#: 1418 S. Pearl St, Pageland, SC 29728 United States location: Certification Design Series 13-211 (RVS13) 11170 Number: or catalog number Safety Valve Type Classification: Sec. IV at National Board T L (Picaway) on June 13, 1984 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 475 PPH Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size IV Steam 0.75 in 0.244 in 15 - psi 0.75 NPS 0.75 NPS 0.442 sq in Design Series Certification 13-213 (RVS13) 11181 or catalog number Number: Safety Valve Type Classification: Sec. IV at National Board T L (Picaway) on May 13, 1973 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 1200 PPH Certified Value: Steam Test Medium: Steam Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Lift Set Pressure Range Media Inlet Size Code Section IV Steam 0.57 in 1 in 0.785 sq in 1.25 NPS 15 - 15 psi 1.5 NPS Design Series Certification 13-214 (RVS13) 11192 Number: or catalog number Safety Valve Type Classification: Sec. IV at National Board T L (Picaway) on May 13, 1973 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 1900 PPH Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Set Pressure Range Flow Area Media Code Section Outlet Size Inlet Size IV Steam 1.227 sq in 1.25 in 0.79 in 15 - 15 psi 1.5 NPS 2 NPS Page 263 of 812 Effective Date: 2019-05-31

265 Table of Contents Conbraco Industries, Incorporated (CNB) 11215 NB#: 1418 S. Pearl St, Pageland, SC 29728 United States location: Certification Design Series 14-205 (RVS14) 11215 Number: or catalog number Safety Valve Type Classification: Sec. IV at Ohio State University (Robinson Laboratory) on January 29, 1965 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 3150 PPH Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size IV Steam 1.688 in 0.83 in 15 - 15 psi 2 NPS 2 NPS 2.238 sq in Design Series Certification 14-206 (RVS14) 11226 or catalog number Number: Safety Valve Type Classification: Sec. IV at Ohio State University (Robinson Laboratory) on January 02, 1965 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 4676 PPH Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size IV Steam 0.52 in 2.062 in 3.339 sq in 2.5 NPS 2.5 NPS 15 - 15 psi Certification Design Series 14-207 (RVS14) 11237 or catalog number Number: Safety Valve Type Classification: Sec. IV at Ohio State University (Robinson Laboratory) on January 29, 1965 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 6843 PPH Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Lift Flow Area Inlet Size IV Steam 15 - 15 psi 0.64 in 2.562 in 5.155 sq in 3 NPS 3 NPS Page 264 of 812 Effective Date: 2019-05-31

266 Table of Contents Conbraco Industries, Incorporated (CNB) 11248 NB#: 1418 S. Pearl St, Pageland, SC 29728 United States location: Certification Design Series 15-112 (RVA15) 11248 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on April 17, 1975 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .738 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Lift Inlet Size Code Section Outlet Size Set Pressure Range VIII Div. 1 Air Side 0.265 in 0.25 NPS 15 - 250 psi Certification Design Series 15-115/117 (RVA15) 11259 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on September 06, 1979 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.849 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Code Section Outlet Size Flow Area Lift Set Pressure Range VIII Div. 1 Air 15 - 250 psi 0.375 - 0.5 NPS .5 (Side 2) 0.145 sq in 0.43 in Certification Design Series 19 Series 11282 Number: or catalog number Safety Valve Type Classification: Sec. I at National Board T L (Picaway) on March 27, 1980 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .826 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable by Dual Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Lift Set Pressure Range Media Code Section Flow Area VIII Div. 1 Air 0.5 - 0.75 NPS .75 NPS 0.129 sq in [D] 0.406 in 0.101 in 15 - 300 psi I & VIII Div. 1 Steam VIII Div. 1 Air 1 NPS 15 - 300 psi 0.135 in [E] 0.541 in 0.23 sq in 0.75 - 1 NPS I & VIII Div. 1 Steam VIII Div. 1 Air 15 - 300 psi 0.169 in [F] 0.676 in 0.359 sq in 1.25 NPS 1 - 1.25 NPS I & VIII Div. 1 Steam VIII Div. 1 Air 1.5 NPS 0.589 sq in 1.25 - 1.5 NPS 0.217 in 15 - 300 psi [G] 0.866 in I & VIII Div. 1 Steam VIII Air 15 - 300 psi 0.271 in [H] 1.082 in 2 NPS 1.5 - 2 NPS 0.919 sq in I & VIII Div. 1 Steam VIII Div. 1 Air 1.5 - 2.5 NPS 2.5 NPS 15 - 300 psi 0.347 in [J] 1.386 in 1.509 sq in I & VIII Div. 1 Steam Page 265 of 812 Effective Date: 2019-05-31

267 Table of Contents Conbraco Industries, Incorporated (CNB) 11293 NB#: 1418 S. Pearl St, Pageland, SC 29728 United States location: Certification Design Series 29-102, 29-202, 29-302 11293 Number: or catalog number Safety Valve Type Classification: Sec. I at National Board T L (Picaway) on November 30, 1982 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.596 PPH/PSIA Certified Value: 1.280 SCFM/PSIA Certified Value (alternate medium): Steam Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Air 0.5 in 0.058 in 30 - 205 psi 0.375 - 0.75 NPS 1 NPS 0.196 sq in I Steam VIII Certification Design Series 29-303, 29-402, 29-501 11305 or catalog number Number: Safety Valve Type Classification: Sec. I at National Board T L (Picaway) on February 14, 1983 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 7.23 PPH/PSIA Certified Value: 2.57 SCFM/PSIA Certified Value (alternate medium): Steam Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Lift Set Pressure Range Inlet Size Media Code Section VIII Air 0.08 in 0.737 in 0.203 sq in 1.25 NPS 30 - 210 psi 0.75 - 1.25 NPS I Steam VIII Certification Design Series 13-511/512 (RVS13L) 11350 Number: or catalog number Safety Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on October 02, 1990 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 407 PPH Certified Value: Steam Test Medium: Steam Certified Medium: Low Pressure Steam Heating Boilers Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Code Section Media Outlet Size Lift Set Pressure Range Inlet Size IV Steam 0.272 sq in 0.588 in 0.147 in 15 - 15 psi 0.75 NPS .75 NPS Page 266 of 812 Effective Date: 2019-05-31

268 Table of Contents Conbraco Industries, Incorporated (CNB) 11361 NB#: 1418 S. Pearl St, Pageland, SC 29728 United States location: Certification Design Series 119 Series 11361 Number: or catalog number Safety Valve Type Classification: Sec. I at National Board T L (Worthington) on March 05, 1997 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size Media VIII Air 15 - 250 psi 0.329 in [J] 1.315 in 1.358 in 1.5 NPS 2.5 NPS I Steam VIII VIII Air 2 - 3 NPS 3 NPS 1.926 sq in 0.392 in 15 - 250 psi [K] 1.566 in I Steam VIII VIII Air 4 NPS 0.488 in 15 - 250 psi 2.99 sq in 2.5 - 4 NPS [L] 1.951 in I Steam III VIII Air 15 - 250 psi 3.774 in 3 - 4 NPS 4 NPS [M] 2.192 in 0.548 in I Steam VIII VIII Air 4.55 sq in [N] 2.407 in 0.602 in 15 - 250 psi 4 NPS 6 NPS I Steam VIII VIII Air 15 - 250 psi 6.692 in 0.73 in [P] 2.919 in I Steam VIII VIII Air 8 NPS 0.961 in 11.593 in [Q] 3.842 in 6 NPS 15 - 250 psi I Steam VIII VIII Air 16.786 in [R] 4.623 in 1.156 in 15 - 250 psi I Steam VIII Design Series Certification 15-118 (RVA15) 11372 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on November 05, 1997 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.28 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Code Section Inlet Size Set Pressure Range Media Outlet Size VIII Air 0.219 sq in 0.528 in 0.132 in 15 - 250 psi 0.75 NPS Side Page 267 of 812 Effective Date: 2019-05-31

269 Table of Contents Conbraco Industries, Incorporated (CNB) 11383 NB#: 1418 S. Pearl St, Pageland, SC 29728 United States location: Certification Design Series 15-119 (RVA15) 11383 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on November 05, 1997 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 6.78 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size VIII Air 0.764 in 0.191 in 15 - 250 psi 1 NPS Side 0.458 sq in Design Series Certification 17-402 (RVW17) 11440 or catalog number Number: Safety Relief Valve Type Classification: Sec. IV at National Board T L (Worthington) on March 02, 1999 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 5.2 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size IV Steam 0.117 in 0.47 in 0.173 sq in 0.75 NPS 0.75 NPS 75 - 150 psi Certification Design Series 10-417/418 (RVW40) 11451 or catalog number Number: Safety Relief Valve Type Classification: Sec. IV at National Board T L (Worthington) on March 02, 1999 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 10.0 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Lift Flow Area Inlet Size IV Steam 20 - 80 psi 0.156 in 0.624 in 0.306 sq in .75 NPS 0.75 NPS Page 268 of 812 Effective Date: 2019-05-31

270 Table of Contents Conbraco Industries, Incorporated (CNB) 11462 NB#: 1418 S. Pearl St, Pageland, SC 29728 United States location: Certification Design Series 500 Series 11462 or catalog number Number: Safety Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 12, 2000 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .861 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size Media VIII Div. 1 Air 0.102 in 0.129 sq in 15 - 2000 psi 0.5 - 0.75 NPS [D] 0.406 in .75, 1 NPS VIII Div. 1 Steam VIII Div. 1 Air 0.75 - 1 NPS 1.25 NPS 0.229 sq in [E] 0.539 in 0.135 in 15 - 2000 psi VIII Div. 1 Steam VIII Div. 1 Air 0.169 in 15 - 2000 psi 1.5 NPS 0.359 sq in [F] 0.676 in 1 - 1.25 NPS VIII Div. 1 Steam VIII Div. 1 Air 0.217 in 1.25 - 1.5 NPS 15 - 2000 psi 0.589 sq in 2 NPS [G] 0.866 in VIII Div. 1 Steam VIII Div. 1 Air [H] 1.082 in 0.271 in 15 - 2000 psi 1.5 - 2 NPS 2.5 NPS 0.919 sq in VIII Div. 1 Steam VIII Div. 1 Air [J] 1.384 in 0.346 in 1.504 sq in 3 NPS 15 - 2000 psi 2 NPS VIII Div. 1 Steam Certification Design Series 500 Series (Liquids) 11473 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 25, 2000 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .689 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Water 15 - 1000 psi 0.102 in [D] 0.406 in 0.129 sq in .75, 1 NPS 0.5 - 0.75 NPS VIII Div. 1 Water 15 - 1000 psi 0.135 in [E] 0.539 in 0.229 sq in 1.25 NPS 0.75 - 1 NPS VIII Div. 1 Water 15 - 1000 psi 1 - 1.25 NPS [F] 0.676 in 0.169 in 0.359 sq in 1.5 NPS VIII Div. 1 Water 0.217 in [G] 0.866 in 0.589 sq in 2 NPS 1.25 - 1.5 NPS 15 - 1000 psi VIII Div. 1 Water 0.919 sq in [H] 1.082 in 0.271 in 15 - 1000 psi 1.5 - 2 NPS 2.5 NPS VIII Div. 1 Water 15 - 1000 psi 0.346 in [J] 1.384 in 1.504 sq in 3 NPS 2 NPS Page 269 of 812 Effective Date: 2019-05-31

271 Table of Contents Conbraco Industries, Incorporated (CNB) 11518 NB#: 1418 S. Pearl St, Pageland, SC 29728 United States location: Certification Design Series 10-624/634 (RVW62) 11518 or catalog number Number: Safety Relief Valve Type Classification: Sec. IV at National Board T L (Worthington) on March 13, 2001 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 14.45 PPH/PSIA Certified Value: Steam Test Medium: Saturated Water Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Lift Flow Area Inlet Size IV Steam 30 - 150 psi 0.19 in 0.768 in 0.463 sq in .75 NPS 0.75 NPS Page 270 of 812 Effective Date: 2019-05-31

272 Table of Contents Continental Disc Corporation (CDC) 75002 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Continental Disc Corporation (CDC) 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series CDC (FS) 75002 Number: or catalog number RHI, UNISERT, FLAT SEAT Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on February 13, 1998 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: .34 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Media Outlet Size Inlet Size Flow Area N/A 1 NPS 0.86 sq in 25 - 2160 psi N/A 1.5 NPS 2.04 sq in 22 - 2160 psi N/A 7 - 2160 psi 3.36 sq in 2 NPS N/A 7.39 sq in 3 NPS 6 - 1440 psi N/A 5 - 1440 psi 12.73 sq in 4 NPS N/A 3 - 1440 psi 28.89 sq in 6 NPS N/A 50.03 sq in 8 NPS 2 - 720 psi N/A 2 - 720 psi 78.85 sq in 10 NPS N/A 2 - 720 psi 113.1 sq in 12 NPS N/A 137.89 sq in 2 - 720 psi 14 NPS N/A 2 - 720 psi 182.65 sq in 16 NPS N/A 2 - 720 psi 233.71 sq in 18 NPS N/A 291.04 sq in 2 - 275 psi 20 NPS N/A 424.56 sq in 2 - 275 psi 24 NPS N/A 671.96 sq in 30 NPS 2 - 275 psi N/A 2 - 275 psi 32 NPS 766.99 sq in N/A 2 - 275 psi 975.91 sq in 36 NPS Page 271 of 812 Effective Date: 2019-05-31

273 Table of Contents Continental Disc Corporation (CDC) 75013 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series ENVIRO-SEAL, Isolation Seal 75013 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on February 13, 1998 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 2.00 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Lift Inlet Size Set Pressure Range Media Flow Area Outlet Size N/A 1 NPS 0.86 sq in 15 - 275 psi N/A 1.5 NPS 10 - 275 psi 2.04 sq in N/A 6 - 275 psi 2 NPS 3.36 sq in N/A 4 - 275 psi 3 NPS 7.39 sq in N/A 4 NPS 12.73 sq in 3 - 275 psi N/A 2 - 275 psi 28.89 sq in 6 NPS N/A 1.6 - 275 psi 50.03 sq in 8 NPS N/A 78.85 sq in 10 NPS 1.2 - 275 psi N/A 1 - 275 psi 113.1 sq in 12 NPS N/A 1 - 275 psi 137.89 sq in 14 NPS N/A 1 - 275 psi 16 NPS 182.65 sq in N/A 1 - 275 psi 233.71 sq in 18 NPS N/A 1 - 275 psi 291.04 sq in 20 NPS N/A 424.56 sq in 1 - 275 psi 24 NPS N/A 1 - 275 psi 671.96 sq in 30 NPS N/A 1 - 275 psi 32 NPS 766.99 sq in N/A 975.91 sq in 1 - 275 psi 36 NPS Design Series Certification ZAP 75024 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on February 13, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 5.88 Unitless Certified Value: Air or gases (Krg) Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Set Pressure Range Lift Inlet Size Flow Area Outlet Size N/A 50 - 1440 psi 0.56 sq in 1 NPS N/A 45 - 1440 psi 1.45 sq in 1.5 NPS N/A 2 NPS 35 - 1440 psi 2.36 sq in N/A 30 - 1440 psi 4.85 sq in 3 NPS N/A 4 NPS 7.99 sq in 25 - 1440 psi N/A 17.27 sq in 20 - 1440 psi 6 NPS N/A 15 - 720 psi 30.1 sq in 8 NPS Page 272 of 812 Effective Date: 2019-05-31

274 Table of Contents Continental Disc Corporation (CDC) 75035 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series KBA 75035 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on February 12, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 3.62 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section VIII Div. 1 1 NPS 0.72 sq in 35 - 2160 psi VIII Div. 1 1.5 NPS 1.77 sq in 30 - 2160 psi VIII Div. 1 2 NPS 26 - 2160 psi 2.95 sq in VIII Div. 1 6.61 sq in 24 - 1440 psi 3 NPS VIII Div. 1 23 - 1440 psi 4 NPS 11.5 sq in VIII Div. 1 20 - 1440 psi 26.07 sq in 6 NPS VIII Div. 1 15 - 720 psi 45.66 sq in 8 NPS VIII Div. 1 18 - 720 psi 10 NPS 71.81 sq in VIII Div. 1 18 - 275 psi 101.6 sq in 12 NPS VIII Div. 1 122.7 sq in 14 NPS 17 - 275 psi VIII Div. 1 16 - 275 psi 16 NPS 160.9 sq in VIII Div. 1 15 - 275 psi 18 NPS 204.2 sq in VIII Div. 1 20 NPS 252.7 sq in 12 - 275 psi VIII Div. 1 12 - 275 psi 24 NPS 365.2 sq in VIII Div. 1 498.2 sq in 11 - 275 psi 28 NPS VIII Div. 1 572.5 sq in 10 - 275 psi 30 NPS VIII Div. 1 651.9 sq in 9 - 275 psi 32 NPS Page 273 of 812 Effective Date: 2019-05-31

275 Table of Contents Continental Disc Corporation (CDC) 75046 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series CDCV (FS) 75046 or catalog number Number: RHI, UNISERT, Flat Seat Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on February 13, 1998 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.04 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Div. 1 1 NPS 0.86 sq in 30 - 2160 psi VIII Div. 1 1.5 NPS 2.04 sq in 18 - 2160 psi VIII Div. 1 10 - 2160 psi 2 NPS 3.36 sq in VIII Div. 1 3 NPS 7.39 sq in 6.5 - 1440 psi VIII Div. 1 7 - 1440 psi 4 NPS 12.73 sq in VIII Div. 1 6 NPS 5 - 1440 psi 28.89 sq in VIII Div. 1 5 - 720 psi 50.03 sq in 8 NPS VIII Div. 1 5 - 720 psi 10 NPS 78.85 sq in VIII Div. 1 4 - 720 psi 113.1 sq in 12 NPS VIII Div. 1 4 - 720 psi 137.9 sq in 14 NPS VIII Div. 1 182.7 sq in 16 NPS 4 - 720 psi VIII Div. 1 4 - 720 psi 233.7 sq in 18 NPS VIII Div. 1 20 NPS 4 - 275 psi 291 sq in VIII Div. 1 4 - 275 psi 24 NPS 424.6 sq in VIII Div. 1 4 - 275 psi 28 NPS 583.2 sq in VIII Div. 1 4 - 275 psi 30 NPS 672 sq in VIII Div. 1 4 - 275 psi 767 sq in 32 NPS VIII Div. 1 4 - 275 psi 975.9 sq in 36 NPS VIII Div. 1 1090 sq in 4 - 275 psi 38 NPS VIII Div. 1 1210 sq in 40 NPS 4 - 275 psi VIII Div. 1 4 - 275 psi 1336 sq in 42 NPS VIII Div. 1 44 NPS 1469 sq in 4 - 275 psi VIII Div. 1 1608 sq in 4 - 275 psi 46 NPS VIII Div. 1 4 - 275 psi 1753 sq in 48 NPS Page 274 of 812 Effective Date: 2019-05-31

276 Table of Contents Continental Disc Corporation (CDC) 75057 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series CDC/LD/ (LL) 75057 Number: or catalog number Insert, Full Bolted #1 thru #9, Union 2U, 3U, 5U, 6U Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on February 13, 1998 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.81 Unitless Certified Value: Air or gases (Krg) Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size N/A 1 NPS 0.72 sq in 25 - 2160 psi N/A 1.77 sq in 22 - 2160 psi 1.5 NPS N/A 3.36 sq in 2 NPS 7 - 2160 psi N/A 7.39 sq in 6 - 1440 psi 3 NPS N/A 12.73 sq in 5 - 1440 psi 4 NPS N/A 3 - 1440 psi 28.89 sq in 6 NPS N/A 2 - 1440 psi 8 NPS 50.03 sq in N/A 78.85 sq in 2 - 720 psi 10 NPS N/A 12 NPS 113.1 sq in 2 - 720 psi N/A 14 NPS 2 - 720 psi 137.89 sq in N/A 2 - 720 psi 182.65 sq in 16 NPS N/A 233.71 sq in 2 - 720 psi 18 NPS N/A 2 - 720 psi 291.04 sq in 20 NPS N/A 424.56 sq in 2 - 275 psi 24 NPS N/A 2 - 275 psi 671.96 sq in 30 NPS Page 275 of 812 Effective Date: 2019-05-31

277 Table of Contents Continental Disc Corporation (CDC) 75079 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series MICRO X, MX-9T & SCORED FLAT SEAT 75079 Number: or catalog number RHI, UNISERT, FLAT SEAT, MX-9T, MX-9T-RH Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on February 12, 1998 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: .29 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size N/A 0.86 sq in 1 NPS 140 - 6000 psi N/A 1.5 NPS 2.04 sq in 120 - 6000 psi N/A 2 NPS 55 - 6000 psi 3.36 sq in N/A 7.39 sq in 50 - 6000 psi 3 NPS N/A 50 - 6000 psi 4 NPS 12.73 sq in N/A 45 - 6000 psi 28.89 sq in 6 NPS N/A 40 - 6000 psi 50.03 sq in 8 NPS N/A 78.85 sq in 10 NPS 40 - 720 psi N/A 35 - 720 psi 113.1 sq in 12 NPS N/A 21 - 720 psi 137.89 sq in 14 NPS N/A 182.65 sq in 18 - 720 psi 16 NPS N/A 16 - 720 psi 233.71 sq in 18 NPS N/A 15 - 720 psi 291.04 sq in 20 NPS N/A 424.56 sq in 15 - 720 psi 24 NPS N/A 583.21 sq in 15 - 720 psi 28 NPS N/A 671.96 sq in 30 NPS 15 - 720 psi N/A 15 - 720 psi 32 NPS 766.99 sq in N/A 15 - 275 psi 975.91 sq in 36 NPS Page 276 of 812 Effective Date: 2019-05-31

278 Table of Contents Continental Disc Corporation (CDC) 75080 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series MICRO X-V, MX-9T-V & SCORED FLAT SEAT 75080 Number: or catalog number RHI, UNISERT, FLAT SEAT, MX-9T, MX-9T-RH Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on February 13, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .29 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size N/A 0.86 sq in 1 NPS 140 - 6000 psi N/A 1.5 NPS 2.04 sq in 120 - 6000 psi N/A 2 NPS 55 - 3600 psi 3.36 sq in N/A 7.39 sq in 50 - 3600 psi 3 NPS N/A 50 - 3600 psi 4 NPS 12.73 sq in N/A 45 - 1440 psi 28.89 sq in 6 NPS N/A 40 - 1440 psi 50.03 sq in 8 NPS N/A 78.85 sq in 10 NPS 40 - 720 psi N/A 35 - 720 psi 113.1 sq in 12 NPS N/A 21 - 720 psi 137.89 sq in 14 NPS N/A 182.65 sq in 18 - 720 psi 16 NPS N/A 16 - 720 psi 233.71 sq in 18 NPS N/A 15 - 720 psi 291.04 sq in 20 NPS N/A 424.56 sq in 15 - 720 psi 24 NPS N/A 583.21 sq in 15 - 720 psi 28 NPS N/A 671.96 sq in 30 NPS 15 - 720 psi N/A 15 - 720 psi 32 NPS 766.99 sq in N/A 15 - 275 psi 975.91 sq in 36 NPS Page 277 of 812 Effective Date: 2019-05-31

279 Table of Contents Continental Disc Corporation (CDC) 75091 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series STANDARD 75091 or catalog number Number: Insert, Full Bolted #1 thru #9, Union 2U, 3U, 5U, 6U Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on February 13, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.13 Unitless Certified Value: Air or gases (Krg) Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size Media N/A 0.5 NPS 0.23 sq in 65 - 6000 psi N/A 50 - 6000 psi 0.43 sq in 0.75 NPS N/A 0.72 sq in 29 - 6000 psi 1 NPS N/A 1.5 NPS 1.77 sq in 22 - 6000 psi N/A 2 NPS 3.36 sq in 10 - 6000 psi N/A 9 - 6000 psi 3 NPS 7.39 sq in N/A 7 - 6000 psi 12.73 sq in 4 NPS N/A 28.89 sq in 6 NPS 5 - 6000 psi N/A 50.03 sq in 8 NPS 4 - 3600 psi N/A 4 - 3600 psi 78.85 sq in 10 NPS N/A 3 - 3600 psi 12 NPS 113.1 sq in N/A 14 NPS 137.89 sq in 3 - 2160 psi N/A 3 - 2160 psi 182.65 sq in 16 NPS N/A 18 NPS 3 - 1440 psi 233.71 sq in N/A 291.04 sq in 3 - 1400 psi 20 NPS N/A 3 - 1400 psi 424.56 sq in 24 NPS N/A 3 - 1440 psi 30 NPS 671.96 sq in Certification Design Series ULTRX, ULTRX HP 75125 Number: or catalog number ULTRX, ULTRX-T Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on February 13, 1998 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: .62 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Flow Area Outlet Size Lift Inlet Size Code Section Media VIII Div. 1 100 - 2160 psi 0.86 sq in 1 NPS N/A 2.04 sq in 85 - 2160 psi 1.5 NPS N/A 65 - 1440 psi 3.36 sq in 2 NPS N/A 50 - 1440 psi 7.39 sq in 3 NPS N/A 4 NPS 45 - 1440 psi 12.73 sq in N/A 40 - 720 psi 28.89 sq in 6 NPS N/A 8 NPS 50.03 sq in 35 - 720 psi N/A 78.85 sq in 15 - 720 psi 10 NPS N/A 10 - 720 psi 113.1 sq in 12 NPS Page 278 of 812 Effective Date: 2019-05-31

280 Table of Contents Continental Disc Corporation (CDC) 75147 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series RCS 75147 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on February 13, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .59 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section Media N/A 1 NPS 0.86 sq in 115 - 2160 psi N/A 2.04 sq in 1.5 NPS 83 - 2160 psi N/A 3.36 sq in 70 - 1440 psi 2 NPS N/A 3 NPS 7.39 sq in 65 - 1440 psi N/A 4 NPS 12.73 sq in 55 - 1440 psi N/A 40 - 1440 psi 6 NPS 28.89 sq in N/A 8 NPS 35 - 1440 psi 50.03 sq in Design Series Certification PL, PLV, LPL, LPLV (Flat Seat) 75169 Number: or catalog number RHI, Unisert, Flat Seat Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on May 14, 1998 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.60 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size VIII Div. 1 35 - 2160 psi 0.86 sq in 1 NPS VIII Div. 1 32 - 2160 psi 1.5 NPS 2.04 sq in VIII Div. 1 3.36 sq in 2 NPS 15 - 2160 psi VIII Div. 1 8 - 1440 psi 7.39 sq in 3 NPS VIII Div. 1 4 NPS 12.73 sq in 6 - 1440 psi VIII Div. 1 5 - 1440 psi 6 NPS 28.89 sq in VIII Div. 1 8 NPS 50.03 sq in 4 - 720 psi VIII Div. 1 5 - 720 psi 78.85 sq in 10 NPS VIII Div. 1 12 NPS 5 - 720 psi 113.1 sq in VIII Div. 1 5 - 720 psi 137.9 sq in 14 NPS VIII Div. 1 5 - 720 psi 182.7 sq in 16 NPS VIII Div. 1 5 - 720 psi 233.7 sq in 18 NPS VIII Div. 1 291 sq in 5 - 275 psi 20 NPS VIII Div. 1 5 - 275 psi 424.6 sq in 24 NPS VIII Div. 1 28 NPS 5 - 275 psi 583.2 sq in VIII Div. 1 30 NPS 672 sq in 5 - 275 psi VIII Div. 1 767 sq in 5 - 275 psi 32 NPS VIII Div. 1 36 NPS 5 - 275 psi 975.9 sq in Page 279 of 812 Effective Date: 2019-05-31

281 Table of Contents Continental Disc Corporation (CDC) 75170 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series PL, PLV, LPL, LPLV (Angular seat) 75170 Number: or catalog number Insert, Full bolted #1 thru #9, Union 2U, 3U, 5U,6U Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on May 14, 1998 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 5.00 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 1 NPS 0.52 sq in 35 - 2160 psi VIII Div. 1 1.4 sq in 32 - 2160 psi 1.5 NPS VIII Div. 1 3.36 sq in 2 NPS 15 - 2160 psi VIII Div. 1 7.39 sq in 11 - 1440 psi 3 NPS VIII Div. 1 12.73 sq in 6 - 1440 psi 4 NPS VIII Div. 1 5 - 1440 psi 28.89 sq in 6 NPS VIII Div. 1 4 - 1440 psi 8 NPS 50.03 sq in VIII Div. 1 78.85 sq in 5 - 720 psi 10 NPS VIII Div. 1 12 NPS 113.1 sq in 5 - 720 psi VIII Div. 1 14 NPS 5 - 720 psi 137.9 sq in VIII Div. 1 5 - 720 psi 182.7 sq in 16 NPS VIII Div. 1 233.7 sq in 5 - 720 psi 18 NPS VIII Div. 1 5 - 720 psi 291 sq in 20 NPS VIII Div. 1 424.6 sq in 5 - 275 psi 24 NPS VIII Div. 1 5 - 275 psi 672 sq in 30 NPS Page 280 of 812 Effective Date: 2019-05-31

282 Table of Contents Continental Disc Corporation (CDC) 75181 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series MICRO-X-V, MX-9T-V Flat Seat (liquid) 75181 Number: or catalog number RHI, Unisert and Flat Seat, MX-9T, MX-9T-RH Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on May 13, 1998 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 1.10 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size VIII Div. 1 0.86 sq in 1 NPS 140 - 6000 psi VIII Div. 1 1.5 NPS 2.04 sq in 120 - 6000 psi VIII Div. 1 2 NPS 55 - 3600 psi 3.36 sq in VIII Div. 1 7.39 sq in 50 - 3600 psi 3 NPS VIII Div. 1 50 - 3600 psi 4 NPS 12.73 sq in VIII Div. 1 45 - 1440 psi 28.89 sq in 6 NPS VIII Div. 1 40 - 1440 psi 50.03 sq in 8 NPS VIII Div. 1 78.85 sq in 10 NPS 40 - 720 psi VIII Div. 1 35 - 720 psi 113.1 sq in 12 NPS VIII Div. 1 21 - 720 psi 137.9 sq in 14 NPS VIII Div. 1 182.7 sq in 18 - 720 psi 16 NPS VIII Div. 1 15 - 720 psi 233.7 sq in 18 NPS VIII Div. 1 15 - 720 psi 291 sq in 20 NPS VIII Div. 1 424.6 sq in 75 - 720 psi 24 NPS VIII Div. 1 583.2 sq in 64 - 720 psi 28 NPS VIII Div. 1 672 sq in 30 NPS 60 - 720 psi VIII Div. 1 56 - 720 psi 32 NPS 767 sq in VIII Div. 1 50 - 275 psi 975.9 sq in 36 NPS Page 281 of 812 Effective Date: 2019-05-31

283 Table of Contents Continental Disc Corporation (CDC) 75215 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series CDCV (FS) (No Options) 75215 or catalog number Number: RHI, UNISERT Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on October 27, 1998 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: .53 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Div. 1 1 NPS 0.86 sq in 30 - 2160 psi VIII Div. 1 1.5 NPS 2.04 sq in 18 - 2160 psi VIII Div. 1 10 - 2160 psi 2 NPS 3.36 sq in VIII Div. 1 3 NPS 7.39 sq in 6.5 - 1440 psi VIII Div. 1 7 - 1440 psi 4 NPS 12.73 sq in VIII Div. 1 6 NPS 5 - 1440 psi 28.89 sq in VIII Div. 1 5 - 720 psi 50.03 sq in 8 NPS VIII Div. 1 5 - 720 psi 10 NPS 78.85 sq in VIII Div. 1 4 - 720 psi 113.1 sq in 12 NPS VIII Div. 1 4 - 720 psi 137.89 sq in 14 NPS VIII Div. 1 182.65 sq in 16 NPS 4 - 720 psi VIII Div. 1 4 - 720 psi 233.71 sq in 18 NPS VIII Div. 1 20 NPS 4 - 275 psi 291.04 sq in VIII Div. 1 4 - 275 psi 24 NPS 424.56 sq in VIII Div. 1 4 - 40 psi 28 NPS 583.21 sq in VIII Div. 1 4 - 40 psi 30 NPS 671.96 sq in VIII Div. 1 4 - 40 psi 766.99 sq in 32 NPS VIII Div. 1 4 - 275 psi 975.91 sq in 36 NPS VIII Div. 1 1090 sq in 4 - 275 psi 38 NPS VIII Div. 1 1210 sq in 40 NPS 4 - 275 psi VIII Div. 1 4 - 275 psi 1336 sq in 42 NPS VIII Div. 1 44 NPS 1469 sq in 4 - 275 psi VIII Div. 1 1608 sq in 4 - 275 psi 46 NPS VIII Div. 1 4 - 275 psi 1753 sq in 48 NPS Page 282 of 812 Effective Date: 2019-05-31

284 Table of Contents Continental Disc Corporation (CDC) 75226 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series RCS (No Options) 75226 or catalog number Number: RCS Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on May 14, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .35 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Media Set Pressure Range Lift Outlet Size Flow Area VIII Div. 1 1 NPS 115 - 2160 psi 0.86 sq in VIII Div. 1 83 - 2160 psi 2.04 sq in 1.5 NPS VIII Div. 1 2 NPS 3.36 sq in 70 - 1440 psi VIII Div. 1 3 NPS 7.39 sq in 65 - 1440 psi VIII Div. 1 55 - 1440 psi 4 NPS 12.73 sq in VIII Div. 1 40 - 1440 psi 28.89 sq in 6 NPS VIII Div. 1 50.03 sq in 8 NPS 35 - 1440 psi VIII Div. 1 78.85 sq in 10 NPS 30 - 1440 psi VIII Div. 1 25 - 1440 psi 113.1 sq in 12 NPS VIII Div. 1 20 - 720 psi 14 NPS 137.9 sq in VIII Div. 1 20 - 720 psi 16 NPS 182.7 sq in VIII Div. 1 20 - 720 psi 233.7 sq in 18 NPS VIII Div. 1 291 sq in 20 - 720 psi 20 NPS VIII Div. 1 20 - 275 psi 424.6 sq in 24 NPS VIII Div. 1 20 - 275 psi 30 NPS 672 sq in VIII Div. 1 767 sq in 32 NPS 20 - 275 psi Certification Design Series MINTRX (No Options) 75237 Number: or catalog number MINTRX Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on May 13, 1998 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: .46 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Outlet Size Flow Area Code Section VIII Div. 1 50 - 275 psi 0.86 sq in 1 NPS VIII Div. 1 45 - 275 psi 2.04 sq in 1.5 NPS VIII Div. 1 2 NPS 35 - 275 psi 3.36 sq in VIII Div. 1 25 - 275 psi 7.39 sq in 3 NPS VIII Div. 1 4 NPS 12.73 sq in 20 - 275 psi VIII Div. 1 28.89 sq in 15 - 275 psi 6 NPS VIII Div. 1 15 - 275 psi 50.03 sq in 8 NPS Page 283 of 812 Effective Date: 2019-05-31

285 Table of Contents Continental Disc Corporation (CDC) 75248 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series ULTRX, ULTRX HP (No Options) 75248 Number: or catalog number ULTRX, ULTRX-T Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on May 14, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .36 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Lift Outlet Size Inlet Size Code Section Set Pressure Range Flow Area VIII Div. 1 1 NPS 0.86 sq in 100 - 2160 psi VIII Div. 1 1.5 NPS 2.04 sq in 85 - 2160 psi VIII Div. 1 65 - 1440 psi 2 NPS 3.36 sq in VIII Div. 1 7.39 sq in 50 - 1440 psi 3 NPS VIII Div. 1 45 - 1440 psi 4 NPS 12.73 sq in VIII Div. 1 6 NPS 28.89 sq in 40 - 720 psi VIII Div. 1 35 - 720 psi 50.03 sq in 8 NPS VIII Div. 1 15 - 720 psi 78.85 sq in 10 NPS VIII Div. 1 12 NPS 113.1 sq in 10 - 720 psi Certification Design Series CD30935 75259 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on January 09, 1999 Capacity Tests: Resistance Factor, 1 Size, Krgl Method of Establishing Relieving Capacity: 1.0 Unitless Certified Value: Air/Gas Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Set Pressure Range Media Code Section Outlet Size Inlet Size Flow Area VIII Div. 1 140 - 1000 psi 0.58 in 0.26 sq in .5 NPS 0.5 NPS Certification Design Series CD30936 75260 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on January 14, 1999 Capacity Tests: Resistance Factor, 1 Size, Krgl Method of Establishing Relieving Capacity: 1.0 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Set Pressure Range Media Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 0.44 sq in 0.75 in 140 - 1000 psi 0.75 NPS .75 NPS Page 284 of 812 Effective Date: 2019-05-31

286 Table of Contents Continental Disc Corporation (CDC) 75271 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series ULTRX (DD) 75271 or catalog number Number: ULTRX Double Disk Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on October 17, 1998 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: .97 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size Media VIII Div. 1 100 - 2160 psi 0.86 sq in 1 NPS VIII Div. 1 1.5 NPS 2.04 sq in 85 - 2160 psi VIII Div. 1 2 NPS 3.36 sq in 65 - 1440 psi VIII Div. 1 50 - 1440 psi 3 NPS 7.39 sq in VIII Div. 1 4 NPS 45 - 1440 psi 12.73 sq in VIII Div. 1 40 - 720 psi 28.89 sq in 6 NPS VIII Div. 1 50.03 sq in 8 NPS 35 - 720 psi VIII Div. 1 15 - 720 psi 10 NPS 78.85 sq in VIII Div. 1 113.1 sq in 12 NPS 10 - 720 psi Design Series Certification SRA (FS) 75282 Number: or catalog number SRA Tite seal, SRA screw type, SRA Insert, WSRA, SRA Union Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on April 15, 1999 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 3.59 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Media Inlet Size Outlet Size VIII Div. 1 35 - 3600 psi 0.04 sq in 0.125 NPS VIII Div. 1 0.07 sq in 35 - 3600 psi 0.25 NPS VIII Div. 1 0.375 NPS 0.14 sq in 35 - 3600 psi VIII Div. 1 0.5 NPS 0.23 sq in 35 - 3600 psi VIII Div. 1 0.75 NPS 15 - 2000 psi 0.43 sq in VIII Div. 1 10 - 2000 psi 0.72 sq in 1 NPS VIII Div. 1 1.28 sq in 10 - 1000 psi 1.25 NPS Page 285 of 812 Effective Date: 2019-05-31

287 Table of Contents Continental Disc Corporation (CDC) 75293 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series Standard-V (flat seat threaded) 75293 Number: or catalog number Tite-seal, screw type, throw-away Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on April 26, 1999 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 10.5 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Div. 1 85 - 15000 psi 0.125 NPS 0.01 sq in VIII Div. 1 85 - 15000 psi 0.25 NPS 0.04 sq in VIII Div. 1 85 - 15000 psi 0.1 sq in 0.375 NPS VIII Div. 1 85 - 15000 psi 0.5 NPS 0.17 sq in VIII Div. 1 29 - 5000 psi 0.29 sq in 0.75 NPS VIII Div. 1 29 - 5000 psi 0.52 sq in 1 NPS VIII Div. 1 29 - 5000 psi 1.25 NPS 1.05 sq in Certification Design Series Standard (angle seat threaded) 75305 Number: or catalog number Screw type Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on April 14, 1999 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 6.09 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Media Outlet Size Inlet Size Flow Area VIII Div. 1 65 - 3000 psi 0.01 sq in 0.125 NPS VIII Div. 1 0.04 sq in 65 - 3000 psi 0.25 NPS VIII Div. 1 0.375 NPS 0.1 sq in 65 - 3000 psi VIII Div. 1 0.5 NPS 0.17 sq in 65 - 3000 psi VIII Div. 1 0.75 NPS 50 - 3000 psi 0.29 sq in VIII Div. 1 29 - 3000 psi 0.52 sq in 1 NPS VIII Div. 1 1.05 sq in 22 - 3000 psi 1.25 NPS Page 286 of 812 Effective Date: 2019-05-31

288 Table of Contents Continental Disc Corporation (CDC) 75316 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series Standard-V (Angle seat threaded) 75316 Number: or catalog number Screw type Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on April 14, 1999 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 13.3 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Div. 1 85 - 3000 psi 0.125 NPS 0.01 sq in VIII Div. 1 85 - 3000 psi 0.25 NPS 0.04 sq in VIII Div. 1 85 - 3000 psi 0.1 sq in 0.375 NPS VIII Div. 1 85 - 3000 psi 0.5 NPS 0.17 sq in VIII Div. 1 50 - 3000 psi 0.29 sq in 0.75 NPS VIII Div. 1 29 - 3000 psi 0.52 sq in 1 NPS VIII Div. 1 29 - 3000 psi 1.25 NPS 1.05 sq in Certification Design Series Standard (flat seat threaded) 75327 Number: or catalog number Tite-seal, screw type, Throw-away Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on April 14, 1999 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 9.59 Unitless Certified Value: Air/Gas Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Media Outlet Size Inlet Size Flow Area VIII Div. 1 65 - 15000 psi 0.01 sq in 0.125 NPS VIII Div. 1 0.04 sq in 65 - 15000 psi 0.25 NPS VIII Div. 1 0.375 NPS 0.1 sq in 65 - 15000 psi VIII Div. 1 0.5 NPS 0.17 sq in 65 - 15000 psi VIII Div. 1 0.75 NPS 29 - 5000 psi 0.29 sq in VIII Div. 1 29 - 5000 psi 0.52 sq in 1 NPS VIII Div. 1 1.05 sq in 22 - 5000 psi 1.25 NPS Page 287 of 812 Effective Date: 2019-05-31

289 Table of Contents Continental Disc Corporation (CDC) 75338 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series CDCV (FS threaded) 75338 Number: or catalog number Tite-seal, screw type, throwaway Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on April 26, 1999 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 5.73 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Lift Inlet Size Set Pressure Range Media Flow Area Outlet Size VIII Div. 1 0.125 NPS 0.01 sq in 30 - 3000 psi VIII Div. 1 0.25 NPS 30 - 3000 psi 0.04 sq in VIII Div. 1 30 - 3000 psi 0.375 NPS 0.1 sq in VIII Div. 1 30 - 3000 psi 0.5 NPS 0.17 sq in VIII Div. 1 0.75 NPS 0.29 sq in 30 - 3000 psi VIII Div. 1 30 - 3000 psi 0.52 sq in 1 NPS VIII Div. 1 1.05 sq in 25 - 3000 psi 1.25 NPS Certification Design Series PL (CF) 75349 or catalog number Number: Clean Sweep CU8, CU9, CR8, CR9 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on July 19, 2000 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.57 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size VIII Div. 1 35 - 2160 psi 0.86 sq in 1 NPS VIII Div. 1 32 - 2160 psi 1.5 NPS 2.04 sq in VIII Div. 1 3.36 sq in 2 NPS 15 - 2160 psi VIII Div. 1 11 - 1440 psi 7.39 sq in 3 NPS VIII Div. 1 4 NPS 12.73 sq in 6 - 1440 psi VIII Div. 1 5 - 1440 psi 6 NPS 28.89 sq in VIII Div. 1 8 NPS 50.03 sq in 4 - 720 psi VIII Div. 1 5 - 720 psi 78.85 sq in 10 NPS VIII Div. 1 12 NPS 5 - 720 psi 113.1 sq in VIII Div. 1 5 - 720 psi 137.9 sq in 14 NPS VIII Div. 1 5 - 720 psi 182.7 sq in 16 NPS VIII Div. 1 5 - 720 psi 233.7 sq in 18 NPS VIII Div. 1 291 sq in 5 - 275 psi 20 NPS VIII Div. 1 5 - 275 psi 424.6 sq in 24 NPS VIII Div. 1 28 NPS 5 - 275 psi 583.2 sq in VIII Div. 1 30 NPS 672 sq in 5 - 275 psi VIII Div. 1 767 sq in 5 - 275 psi 32 NPS VIII Div. 1 36 NPS 5 - 275 psi 975.9 sq in Page 288 of 812 Effective Date: 2019-05-31

290 Table of Contents Continental Disc Corporation (CDC) 75350 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series PLV (CF) 75350 Number: or catalog number Clean Sweep CU8, CU9, CR8, CR9 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on July 18, 2000 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 2.64 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Div. 1 60 - 2160 psi 1 NPS 0.86 sq in VIII Div. 1 2.04 sq in 1.5 NPS 60 - 2160 psi VIII Div. 1 28 - 2160 psi 2 NPS 3.36 sq in VIII Div. 1 7.39 sq in 3 NPS 8 - 1440 psi VIII Div. 1 12.73 sq in 15 - 1440 psi 4 NPS VIII Div. 1 12 - 1440 psi 6 NPS 28.89 sq in VIII Div. 1 50.03 sq in 11 - 720 psi 8 NPS VIII Div. 1 8 - 720 psi 78.85 sq in 10 NPS VIII Div. 1 8 - 720 psi 12 NPS 113.1 sq in VIII Div. 1 137.9 sq in 8 - 720 psi 14 NPS VIII Div. 1 8 - 720 psi 16 NPS 182.7 sq in VIII Div. 1 233.7 sq in 18 NPS 8 - 720 psi VIII Div. 1 8 - 275 psi 20 NPS 291 sq in VIII Div. 1 8 - 275 psi 24 NPS 424.6 sq in VIII Div. 1 583.2 sq in 8 - 275 psi 28 NPS VIII Div. 1 30 NPS 275 sq in 8 - 275 psi VIII Div. 1 32 NPS 767 sq in 8 - 275 psi VIII Div. 1 8 - 275 psi 975.9 sq in 36 NPS Page 289 of 812 Effective Date: 2019-05-31

291 Table of Contents Continental Disc Corporation (CDC) 75361 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series CDC (CF) 75361 Number: or catalog number Clean-Sweep CU8, CU9. CR8, CR9 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on July 19, 2000 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.57 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size VIII Div. 1 1 NPS 0.86 sq in 25 - 2160 psi VIII Div. 1 22 - 2160 psi 1.5 NPS 2.04 sq in VIII Div. 1 3.36 sq in 2 NPS 7 - 2160 psi VIII Div. 1 7.39 sq in 6 - 1440 psi 3 NPS VIII Div. 1 5 - 1440 psi 4 NPS 12.73 sq in VIII Div. 1 28.89 sq in 3 - 1440 psi 6 NPS VIII Div. 1 2 - 720 psi 50.03 sq in 8 NPS VIII Div. 1 2 - 720 psi 10 NPS 78.85 sq in VIII Div. 1 113.1 sq in 2 - 720 psi 12 NPS VIII Div. 1 2 - 720 psi 14 NPS 137.9 sq in VIII Div. 1 182.7 sq in 16 NPS 2 - 720 psi VIII Div. 1 2 - 720 psi 18 NPS 233.7 sq in VIII Div. 1 2 - 275 psi 20 NPS 291 sq in VIII Div. 1 424.6 sq in 2 - 275 psi 24 NPS VIII Div. 1 30 NPS 672 sq in 2 - 275 psi VIII Div. 1 32 NPS 767 sq in 2 - 275 psi VIII Div. 1 2 - 275 psi 975.9 sq in 36 NPS Page 290 of 812 Effective Date: 2019-05-31

292 Table of Contents Continental Disc Corporation (CDC) 75372 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series CDCV (CF) 75372 Number: or catalog number Clean-sweep CU8, CU9, CR8, CR9 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on July 14, 2000 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 2.54 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Div. 1 30 - 2160 psi 1 NPS 0.86 sq in VIII Div. 1 2.04 sq in 1.5 NPS 18 - 2160 psi VIII Div. 1 10 - 2160 psi 2 NPS 3.36 sq in VIII Div. 1 7.39 sq in 3 NPS 6.5 - 1440 psi VIII Div. 1 12.73 sq in 7 - 1440 psi 4 NPS VIII Div. 1 5 - 1440 psi 6 NPS 28.89 sq in VIII Div. 1 50.03 sq in 5 - 720 psi 8 NPS VIII Div. 1 5 - 720 psi 78.85 sq in 10 NPS VIII Div. 1 4 - 720 psi 12 NPS 113.1 sq in VIII Div. 1 137.89 sq in 4 - 720 psi 14 NPS VIII Div. 1 4 - 720 psi 16 NPS 182.65 sq in VIII Div. 1 233.71 sq in 18 NPS 4 - 720 psi VIII Div. 1 4 - 275 psi 20 NPS 291.04 sq in VIII Div. 1 4 - 275 psi 24 NPS 424.56 sq in VIII Div. 1 583.21 sq in 4 - 275 psi 28 NPS VIII Div. 1 30 NPS 671.96 sq in 4 - 275 psi VIII Div. 1 32 NPS 766.99 sq in 4 - 275 psi VIII Div. 1 4 - 275 psi 975.91 sq in 36 NPS Page 291 of 812 Effective Date: 2019-05-31

293 Table of Contents Continental Disc Corporation (CDC) 75383 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series MICRO X, MX-9T (CF) 75383 Number: or catalog number CU8, CU9, CR8, CR9 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on July 12, 2000 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.52 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size VIII Div. 1 0.86 sq in 1 NPS 140 - 6000 psi VIII Div. 1 1.5 NPS 2.04 sq in 120 - 6000 psi VIII Div. 1 2 NPS 55 - 6000 psi 3.36 sq in VIII Div. 1 7.39 sq in 50 - 6000 psi 3 NPS VIII Div. 1 50 - 6000 psi 4 NPS 12.73 sq in VIII Div. 1 45 - 6000 psi 28.89 sq in 6 NPS VIII Div. 1 40 - 6000 psi 50.03 sq in 8 NPS VIII Div. 1 78.85 sq in 10 NPS 40 - 720 psi VIII Div. 1 35 - 720 psi 113.1 sq in 12 NPS VIII Div. 1 21 - 720 psi 137.9 sq in 14 NPS VIII Div. 1 182.7 sq in 18 - 720 psi 16 NPS VIII Div. 1 16 - 720 psi 233.7 sq in 18 NPS VIII Div. 1 15 - 720 psi 291 sq in 20 NPS VIII Div. 1 424.6 sq in 15 - 720 psi 24 NPS VIII Div. 1 583.2 sq in 15 - 720 psi 28 NPS VIII Div. 1 672 sq in 30 NPS 15 - 720 psi VIII Div. 1 15 - 720 psi 32 NPS 767 sq in VIII Div. 1 15 - 275 psi 975.9 sq in 36 NPS Page 292 of 812 Effective Date: 2019-05-31

294 Table of Contents Continental Disc Corporation (CDC) 75394 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series Micro-X-V, MX-9T-V (CF) 75394 or catalog number Number: Clean-sweep, CU8, CU9, CR8, CR9 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on July 18, 2000 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.74 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size Media N/A 1 NPS 0.86 sq in 140 - 6000 psi N/A 120 - 6000 psi 2.04 sq in 1.5 NPS N/A 3.36 sq in 55 - 3600 psi 2 NPS N/A 3 NPS 7.39 sq in 50 - 3600 psi N/A 4 NPS 12.73 sq in 50 - 3600 psi N/A 45 - 1440 psi 6 NPS 28.89 sq in N/A 40 - 1440 psi 50.03 sq in 8 NPS N/A 78.85 sq in 10 NPS 40 - 720 psi N/A 113.1 sq in 12 NPS 35 - 720 psi N/A 21 - 720 psi 137.9 sq in 14 NPS N/A 18 - 720 psi 16 NPS 182.7 sq in N/A 18 NPS 233.7 sq in 16 - 720 psi N/A 15 - 720 psi 291 sq in 20 NPS N/A 24 NPS 15 - 720 psi 424.6 sq in N/A 583.2 sq in 15 - 720 psi 28 NPS N/A 15 - 720 psi 672 sq in 30 NPS N/A 15 - 720 psi 32 NPS 767 sq in N/A 975.9 sq in 36 NPS 15 - 275 psi Certification Design Series SRA RVI (FS) 75406 or catalog number Number: RVI, RVI Tite-Seal, RVI Screw Type Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on July 28, 2000 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 4.71 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Inlet Size Flow Area Set Pressure Range Media Code Section Lift VIII Div. 1 35 - 1000 psi 0.125 NPS 1/8 - 1-1/4 NPS 0.03 sq in VIII Div. 1 35 - 2000 psi 0.05 sq in 1/4 - 1 1/4 NPS 0.25 NPS VIII Div. 1 3/8 - 1 1/4 NPS 0.375 NPS 0.1 sq in 35 - 2000 psi VIII Div. 1 0.5 NPS 20 - 2000 psi 0.17 sq in 1/2 - 1 1/4 NPS VIII Div. 1 0.75 NPS 3/4 - 1 1/4 NPS 15 - 2000 psi 0.29 sq in VIII Div. 1 10 - 2000 psi 1 NPS 1, 1 1/4 NPS 0.52 sq in N/A 10 - 1000 psi 1.06 sq in 1 1/4 NPS 1.25 NPS Page 293 of 812 Effective Date: 2019-05-31

295 Table of Contents Continental Disc Corporation (CDC) 75428 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series VRD 75428 Number: or catalog number VRD Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on July 02, 2002 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 0.48 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section Media VIII Div. 1 13 - 1000 psi 1 NPS 0.86 sq in VIII Div. 1 10 - 1000 psi 1.5 NPS 2.04 sq in VIII Div. 1 3.36 sq in 9 - 1000 psi 2 NPS VIII Div. 1 9 - 1000 psi 3 NPS 7.39 sq in VIII Div. 1 9 - 800 psi 4 NPS 12.73 sq in VIII Div. 1 8 - 500 psi 28.89 sq in 6 NPS VIII Div. 1 50.03 sq in 19 - 350 psi 8 NPS Certification Design Series Sanitrx, Sanitrx LP-NA (liquid) 75439 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on December 17, 2002 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 0.32 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size VIII Div. 1 25 - 250 psi 0.493 sq in 1 NPS VIII Div. 1 10 - 60 psi 1.5 NPS 1.18 sq in VIII Div. 1 2 NPS 10 - 60 psi 2.25 sq in VIII Div. 1 5.49 sq in 3 NPS 10 - 60 psi VIII Div. 1 9.77 sq in 10 - 60 psi 4 NPS Certification Design Series Sanitrx LP, Sanitrx LP-NA 75440 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on December 17, 2002 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.29 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Lift Set Pressure Range Media Code Section Inlet Size VIII Div. 1 1 NPS 25 - 250 psi 0.493 sq in VIII Div. 1 10 - 60 psi 1.18 sq in 1.5 NPS VIII Div. 1 2 NPS 2.25 sq in 10 - 60 psi VIII Div. 1 5.49 sq in 10 - 60 psi 3 NPS VIII Div. 1 10 - 60 psi 9.77 sq in 4 NPS Page 294 of 812 Effective Date: 2019-05-31

296 Table of Contents Continental Disc Corporation (CDC) 75451 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series Sanitrx , Sanitrx NA (liquid) 75451 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on January 07, 2003 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 1.60 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size VIII Div. 1 25 - 1500 psi 1 NPS 0.493 sq in VIII Div. 1 1.5 NPS 1.18 sq in 14 - 1500 psi VIII Div. 1 2 NPS 11 - 1000 psi 2.25 sq in VIII Div. 1 5.49 sq in 10 - 1000 psi 3 NPS VIII Div. 1 10 - 1000 psi 4 NPS 9.77 sq in Certification Design Series Sanitrx , Sanitrx-NA(Air/Gas) 75462 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on January 07, 2003 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.13 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Code Section Media Flow Area Outlet Size Inlet Size Lift VIII Div. 1 0.493 sq in 25 - 1500 psi 1 NPS VIII Div. 1 1.18 sq in 14 - 1500 psi 1.5 NPS VIII Div. 1 2.25 sq in 2 NPS 11 - 1000 psi VIII Div. 1 10 - 1000 psi 3 NPS 5.49 sq in VIII Div. 1 10 - 1000 psi 9.77 sq in 4 NPS Page 295 of 812 Effective Date: 2019-05-31

297 Table of Contents Continental Disc Corporation (CDC) 75473 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series MICRO X-V(DD), MICRO X, MX-9T-V, MX-9T 75473 or catalog number Number: UNISERT (DD), MX-9T (DD) Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on January 02, 2003 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 5.59 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Media Set Pressure Range Lift Outlet Size Flow Area VIII Div. 1 1 NPS 140 - 6000 psi 0.86 sq in VIII Div. 1 120 - 6000 psi 2.04 sq in 1.5 NPS VIII Div. 1 2 NPS 3.36 sq in 55 - 3600 psi VIII Div. 1 3 NPS 7.39 sq in 50 - 3600 psi VIII Div. 1 50 - 3600 psi 4 NPS 12.73 sq in VIII Div. 1 45 - 1440 psi 28.89 sq in 6 NPS VIII Div. 1 50.03 sq in 8 NPS 40 - 1440 psi VIII Div. 1 78.85 sq in 10 NPS 40 - 720 psi VIII Div. 1 35 - 720 psi 113.1 sq in 12 NPS VIII Div. 1 21 - 720 psi 14 NPS 137.9 sq in VIII Div. 1 18 - 720 psi 16 NPS 182.6 sq in VIII Div. 1 16 - 720 psi 233.7 sq in 18 NPS VIII Div. 1 291 sq in 15 - 720 psi 20 NPS VIII Div. 1 15 - 720 psi 424.6 sq in 24 NPS VIII Div. 1 15 - 720 psi 28 NPS 583.2 sq in VIII Div. 1 30 NPS 15 - 720 psi 672 sq in VIII Div. 1 767 sq in 32 NPS 15 - 720 psi VIII Div. 1 975.9 sq in 15 - 275 psi 36 NPS Certification Design Series CD 31074 75484 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on January 14, 2003 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 10.0 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Lift Set Pressure Range Media Code Section Inlet Size VIII Div. 1 0.3125 NPS 250 - 1200 psi 0.037 sq in VIII Div. 1 250 - 1200 psi 0.117 sq in 0.5 NPS VIII Div. 1 0.75 NPS 0.29 sq in 150 - 1000 psi VIII Div. 1 0.462 sq in 100 - 1000 psi 1 NPS VIII Div. 1 50 - 1000 psi 0.688 sq in 1.25 NPS Page 296 of 812 Effective Date: 2019-05-31

298 Table of Contents Continental Disc Corporation (CDC) 75495 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series Standard V (LL) 75495 Number: or catalog number Insert (LL, HL), Full bolted #1 through #9 (LL, HL), Union 2U, 3U, 5U, 6U(UL) Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on June 10, 2003 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.88 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Inlet Size Lift Media Code Section Flow Area Outlet Size VIII Div. 1 30 - 6000 psi 0.72 sq in 1 NPS VIII Div. 1 1.5 NPS 1.77 sq in 23 - 6000 psi VIII Div. 1 2 NPS 2.95 sq in 10 - 6000 psi [HL] VIII Div. 1 3.36 sq in 10 - 4000 psi VIII Div. 1 9 - 6000 psi 7.39 sq in 3 NPS VIII Div. 1 4 NPS 11.4 sq in [HL] 7 - 6000 psi VIII Div. 1 12.7 sq in 7 - 1440 psi VIII Div. 1 6 NPS 28.8 sq in 5 - 1440 psi VIII Div. 1 5 - 1440 psi 8 NPS 50 sq in VIII Div. 1 5 - 720 psi 78.85 sq in 10 NPS VIII Div. 1 113 sq in 12 NPS 4 - 720 psi VIII Div. 1 137 sq in 14 NPS 4 - 720 psi VIII Div. 1 4 - 720 psi 182 sq in 16 NPS VIII Div. 1 4 - 720 psi 18 NPS 233 sq in VIII Div. 1 20 NPS 291 sq in 4 - 720 psi VIII Div. 1 4 - 275 psi 24 NPS 424 sq in VIII Div. 1 30 NPS 4 - 275 psi 671 sq in Design Series Certification CDCV , LDV (LL) 75507 Number: or catalog number Insert, Full bolted #1 - #9, Union 2U, 3U, 5U, 6U Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on June 10, 2003 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 2.80 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Set Pressure Range Outlet Size Inlet Size Media Flow Area VIII Div. 1 1 NPS 0.72 sq in 30 - 2160 psi VIII Div. 1 25 - 2160 psi 1.5 NPS 1.77 sq in VIII Div. 1 10 - 2160 psi 2 NPS 3.36 sq in VIII Div. 1 7 - 1440 psi 7.39 sq in 3 NPS VIII Div. 1 12.73 sq in 4 NPS 7 - 1440 psi VIII Div. 1 28.89 sq in 5 - 1440 psi 6 NPS VIII Div. 1 5 - 1440 psi 50.03 sq in 8 NPS VIII Div. 1 5 - 720 psi 10 NPS 78.85 sq in VIII Div. 1 113.1 sq in 4 - 720 psi 12 NPS VIII Div. 1 14 NPS 137.9 sq in 4 - 720 psi VIII Div. 1 16 NPS 4 - 720 psi 182.7 sq in VIII Div. 1 4 - 720 psi 233.7 sq in 18 NPS VIII Div. 1 291 sq in 4 - 720 psi 20 NPS VIII Div. 1 4 - 275 psi 425.6 sq in 24 NPS VIII Div. 1 4 - 275 psi 672 sq in 30 NPS Page 297 of 812 Effective Date: 2019-05-31

299 Table of Contents Continental Disc Corporation (CDC) 75518 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series RCS (DD) 75518 Number: or catalog number RCS (DD) Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on September 23, 2003 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.60 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Lift Inlet Size Set Pressure Range Media Flow Area Outlet Size VIII Div. 1 1 NPS 0.86 sq in 115 - 2160 psi VIII Div. 1 1.5 NPS 83 - 2160 psi 2.04 sq in VIII Div. 1 70 - 1440 psi 2 NPS 3.36 sq in VIII Div. 1 65 - 1440 psi 3 NPS 7.39 sq in VIII Div. 1 12.73 sq in 4 NPS 55 - 1440 psi VIII Div. 1 40 - 1440 psi 28.89 sq in 6 NPS VIII Div. 1 8 NPS 50.03 sq in 35 - 1440 psi VIII Div. 1 30 - 1440 psi 78.85 sq in 10 NPS VIII Div. 1 25 - 1440 psi 113.1 sq in 12 NPS VIII Div. 1 14 NPS 137.9 sq in 20 - 720 psi VIII Div. 1 182.7 sq in 20 - 720 psi 16 NPS VIII Div. 1 233.7 sq in 20 - 720 psi 18 NPS VIII Div. 1 291 sq in 20 - 720 psi 20 NPS VIII Div. 1 20 - 275 psi 424.6 sq in 24 NPS VIII Div. 1 20 - 275 psi 30 NPS 672 sq in VIII Div. 1 767 sq in 20 - 275 psi 32 NPS Design Series Certification STAR X, STAR X HP (gas) 75529 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on July 21, 2008 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.29 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Flow Area Code Section Outlet Size VIII Div. 1 18 - 275 psi 0.86 sq in 1 NPS VIII Div. 1 16 - 275 psi 1.5 NPS 2.04 sq in VIII Div. 1 2 NPS 15 - 275 psi 3.36 sq in VIII Div. 1 14 - 275 psi 7.39 sq in 3 NPS VIII Div. 1 13 - 275 psi 12.73 sq in 4 NPS VIII Div. 1 12 - 275 psi 28.89 sq in 6 NPS Page 298 of 812 Effective Date: 2019-05-31

300 Table of Contents Continental Disc Corporation (CDC) 75530 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series STAR X, STAR X HP (liquid) 75530 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on July 21, 2008 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 0.38 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size VIII Div. 1 1 NPS 0.86 sq in 18 - 275 psi VIII Div. 1 1.5 NPS 2.04 sq in 16 - 275 psi VIII Div. 1 15 - 275 psi 2 NPS 3.36 sq in VIII Div. 1 3 NPS 7.39 sq in 14 - 275 psi VIII Div. 1 13 - 275 psi 4 NPS 12.73 sq in VIII Div. 1 6 NPS 12 - 275 psi 28.89 sq in Design Series Certification MINTRX (liquid) 75541 Number: or catalog number MINTRX Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on July 21, 2008 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 0.50 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size VIII Div. 1 50 - 275 psi 1 NPS 0.86 sq in VIII Div. 1 45 - 275 psi 2.04 sq in 1.5 NPS VIII Div. 1 3.36 sq in 35 - 275 psi 2 NPS VIII Div. 1 7.39 sq in 25 - 275 psi 3 NPS VIII Div. 1 12.73 sq in 4 NPS 20 - 275 psi VIII Div. 1 15 - 275 psi 6 NPS 28.89 sq in VIII Div. 1 15 - 275 psi 50.03 sq in 8 NPS Page 299 of 812 Effective Date: 2019-05-31

301 Table of Contents Continental Disc Corporation (CDC) 75552 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series MINTRX (gas) 75552 or catalog number Number: MINTRX Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on July 21, 2008 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.45 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Media Set Pressure Range Lift Outlet Size Flow Area VIII Div. 1 1 NPS 50 - 275 psi 0.86 sq in VIII Div. 1 45 - 275 psi 2.04 sq in 1.5 NPS VIII Div. 1 2 NPS 3.36 sq in 35 - 275 psi VIII Div. 1 3 NPS 7.39 sq in 25 - 275 psi VIII Div. 1 20 - 275 psi 12.73 sq in 4 NPS VIII Div. 1 6 NPS 15 - 275 psi 28.89 sq in VIII Div. 1 15 - 275 psi 50.03 sq in 8 NPS Design Series Certification SANITRX MP (SF, NA, IS) (liquid) 75563 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on November 03, 2008 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 1.6 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Media Code Section Flow Area Lift Inlet Size Outlet Size VIII Div. 1 35 - 100 psi 0.493 sq in 1 NPS VIII Div. 1 1.5 NPS 1.18 sq in 15 - 100 psi VIII Div. 1 15 - 100 psi 2.25 sq in 2 NPS VIII Div. 1 5.49 sq in 3 NPS 10 - 60 psi Certification Design Series SANITRX MP (SF, NA, IS) (gas) 75574 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on November 20, 2008 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.13 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Media Set Pressure Range Lift Outlet Size Code Section Inlet Size VIII Div. 1 1 NPS 35 - 100 psi 0.493 sq in VIII Div. 1 1.5 NPS 1.18 sq in 15 - 100 psi VIII Div. 1 2.25 sq in 15 - 100 psi 2 NPS VIII Div. 1 3 NPS 10 - 60 psi 5.49 sq in Page 300 of 812 Effective Date: 2019-05-31

302 Table of Contents Continental Disc Corporation (CDC) 75585 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series HPX (FS)(GAS) 75585 or catalog number Number: Star-X, HPX, HPX-RH, HPX-PT, HPX-PT-RH, VRD, ULTRX Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on October 21, 2009 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 0.29 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Outlet Size Media Set Pressure Range Inlet Size VIII Div. 1 15 - 2160 psi 0.86 sq in 1 NPS VIII Div. 1 1.5 NPS 2.04 sq in 10 - 2160 psi VIII Div. 1 2 NPS 3.36 sq in 10 - 1440 psi VIII Div. 1 9 - 1440 psi 3 NPS 7.39 sq in VIII Div. 1 3.5 NPS 9 - 1440 psi 9.89 sq in VIII Div. 1 9 - 1440 psi 4 NPS 12.73 sq in VIII Div. 1 28.89 sq in 6 NPS 9 - 720 psi VIII Div. 1 9 - 720 psi 8 NPS 50.03 sq in VIII Div. 1 9 - 720 psi 78.8 sq in 10 NPS VIII Div. 1 9 - 720 psi 113.1 sq in 12 NPS Certification Design Series HPX (FS)(Liquid) 75596 Number: or catalog number Star-X, HPX, HPX-RH, HPX-PT, HPX-PT-RH, VRD, ULTRX Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on October 21, 2009 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 0.38 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Media Inlet Size Outlet Size VIII Div. 1 15 - 2160 psi 0.86 sq in 1 NPS VIII Div. 1 10 - 2160 psi 2.04 sq in 1.5 NPS VIII Div. 1 10 - 1440 psi 3.36 sq in 2 NPS VIII Div. 1 9 - 1440 psi 7.39 sq in 3 NPS VIII Div. 1 9.89 sq in 9 - 1440 psi 3.5 NPS VIII Div. 1 9 - 1440 psi 12.73 sq in 4 NPS VIII Div. 1 6 NPS 9 - 720 psi 28.89 sq in VIII Div. 1 8 NPS 50.03 sq in 9 - 720 psi VIII Div. 1 78.8 sq in 9 - 720 psi 10 NPS VIII Div. 1 12 NPS 9 - 720 psi 113.1 sq in Page 301 of 812 Effective Date: 2019-05-31

303 Table of Contents Continental Disc Corporation (CDC) 75608 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series HPX Sanitary, Sanitrx HPX, Sanitrx LPX (SF,NA,IS)(Gas) 75608 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on October 29, 2009 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.13 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Lift Inlet Size Set Pressure Range Media Flow Area Outlet Size VIII Div. 1 0.75 NPS 0.265 sq in 40 - 400 psi VIII Div. 1 1 NPS 25 - 300 psi 0.493 sq in VIII Div. 1 4 - 200 psi 1.5 NPS 1.18 sq in VIII Div. 1 4 - 150 psi 2 NPS 2.25 sq in VIII Div. 1 4 - 100 psi 3 NPS 5.49 sq in Design Series Certification HPX Sanitary, Sanitrx HPX, Sanitrx LPX (SF,NA,IS)(Liquid) 75619 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on October 29, 2009 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 1.6 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Outlet Size Inlet Size Lift Set Pressure Range Code Section Media VIII Div. 1 40 - 400 psi 0.265 sq in 0.75 NPS VIII Div. 1 25 - 300 psi 0.493 sq in 1 NPS VIII Div. 1 1.5 NPS 1.18 sq in 4 - 200 psi VIII Div. 1 4 - 150 psi 2 NPS 2.25 sq in VIII Div. 1 5.49 sq in 3 NPS 4 - 100 psi Design Series Certification LOTRX (Gas) 75620 Number: or catalog number LOTRX Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on January 28, 2010 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.42 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size VIII Div. 1 2 - 40 psi 0.86 sq in 1 NPS VIII Div. 1 2 - 30 psi 2.04 sq in 1.5 NPS VIII Div. 1 2 NPS 2 - 25 psi 3.36 sq in VIII Div. 1 1 - 22 psi 7.39 sq in 3 NPS VIII Div. 1 4 NPS 12.73 sq in 1 - 22 psi VIII Div. 1 28.89 sq in 1 - 20 psi 6 NPS VIII Div. 1 1 - 35 psi 50.03 sq in 8 NPS Page 302 of 812 Effective Date: 2019-05-31

304 Table of Contents Continental Disc Corporation (CDC) 75631 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series LOTRX (Liquid) 75631 or catalog number Number: LOTRX Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on February 11, 2010 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 0.42 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Inlet Size Code Section Flow Area Set Pressure Range Lift Outlet Size VIII Div. 1 1 NPS 0.86 sq in 2 - 40 psi VIII Div. 1 2.04 sq in 1.5 NPS 2 - 30 psi VIII Div. 1 2 - 25 psi 3.36 sq in 2 NPS VIII Div. 1 7.39 sq in 1 - 22 psi 3 NPS VIII Div. 1 4 NPS 12.73 sq in 1 - 22 psi VIII Div. 1 6 NPS 28.89 sq in 1 - 20 psi VIII Div. 1 1 - 35 psi 8 NPS 50.03 sq in Certification Design Series CDC, CDCV (DD) 75642 Number: or catalog number Unisert double disk Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on August 13, 2010 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.81 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Flow Area Outlet Size Lift Code Section Inlet Size Media VIII Div. 1 30 - 2160 psi 0.86 sq in 1 NPS VIII Div. 1 2.04 sq in 27 - 2160 psi 1.5 NPS VIII Div. 1 15 - 2160 psi 3.36 sq in 2 NPS VIII Div. 1 6.5 - 1440 psi 3 NPS 7.39 sq in VIII Div. 1 4 NPS 7 - 1440 psi 12.7 sq in VIII Div. 1 5 - 1440 psi 28.8 sq in 6 NPS VIII Div. 1 8 NPS 50 sq in 5 - 720 psi VIII Div. 1 5 - 720 psi 78.8 sq in 10 NPS VIII Div. 1 113 sq in 12 NPS 4 - 720 psi VIII Div. 1 14 NPS 137 sq in 3 - 720 psi VIII Div. 1 16 NPS 182 sq in 1.3 - 720 psi VIII Div. 1 4 - 720 psi 233 sq in 18 NPS VIII Div. 1 4 - 275 psi 291 sq in 20 NPS VIII Div. 1 4 - 275 psi 24 NPS 424 sq in VIII Div. 1 4 - 275 psi 583 sq in 28 NPS VIII Div. 1 4 - 275 psi 671 sq in 30 NPS VIII Div. 1 4 - 275 psi 766 sq in 32 NPS VIII Div. 1 36 NPS 975 sq in 4 - 275 psi VIII Div. 1 38 NPS 4 - 275 psi 1089 sq in VIII Div. 1 4 - 275 psi 1209 sq in 40 NPS VIII Div. 1 1336 sq in 4 - 275 psi 42 NPS VIII Div. 1 4 - 275 psi 1469 sq in 44 NPS VIII Div. 1 1608 sq in 4 - 275 psi 46 NPS VIII Div. 1 4 - 275 psi 1753 sq in 48 NPS Page 303 of 812 Effective Date: 2019-05-31

305 Table of Contents Continental Disc Corporation (CDC) 75653 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series CD 31327 75653 or catalog number Number: CD 31327 Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on August 12, 2010 Capacity Tests: Resistance Factor, 1 Size, Krgl Method of Establishing Relieving Capacity: 18 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size Media VIII Div. 1 0.13 sq in 0.5 NPS 22 - 175 psi Certification Design Series HPX (DD) 75664 Number: or catalog number HPX (DD), ULTRX Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on June 22, 2011 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 0.97 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Media Lift Code Section Inlet Size Set Pressure Range Outlet Size VIII 1 NPS 0.86 sq in 15 - 2160 psi VIII 10 - 2160 psi 1.5 NPS 2.04 sq in VIII 3.36 sq in 10 - 1440 psi 2 NPS VIII 9 - 1440 psi 7.39 sq in 3 NPS VIII Div. 1 9 - 1440 psi 9.89 sq in 3.5 NPS VIII 4 NPS 12.7 sq in 9 - 1440 psi VIII 28.8 sq in 9 - 720 psi 6 NPS VIII 50 sq in 8 NPS 9 - 720 psi VIII Div. 1 78.8 sq in 9 - 720 psi 10 NPS VIII Div. 1 12 NPS 113.1 sq in 9 - 720 psi Design Series Certification SANITRX HPX II (SF, NA, IS)(GAS) 75675 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on June 17, 2011 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.60 Unitless Certified Value: Air Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Outlet Size Inlet Size Code Section Lift Set Pressure Range VIII 300 - 1500 psi 0.49 sq in 1 NPS VIII 200 - 1500 psi 1.5 NPS 1.18 sq in VIII 2.25 sq in 150 - 1000 psi 2 NPS VIII 100 - 1000 psi 5.49 sq in 3 NPS VIII 10 - 1000 psi 9.77 sq in 4 NPS Page 304 of 812 Effective Date: 2019-05-31

306 Table of Contents Continental Disc Corporation (CDC) 75686 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series SANITRX HPX II (SF, NA, IS)(Liquid) 75686 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on June 17, 2011 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 1.88 Unitless Certified Value: Air/Gas & Liquid Test Medium: Liquid (Krl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Outlet Size Set Pressure Range Flow Area Media Code Section Inlet Size VIII 1 NPS 0.49 sq in 300 - 1500 psi VIII 200 - 1500 psi 1.18 sq in 1.5 NPS VIII 150 - 1000 psi 2.25 sq in 2 NPS VIII 100 - 1000 psi 3 NPS 5.49 sq in VIII 9.77 sq in 4 NPS 10 - 1000 psi Design Series Certification SRA (Gas) 75697 or catalog number Number: Screw Type Tite-Seal Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on October 13, 2012 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .85 Unitless Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Flow Area Code Section Outlet Size VIII Div. 1 Air 35 - 1000 psi 0.049 sq in Top 0.25 NPS VIII Div. 1 Air Top 35 - 1000 psi 0.11 sq in 0.375 NPS VIII Div. 1 Air 35 - 1000 psi 0.169 sq in Top 0.5 NPS Certification Design Series SRA (Liquid) 75709 Number: or catalog number Screw Type Tite-Seal Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on October 13, 2012 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .65 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Set Pressure Range Code Section Outlet Size Inlet Size Flow Area Media VIII Div. 1 Water 35 - 1000 psi 0.049 sq in Top 0.25 NPS VIII Div. 1 Water 35 - 1000 psi 0.11 sq in Top 0.375 NPS VIII Div. 1 Water 35 - 1000 psi 0.169 sq in Top 0.5 NPS Page 305 of 812 Effective Date: 2019-05-31

307 Table of Contents Continental Disc Corporation (CDC) 75710 NB#: 3160 West Heartland Drive, Liberty, MO 64068 United States location: Certification Design Series WMP (Gas) 75710 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on October 31, 2012 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .80 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Set Pressure Range Media Inlet Size Code Section Outlet Size Lift VIII Div. 1 Air 0.006 sq in 1200 - 15000 psi 0.125 NPS Top VIII Div. 1 Air 0.25 NPS 0.026 sq in 800 - 15000 psi Top VIII Div. 1 Air 500 - 15000 psi 0.375 NPS Top 0.059 sq in VIII Div. 1 Air 0.5 NPS Top 0.082 sq in 450 - 15000 psi VIII Div. 1 Air 0.168 sq in 0.75 NPS Top 350 - 7500 psi VIII Div. 1 Air Top 1 NPS 300 - 6000 psi 0.332 sq in Certification Design Series WMP (Liquid) 75721 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on October 31, 2012 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .59 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Lift Set Pressure Range Media Inlet Size Code Section VIII Div. 1 Water 0.125 NPS 1200 - 15000 psi Top 0.006 sq in VIII Div. 1 Water Top 800 - 15000 psi 0.026 sq in 0.25 NPS VIII Div. 1 Water 500 - 15000 psi 0.059 sq in Top 0.375 NPS VIII Div. 1 Water 0.5 NPS Top 0.082 sq in 450 - 15000 psi VIII Div. 1 Water 350 - 7500 psi 0.75 NPS Top 0.168 sq in VIII Div. 1 Water 300 - 6000 psi 0.332 sq in Top 1 NPS Design Series Certification CD31159 75732 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at Continental Disc. Corp. on May 09, 2017 Capacity Tests: Resistance Factor, 1 Size, Krgl Method of Establishing Relieving Capacity: 20.0 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size VIII Div. 1 15 - 500 psi 1.13 sq in 2 NPS Page 306 of 812 Effective Date: 2019-05-31

308 Table of Contents Continental NH3 Products Co., Inc. (CNT) 12003 NB#: 130 Yorktown, Dallas, TX 75208 United States location: Continental NH3 Products Co., Inc. (CNT) 130 Yorktown, Dallas, TX 75208 United States location: Certification Design Series AA-402VA 12003 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on March 02, 1987 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 2057 SCFM Certified Value: Air/Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media Code Section VIII Air Top 0.44 sq in 0.75 NPS 250 - 250 psi 0.75 in Design Series Certification AA-402VA (265 psig) 12025 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 20, 1996 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 2130 SCFM Certified Value: Air/Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Lift Outlet Size Inlet Size Flow Area Set Pressure Range VIII Air 265 - 265 psi 0.75 in 0.44 sq in Top 0.75 NPS Certification Design Series AA-417-AB 12036 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on October 14, 1998 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 5886 SCFM Certified Value: Air/Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 1.25 in 250 - 250 psi 1.25 NPS Top 1.22 sq in Page 307 of 812 Effective Date: 2019-05-31

309 Table of Contents Control Devices, LLC (CDV) 14016 NB#: 1555 Larkin Williams Road, Fenton, MO 63026 United States location: Acceptable Abbrev.: CD STL, MO Control Devices, LLC (CDV) 1555 Larkin Williams Road, Fenton, MO 63026 United States location: Acceptable Abbrev.: CD STL, MO Certification Design Series ST 14016 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on May 12, 1988 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .759 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media Code Section VIII Div. 1 Air 0.049 sq in 0.125 - 0.375 NPS Side 0.25 in 0.138 in 25 - 350 psi Certification Design Series SA 14038 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on April 01, 1996 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .716 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Media Code Section Flow Area Outlet Size Inlet Size Lift VIII Div. 1 Air 0.088 in 0.25 in 0.049 sq in 50 - 350 psi 0.125 - 0.375 NPS Side Certification Design Series SP 14049 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 12, 1992 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .276 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Inlet Size Code Section Media Lift Set Pressure Range VIII Div. 1 Air 75 - 250 psi 0.11 in 0.156 in 0.0191 sq in Side 0.125 - 0.25 NPS Page 308 of 812 Effective Date: 2019-05-31

310 Table of Contents Control Devices, LLC (CDV) 14050 NB#: 1555 Larkin Williams Road, Fenton, MO 63026 United States location: Acceptable Abbrev.: CD STL, MO Certification Design Series SF 14050 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on January 27, 1993 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.526 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Air 0.17 in 50 - 250 psi 0.5 NPS Side 0.11 sq in 0.375 in Design Series Certification SB 14061 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 26, 1996 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.31 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Flow Area Outlet Size Lift Set Pressure Range Media Code Section VIII Div. 1 Air 0.5 - 0.75 NPS 25 - 300 psi 0.267 in Side 0.531 in 0.221 sq in Design Series Certification SW 14072 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 16, 1996 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 6.92 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Flow Area Media Code Section Outlet Size Inlet Size Lift VIII Div. 1 Air 0.765 in 0.314 in 25 - 300 psi 1 - 1.25 NPS Side 0.46 sq in Page 309 of 812 Effective Date: 2019-05-31

311 Table of Contents Control Devices, LLC (CDV) 14083 NB#: 1555 Larkin Williams Road, Fenton, MO 63026 United States location: Acceptable Abbrev.: CD STL, MO Certification Design Series SCB 14083 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on April 14, 1997 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.26 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Div. 1 Air 25 - 300 psi 0.254 in 0.53 in 0.2206 sq in .75, 1 NPS 0.5 - 0.75 NPS Design Series Certification SN 14094 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 06, 1998 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.75 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size VIII Air 50 - 350 psi 0.15 in 0.375 in 0.11 sq in Side 0.5 NPS Page 310 of 812 Effective Date: 2019-05-31

312 Table of Contents Crosby Valve, LLC (CVM) 15017 NB#: 55 Cabot Blvd, Mansfield, MA 02048 United States location: Acceptable Abbrev.: CVM Crosby Valve, LLC (CVM) 55 Cabot Blvd, Mansfield, MA 02048 United States location: Acceptable Abbrev.: CVM Certification Design Series HA-HAA (Class 1) 15017 or catalog number Number: Safety Valve Type Classification: Sec. III at Crosby Valve & Gage on February 17, 1968 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Adjustable by Dual Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Inlet Size Set Pressure Range Media Lift Outlet Size Flow Area III Steam [R4] 4.5835 in 6 NPS 10, Dual 8 NPS 16.5 sq in 1.146 in 15 - 3000 psi III Steam 15 - 3000 psi 12.174 sq in [Q] 3.937 in 0.984 in 8, 8 dual NPS 6 - 8 NPS III Steam 15 - 3000 psi 1.128 in [R] 4.513 in 16 sq in 8,10,8 dual NPS III Steam [R2] 4.75 in 8 NPS 10 NPS 17.72 sq in 1.188 in 15 - 3000 psi III Steam 15 - 3000 psi 28.27 sq in 1.5 in 12,10 dual, 12 dual NPS [T] 6 in Certification Design Series HB (Class 1) 15028 Number: or catalog number Safety Valve Type Classification: Sec. III at Crosby Valve & Gage on November 25, 1968 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .869 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Adjustable by Dual Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Set Pressure Range Lift Flow Area Outlet Size Inlet Size III Steam 15 - 3000 psi 0.125 in [E] 0.5 in 0.196 sq in 2, 2-1/2 NPS 1.5 NPS III Steam 15 - 3000 psi 0.14 in 0.563 in 0.249 sq in III Steam 0.156 in 2 - 3 NPS [F] 0.625 in 15 - 3000 psi 0.307 sq in III Steam 15 - 3000 psi 0.2 in [G] 0.8 in 0.503 sq in 2-1/2 - 4 NPS III Steam 0.65 sq in 15 - 3000 psi 0.227 in 2 1/2 - 4 NPS 0.909 in III Steam 15 - 3000 psi 0.25 in [H] 1 in 0.785 sq in 3, 4 NPS 1.5 - 3 NPS III Steam 2 - 3 NPS 4, 6 NPS 1.288 sq in [J] 1.281 in 0.32 in 15 - 3000 psi III Steam 4, 6 NPS [K] 1.531 in 0.382 in 2.5 - 4 NPS 15 - 3000 psi 1.84 sq in III Steam 3 - 6 NPS 15 - 3000 psi 0.45 in [K2] 1.8 in 2.545 sq in 6 NPS III Steam 15 - 3000 psi 2.853 sq in [L] 1.906 in 0.476 in III Steam [M1] 1.952 in 0.488 in 15 - 3000 psi 2.993 sq in III Steam 15 - 3000 psi 0.538 in [M] 2.154 in 3.644 sq in III Steam 6, 8 NPS 15 - 3000 psi 4 - 6 NPS 0.591 in 4.382 sq in [N] 2.362 in III Steam 6.38 sq in 15 - 3000 psi 0.712 in [P] 2.85 in III 8 NPS 15 - 3000 psi 7.917 sq in 6 NPS 0.794 in [P3] 3.175 in III Steam 15 - 1500 psi 10 NPS 16.12 sq in [R] 4.531 in 1.133 in III Steam 15 - 1500 psi 1.145 in [R] 4.58 in 16.474 sq in 10 NPS 8 NPS Page 311 of 812 Effective Date: 2019-05-31

313 Table of Contents Crosby Valve, LLC (CVM) NB#: 15073 location: 55 Cabot Blvd, Mansfield, MA 02048 United States Acceptable Abbrev.: CVM Design Series Certification JB 15073 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on August 08, 1957 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .856 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Inlet Size Set Pressure Range Lift Media III Steam [D] 0.398 in 0.099 in 15 - 2900 psi 2 NPS 1 NPS 0.1244 sq in VIII VIII Air 15 - 6000 psi III Steam 0.2223 sq in 0.133 in 15 - 2900 psi [E] 0.532 in VIII VIII Air 15 - 6000 psi III Steam 15 - 2900 psi [F] 0.666 in 1.5 NPS 2 NPS 0.167 in 0.3484 sq in VIII VIII Air 15 - 5000 psi III Steam 0.213 in [G] 0.852 in 0.57 sq in 2.5 NPS 15 - 2900 psi VIII III Air 15 - 3705 psi VIII VIII Air 15 - 2900 psi 0.266 in 0.891 sq in 3 NPS [H] 1.065 in III Steam VIII VIII Air [J] 1.363 in 0.34 in 15 - 2900 psi 2 NPS 3 NPS 1.459 sq in III Steam VIII VIII Air 15 - 2900 psi 4 NPS 0.408 in 2.087 sq in 3 NPS [K] 1.63 in III Steam VIII VIII Air 3.237 sq in 0.508 in [L] 2.03 in 15 - 1500 psi III Steam VIII VIII Air 0.57 in 4 NPS 6 NPS 4.083 sq in [M] 2.28 in 15 - 1100 psi III Steam VIII VIII Air 4.924 sq in 0.626 in 15 - 1000 psi [N] 2.504 in III Steam VIII VIII Air 0.759 in 15 - 1000 psi [P] 3.035 in 7.234 sq in III Steam VIII VIII Air 0.999 in 15 - 600 psi 6 NPS [Q] 3.994 in 8 NPS 12.53 sq in III Steam VIII VIII Air [R] 4.807 in 1.2 in 18.148 sq in 15 - 500 psi III Steam VIII VIII Air [T] 6.128 in 1.532 in 15 - 500 psi 8 NPS 10 NPS 29.494 sq in III Steam VIII VIII Air [V] 7.805 in 15 - 500 psi 47.85 sq in 14 NPS 1.951 in 10 NPS III Steam VIII Page 312 of 812 Effective Date: 2019-05-31

314 Table of Contents Crosby Valve, LLC (CVM) 15073 NB#: 55 Cabot Blvd, Mansfield, MA 02048 United States location: Acceptable Abbrev.: CVM ...Continued Orifice [designator] diameter Inlet Size Outlet Size Flow Area Code Section Lift Set Pressure Range Media VIII Air 10 - 12 NPS 7 in 1.75 in 15 - 600 psi 14 NPS 38.485 sq in III Steam VIII VIII Air 15 - 500 psi 16 NPS 68.9 sq in [W] 9.366 in 2.341 in 12 NPS III Steam VIII III Air 72 sq in [W1] 9.575 in 15 - 400 psi 2.394 in VIII Div. 1 III Steam VIII Div. 1 VIII Air 18 NPS [Y] 10.927 in 2.732 in 15 - 400 psi 14 NPS 93.78 sq in III Steam VIII VIII Air 2.865 in 16 NPS 18 NPS 103.15 sq in [Z] 11.46 in 15 - 400 psi III Steam VIII III Air 15 - 400 psi 2.959 in 11.835 in 110 sq in VIII Div. 1 III Steam VIII Div. 1 VIII Air 123.47 sq in 15 - 400 psi 3.135 in [Z2] 12.538 in 20 NPS III Steam VIII VIII Air 18 - 20 NPS 15 - 600 psi 2.938 in 11.75 in 24 NPS 108.434 sq in III Steam VIII VIII Air 15 - 400 psi 3.513 in [AA] 14.05 in 155.04 sq in III Steam VIII VIII Air 20 NPS [BB] 15.61 in 3.902 in 15 - 400 psi 24 NPS 191.38 sq in III Steam VIII VIII Air 15 - 300 psi 4.125 in [BB2] 16.5 in 213.82 sq in III Steam VIII Design Series Certification JMBL (Liquids) 15129 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on October 05, 1984 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .657 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size III Water 0.0552 sq in [2] 0.265 in 0.07 in 15 - 5000 psi 1 NPS 0.5 - 1 NPS VIII Div. 1 III Water 0.0845 sq in [4] 0.328 in 0.095 in 15 - 5000 psi VIII Div. 1 III Water 0.5 - 1.5 NPS 0.1244 sq in [6] 0.398 in 0.125 in 1, 1.5 NPS 15 - 5000 psi VIII Div. 1 III Water [8] 0.531 in 0.2 in 15 - 5000 psi 0.75 - 1.5 NPS 1, 1.5 NPS 0.2214 sq in VIII Div. 1 Page 313 of 812 Effective Date: 2019-05-31

315 Table of Contents Crosby Valve, LLC (CVM) 15174 NB#: 55 Cabot Blvd, Mansfield, MA 02048 United States location: Acceptable Abbrev.: CVM Certification Design Series JMB-WR 15174 or catalog number Number: Safety Relief Valve Type Classification: Sec. III at Crosby Valve & Gage on February 10, 1981 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .563 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Inlet Size Media Outlet Size Set Pressure Range III Water 0.124 in 0.012 in 5 - 2750 psi 0.75 - 1.5 NPS 1, 1.5 NPS 0.012 sq in VIII Div. 1 III Water 5 - 2750 psi 0.015 in 0.187 in 0.0274 sq in VIII Div. 1 III Water 0.249 in 0.0486 sq in 5 - 2750 psi 0.021 in VIII Div. 1 VIII Water 5 - 2750 psi 0.04 in 0.374 in 0.1098 sq in VIII Page 314 of 812 Effective Date: 2019-05-31

316 Table of Contents Crosby Valve, LLC (CVM) 15196 NB#: 55 Cabot Blvd, Mansfield, MA 02048 United States location: Acceptable Abbrev.: CVM Certification Design Series JO/HSU (Class 2 and 3) 15196 Number: or catalog number Safety Relief Valve Type Classification: Sec. III at Phillips Petroleum on October 19, 1955 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .870 Unitless Certified Value: Gas Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Inlet Size Flow Area Outlet Size Lift Media Code Section III & VIII Div.1 Air [D] 0.398 in 1 - 1.5 NPS 2, 2.5 NPS 15 - 10000 psi 0.1244 sq in 0.099 in III & VIII Div.1 Steam 15 - 2900 psi III & VIII Div.1 Steam 15 - 2900 psi 0.2223 sq in [E] 0.532 in 0.133 in III & VIII Div.1 Air 15 - 7500 psi III & VIII Div.1 Steam 0.167 in 15 - 2900 psi [F] 0.666 in 0.3484 sq in 2 NPS 1.5 NPS III & VIII Div.1 Air 15 - 5000 psi III & VIII Div.1 Steam 0.57 sq in 2.5 NPS [G] 0.852 in 0.213 in 15 - 2900 psi III & VIII Div.1 Air 15 - 3705 psi III & VIII Div.1 Air 15 - 2900 psi 0.266 in [H] 1.065 in 3 NPS 0.891 sq in III & VIII Div.1 Steam III & VIII Div.1 Air [J] 1.363 in 15 - 2900 psi 3 NPS 2 NPS 0.34 in 1.459 sq in III & VIII Div.1 Steam III & VIII Div.1 Air 4 NPS 2.087 sq in [K] 1.63 in 3 NPS 15 - 2900 psi 0.408 in III & VIII Div.1 Steam III & VIII Div.1 Air [L] 2.03 in 3.237 sq in 15 - 1500 psi 0.508 in III & VIII Div.1 Steam III & VIII Div.1 Air 0.57 in 15 - 1100 psi 4 NPS 4.083 sq in [M] 2.28 in 6 NPS III & VIII Div.1 Steam III & VIII Div.1 Air 15 - 1000 psi 0.626 in [N] 2.504 in 4.924 sq in III & VIII Div.1 Steam III & VIII Div.1 Air 7.234 sq in 15 - 1000 psi [P] 3.035 in 0.759 in III & VIII Div.1 Steam III & VIII Div.1 Air 15 - 600 psi 6 NPS 8 NPS 12.53 sq in [Q] 3.994 in 0.999 in III & VIII Div.1 Steam III & VIII Div.1 Air 15 - 500 psi 18.148 sq in 1.2 in [R] 4.807 in III & VIII Div.1 Steam III & VIII Div.1 Air 10 NPS 15 - 500 psi 1.532 in 8 NPS [T] 6.128 in 29.494 sq in III & VIII Div.1 Steam III & VIII Div.1 Air 15 - 500 psi 14 NPS 47.85 sq in [V] 7.805 in 10 NPS 1.951 in III & VIII Div.1 Steam III & VIII Div.1 Air 15 - 500 psi 12 NPS 14 NPS 2.341 in 68.9 sq in [W] 9.366 in III & VIII Div.1 Steam III & VIII Div.1 Air [Y] 10.927 in 2.732 in 15 - 400 psi 14 NPS 18 NPS 93.78 sq in III & VIII Div.1 Steam III & VIII Div.1 Air 15 - 400 psi 16 NPS 2.865 in [Z] 11.46 in 103.15 sq in 18 NPS III & VIII Div.1 Steam III & VIII Div.1 Air 15 - 400 psi 20 NPS 3.135 in [Z2] 12.538 in 123.47 sq in III & VIII Div.1 Steam III & VIII Div.1 Air 3.513 in 15 - 400 psi 18 NPS 24 NPS 155.04 sq in [AA] 14.05 in III & VIII Div.1 Steam III & VIII Div.1 Air [BB] 15.61 in 3.902 in 15 - 400 psi 20 NPS 24 NPS 191.38 sq in III & VIII Div.1 Steam III & VIII Div.1 Air 15 - 300 psi 4.125 in [BB2] 16.5 in 213.82 sq in III & VIII Div.1 Steam Page 315 of 812 Effective Date: 2019-05-31

317 Table of Contents Crosby Valve, LLC (CVM) 15231 NB#: 55 Cabot Blvd, Mansfield, MA 02048 United States location: Acceptable Abbrev.: CVM Certification Design Series JPV-A 15231 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on April 29, 1968 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Media Code Section Flow Area Inlet Size Lift Set Pressure Range VIII Div. 1 Steam [V] 7.5 in 10 NPS 14 NPS 44.18 sq in 1.875 in 15 - 1500 psi VIII Div. 1 Steam 12 NPS [W] 9 in 16 NPS 15 - 1500 psi 2.25 in 63.62 sq in VIII Div. 1 Steam 14 NPS 18 NPS 86.59 sq in [Y] 10.5 in 2.625 in 15 - 1500 psi VIII Div. 1 Steam 95.21 sq in 15 - 1500 psi [Z] 11.01 in 2.753 in 16 NPS 18 NPS VIII Div. 1 Steam 20 NPS 114.04 sq in [Z2] 12.05 in 3.012 in 15 - 1500 psi VIII Div. 1 Steam 22, 24 NPS 3.375 in 18 NPS 143.14 sq in 15 - 1500 psi [AA] 13.5 in VIII Div. 1 Steam 3.75 in 15 - 1500 psi 20 NPS 24 NPS 176.71 sq in [BB] 15 in Design Series Certification JRAK-BS (Class 1, 2, 3 Liquids) 15309 or catalog number Number: Relief Valve Type Classification: Sec. III at Crosby Valve & Gage on February 19, 1981 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .646 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Lift Set Pressure Range Media Code Section Inlet Size Flow Area III Water 1 NPS 0.5 - 1 NPS 0.012 sq in 0.124 in 0.008 in 5 - 3600 psi III Water 0.019 in 0.0274 sq in 5 - 3600 psi 0.187 in III Water 0.029 in 5 - 3600 psi 0.0486 sq in 0.249 in III Water 0.0674 sq in 0.293 in 0.04 in 5 - 3600 psi III Water 0.061 in 0.374 in 5 - 3600 psi 0.1098 sq in Certification Design Series JRL (Liquids) 15310 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on October 03, 1984 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 2.145 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size III Water 0.328 in 15 - 2000 psi 0.125 in 0.5 - 1 NPS 0.084 sq in 1 NPS VIII Div. 1 Page 316 of 812 Effective Date: 2019-05-31

318 Table of Contents Crosby Valve, LLC (CVM) 15332 NB#: 55 Cabot Blvd, Mansfield, MA 02048 United States location: Acceptable Abbrev.: CVM Certification Design Series JRU 15332 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on December 23, 1968 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.32 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Set Pressure Range Code Section Media Lift III Air 0.11 sq in 15 - 2000 psi 0.5 - 1 NPS 1 NPS 0.1 in 0.375 in VIII Div. 1 Certification Design Series JO/JB-WR (Class 1, 2, 3 Liquids) 15343 Number: or catalog number Relief Valve Type Classification: Sec. III at Crosby Valve & Gage on October 03, 1980 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .564 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Media Code Section Set Pressure Range III Water 0.75 - 1.5 NPS 0.114 sq in [D] 0.455 in 0.08 in 2, 2-1/2 NPS 5 - 6000 psi III Water 5 - 6000 psi 0.107 in [E] 0.61 in 0.205 sq in III Water 2 - 3 NPS 1 - 1.5 NPS 5 - 5000 psi 0.134 in [F] 0.751 in 0.316 sq in III Water [G] 0.93 in 1.5 - 2 NPS 0.5 sq in 0.171 in 2-1/2, 3 NPS 5 - 3600 psi III Water 5 - 2480 psi 3,4 NPS 0.778 sq in [H] 1.163 in 0.213 in III Water 2 - 3 NPS 3 - 6 NPS 1.281 sq in [J] 1.494 in 0.273 in 5 - 2440 psi III Water 1.831 sq in 3 NPS 5 - 1950 psi [K] 1.782 in 4, 6 NPS 0.327 in III Water 5 - 1500 psi 0.407 in [L] 2.211 in 2.827 sq in 3 - 4 NPS 4,6 NPS III Water 6 NPS [M] 2.481 in 0.457 in 4 NPS 5 - 1100 psi 3.562 sq in III Water 5 - 1000 psi 6,8 NPS 4.312 sq in [N] 2.734 in 0.502 in III Water 6.315 sq in [P] 3.306 in 0.608 in 5 - 1000 psi III Water 0.8 in 6 NPS 8 NPS 5 - 600 psi 10.998 sq in [Q] 4.376 in Design Series Certification JB-TD 15387 Number: or catalog number Relief Valve Type Classification: Sec. III at Anderson Greenwood Crosby (Wrentham MA) on February 19, 2008 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 0.678 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size III NB, NC, ND Water 125 - 1600 psi 0.007 in 0.398 in 0.013 sq in 1 NPS 0.75 NPS Page 317 of 812 Effective Date: 2019-05-31

319 Table of Contents Crosby Valve, LLC (CVM) 15398 NB#: 55 Cabot Blvd, Mansfield, MA 02048 United States location: Acceptable Abbrev.: CVM Design Series Certification CV1B 15398 Number: or catalog number Vacuum Relief Valve Type Classification: Sec. III NC at Anderson Greenwood (El Campo TX) on December 11, 2013 Capacity Tests: Flow Capacity, 1 valve method Method of Establishing Relieving Capacity: 1652 SCFM Certified Value: Gas Test Medium: Air Certified Medium: Start-to-Leak Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Outlet Size Flow Area Code Section Lift Set Pressure Range III -0.2 psi 4.65 in 16.98 sq in 6, 8 NPS 6 - 8 NPS Certification Design Series JMAK (Liquid Service) 15422 or catalog number Number: Relief Valve Type Classification: Sec. III at Crosby Valve & Gage on February 19, 1981 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .617 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size III Water 5 - 3000 psi 0.009 in 0.124 in 0.012 sq in .75 - 2 NPS 0.5 - 0.75 NPS VIII III Water 0.5 - 1 NPS 5 - 3000 psi 0.018 in 0.187 in 0.0274 sq in .75 - 2 NPS VIII III Water 0.0486 sq in 0.5 - 1.5 NPS .75 - 2 NPS 5 - 3000 psi 0.028 in 0.249 in VIII III Water 0.05 in 5 - 3000 psi 0.5 - 2 NPS .75 - 2 NPS 0.1098 sq in 0.374 in VIII Certification Design Series VR (1") 15488 Number: or catalog number Vacuum Relief Valve Type Classification: Sec. III at Crosby Valve & Gage on December 20, 1991 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 10.6 SCFM/F(P*(P-Po)^.5 Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Inlet Size Flow Area Set Pressure Range Media Outlet Size III Air 1 NPS 0.442 sq in .1 - 7.0 psi 1 NPS Page 318 of 812 Effective Date: 2019-05-31

320 Table of Contents Crosby Valve, LLC (CVM) 15556 NB#: 55 Cabot Blvd, Mansfield, MA 02048 United States location: Acceptable Abbrev.: CVM Certification Design Series VR (3") 15556 Number: or catalog number Vacuum Relief Valve Type Classification: Sec. III at Crosby Valve & Gage on November 07, 1996 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 87.11 SCFM/F(P*(P-Po)^.5 Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Lift Inlet Size Flow Area III Air 3 NPS .1 - 7.0 psi 4.146 sq in 3 NPS Design Series Certification VR (2") 15578 Number: or catalog number Vacuum Relief Valve Type Classification: Sec. III at Crosby Valve & Gage on January 23, 1992 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 38.3 SCFM/F(P*(P-Po)^.5 Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Inlet Size Flow Area Lift Set Pressure Range Media Code Section III Air 1.841 sq in .1 - 7.0 psi 2 NPS 2 NPS Page 319 of 812 Effective Date: 2019-05-31

321 Table of Contents Cyrus Shank Company (SHK) 51017 NB#: 4645 W. Roosevelt Road, Cicero, IL 60804 United States location: Cyrus Shank Company (SHK) 4645 W. Roosevelt Road, Cicero, IL 60804 United States location: Certification Design Series 804, 804QR Series 51017 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on April 05, 2000 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.04 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media Code Section VIII Div. 1 Air 0.75 NPS 75 - 400 psi 1 NPS 0.2821 sq in 0.708 in 0.12 in Design Series Certification 805-T, 805QR, 815, 815QR Series 51028 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on January 27, 1984 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 4.09 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Lift Outlet Size Inlet Size Flow Area Set Pressure Range VIII Air 75 - 400 psi 1.05 in 0.866 sq in 1.25, 1.5 NPS 1 NPS Certification Design Series 803 LQ 75 psig (liquids) 51039 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 23, 1995 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 20.7 GPM Certified Value: Water Test Medium: Liquid Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Outlet Size Flow Area Lift Set Pressure Range Code Section VIII Div. 1 Water 0.1148 sq in 0.466 in 0.14 in 75 - 75 psi 0.5 NPS .75 NPS Page 320 of 812 Effective Date: 2019-05-31

322 Table of Contents Cyrus Shank Company (SHK) 51040 NB#: 4645 W. Roosevelt Road, Cicero, IL 60804 United States location: Certification Design Series 900, 901, 902, 903 51040 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 28, 1997 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 15.18 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Air 150 - 400 psi 1.25 - 1.5 NPS 2, 3 NPS 1.2275 sq in 1.25 in Design Series Certification 850, 851 51051 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 15, 1998 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 6.17 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Lift Set Pressure Range Inlet Size Media Code Section VIII Air 0.5 in 0.75 in 0.442 sq in 0.75 - 1.25 NPS 150 - 400 psi 1.5, 2 NPS Design Series Certification 805 LQ 100 psig 51062 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 15, 1998 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 36.5 GPM Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Outlet Size Flow Area Lift Set Pressure Range Code Section VIII Water 0.445 sq in 1.05 in 0.135 in 100 - 100 psi 1 NPS 1.25 NPS Page 321 of 812 Effective Date: 2019-05-31

323 Table of Contents Cyrus Shank Company (SHK) 51073 NB#: 4645 W. Roosevelt Road, Cicero, IL 60804 United States location: Certification Design Series 803 LQ 100 psig liquid, 803 LQ QC 100 psig liquid 51073 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 19, 1998 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 25.9 GPM Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Water 100 - 100 psi 0.5 NPS .75 NPS 0.1148 sq in 0.466 in Design Series Certification 803, 803QC 51129 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on November 30, 1999 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.978 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Lift Set Pressure Range Media Inlet Size Code Section VIII Div. 1 Air 0.14 in 0.466 in 0.1312 sq in 0.5 NPS 50 - 400 psi .75 NPS Design Series Certification 814 51130 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 17, 2001 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.29 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 0.708 in 75 - 400 psi 0.75 NPS 1.25 NPS 0.2821 sq in Page 322 of 812 Effective Date: 2019-05-31

324 Table of Contents Cyrus Shank Company (SHK) 51141 NB#: 4645 W. Roosevelt Road, Cicero, IL 60804 United States location: Certification Design Series 813 51141 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on August 23, 2001 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.99 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Div. 1 Air 0.466 in 0.14 in 75 - 400 psi 0.5 NPS 1 NPS 0.1312 sq in Design Series Certification 801, 801D, 801QR, 801QRW 51152 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 28, 2002 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 0.73 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size VIII Div. 1 Air 0.125 in 0.466 in 0.0487 sq in 75 - 400 psi .75 NPS 0.5 NPS Certification Design Series 800, 800D, 800QR, 800QRW, 800QRM 51163 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on June 03, 2002 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 0.42 SCFM/PSIA Certified Value: Gas Test Medium: Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Outlet Size Flow Area Set Pressure Range Media Code Section Inlet Size VIII Div. 1 Air 0.02771 sq in 0.466 in 0.12 in 50 - 400 psi 0.5 NPS .75 NPS Page 323 of 812 Effective Date: 2019-05-31

325 Table of Contents Cyrus Shank Company (SHK) 51174 NB#: 4645 W. Roosevelt Road, Cicero, IL 60804 United States location: Certification Design Series 812 51174 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on January 27, 2005 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.339 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size VIII Div. 1 Air 0.466 in 0.14 in 75 - 400 psi 0.5 NPS 1 NPS 0.1312 sq in Design Series Certification CS 5602A, CS5602AQR 51185 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 22, 2010 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.32 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size VIII Div. 1 Air 75 - 400 psi 0.282 sq in .75 NPS 0.5 NPS Certification Design Series CS 5602B, CS 5602BQR, CS 5602C, CS 5602CQR 51196 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 01, 2010 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.65 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Lift Flow Area Inlet Size VIII Div. 1 Air 75 - 400 psi 0.12 in 0.708 in 0.305 sq in 1 NPS 0.5 - 0.75 NPS Page 324 of 812 Effective Date: 2019-05-31

326 Table of Contents Cyrus Shank Company (SHK) 51208 NB#: 4645 W. Roosevelt Road, Cicero, IL 60804 United States location: Certification Design Series 801DHC/801DHC QR 51208 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII at National Board T L (Worthington) on April 08, 2011 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .781 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section VIII Div. 1 Air 0.5 NPS .75 NPS 75 - 400 psi Certification Design Series 804R, 804R-QR 51219 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 06, 2012 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.63 SCFM/PSIA Certified Value: Air Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Set Pressure Range Outlet Size Inlet Size Flow Area Media VIII Div. 1 Air 0.75 NPS 75 - 400 psi 1 NPS Certification Design Series 805R, 805R-QR 51220 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 21, 2012 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.1 SCFM/PSIA Certified Value: Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Outlet Size Flow Area Lift Set Pressure Range Code Section VIII Div. 1 Air 1.05 in 75 - 400 psi 1 NPS 1.25 NPS 0.168 sq in Page 325 of 812 Effective Date: 2019-05-31

327 Table of Contents Cyrus Shank Company (SHK) 51231 NB#: 4645 W. Roosevelt Road, Cicero, IL 60804 United States location: Certification Design Series 850DR, 851DR, 850AR, 851AR 51231 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 03, 2013 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.50 SCFM/PSIA Certified Value: Air Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Div. 1 Air 0.75 - 1.25 NPS 1.5, 2 NPS 75 - 350 psi Certification Design Series 800OP, 800OPQR, 800D OP, 800SS OP, 800QRW OP 51253 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 24, 2017 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 0.216 SCFM/PSIA Certified Value: Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Set Pressure Range Lift Code Section Flow Area Outlet Size VIII Div. 1 Air 0.12 0.466 in 0.162 sq in .75 NPS 0.5 NPS 250 - 300 psi Certification Design Series CS 5602R 51264 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 11, 2017 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 0.781 SCFM/PSIA Certified Value: Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Lift Flow Area Inlet Size VIII Div. 1 Air 75 - 400 psi 0.12 in 0.708 sq in 0.0574 sq in 1 NPS 0.75 NPS Page 326 of 812 Effective Date: 2019-05-31

328 Table of Contents DonadonSDD Srl (DON) 00516 NB#: Via Franceschelli, 7, Corbetta Milano 20011 Italy location: Acceptable Abbrev.: DonadonSDD DonadonSDD Srl (DON) location: Via Franceschelli, 7, Corbetta Milano 20011 Italy Acceptable Abbrev.: DonadonSDD Design Series Certification KRD 00516 Number: or catalog number HRA, HRP, HRF Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on September 10, 2014 Capacity Tests: Resistance Factor, 3 Size, Krl Method of Establishing Relieving Capacity: 0.48 Unitless Certified Value: Gas Test Medium: Liquid Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Inlet Size Media Code Section Flow Area Outlet Size Set Pressure Range VIII Div. 1 Water 1 NPS 0.79 sq in 15 - 2000 psi VIII Div. 1 Water 1.77 sq in 1.5 NPS 6 - 1500 psi VIII Div. 1 Water 6 - 1500 psi 2 NPS 3.14 sq in VIII Div. 1 Water 6 - 900 psi 2.5 NPS 4.91 sq in VIII Div. 1 Water 6 - 900 psi 7.07 sq in 3 NPS VIII Div. 1 Water 12.57 sq in 6 - 800 psi 4 NPS VIII Div. 1 Water 6 - 800 psi 19.63 sq in 5 NPS VIII Div. 1 Water 6 NPS 28.27 sq in 6 - 600 psi VIII Div. 1 Water 6 - 600 psi 50.27 sq in 8 NPS VIII Div. 1 Water 6 - 400 psi 10 NPS 78.54 sq in VIII Div. 1 Water 6 - 300 psi 113.1 sq in 12 NPS VIII Div. 1 Water 6 - 200 psi 153.94 sq in 14 NPS VIII Div. 1 Water 16 NPS 6 - 150 psi 201.06 sq in VIII Div. 1 Water 254.47 sq in 6 - 150 psi 18 NPS VIII Div. 1 Water 6 - 150 psi 20 NPS 314.16 sq in VIII Div. 1 Water 24 NPS 452.39 sq in 6 - 120 psi VIII Div. 1 Water 28 NPS 615.75 sq in 6 - 45 psi VIII Div. 1 Water 706.86 sq in 6 - 45 psi 30 NPS VIII Div. 1 Water 32 NPS 6 - 30 psi 804.25 sq in VIII Div. 1 Water 36 NPS 1017.88 sq in 6 - 30 psi Page 327 of 812 Effective Date: 2019-05-31

329 Table of Contents DonadonSDD Srl (DON) 00527 NB#: Via Franceschelli, 7, Corbetta Milano 20011 Italy location: Acceptable Abbrev.: DonadonSDD Certification Design Series SCD 00527 Number: or catalog number HIA, HIP, HIF Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 25, 2015 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.33 Unitless Certified Value: Gas Test Medium: Air/Gas & Liquid Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Lift Media Code Section Flow Area Outlet Size Set Pressure Range VIII Div. 1 Air 30 - 6000 psi 1 NPS 0.79 sq in VIII Div. 1 Water VIII Div. 1 Air 30 - 2500 psi 1.77 sq in 1.5 NPS VIII Div. 1 Water VIII Div. 1 Air 3.14 sq in 30 - 2500 psi 2 NPS VIII Div. 1 Water VIII Div. 1 Air 2.5 NPS 4.91 sq in 30 - 2500 psi VIII Div. 1 Water VIII Div. 1 Air 30 - 1500 psi 7.07 sq in 3 NPS VIII Div. 1 Water VIII Div. 1 Air 4 NPS 30 - 1500 psi 12.57 sq in VIII Div. 1 Water VIII Div. 1 Air 5 NPS 19.63 sq in 30 - 1500 psi VIII Div. 1 Water VIII Div. 1 Air 30 - 900 psi 6 NPS 28.27 sq in VIII Div. 1 Water VIII Div. 1 Air 8 NPS 50.27 sq in 30 - 900 psi VIII Div. 1 Water VIII Div. 1 Air 30 - 900 psi 78.54 sq in 10 NPS VIII Div. 1 Water VIII Div. 1 Air 30 - 300 psi 113.1 sq in 12 NPS VIII Div. 1 Water VIII Div. 1 Air 153.94 sq in 14 NPS 30 - 300 psi VIII Div. 1 Water VIII Div. 1 Air 30 - 300 psi 201.06 sq in 16 NPS VIII Div. 1 Water VIII Div. 1 Air 254.47 sq in 30 - 300 psi 18 NPS VIII Div. 1 Water VIII Div. 1 Air 30 - 300 psi 314.16 sq in 20 NPS VIII Div. 1 Water VIII Div. 1 Air 30 - 300 psi 452.39 sq in 24 NPS VIII Div. 1 Water VIII Div. 1 Air 30 - 300 psi 28 NPS 615.75 sq in VIII Div. 1 Water VIII Div. 1 Air 30 - 300 psi 706.86 sq in 30 NPS VIII Div. 1 Water VIII Div. 1 Air 30 - 300 psi 804.25 sq in 32 NPS VIII Div. 1 Water VIII Div. 1 Air 30 - 300 psi 1017.88 sq in 36 NPS VIII Div. 1 Water Page 328 of 812 Effective Date: 2019-05-31

330 Table of Contents DonadonSDD Srl (DON) 00538 NB#: Via Franceschelli, 7, Corbetta Milano 20011 Italy location: Acceptable Abbrev.: DonadonSDD Certification Design Series SCR 00538 Number: or catalog number HRA, HRP, HRF Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on December 05, 2014 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 0.48 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Code Section Outlet Size Inlet Size Media Set Pressure Range VIII Div. 1 Air 15 - 2000 psi 1 NPS 0.79 sq in VIII Div. 1 Air 1.77 sq in 6 - 1500 psi 1.5 NPS VIII Div. 1 Air 3.14 sq in 2 NPS 6 - 1500 psi VIII Div. 1 Air 6 - 900 psi 2.5 NPS 4.91 sq in VIII Div. 1 Air 3 NPS 7.07 sq in 6 - 900 psi VIII Div. 1 Air 12.57 sq in 6 - 800 psi 4 NPS VIII Div. 1 Air 6 - 800 psi 5 NPS 19.63 sq in VIII Div. 1 Air 6 NPS 28.27 sq in 6 - 600 psi VIII Div. 1 Air 6 - 600 psi 50.27 sq in 8 NPS VIII Div. 1 Air 6 - 400 psi 10 NPS 78.54 sq in VIII Div. 1 Air 6 - 300 psi 113.1 sq in 12 NPS VIII Div. 1 Air 6 - 200 psi 153.94 sq in 14 NPS VIII Div. 1 Air 16 NPS 6 - 150 psi 201.06 sq in VIII Div. 1 Air 254.47 sq in 6 - 150 psi 18 NPS VIII Div. 1 Air 6 - 150 psi 20 NPS 314.16 sq in VIII Div. 1 Air 24 NPS 452.39 sq in 6 - 120 psi VIII Div. 1 Air 28 NPS 615.75 sq in 6 - 45 psi VIII Div. 1 Air 706.86 sq in 6 - 45 psi 30 NPS VIII Div. 1 Air 32 NPS 6 - 30 psi 804.25 sq in VIII Div. 1 Air 36 NPS 1017.88 sq in 6 - 30 psi Page 329 of 812 Effective Date: 2019-05-31

331 Table of Contents Dresser Machinery (Suzhou) Co., Ltd. (DMS) 00864 NB#: 81 Suhong Zhong Road, Suzhou Industrial Park, Suzhou, Jiangsu 215021 Peoples Republic Of China location: Seal Identification: DMS Dresser Machinery (Suzhou) Co., Ltd. (DMS) location: 81 Suhong Zhong Road, Suzhou Industrial Park, Suzhou, Jiangsu 215021 Peoples Republic Of China Seal Identification: DMS Certification Design Series 11000 E Liquid 00864 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on March 23, 2016 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 4.9748 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media Code Section VIII Div. 1 Water 0.75 - 1 NPS 1 NPS 0.246 sq in [E] 0.56 in 0.25 in 75 - 1505 psi Design Series Certification 11000 E gas 00875 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on March 24, 2016 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.5733 SCFM/PSIA Certified Value: Air Test Medium: Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Media Code Section Outlet Size Flow Area Inlet Size Lift VIII Div. 1 Air 0.184 in [E] 0.56 in 0.246 sq in 75 - 2000 psi 0.75 - 1 NPS 1 NPS Certification Design Series 11000 D gas 00886 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on March 28, 2016 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.1078 SCFM/PSIA Certified Value: Air Test Medium: Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size Media VIII Div. 1 Air [D] 0.41 in 0.136 in 75 - 2000 psi 0.5 - 1 NPS 1 NPS 0.132 sq in Page 330 of 812 Effective Date: 2019-05-31

332 Table of Contents Dresser, LLC (DRJ) 18032 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Dresser, LLC (DRJ) location: 12970 Normandy Blvd, Jacksonville, FL 32221 United States Acceptable Abbrev.: JAX Certification Design Series 1541, 1543, 1541-3, 1543-3 18032 Number: or catalog number Safety Valve Type Classification: Sec. I & VIII Div. 1 at Dresser Industries Inc. on March 11, 1975 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media Code Section I, III, & VIII Div. 1 Steam 0.094 in 15 - 250 psi 0.5 - 0.75 NPS .75 NPS 0.11 sq in [D] 0.375 in III & VIII Div.1 Air 15 - 300 psi I, III, & VIII Div. 1 Steam [D3] 0.393 in 0.094 in 15 - 300 psi III & VIII Div.1 Air 15 - 350 psi I, III, & VIII Div. 1 Steam 1 NPS 15 - 250 psi [E] 0.5 in 0.75 - 1 NPS 0.196 sq in 0.125 in III & VIII Div.1 Air 15 - 300 psi I, III, & VIII Div. 1 Steam 0.125 in 15 - 300 psi [E3] 0.524 in III & VIII Div.1 Air 15 - 350 psi I, III, & VIII Div. 1 Steam [F] 0.625 in 0.156 in 15 - 250 psi 1 - 1.25 NPS 1.25 NPS 0.307 sq in III & VIII Div.1 Air 15 - 300 psi I, III, & VIII Div. 1 Steam [F3] 0.65 in 0.156 in 15 - 300 psi III & VIII Div.1 Air 15 - 350 psi I, III, & VIII Div. 1 Steam 0.503 sq in 15 - 250 psi 1.5 NPS 0.2 in 1.25 - 1.5 NPS [G] 0.8 in III & VIII Div.1 Air 15 - 300 psi I, III, & VIII Div. 1 Steam 15 - 300 psi 0.2 in [G3] 0.835 in III & VIII Div.1 Air 15 - 350 psi I, III, & VIII Div. 1 Steam 1.5 - 2 NPS 15 - 250 psi 2 NPS 0.785 sq in 0.25 in [H] 1 in III & VIII Div.1 Air 15 - 300 psi I, III, & VIII Div. 1 Steam [H3] 1.045 in 0.25 in 15 - 300 psi III & VIII Div.1 Air 15 - 350 psi I, III, & VIII Div. 1 Steam 2 - 2.5 NPS 2.5 NPS 1.287 sq in [J] 1.281 in 15 - 250 psi 0.32 in III & VIII Div.1 Air 15 - 300 psi I, III, & VIII Div. 1 Steam 15 - 300 psi 0.32 in [J3] 1.335 in III & VIII Div.1 Air 15 - 350 psi Page 331 of 812 Effective Date: 2019-05-31

333 Table of Contents Dresser, LLC (DRJ) 18087 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1700 & 2700 (4" #7 & Ovrszd Q) 18087 Number: or catalog number Safety Valve Type Classification: Sec. I at Dresser Industries Inc. on January 09, 2004 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .785 Unitless Certified Value: per CC 2397 Certification Provisions: Steam Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size Media I Steam 8 NPS 11.05 sq in [#7] 3.75 in 0.938 in 15 - 1800 psi 4 NPS VIII Div. 1 I Steam 12.25 sq in 100 - 1000 psi 0.987 in [Q] 3.948 in VIII Div. 1 Design Series Certification 1700 & 2700 (4" #7 & Ovrszd Q) (Restricted Lift version of Cert. #18087) 18098 Number: or catalog number Safety Valve Type Classification: Sec. I at Dresser Industries Inc. on January 09, 2004 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .785 Unitless Certified Value: per CC 1923 &/or 1945 Certification Provisions: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area I Steam [7] 3.75 in 0.281 in 100 - 900 psi 4 NPS 8 NPS 11.05 sq in VIII Div. 1 I Steam 100 - 1000 psi 0.296 in [Q] 3.948 in 12.25 sq in VIII Div. 1 Page 332 of 812 Effective Date: 2019-05-31

334 Table of Contents Dresser, LLC (DRJ) 18100 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1700 & 2700 18100 Number: or catalog number Safety Valve Type Classification: Sec. I & VIII Div. 1 at Dresser Industries Inc. on August 01, 1957 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Inlet Size Code Section Outlet Size Set Pressure Range Media VIII Div. 1 Steam 15 - 3000 psi 1 - 1.5 NPS 3 NPS 0.442 sq in [#9] 0.75 in 0.188 in I Steam 50 - 3000 psi VIII Div. 1 Steam 0.281 in 0.994 sq in 3 NPS 1.25 - 2.5 NPS 15 - 3100 psi [#1] 1.125 in I Steam 50 - 5800 psi I Steam 1.431 sq in 1.5 - 2.5 NPS 3 NPS [#2] 1.35 in 0.338 in 15 - 3100 psi VIII Div. 1 Steam 50 - 5800 psi I & VIII Div. 1 Steam 2 - 3 NPS 6 NPS 2.545 sq in [#3] 1.8 in 0.45 in 50 - 5800 psi VIII Div. 1 Steam [L] 1.906 in 2.5 NPS 2.853 sq in 6 NPS 0.477 in 15 - 2575 psi I Steam 50 - 2575 psi VIII Div. 1 Steam 2.5 - 3 NPS 15 - 3100 psi [#5] 2.062 in 3.341 sq in 6, 8 NPS 0.516 in I Steam 50 - 5800 psi VIII Div. 1 Steam 3 NPS 6, 8 NPS 3.976 sq in [#4] 2.25 in 0.563 in 15 - 3100 psi I Steam 50 - 5800 psi I Steam 4 dual NPS 1.84 sq in [K] 1.531 in 0.383 in 4 NPS 50 - 5800 psi VIII Div. 1 Steam 7.07 sq in [#6] 3 in 0.75 in 15 - 3100 psi 6 NPS 4 - 6 NPS I Steam 50 - 3100 psi VIII Div. 1 Steam 15 - 1800 psi 8 NPS 11.05 sq in [Q] 3.75 in 6 NPS 0.938 in I Steam 50 - 1500 psi I Steam [Q] 3.948 in 12.25 sq in 15 - 1800 psi 0.987 in VIII Div. 1 VIII Div. 1 Steam [#8] 4.25 in 1.063 in 15 - 1800 psi 6 - 8 NPS 8, 10 NPS 14.18 sq in I Steam 50 - 2000 psi VIII Div. 1 Steam 15 - 1800 psi 16 sq in [R] 4.515 in 1.129 in I Steam 50 - 2000 psi I Steam 1.24 in 19.29 sq in 50 - 1600 psi [RR] 4.956 in I & VIII Div. 1 28.3 sq in [T] 6 in 1.5 in 50 - 1500 psi 8 - 10 NPS 10,12 NPS Page 333 of 812 Effective Date: 2019-05-31

335 Table of Contents Dresser, LLC (DRJ) 18111 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1700 & 2700 (Restricted Lift version of Cert. # 18100) 18111 Number: or catalog number Safety Valve Type Classification: Sec. I & VIII Div. 1 at National Board T L (Picaway) on October 13, 1981 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: per CC 1923 &/or 1945 Certification Provisions: Steam Test Medium: Steam Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Inlet Size Flow Area Outlet Size Code Section Media Set Pressure Range VIII Div. 1 Steam 1 - 1.5 NPS 3 NPS 0.442 sq in [9] 0.75 in 0.08 in 15 - 3000 psi I Steam 50 - 3000 psi VIII Div. 1 Steam 0.084 in 15 - 3100 psi 1.25 - 2.5 NPS 3, 4 NPS 0.994 sq in [1] 1.125 in I Steam 50 - 5800 psi VIII Div. 1 Steam 1.5 - 2.5 NPS 3, 4 NPS 1.431 sq in [2] 1.35 in 0.101 in 15 - 3100 psi I Steam 50 - 5800 psi VIII Div. 1 Steam 0.135 in 2.545 sq in 6 NPS 15 - 3100 psi 2 - 3 NPS [3] 1.8 in I Steam 50 - 5800 psi VIII Div. 1 Steam 15 - 2575 psi 2.5 - 3 NPS 6 NPS [L] 1.906 in 2.853 sq in 0.143 in I Steam 50 - 2575 psi VIII Div. 1 Steam [5] 2.062 in 0.155 in 15 - 3100 psi 3.341 sq in I Steam 50 - 5800 psi VIII Div. 1 Steam 0.169 in [4] 2.25 in 3.976 sq in 6 NPS 15 - 3100 psi 3 - 4 NPS I Steam 50 - 5800 psi VIII Div. 1 Steam 0.225 in 15 - 3100 psi 7.07 sq in 6 NPS 4 - 6 NPS [6] 3 in I Steam 50 - 3100 psi VIII Div. 1 Steam 0.281 in 15 - 1800 psi 6 NPS 8 NPS 11.05 sq in [Q] 3.75 in I Steam 50 - 1500 psi I & VIII Div. 1 Steam 15 - 1800 psi [Q] 3.946 in 12.25 sq in 0.296 VIII Div. 1 Steam [8] 4.25 in 0.319 in 15 - 1800 psi 6 - 8 NPS 8, 10 NPS 14.18 sq in I Steam 50 - 2000 psi VIII Div. 1 Steam 15 - 1800 psi 0.339 in [R] 4.515 in 16 sq in I Steam 50 - 2000 psi I Steam 50 - 1600 psi 19.29 sq in [RR] 4.956 in 0.372 in I & VIII Div. 1 Steam [T] 6 in 0.45 in 50 - 1500 psi 8 - 10 NPS 10, 12 NPS 28.3 sq in Page 334 of 812 Effective Date: 2019-05-31

336 Table of Contents Dresser, LLC (DRJ) 18122 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1811, 1511 18122 or catalog number Number: Safety Valve Type Classification: Sec. I at Dresser Industries Inc. on March 11, 1975 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .877 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Inlet Size Flow Area Outlet Size Code Section Media Set Pressure Range I Steam 15 - 1500 psi 0.156 in 0.307 sq in 1.5 NPS 1.25 NPS [F] 0.625 in VIII Div. 1 I Steam 0.503 sq in [G] 0.8 in 0.2 in 15 - 1500 psi VIII Div. 1 I Steam 0.785 sq in 15 - 1500 psi [H] 1 in 0.25 in 1.5 NPS 2.5 NPS VIII Div. 1 I Steam 1.287 sq in [J] 1.281 in 0.321 in 15 - 1500 psi VIII Div. 1 I Steam 15 - 1500 psi 2 NPS 1.84 sq in [K] 1.531 in 3 NPS 0.383 in VIII Div. 1 I Steam 15 - 1500 psi 2.5 NPS 0.477 in 4 NPS 2.853 sq in [L] 1.906 in VIII Div. 1 I Steam [M] 2.14 in 0.535 in 15 - 1500 psi 3 NPS 4 NPS 3.6 sq in VIII Div. 1 I Steam [N] 2.351 in 4.34 sq in 6 NPS 4 NPS 15 - 1500 psi 0.588 in VIII Div. 1 I Steam 6.38 sq in [P] 2.85 in 0.713 in 15 - 1500 psi VIII Div. 1 I Steam 6 NPS [Q] 3.75 in 0.938 in 11.05 sq in 15 - 1500 psi 8 NPS VIII Div. 1 Certification Design Series 1900D-2, 1900-30D-2 18144 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on August 16, 1977 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 5.63 PPH/PSIA Certified Value: 2.004 SCFM/PSIA Certified Value (alternate medium): Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Media Outlet Size Flow Area Lift Set Pressure Range Code Section III Steam [D] 0.674 in 15 - 2000 psi 0.066 in 0.1279 sq in 2, 3 NPS 1 - 1.5 NPS VIII Div. 1 VIII Div. 1 Air 15 - 6250 psi Page 335 of 812 Effective Date: 2019-05-31

337 Table of Contents Dresser, LLC (DRJ) 18166 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1900E-2, 1900-30E-2 18166 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on August 16, 1977 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 10.04 PPH/PSIA Certified Value: 3.57 SCFM/PSIA Certified Value (alternate medium): Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size III & VIII Div.1 Steam 1 - 1.5 NPS 2, 3 NPS 0.119 in 15 - 2000 psi 0.2279 sq in [E] 0.674 in III & VIII Div.1 Air 15 - 6250 psi Page 336 of 812 Effective Date: 2019-05-31

338 Table of Contents Dresser, LLC (DRJ) 18201 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1900, 1900-30, 1900-35 18201 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on October 11, 1954 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .855 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Lift Media Code Section Flow Area Outlet Size Set Pressure Range III & VIII Div.1 Steam 15 - 2000 psi 1 - 1.5 NPS 2, 3 NPS 0.1279 sq in [D] 0.4035 in 0.11 in III & VIII Div.1 Air 15 - 6250 psi III & VIII Div.1 Steam 0.2279 sq in 15 - 2000 psi [E] 0.5387 in 0.147 in III & VIII Div.1 Air 15 - 6250 psi III & VIII Div.1 Steam 0.182 in 15 - 2000 psi 1.5 NPS 2, 3 NPS 0.3568 sq in [F] 0.674 in III & VIII Div.1 Air 15 - 7200 psi III & VIII Div.1 Steam 1.5 - 2 NPS 2-1/2, 3 NPS 0.5849 sq in [G] 0.863 in 0.234 in 15 - 2000 psi III & VIII Div.1 Air 15 - 6000 psi III & VIII Div.1 Steam 0.9127 sq in [H] 1.078 in 15 - 2500 psi 0.292 in 3 NPS III & VIII Div.1 Air 15 - 3300 psi III & VIII Div.1 Steam 2 - 3 NPS 3, 4 NPS 1.496 sq in [J] 1.38 in 0.374 in 15 - 2500 psi III & VIII Div.1 Air 15 - 3100 psi III & VIII Div.1 Steam 3 NPS 15 - 2000 psi 0.446 in [K] 1.65 in 2.138 sq in 4, 6 NPS III & VIII Div.1 Air 15 - 3400 psi III & VIII Div.1 Air 3 - 4 NPS 4, 6 NPS 3.317 sq in [L] 2.055 in 0.556 in 15 - 2900 psi III & VIII Div.1 Steam III & VIII Div.1 Air [M] 2.3086 in 0.625 in 15 - 1600 psi 6 NPS 4 NPS 4.186 sq in III & VIII Div.1 Steam III & VIII Div.1 Air 5.047 sq in [N] 2.535 in 0.685 in 15 - 1600 psi III & VIII Div.1 Steam III & VIII Div.1 Air 7.417 sq in 15 - 1700 psi 0.83 in [P] 3.073 in III & VIII Div.1 Steam III & VIII Div.1 Air 6 NPS 8 NPS 12.85 sq in [Q] 4.045 in 1.09 in 15 - 900 psi III & VIII Div.1 Steam III & VIII Div.1 Air 8, 10 NPS 15 - 300 psi 1.29 in [R] 4.867 in 18.6 sq in III & VIII Div.1 Steam III & VIII Div.1 Air [T] 6.205 in 30.21 sq in 10 NPS 8 NPS 15 - 300 psi 1.723 in III & VIII Div.1 Steam III & VIII Div.1 Air 35 sq in [U] 6.688 in 1.841 in 15 - 300 psi III & VIII Div.1 Steam III & VIII Div.1 Air 15 - 300 psi 2.162 in 50.26 sq in 14 NPS 10 NPS [V] 8 in III & VIII Div.1 Steam III & VIII Div.1 Air 12 NPS [W] 10.029 in 15 - 300 psi 2.523 in 16 NPS 78.996 sq in III & VIII Div.1 Steam Page 337 of 812 Effective Date: 2019-05-31

339 Table of Contents Dresser, LLC (DRJ) 18223 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1900, 1900-30, 1900-35 (R.L.) 18223 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on June 19, 1985 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .855 Unitless Certified Value: per CC N-394 or 1945 Certification Provisions: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Outlet Size Inlet Size Lift Set Pressure Range Media Code Section III & VIII Div.1 Air 0.1279 sq in 1 - 1.5 NPS 2, 3 NPS [D] 0.4036 in 0.08 in 15 - 6250 psi III & VIII Div.1 Steam III & VIII Div.1 Air 0.2279 sq in 0.08 in 15 - 6250 psi [E] 0.5387 in III & VIII Div.1 Steam III & VIII Div.1 Air 2, 3 NPS 1.5 NPS 0.3568 sq in [F] 0.674 in 0.08 in 15 - 6250 psi III & VIII Div.1 Steam III & VIII Div.1 Air 15 - 6000 psi 1.5 - 2 NPS 0.5849 sq in [G] 0.863 in 0.08 in 2.5, 3 NPS III & VIII Div.1 Steam III & VIII Div.1 Air 3 NPS 0.9127 sq in [H] 1.078 in 0.087 in 15 - 3300 psi III & VIII Div.1 Steam III & VIII Div.1 Air 0.112 in 15 - 3100 psi 2 - 3 NPS 3, 4 NPS 1.496 sq in [J] 1.38 in III & VIII Div.1 Steam III & VIII Div.1 Air 0.134 in 15 - 3400 psi 4, 6 NPS 3 NPS 2.138 sq in [K] 1.65 in III & VIII Div.1 Steam III & VIII Div.1 Air 3 - 4 NPS 4, 6 NPS 3.317 sq in [L] 2.055 in 0.167 in 15 - 2900 psi III & VIII Div.1 Steam III & VIII Div.1 Air [M] 2.3086 in 0.187 in 6 NPS 15 - 1600 psi 4 NPS 4.186 sq in III & VIII Div.1 Steam III & VIII Div.1 Air 5.047 sq in [N] 2.535 in 0.205 in 15 - 1600 psi III & VIII Div.1 Steam III & VIII Div.1 Air 7.417 sq in 15 - 1700 psi 0.249 in [P] 3.073 in III & VIII Div.1 Steam III & VIII Div.1 Air 8 NPS 12.85 sq in [Q] 4.045 in 0.327 in 15 - 900 psi 6 NPS III & VIII Div.1 Steam III & VIII Div.1 Air 15 - 650 psi 0.387 in [R] 4.867 in 18.6 sq in 8, 10 NPS III & VIII Div.1 Steam III & VIII Div.1 Air [T] 6.04 in 0.504 in 15 - 360 psi 28.624 sq in 10 NPS 8 NPS III & VIII Div.1 Steam III & VIII Div.1 Air 30.21 sq in [T4] 6.205 in 0.517 in 15 - 360 psi III & VIII Div.1 Steam III & VIII Div.1 Air 15 - 300 psi 0.552 in [U] 6.688 in 35 sq in III & VIII Div.1 Steam III & VIII Div.1 Air [V] 8 in 0.648 in 15 - 300 psi 10 NPS 14 NPS 50.26 sq in III & VIII Div.1 Steam Page 338 of 812 Effective Date: 2019-05-31

340 Table of Contents Dresser, LLC (DRJ) 18256 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1900D/P, 1900-30D/P (Rest. Lift) 18256 or catalog number Number: Safety Relief Valve Type Classification: Sec. I at Dresser Industries Inc. on August 16, 1977 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 5.61 PPH/PSIA Certified Value: 1.997 SCFM/PSIA Certified Value (alternate medium): Steam Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Set Pressure Range Lift Flow Area Outlet Size Inlet Size I Steam 1 - 1.5 NPS [D] 0.674 in 0.066 in 0.1279 sq in 15 - 4460 psi 2, 3 NPS III VIII Div. 1 VIII Div. 1 Air 15 - 5000 psi Certification Design Series 1900E/P, 1900-30E/P (Rest. Lift) 18278 Number: or catalog number Safety Relief Valve Type Classification: Sec. I at Dresser Industries Inc. on August 16, 1977 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 9.98 PPH/PSIA Certified Value: 3.552 SCFM/PSIA Certified Value (alternate medium): Steam Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section I Steam 1 - 1.5 NPS 2 ,3 NPS 0.2279 sq in [E] 0.674 in 15 - 4460 psi 0.119 in III VIII Div. 1 VIII Div. 1 Air 15 - 5000 psi Page 339 of 812 Effective Date: 2019-05-31

341 Table of Contents Dresser, LLC (DRJ) 18290 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1900/P, 1900-30/P 18290 or catalog number Number: Safety Relief Valve Type Classification: Sec. I at Dresser Industries Inc. on October 11, 1954 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .851 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Outlet Size Code Section Flow Area Inlet Size Lift Media I Steam 0.182 in 2, 3 NPS 1.5 NPS 0.3568 sq in [F] 0.674 in 15 - 4460 psi III VIII VIII Air 15 - 5000 psi VIII Air 1.5 - 2 NPS 3 NPS 0.5849 sq in [G] 0.863 in 0.234 in 15 - 3600 psi I Steam III VIII III Steam 15 - 2500 psi 0.292 in [H] 1.078 in 0.9127 sq in VIII VIII Air 15 - 3300 psi I Steam III Steam 2 - 3 NPS 15 - 2500 psi 0.374 in [J] 1.38 in 1.496 sq in 3, 4 NPS VIII VIII Air 15 - 3100 psi I Steam III Steam 3 NPS 4, 6 NPS 15 - 2000 psi [K] 1.65 in 2.138 sq in 0.446 in VIII VIII Air 15 - 3000 psi I Steam VIII Air 15 - 2900 psi 3 - 4 NPS 0.556 in [L] 2.055 in 3.317 sq in 4, 6 NPS I Steam III VIII VIII Air 0.625 in 6 NPS 4 NPS 4.186 sq in [M] 2.086 in 15 - 1600 psi I Steam III VIII VIII Air 15 - 1600 psi [N] 2.535 in 0.685 in 5.047 sq in I Steam III VIII VIII Air [P] 3.073 in 7.417 sq in 0.83 in 15 - 1700 psi I Steam III VIII VIII Air [Q] 4.045 in 1.09 in 15 - 900 psi 6 NPS 8 NPS 12.85 sq in I Steam III VIII VIII Air 1.29 in 15 - 500 psi 18.6 sq in 8, 10 NPS [R] 4.867 in I Steam III VIII VIII Air [T] 6.205 in 8 NPS 10 NPS 15 - 300 psi 1.723 in 30.21 sq in I Steam III VIII Page 340 of 812 Effective Date: 2019-05-31

342 Table of Contents Dresser, LLC (DRJ) 18379 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1982 18379 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on May 06, 1980 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .855 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Inlet Size Flow Area Outlet Size Code Section Media Set Pressure Range III & VIII Div.1 Air 15 - 500 psi .75 NPS 0.092 in 0.5 NPS 0.121 sq in 0.393 in III & VIII Div.1 Steam III & VIII Div.1 Air 0.123 in 15 - 500 psi 0.75 NPS 1 NPS 0.216 sq in 0.524 in III & VIII Div.1 Steam III & VIII Div.1 Air 0.332 sq in 0.65 in 0.15 in 15 - 500 psi 1.5 NPS 1 NPS III & VIII Div.1 Steam III & VIII Div.1 Air 0.857 sq in 1.045 in 0.243 in 15 - 500 psi 1.5 NPS 2 NPS III & VIII Div.1 Steam III & VIII Div.1 Steam 15 - 100 psi 2.5 NPS 1.399 sq in 1.335 in 2 NPS 0.31 in III & VIII Div.1 Air 15 - 500 psi Design Series Certification 1982 LS, 820000LS 18380 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on December 19, 1984 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .758 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size Media III Water 15 - 500 psi 0.121 sq in .75 - 1 NPS 0.5 - 0.75 NPS 0.137 in 0.393 in VIII Div. 1 III Water 0.524 in 0.162 in 15 - 500 psi 0.75 - 1 NPS 1 , 1.5 NPS 0.216 sq in VIII Div. 1 III Water 0.332 sq in 0.65 in 0.236 in 15 - 500 psi 1 - 1.25 NPS 1.5 NPS VIII Div. 1 III Water 1.5 - 2 NPS 2, 2.5 NPS 15 - 500 psi 0.343 in 1.045 in 0.857 sq in VIII Div. 1 III Water 1.335 in 0.43 in 15 - 500 psi 2 NPS 2.5 NPS 1.399 sq in VIII Div. 1 Page 341 of 812 Effective Date: 2019-05-31

343 Table of Contents Dresser, LLC (DRJ) 18403 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1990 - 3999 LS & DL (Liquids) 18403 Number: or catalog number Relief Valve Type Classification: Sec. III & VIII Div.1 at Dresser Industries Inc. on November 02, 1984 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.669 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Inlet Size Code Section Media Flow Area Set Pressure Range Lift III Water 0.5 - 0.75 NPS 0.045 in 15 - 1000 psi .5 - 1 NPS 0.019 sq in 0.156 in VIII Div. 1 Water 15 - 11000 psi III Water 0.11 sq in 0.5 - 1 NPS 1 NPS 0.375 in 0.17 in 15 - 6000 psi VIII Div. 1 III Water 1 NPS 15 - 8000 psi 0.104 in 0.401 in 0.126 sq in 0.75 NPS VIII Div. 1 III Water 0.205 in 1 NPS 1.5 NPS 0.196 sq in 0.5 in 15 - 3000 psi VIII Div. 1 III Water 15 - 6400 psi 0.2 in 0.537 in 0.226 sq in VIII Div. 1 III Water 0.61 in 0.215 in 0.292 sq in 15 - 1500 psi VIII Div. 1 III Water 0.75 in 1.5 - 2 NPS 0.24 in 15 - 1500 psi 0.442 sq in 2 NPS VIII Div. 1 III Water 2 NPS 3 NPS 0.754 sq in 0.98 in 0.39 in 15 - 500 psi VIII Div. 1 Certification Design Series 3700-RT 18414 or catalog number Number: Safety Valve Type Classification: Sec. III NB at Dresser Industries Inc. on October 13, 1967 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .8775 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Outlet Size Inlet Size Media Code Section Flow Area III Steam 50 - 1500 psi 0.45 in [#3] 1.8 in 2.5 - 3 NPS 2.545 sq in 6 NPS III Steam 6 NPS [#5] 2.062 in 0.516 in 3 - 4 NPS 50 - 1500 psi 3.341 sq in III Steam 3.976 sq in [#4] 2.25 in 0.563 in 50 - 1500 psi III Steam 0.75 in 4 - 6 NPS 6 NPS 7.07 sq in 50 - 1500 psi [#6] 3 in III Steam 50 - 1500 psi 0.89 in [#7] 3.562 in 9.965 sq in III Steam [Q] 3.75 in 0.938 in 50 - 1500 psi 6 NPS 8 NPS 11.04 sq in III Steam [#8] 4.25 in 14.18 sq in 8, 10 NPS 6 - 8 NPS 50 - 1500 psi 1.063 in III Steam [R] 4.515 in 50 - 1500 psi 16 sq in 1.129 in III Steam 50 - 1500 psi 1.239 in [RR] 4.956 in 19.29 sq in III Steam 50 - 1500 psi 1.59 in [S] 6.375 in 31.92 sq in 10 Dual NPS 8 NPS III Steam 28.3 sq in 1.5 in 50 - 1500 psi 10, 12 NPS [T] 6 in 8 - 10 NPS Page 342 of 812 Effective Date: 2019-05-31

344 Table of Contents Dresser, LLC (DRJ) NB#: 18447 location: 12970 Normandy Blvd, Jacksonville, FL 32221 United States Acceptable Abbrev.: JAX Certification Design Series 3900 (39PV, 39MV pilots) 18447 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on May 19, 1988 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.878 Unitless Certified Value: Air Test Medium: Steam & Air/Gas Certified Medium: None Special Service: 1.Pop 2.Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Outlet Size Inlet Size Code Section Set Pressure Range Media VIII Air 15 - 6250 psi 0.128 sq in [D] 0.404 in 1 - 1.5 NPS 2 NPS 0.205 in III Steam 15 - 750 psi VIII VIII Air [E] 0.539 in 0.228 sq in 15 - 6250 psi 0.25 in III Steam 15 - 750 psi VIII VIII Air 15 - 6250 psi [F] 0.674 in 0.357 sq in 0.25 in III Steam 15 - 750 psi VIII VIII Steam 1.621 sq in 1.437 in 0.25 in 1.5 NPS 15 - 30 psi VIII Air 15 - 6250 psi VIII Air 15 - 6250 psi 1.5 - 2 NPS [G] 0.863 in 0.5 in 0.585 sq in III Steam 15 - 750 psi VIII VIII Air 0.5 in 15 - 6250 psi [H] 1.07 in 0.913 sq in III Steam 15 - 750 psi VIII VIII Steam 2 NPS 2.764 sq in 0.5 in 15 - 30 psi 1.876 in VIII Air 15 - 6250 psi VIII Air 2 - 3 NPS [J] 1.38 in 1.496 sq in 0.5 in 15 - 6250 psi III Steam 15 - 750 psi VIII VIII Air 15 - 6250 psi 2.138 sq in [K] 1.65 in 3 NPS 0.68 in III Steam 15 - 750 psi VIII VIII Steam 15 - 30 psi 2.837 in 6.321 sq in 0.68 in VIII Air 15 - 3750 psi VIII Air [L] 2.055 in 3 - 4 NPS 3.317 sq in 0.68 in 15 - 6250 psi III Steam 15 - 750 psi VIII VIII Air 1 in [M] 2.309 in 4 NPS 15 - 3750 psi 4.186 sq in III Steam 15 - 750 psi VIII VIII Air 5.047 sq in 15 - 3750 psi 1 in [N] 2.535 in III Steam 15 - 750 psi VIII VIII Air 7.417 sq in 15 - 3750 psi [P] 3.073 in 1 in III Steam 15 - 750 psi VIII VIII Steam 15 - 30 psi 10.76 sq in 3.701 in 1 in VIII Air 15 - 3750 psi Page 343 of 812 Effective Date: 2019-05-31

345 Table of Contents Dresser, LLC (DRJ) 18447 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX ...Continued Orifice [designator] diameter Set Pressure Range Code Section Inlet Size Outlet Size Media Lift Flow Area VIII Air [Q] 4.045 in 6 NPS 1.31 in 15 - 1500 psi 12.85 sq in III Steam 15 - 750 psi VIII VIII Air 18.6 sq in [R] 4.866 in 1.31 in 15 - 1500 psi III Steam 15 - 750 psi VIII VIII Air 24.95 sq in 1.31 in 15 - 1500 psi 5.636 in VIII Steam 15 - 700 psi VIII Air 15 - 1500 psi 8 NPS 30.21 sq in [T] 6.205 in 2 in III Steam VIII VIII Air 44.18 sq in 7.5 in 2 in 15 - 1500 psi VIII Steam 15 - 700 psi VIII Air [W] 9 in 10 NPS 63.62 sq in 3 in 15 - 1500 psi III Steam 15 - 750 psi VIII VIII Air 9.437 in 3 in 15 - 1500 psi 69.94 sq in VIII Steam 15 - 700 psi Page 344 of 812 Effective Date: 2019-05-31

346 Table of Contents Dresser, LLC (DRJ) 18458 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 3900 (39PV, 39MV pilots, liquid) 18458 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on June 01, 1988 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.743 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Set Pressure Range Code Section Media Lift III Water 1 - 1.5 NPS 2 NPS 0.128 sq in [D] 0.404 in 0.25 in 15 - 6250 psi VIII III Water [E] 0.539 in 0.25 in 15 - 6250 psi 0.228 sq in VIII III Water 15 - 6250 psi 0.25 in [F] 0.674 in 0.357 sq in VIII VIII Water 1.5 NPS 1.621 sq in 1.437 in 0.25 in 15 - 6250 psi III Water 0.5 in 1.5 - 2 NPS 0.585 sq in [G] 0.863 in 15 - 6250 psi VIII III Water 0.913 sq in [H] 1.078 in 0.5 in 15 - 6250 psi VIII VIII Water 15 - 6250 psi 2.764 sq in 2 NPS 1.876 in 0.5 in III Water 2 - 3 NPS 1.496 sq in [J] 1.38 in 0.5 in 15 - 6250 psi VIII III Water 15 - 6250 psi 2.138 sq in 3 NPS 0.68 in [K] 1.65 in VIII VIII Water 2.837 in 0.68 in 15 - 3750 psi 6.321 sq in III Water 15 - 6250 psi 0.68 in [L] 2.055 in 3.317 sq in 3 - 4 NPS VIII III Water 4 NPS 15 - 3750 psi 1 in [M] 2.309 in 4.186 sq in VIII III Water [N] 2.535 in 15 - 3750 psi 1 in 5.047 sq in VIII III Water 15 - 3750 psi 1 in [P] 3.073 in 7.417 sq in VIII VIII Water 1 in 15 - 3750 psi 10.76 sq in 3.701 in III Water 6 NPS [Q] 4.045 in 1.31 in 15 - 1500 psi 12.85 sq in VIII III Water [R] 4.866 in 15 - 1500 psi 1.31 in 18.6 sq in VIII VIII Water 15 - 1500 psi 1.31 in 5.636 in 24.95 sq in III Water 30.21 sq in [T] 6.205 in 2 in 15 - 1500 psi 8 NPS VIII VIII Water 15 - 1500 psi 2 in 7.5 in 44.18 sq in III Water 15 - 1500 psi 3 in [W] 9 in 63.62 sq in 10 NPS VIII VIII Water 15 - 1500 psi 69.94 sq in 9.437 in 3 in Page 345 of 812 Effective Date: 2019-05-31

347 Table of Contents Dresser, LLC (DRJ) 18469 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 13900 TRH 18469 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on June 13, 1969 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .877 Unitless Certified Value: per CC 2397 Certification Provisions: Steam Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size Media VIII Div. 1 Steam 16 NPS 18 NPS 50 - 300 psi 3.81 in 12.05 in 114 sq in VIII Div. 1 Steam 4.07 in 50 - 300 psi 18 NPS 143.1 sq in 13.5 in 22 NPS VIII Div. 1 Steam 15 in 4.53 in 50 - 300 psi 20 NPS 24 NPS 176.7 sq in Design Series Certification 13900 TRH 20" 18470 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on December 16, 2008 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .784 Unitless Certified Value: per CC 2397 Certification Provisions: Steam Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Steam 50 - 300 psi 4.77 in [13906] 16 in 201 sq in 24 NPS 20 NPS Page 346 of 812 Effective Date: 2019-05-31

348 Table of Contents Dresser, LLC (DRJ) 18706 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 19000 Series 18706 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on August 26, 1994 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Air Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Media Inlet Size Set Pressure Range Lift Outlet Size VIII Div. 1 Air 0.019 sq in 0.5 - 1 NPS 1 NPS 0.156 in 0.039 in 15 - 1500 psi III Steam VIII Air 0.11 in 15 - 1500 psi 0.096 sq in 0.35 in III Steam VIII III Air 15 - 5000 psi VIII III Steam 15 - 1500 psi 0.118 in 0.375 in 0.11 sq in VIII III Air 15 - 5000 psi VIII III Steam 0.401 in 1 NPS 0.75 - 1 NPS 0.126 sq in 0.126 in 15 - 2000 psi VIII III Air 15 - 8000 psi VIII III Steam 0.226 sq in 15 - 2000 psi 0.537 in 0.169 in 1 NPS 1.5 NPS VIII III Air 15 - 6400 psi VIII III Air 0.675 in 0.212 in 15 - 1500 psi 1.5 NPS 2 NPS 0.357 sq in VIII III Steam VIII III Air 0.567 sq in 0.85 in 15 - 1000 psi 0.266 in 2.5 NPS 2 NPS VIII III Steam VIII Page 347 of 812 Effective Date: 2019-05-31

349 Table of Contents Dresser, LLC (DRJ) 18717 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Design Series Certification 19000 Series, Liquid 18717 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on August 30, 1994 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .673 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Code Section Outlet Size Inlet Size Media Set Pressure Range III NC, ND Water 15 - 5000 psi 0.045 in 0.156 in 1 NPS 0.5 - 1 NPS 0.019 sq in VIII Div. 1 III NB Water 15 - 550 psi III NC, ND Water 0.096 sq in 0.11 in 15 - 5000 psi 0.35 in VIII Div. 1 III NB Water 15 - 550 psi III NB, NC, ND Water 15 - 290 psi 0.118 in 0.375 in 0.11 sq in VIII Div. 1 III NB Water 0.126 in 15 - 550 psi 0.75 - 1 NPS 1 NPS 0.126 sq in 0.401 in III NC, ND Water 15 - 8000 psi VIII Div. 1 III NB Water 15 - 550 psi 0.169 in 0.537 in 0.226 sq in 1.5 NPS 1 NPS III NC, ND Water 15 - 6400 psi VIII Div. 1 III NC, ND Water 15 - 1500 psi 0.212 in 0.675 in 0.357 sq in 2 NPS 1.5 NPS VIII Div. 1 III NB Water 15 - 550 psi III NC, ND Water 2 NPS 15 - 1000 psi 0.266 in 0.85 in 0.567 sq in 2.5 NPS VIII Div. 1 III NB Water 15 - 550 psi Design Series Certification 1900D-2, 1900-30D-2 LA & DALA (Liquids) 18751 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on July 12, 1995 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 3.256 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Inlet Size Outlet Size Set Pressure Range Media Flow Area I, III, & VIII Div. 1 Water [D] 0.674 in 0.056 in 15 - 6250 psi 1 - 1.5 NPS 2 - 3 NPS 0.1279 sq in Page 348 of 812 Effective Date: 2019-05-31

350 Table of Contents Dresser, LLC (DRJ) 18762 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1900E-2, 1900-30E-2 LA & DALA (Liquids) 18762 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on July 12, 1995 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 5.798 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Inlet Size Media Code Section Outlet Size Set Pressure Range I, III, & VIII Div. 1 Water 15 - 6250 psi 1 - 1.5 NPS 2 - 3 NPS 0.2279 sq in [E] 0.674 in 0.093 in Design Series Certification 1900, 1900-30 1900-35 LA & DALA (Liquids) 18784 or catalog number Number: Relief Valve Type Classification: Sec. VIII at Dresser Industries Inc. on July 12, 1995 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .670 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Media Code Section Outlet Size Lift Inlet Size Flow Area I, III, & VIII Div. 1 Water 1 - 1.5 NPS 2 - 3 NPS 15 - 6250 psi 0.095 in [D] 0.4036 in 0.128 sq in I, III, & VIII Div. 1 Water [E] 0.5387 in 15 - 6250 psi 0.127 in 0.228 sq in I, III, & VIII Div. 1 Water 1.5 NPS 2 - 3 NPS 0.357 sq in [F] 0.674 in 0.16 in 15 - 6250 psi I, III, & VIII Div. 1 Water 15 - 6000 psi [G] 0.863 in 0.585 sq in 2.5, 3 NPS 1.5 - 2 NPS 0.205 in I, III, & VIII Div. 1 Water 15 - 3300 psi 3 NPS 0.913 sq in [H] 1.078 in 0.395 in I, III, & VIII Div. 1 Water 2 - 3 NPS 3, 4 NPS 1.496 sq in [J] 1.38 in 0.506 in 15 - 3100 psi I, III, & VIII Div. 1 Water 2.138 sq in 4, 6 NPS 15 - 3400 psi 3 NPS [K] 1.65 in 0.605 in I, III, & VIII Div. 1 Water 15 - 2900 psi 0.753 in [L] 2.055 in 3 - 4 NPS 3.317 sq in 4, 6 NPS I, III, & VIII Div. 1 Water 6 NPS [M] 2.3086 in 0.846 in 4 NPS 15 - 1600 psi 4.186 sq in I, III, & VIII Div. 1 Water 15 - 1600 psi 5.047 sq in [N] 2.535 in 0.929 in I, III, & VIII Div. 1 Water 1.126 in 15 - 1700 psi 7.417 sq in [P] 3.073 in I, III, & VIII Div. 1 Water [Q] 4.045 in 15 - 900 psi 12.851 sq in 8 NPS 6 NPS 1.482 in I, III, & VIII Div. 1 Water 15 - 300 psi 8, 10 NPS 18.604 sq in [R] 4.867 in 1.782 in I, III, & VIII Div. 1 Water [T] 6.04 in 28.624 sq in 10 NPS 8 NPS 15 - 360 psi 2.212 in I, III, & VIII Div. 1 Water [T-4] 6.205 in 15 - 360 psi 30.21 sq in 2.272 in I, III, & VIII Div. 1 Water 15 - 300 psi 2.272 in [U] 6.688 in 35 sq in I, III, & VIII Div. 1 Water 15 - 300 psi 2.93 in [V] 8 in 50.26 sq in 12 NPS 10 NPS I, III, & VIII Div. 1 Water 78.996 sq in 3.675 in 15 - 300 psi 16 NPS [W] 10.029 in 12 NPS Page 349 of 812 Effective Date: 2019-05-31

351 Table of Contents Dresser, LLC (DRJ) 18863 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 2900 (39PV & 39MV pilots) 18863 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on June 25, 1999 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.855 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: 1.Pop 2.Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Inlet Size Code Section Outlet Size Set Pressure Range Media VIII Steam 15 - 2000 psi 1 - 1.5 NPS 2 - 2.5 NPS 0.1279 sq in [D] 0.4036 in 0.11 in VIII Air 15 - 7200 psi VIII Steam 0.2279 sq in 15 - 2000 psi [E] 0.5387 in 0.147 in VIII Air 15 - 6250 psi VIII Steam 0.182 in 15 - 2000 psi 1.5 NPS 2 - 2.5 NPS 0.3568 sq in [F] 0.674 in VIII Air 15 - 7200 psi VIII Steam 1.5 - 2 NPS 2.5 - 3 NPS 0.5849 sq in [G] 0.863 in 0.234 in 15 - 2000 psi VIII Air 15 - 6000 psi VIII Steam 0.9127 sq in [H] 1.078 in 15 - 2500 psi 0.292 in 3 NPS VIII Air 15 - 3300 psi VIII Steam 2 - 3 NPS 3 - 4 NPS 1.496 sq in [J] 1.38 in 0.374 in 15 - 2500 psi VIII Air 15 - 3100 psi VIII Steam 15 - 2000 psi 0.446 in [K] 1.65 in 2.138 sq in 4 - 6 NPS 3 NPS VIII Air 15 - 3000 psi VIII Air [L] 2.055 in 3.317 sq in 4 - 6 NPS 3 - 4 NPS 15 - 2900 psi 0.556 in VIII Steam VIII Air 4.186 sq in 6 NPS 15 - 1600 psi 4 NPS 0.625 in [M] 2.3086 in VIII Steam VIII Air 15 - 1600 psi 0.685 in [N] 2.535 in 5.047 sq in VIII Steam VIII Air 7.417 sq in [P] 3.073 in 0.83 in 15 - 1700 psi VIII Steam VIII Air 12.85 sq in 6 NPS 8 NPS [Q] 4.045 in 1.09 in 15 - 900 psi VIII Steam VIII Air 15 - 300 psi 1.29 in [R] 4.867 in 18.6 sq in 8 - 10 NPS VIII Steam VIII Air [T] 6.205 in 30.21 sq in 10 NPS 8 NPS 15 - 300 psi 1.723 in VIII Steam VIII Div. 1 Air 35 sq in [U] 6.688 in 1.841 in 15 - 905 psi VIII Div. 1 Steam VIII Air 15 - 300 psi 2.162 in 50.26 sq in 14 NPS 10 NPS [V] 8.002 in VIII Steam VIII Air 12 NPS [W] 10.029 in 15 - 300 psi 2.523 in 16 NPS 78.996 sq in VIII Steam Page 350 of 812 Effective Date: 2019-05-31

352 Table of Contents Dresser, LLC (DRJ) 18874 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Design Series Certification 2900 (39PV & 39MV pilots - Liquid) 18874 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on June 25, 1999 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .670 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Inlet Size Flow Area Outlet Size Code Section Media Set Pressure Range I & VIII Div. 1 Water 15 - 6250 psi [D] 0.4036 in 0.1279 sq in 2 - 2.5 NPS 1 - 1.5 NPS 0.092 in I & VIII Div. 1 Water 0.105 in 15 - 6250 psi 0.2279 sq in [E] 0.5387 in I & VIII Div. 1 Water 0.3568 sq in 1.5 NPS 2 - 2.5 NPS [F] 0.674 in 0.141 in 15 - 6250 psi I & VIII Div. 1 Water 15 - 6000 psi 1.5 - 2 NPS 0.5849 sq in [G] 0.863 in 0.25 in 2.5 - 3 NPS I & VIII Div. 1 Water 15 - 3300 psi 0.395 in [H] 1.078 in 0.9127 sq in 3 NPS I & VIII Div. 1 Water 15 - 3100 psi 2 - 3 NPS [J] 1.38 in 0.506 in 1.496 sq in 3 - 4 NPS I & VIII Div. 1 Water 15 - 3000 psi 0.605 in [K] 1.65 in 2.138 sq in 4 - 6 NPS 3 NPS I & VIII Div. 1 Water 4 - 6 NPS 0.753 in 15 - 2900 psi 3.317 sq in 3 - 4 NPS [L] 2.055 in I & VIII Div. 1 Water 15 - 1600 psi 0.846 in [M] 2.3086 in 4 NPS 4.186 sq in 6 NPS I & VIII Div. 1 Water 0.929 in [N] 2.535 in 15 - 1600 psi 5.047 sq in I & VIII Div. 1 Water 1.126 in 15 - 1700 psi 7.417 sq in [P] 3.073 in I & VIII Div. 1 Water 15 - 900 psi 1.482 in [Q] 4.045 in 8 NPS 6 NPS 12.85 sq in I & VIII Div. 1 Water 15 - 500 psi 1.738 in [R] 4.867 in 8 - 10 NPS 18.6 sq in I & VIII Div. 1 Water 30.21 sq in 15 - 300 psi [T] 6.205 in 2.272 in 8 NPS 10 NPS I & VIII Div. 1 Water 15 - 905 psi 1.841 in [U] 6.688 in 35 sq in I & VIII Div. 1 Water 15 - 300 psi 2.93 in [V] 8.002 in 50.26 sq in 14 NPS 10 NPS I & VIII Div. 1 Water 78.996 sq in 3.675 in 15 - 300 psi 16 NPS [W] 10.029 in 12 NPS Page 351 of 812 Effective Date: 2019-05-31

353 Table of Contents Dresser, LLC (DRJ) 18885 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 4900 (49PV & 49MV pilots) 18885 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on August 05, 1999 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Media Flow Area Code Section Inlet Size Lift Set Pressure Range VIII Div. 1 Air [D] 0.409 in 1 - 1.5 NPS 2 NPS 0.1314 sq in 0.25 in 15 - 6250 psi VIII Div. 1 Steam 15 - 750 psi VIII Div. 1 Air 0.228 sq in 15 - 6250 psi 0.25 in [E] 0.539 in VIII Div. 1 Steam 15 - 750 psi VIII Div. 1 Air 0.359 sq in [F] 0.676 in 0.25 in 15 - 6250 psi VIII Div. 1 Steam 15 - 750 psi VIII Div. 1 Air 15 - 6250 psi 0.7 in [G] 0.869 in 0.594 sq in 1.5 - 2 NPS 3 NPS VIII Div. 1 Steam 15 - 750 psi VIII Div. 1 Air 15 - 6250 psi 0.7 in [H] 1.088 in 0.93 sq in VIII Div. 1 Steam 15 - 750 psi VIII Div. 1 Air 2 - 3 NPS 15 - 6250 psi 3 - 4 NPS 0.7 in [J] 1.388 in 1.513 sq in VIII Div. 1 Steam 15 - 750 psi VIII Div. 1 Air [K] 1.658 in 0.68 in 15 - 3750 psi 3 NPS 4 NPS 2.16 sq in VIII Div. 1 Steam 15 - 750 psi VIII Div. 1 Air 0.68 in [L] 2.065 in 3.35 sq in 4 - 6 NPS 15 - 3750 psi 3 - 4 NPS VIII Div. 1 Steam 15 - 750 psi VIII Div. 1 Air 4 NPS 6 NPS 1 in 4.229 sq in [M] 2.321 in 15 - 3750 psi VIII Div. 1 Steam 15 - 750 psi VIII Div. 1 Air 5.098 sq in [N] 2.548 in 1 in 15 - 3750 psi VIII Div. 1 Steam 15 - 750 psi VIII Div. 1 Air 15 - 3750 psi 7.491 sq in [P] 3.088 in 1 in VIII Div. 1 Steam 15 - 750 psi VIII Div. 1 Air [Q] 4.065 in 1.31 in 15 - 1500 psi 6 NPS 8 NPS 12.979 sq in VIII Div. 1 Steam 15 - 750 psi VIII Div. 1 Steam 8 - 10 NPS 18.783 sq in [R] 4.89 in 1.31 in 15 - 150 psi VIII Div. 1 Air 15 - 1500 psi VIII Div. 1 Air [T] 6.236 in 15 - 1500 psi 2 in 30.542 sq in 10 NPS 8 NPS VIII Div. 1 Steam 15 - 750 psi Page 352 of 812 Effective Date: 2019-05-31

354 Table of Contents Dresser, LLC (DRJ) 18964 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 2900 POSRV (39 PV, 39 MV Pilots) 18964 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. I at Dresser Industries Inc. on November 02, 2005 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.851 Unitless Certified Value: 0.691 Water Unitless Certified Value (alternate medium): per CC 2446 Certification Provisions: Steam Test Medium: Steam/Water Certified Medium: 1.Pop 2.Initial Audible Discharge 3.First Steady Stream Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Outlet Size Inlet Size Lift Set Pressure Range Media Code Section I Steam 2, 3 NPS 1 - 1.5 NPS 0.1279 sq in [D] 0.4036 in 0.11 in 40 - 5800 psi I Water I Steam 0.2279 sq in 0.147 in 40 - 5800 psi [E] 0.5387 in I Water I Steam 0.3568 sq in 1.5 NPS 2, 3 NPS [F] 0.674 in 0.182 in 40 - 5800 psi I Water I Steam 1.5 - 2 NPS 0.5849 sq in [G] 0.863 in 40 - 5800 psi 3 NPS 0.234 in I Water I Steam 0.9127 sq in 0.292 in [H] 1.078 in 40 - 3750 psi I Water I Steam 0.374 in 40 - 5800 psi 2 - 3 NPS 3, 4 NPS 1.496 sq in [J] 1.38 in I Water I Steam 40 - 5800 psi [K] 1.649 in 2.136 sq in 4, 6 NPS 3 NPS 0.446 in I Water I Steam [L] 2.055 in 0.556 in 40 - 6250 psi 3 - 4 NPS 4, 6 NPS 3.317 sq in I Water I Steam 40 - 2250 psi 4 NPS 0.625 in [M] 2.309 in 4.186 sq in 6 NPS I Water I Steam 40 - 2250 psi 0.685 in [N] 2.535 in 5.047 sq in I Water I Steam 7.417 sq in 40 - 2250 psi 0.83 in [P] 3.073 in I Water I Steam 1.09 in 40 - 1500 psi 6 NPS 8 NPS 12.85 sq in [Q] 4.045 in I Water I Steam 1.29 in [R] 4.867 in 18.6 sq in 8, 10 NPS 40 - 1500 psi I Water I Steam [T] 6.205 in 1.723 in 40 - 905 psi 8 NPS 10 NPS 30.21 sq in I Water I Steam 40 - 905 psi 35 sq in [U] 6.688 in 1.841 in I Water I Steam 10 NPS 14 NPS 50.26 sq in 40 - 675 psi 2.162 in [V] 8.002 in I Water I Steam [W] 10.029 in 2.523 in 40 - 535 psi 12 NPS 16 NPS 78.996 sq in I Water Page 353 of 812 Effective Date: 2019-05-31

355 Table of Contents Dresser, LLC (DRJ) 18997 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1900-UM 18997 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on March 15, 2010 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .855 Unitless Certified Value: Air Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Inlet Size Code Section Outlet Size Set Pressure Range Media VIII Div. 1 Steam 15 - 2000 psi 1.5 NPS 2 - 3 NPS 0.3568 sq in [F] 0.674 in 0.182 in VIII Div. 1 Air 15 - 7200 psi VIII Div. 1 Steam 0.234 in 0.5849 sq in 3 NPS 1.5 - 2 NPS 15 - 2000 psi [G] 0.863 in VIII Div. 1 Air 15 - 6000 psi VIII Div. 1 Steam 0.395 in 0.9127 sq in [H] 1.078 in 15 - 2500 psi VIII Div. 1 Air 15 - 3300 psi VIII Div. 1 Steam 15 - 2500 psi 0.506 in 2 - 3 NPS [J] 1.38 in 1.496 sq in 3, 4 NPS VIII Div. 1 Air 15 - 3100 psi VIII Div. 1 Steam 15 - 2000 psi 3 NPS 2.138 sq in [K] 1.65 in 4, 6 NPS 0.605 in VIII Div. 1 Air 15 - 3000 psi VIII Div. 1 Air 15 - 2900 psi 0.753 in [L] 2.055 in 3.317 sq in 4, 6 NPS 3 - 4 NPS VIII Div. 1 Steam VIII Div. 1 Air 4 NPS 6 NPS 4.186 sq in [M] 2.309 in 0.846 in 15 - 1600 psi VIII Div. 1 Steam VIII Div. 1 Air 15 - 1600 psi 5.047 sq in 0.929 in [N] 2.535 in VIII Div. 1 Steam VIII Div. 1 Air 1.126 in [P] 3.073 in 7.417 sq in 15 - 1700 psi VIII Div. 1 Steam VIII Div. 1 Air 15 - 900 psi 6 NPS 8 NPS 12.85 sq in [Q] 4.045 in 1.482 in VIII Div. 1 Steam VIII Div. 1 Air [R] 4.867 in 1.782 in 8, 10 NPS 15 - 300 psi 18.6 sq in VIII Div. 1 Steam VIII Div. 1 Air [T] 6.205 in 2.212 in 15 - 300 psi 8 NPS 10 NPS 30.21 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 300 psi 35 sq in [U] 6.688 in 2.428 in VIII Div. 1 Steam VIII Div. 1 Air 10 NPS 14 NPS 50.26 sq in 15 - 300 psi 2.93 in [V] 8 in VIII Div. 1 Steam VIII Div. 1 Air [W] 10.029 in 3.675 in 15 - 300 psi 12 NPS 16 NPS 78.996 sq in VIII Div. 1 Steam Page 354 of 812 Effective Date: 2019-05-31

356 Table of Contents Dresser, LLC (DRJ) 19000 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1900-UM (Liquids) 19000 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on March 10, 2010 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .67 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Set Pressure Range Code Section Media Lift VIII Div. 1 Water 1.5 NPS 2, 3 NPS 0.3568 sq in [F] 0.674 in 0.182 in 15 - 6250 psi VIII Div. 1 Water 3 NPS 0.5849 sq in 15 - 6000 psi 0.234 in 1.5 - 2 NPS [G] 0.863 in VIII Div. 1 Water 15 - 3300 psi 0.395 in [H] 1.078 in 0.9127 sq in VIII Div. 1 Water 2 - 3 NPS 3, 4 NPS 1.496 sq in [J] 1.38 in 0.506 in 15 - 3100 psi VIII Div. 1 Water 15 - 3000 psi 0.605 in [K] 1.65 in 2.138 sq in 4, 6 NPS 3 NPS VIII Div. 1 Water 15 - 2900 psi 4, 6 NPS 0.753 in [L] 3.065 in 3.317 sq in 3 - 4 NPS VIII Div. 1 Water 15 - 1600 psi 0.846 in [M] 2.309 in 4.186 sq in 6 NPS 4 NPS VIII Div. 1 Water [N] 2.535 in 0.929 in 5.047 sq in 15 - 1600 psi VIII Div. 1 Water 15 - 1700 psi 1.126 in [P] 3.073 in 7.417 sq in VIII Div. 1 Water [Q] 4.045 in 1.482 in 15 - 900 psi 6 NPS 8 NPS 12.85 sq in VIII Div. 1 Water 15 - 300 psi 1.782 in [R] 4.867 in 18.6 sq in 8, 10 NPS VIII Div. 1 Water 8 NPS [T] 6.205 in 10 NPS 2.212 in 15 - 300 psi 30.21 sq in VIII Div. 1 Water 35 sq in 15 - 300 psi 2.428 in [U] 6.688 in VIII Div. 1 Water 2.93 in 14 NPS [V] 8 in 15 - 300 psi 10 NPS 50.26 sq in VIII Div. 1 Water 3.675 in 15 - 300 psi 12 NPS 16 NPS 78.996 sq in [W] 10.029 in Certification Design Series 1900-UM-D 19011 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on March 18, 2010 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.991 SCFM/PSIA Certified Value: 5.594 PPH/PSIA Certified Value (alternate medium): Air Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Inlet Size Outlet Size Lift Set Pressure Range Media Flow Area VIII Div. 1 Steam [D] 0.674 in 0.067 in 15 - 2000 psi 1 - 1.5 NPS 2 - 3 NPS 0.1279 sq in VIII Div. 1 Air 15 - 6250 psi Page 355 of 812 Effective Date: 2019-05-31

357 Table of Contents Dresser, LLC (DRJ) 19022 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 1900 UM-D (Liquids) 19022 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on March 18, 2010 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 3.256 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Water 1 - 1.5 NPS 2 - 3 NPS 0.1279 sq in [D] 0.674 in 0.067 in 15 - 6250 psi Certification Design Series 1900-UM-E 19033 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on March 10, 2010 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.558 SCFM/PSIA Certified Value: 9.996 PPH/PSIA Certified Value (alternate medium): Air Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Steam 1 - 1.5 NPS 2 - 3 NPS 0.2279 sq in [E] 0.674 in 15 - 2000 psi 0.105 in VIII Div. 1 Air 15 - 6250 psi Design Series Certification 1900-UM-E (Liquids) 19044 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on March 10, 2010 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 5.798 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Steam 1 - 1.5 NPS 2 - 3 NPS 0.105 in 15 - 2000 psi 0.2279 sq in [E] 0.674 in VIII Div. 1 Water 15 - 6250 psi Page 356 of 812 Effective Date: 2019-05-31

358 Table of Contents Dresser, LLC (DRJ) 19077 NB#: 12970 Normandy Blvd, Jacksonville, FL 32221 United States location: Acceptable Abbrev.: JAX Certification Design Series 19110M & 19110H (Liquids) 19077 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at Dresser Industries Inc. on July 29, 2010 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.264 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size III Water 0.375 in 290 - 5000 psi 0.118 in 0.5 - 1 NPS 0.11 sq in 1 NPS VIII Div. 1 Page 357 of 812 Effective Date: 2019-05-31

359 Table of Contents Elfab Limited (ELF) 88062 NB#: Alder Road location: Acceptable Abbrev.: ELFAB Elfab Limited (ELF) location: Alder Road Acceptable Abbrev.: ELFAB Certification Design Series DSC-FCD 88062 Number: or catalog number HLD-STD Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on January 07, 2002 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 2.2 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Air 20 - 30 psi 0.607 sq in 1 NPS VIII Div. 1 1.5 NPS 1.655 sq in 14.5 - 20 psi VIII Div. 1 2 NPS 2.774 sq in 7 - 20 psi VIII Div. 1 2.5 NPS 4.678 sq in 2 - 20 psi VIII Div. 1 3 NPS 2 - 20 psi 7.216 sq in VIII Div. 1 4 NPS 11.81 sq in 2 - 20 psi VIII Div. 1 1 - 10 psi 6 NPS 26.246 sq in VIII Div. 1 8 NPS 47.19 sq in 1 - 10 psi VIII Div. 1 1 - 10 psi 74.22 sq in 10 NPS VIII Div. 1 1 - 10 psi 12 NPS 107.4 sq in VIII Div. 1 1 - 9 psi 146.5 sq in 14 NPS VIII Div. 1 191.9 sq in 16 NPS 1 - 7 psi VIII Div. 1 18 NPS 1 - 209 psi 243.2 sq in VIII Div. 1 1 - 209 psi 292.3 sq in 20 NPS VIII Div. 1 422.6 sq in 1 - 209 psi 24 NPS VIII Div. 1 1 - 209 psi 578.9 sq in 28 NPS VIII Div. 1 1 - 209 psi 669.9 sq in 30 NPS VIII Div. 1 32 NPS 764.77 sq in 1 - 197 psi VIII Div. 1 1 - 184 psi 865.92 sq in 34 NPS VIII Div. 1 1 - 171 psi 973.34 sq in 36 NPS VIII Div. 1 1 - 158 psi 38 NPS 1087.05 sq in VIII Div. 1 40 NPS 1207.04 sq in 1 - 145 psi VIII Div. 1 1333.31 sq in 1 - 132 psi 42 NPS VIII Div. 1 44 NPS 1 - 119 psi 1465.85 sq in VIII Div. 1 1 - 106 psi 46 NPS 1604.68 sq in VIII Div. 1 1 - 93 psi 48 NPS 1749.79 sq in Page 358 of 812 Effective Date: 2019-05-31

360 Table of Contents Elfab Limited (ELF) 88118 NB#: Alder Road location: Acceptable Abbrev.: ELFAB Certification Design Series OPR 88118 Number: or catalog number OPR Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 25, 2003 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.19 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Code Section Outlet Size Inlet Size Media Set Pressure Range VIII Div. 1 50 - 1523 psi 1 NPS 0.766 sq in VIII Div. 1 1.5 NPS 1.651 sq in 27 - 1523 psi VIII Div. 1 14 - 1523 psi 2 NPS 2.789 sq in VIII Div. 1 2.5 NPS 4.119 sq in 10 - 1305 psi VIII Div. 1 3 NPS 7 - 1088 psi 6.722 sq in VIII Div. 1 4 NPS 10.923 sq in 5 - 1440 psi VIII Div. 1 23.309 sq in 5 - 870 psi 6 NPS VIII Div. 1 44.37 sq in 5 - 720 psi 8 NPS VIII Div. 1 5 - 720 psi 10 NPS 65.248 sq in VIII Div. 1 5 - 720 psi 95.006 sq in 12 NPS VIII Div. 1 125.982 sq in 14 NPS 4 - 261 psi VIII Div. 1 16 NPS 171.545 sq in 4 - 150 psi VIII Div. 1 4 - 135 psi 213.795 sq in 18 NPS VIII Div. 1 259.735 sq in 20 NPS 4 - 131 psi VIII Div. 1 4 - 131 psi 372.075 sq in 24 NPS VIII Div. 1 26 NPS 424.74 sq in 4 - 131 psi VIII Div. 1 4 - 131 psi 492.6 sq in 28 NPS VIII Div. 1 4 - 131 psi 30 NPS 565.49 sq in VIII Div. 1 32 NPS 642.4 sq in 4 - 131 psi VIII Div. 1 4 - 131 psi 34 NPS 726.34 sq in VIII Div. 1 36 NPS 4 - 131 psi 814.3 VIII Div. 1 4 - 131 psi 1005.31 40 NPS Page 359 of 812 Effective Date: 2019-05-31

361 Table of Contents Elfab Limited (ELF) 88129 NB#: Alder Road location: Acceptable Abbrev.: ELFAB Certification Design Series DSC-AGS 88129 or catalog number Number: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on January 20, 2004 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 0.69 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Set Pressure Range Media Code Section Flow Area Lift VIII Div. 1 1 in 10 - 800 psi 1 NPS 0.79 sq in VIII Div. 1 10 - 595 psi 1.5 in 1.5 NPS 1.77 sq in VIII Div. 1 10 - 400 psi 2 in 3.14 sq in 2 NPS VIII Div. 1 2.5 NPS 4.79 sq in 2.5 in 3 - 400 psi VIII Div. 1 3 - 350 psi 3 NPS 7.07 sq in 3 in VIII Div. 1 2 - 245 psi 4 in 12.57 sq in 4 NPS VIII Div. 1 1.5 - 145 psi 6 in 28.27 sq in 6 NPS VIII Div. 1 8 NPS 50.03 sq in 8 in 1 - 80 psi VIII Div. 1 1 - 70 psi 78.54 sq in 10 in 10 NPS VIII Div. 1 113.1 sq in 12 in 1 - 60 psi 12 NPS VIII Div. 1 137.9 sq in 14 NPS 1 - 50 psi 14 in VIII Div. 1 1 - 50 psi 182.7 sq in 16 in 16 NPS VIII Div. 1 18 NPS 233.7 sq in 18 in 1 - 40 psi VIII Div. 1 1 - 30 psi 20 in 291 sq in 20 NPS Design Series Certification DSC-OPS 88141 or catalog number Number: OP Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on August 04, 2006 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 0.8 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Media Inlet Size Set Pressure Range Outlet Size VIII Div. 1 14 - 70 psi 0.923 sq in 1 NPS VIII Div. 1 6 - 60 psi 1.996 sq in 1.5 NPS VIII Div. 1 5 - 50 psi 2 NPS 3.387 sq in VIII Div. 1 5.5 - 45 psi 4.97 sq in 2.5 NPS VIII Div. 1 8.114 sq in 4 - 35 psi 3 NPS VIII Div. 1 12.914 sq in 4 NPS 2 - 30 psi VIII Div. 1 4 - 30 psi 27.661 sq in 6 NPS VIII Div. 1 8 NPS 52.007 sq in 4 - 30 psi VIII Div. 1 4 - 30 psi 10 NPS 76.838 sq in VIII Div. 1 4 - 30 psi 112.854 sq in 12 NPS Page 360 of 812 Effective Date: 2019-05-31

362 Table of Contents Elfab Limited (ELF) 88152 NB#: Alder Road location: Acceptable Abbrev.: ELFAB Certification Design Series DSC-CDD 88152 Number: or catalog number HC Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 06, 2006 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.4 Unitless Certified Value: Air or gases, and liquid (Krgl) Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section Media VIII Div. 1 1 NPS 0.78 sq in 1 in 369 - 12000 psi VIII Div. 1 1.5 NPS 1.95 sq in 1.93 in 227 - 6000 psi VIII Div. 1 2 NPS 188 - 6000 psi 2 in 3.14 sq in VIII Div. 1 2.55 in 2.5 NPS 5.1 sq in 150 - 6000 psi VIII Div. 1 3 NPS 7.74 sq in 3.14 in 150 - 6000 psi VIII Div. 1 100 - 6000 psi 4 in 12.56 sq in 4 NPS VIII Div. 1 5.9 in 27.33 sq in 87 - 6000 psi 6 NPS VIII Div. 1 7.87 in 8 NPS 48.64 sq in 70 - 3600 psi VIII Div. 1 60 - 3600 psi 9.84 in 76.04 sq in 10 NPS VIII Div. 1 109.54 sq in 11.81 in 52 - 3600 psi 12 NPS VIII Div. 1 13.77 in 148.92 sq in 14 NPS 42 - 2160 psi VIII Div. 1 16 NPS 194.58 sq in 15.74 in 42 - 2160 psi VIII Div. 1 42 - 1400 psi 17.71 in 246.33 sq in 18 NPS VIII Div. 1 42 - 1400 psi 304.18 sq in 20 NPS 19.68 in Page 361 of 812 Effective Date: 2019-05-31

363 Table of Contents Elfab Limited (ELF) 88185 NB#: Alder Road location: Acceptable Abbrev.: ELFAB Certification Design Series DSC-OPR 88185 Number: or catalog number HLD-REV, HLD-SAN, HLD-SAN(W) Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on April 30, 2013 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.74 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Flow Area Media Code Section Outlet Size Lift Inlet Size VIII Div. 1 1 in 1 in 0.461 sq in 0.87 in 50 - 1500 psi VIII Div. 1 1.12 in 1 NPS 1 NPS 0.766 sq in 50 - 1523 psi VIII Div. 1 50 - 1500 psi 1.37 in 1.146 sq in 1.5 in 1.5 in VIII Div. 1 1.5 NPS 1.5 NPS 1.651 sq in 27 - 1523 psi 1.63 in VIII Div. 1 2 in 2 in 2.132 sq in 1.87 in 13 - 1000 psi VIII Div. 1 2.13 in 2 NPS 2 NPS 2.789 sq in 14 - 1523 psi VIII Div. 1 13 - 1000 psi 2.37 in 3.484 sq in 2.5 in 2.5 in VIII 2.5 NPS 4.119 sq in 10 - 1305 psi 2.61 in 2.5 NPS VIII Div. 1 13 - 1000 psi 2.87 in 5.041 sq in 3 in 3 in VIII Div. 1 7 - 1088 psi 3 NPS 3 NPS 6.722 sq in 3.35 in VIII Div. 1 8.923 sq in 4 in 13 - 1000 psi 3.83 in 4 in VIII Div. 1 10.923 sq in 4 NPS 5 - 1440 psi 4.11 in 4 NPS VIII Div. 1 5.78 in 5 - 650 psi 6 in 6 in 21.03 sq in VIII Div. 1 5 - 1217 psi 6.14 in 23.309 sq in 6 NPS 6 NPS VIII Div. 1 8 NPS 5 - 1104 psi 8 NPS 44.37 sq in 8.18 in VIII Div. 1 10 NPS 5 - 991 psi 10.2 in 65.248 sq in 10 NPS VIII Div. 1 95.006 sq in 12 NPS 5 - 878 psi 12 NPS 12.2 in VIII Div. 1 5 - 765 psi 14.1 in 125.982 sq in 14 NPS 14 NPS VIII Div. 1 16 NPS 16 NPS 171.545 sq in 16.5 in 4 - 652 psi VIII Div. 1 213.795 sq in 18 in 18 NPS 18 NPS 4 - 539 psi VIII Div. 1 20 NPS 4 - 426 psi 20 in 259.735 sq in 20 NPS VIII Div. 1 372.075 sq in 24 NPS 4 - 200 psi 24 NPS 23.9 in VIII Div. 1 26 in 4 - 191 psi 26 NPS 26 NPS 424.74 sq in VIII Div. 1 4 - 182 psi 28 in 492.6 sq in 28 NPS 28 NPS VIII Div. 1 30 NPS 4 - 173 psi 30 NPS 565.49 sq in 30 in VIII Div. 1 32 NPS 4 - 163 psi 32 in 643.3 sq in 32 NPS VIII Div. 1 34 NPS 34 NPS 4 - 154 psi 34 in 726.34 sq in VIII Div. 1 36 in 4 - 145 psi 36 NPS 36 NPS 814.3 sq in VIII Div. 1 4 - 136 psi 40 in 1005.31 sq in 40 NPS 40 NPS Page 362 of 812 Effective Date: 2019-05-31

364 Table of Contents Elfab Limited (ELF) NB#: 88196 location: Alder Road Acceptable Abbrev.: ELFAB Certification Design Series DSC-SGD 88196 or catalog number Number: HLD-STD, HLD-SAN, HLD-SAN(W) Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on April 25, 2012 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 0.68 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Media Outlet Size Inlet Size Code Section Set Pressure Range Flow Area VIII Div. 1 Air 100 - 1500 psi 0.378 sq in 1 in 1 in VIII Div. 1 Water VIII Div. 1 Air 0.5 sq in 1 NPS 1 NPS 100 - 2683 psi VIII Div. 1 Water VIII Div. 1 Air 100 - 1500 psi 0.938 sq in 1.5 in 1.5 in VIII Div. 1 Water VIII Div. 1 Air 100 - 2031 psi 1.5 NPS 1.5 NPS 1.24 sq in VIII Div. 1 Water VIII Div. 1 Air 2 in 100 - 1000 psi 2 in 1.748 sq in VIII Div. 1 Water VIII Div. 1 Air 2 sq in 100 - 1813 psi 2 NPS 2 NPS VIII Div. 1 Water VIII Div. 1 Air 2.5 in 2.5 in 100 - 1000 psi 2.808 sq in VIII Div. 1 Water VIII Div. 1 Air 2.5 NPS 3.27 sq in 100 - 1523 psi 2.5 NPS VIII Div. 1 Water VIII Div. 1 Air 3 in 3 in 75 - 1000 psi 4.118 sq in VIII Div. 1 Water VIII Div. 1 Air 75 - 1309 psi 3 NPS 3 NPS 4.96 sq in VIII Div. 1 Water VIII Div. 1 Air 4 in 7.334 sq in 68 - 1000 psi 4 in VIII Div. 1 Water VIII Div. 1 Air 4 NPS 4 NPS 68 - 1088 psi 8 sq in VIII Div. 1 Water VIII Div. 1 Air 6 in 6 in 25 - 650 psi 16.704 sq in VIII Div. 1 Water VIII Div. 1 Air 75 - 1980 psi 17.43 sq in 6 NPS 6 NPS VIII Div. 1 Water VIII Div. 1 Air 8 NPS 31 sq in 75 - 1650 psi 8 NPS VIII Div. 1 Water VIII Div. 1 Air 48.44 sq in 50 - 1650 psi 10 NPS 10 NPS VIII Div. 1 Water VIII Div. 1 Air 69.75 sq in 12 NPS 50 - 1430 psi 12 NPS VIII Div. 1 Water VIII Div. 1 Air 14 NPS 94.94 sq in 14 NPS 50 - 1100 psi VIII Div. 1 Water VIII Div. 1 Air 50 - 990 psi 124 sq in 16 NPS 16 NPS VIII Div. 1 Water VIII Div. 1 Air 18 NPS 18 NPS 50 - 880 psi 156.94 sq in VIII Div. 1 Water VIII Div. 1 Air 20 NPS 20 NPS 193.75 sq in 50 - 790 psi VIII Div. 1 Water VIII Div. 1 Air 24 NPS 279 sq in 50 - 660 psi 24 NPS VIII Div. 1 Water VIII Div. 1 Air 26 NPS 327.44 sq in 50 - 625 psi 26 NPS VIII Div. 1 Water Page 363 of 812 Effective Date: 2019-05-31

365 Table of Contents Elfab Limited (ELF) 88196 NB#: Alder Road location: Acceptable Abbrev.: ELFAB ...Continued Orifice [designator] diameter Outlet Size Lift Code Section Inlet Size Set Pressure Range Media Flow Area VIII Div. 1 Air 28 NPS 28 NPS 379.75 sq in 50 - 590 psi VIII Div. 1 Water VIII Div. 1 Air 435.94 sq in 30 NPS 50 - 555 psi 30 NPS VIII Div. 1 Water VIII Div. 1 Air 32 NPS 32 NPS 496 sq in 50 - 525 psi VIII Div. 1 Water VIII Div. 1 Air 559.94 sq in 34 NPS 34 NPS 50 - 490 psi VIII Div. 1 Water VIII Div. 1 Air 627.45 sq in 50 - 455 psi 36 NPS 36 NPS VIII Div. 1 Water VIII Div. 1 Air 38 NPS 699.44 sq in 50 - 420 psi 38 NPS VIII Div. 1 Water VIII Div. 1 Air 40 NPS 50 - 385 psi 775 sq in 40 NPS VIII Div. 1 Water VIII Div. 1 Air 42 NPS 854.44 sq in 50 - 350 psi 42 NPS VIII Div. 1 Water VIII Div. 1 Air 50 - 315 psi 937.75 sq in 44 NPS 44 NPS VIII Div. 1 Water VIII Div. 1 Air 46 NPS 1024.94 sq in 50 - 280 psi 46 NPS VIII Div. 1 Water VIII Div. 1 Air 50 - 245 psi 1116 sq in 48 NPS 48 NPS VIII Div. 1 Water Page 364 of 812 Effective Date: 2019-05-31

366 Table of Contents Elfab Limited (ELF) 88208 NB#: Alder Road location: Acceptable Abbrev.: ELFAB Certification Design Series FCD (Flat or Domed Composite Discs) 88208 Number: or catalog number HLD-STD Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on January 28, 2014 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 3.94 Unitless Certified Value: Air/Gas & Liquid Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Outlet Size Flow Area Media Inlet Size Code Section Lift VIII Div. 1 Air 1 NPS 0.42 sq in 15 - 522 psi VIII Div. 1 Air 1.5 NPS 1.12 sq in 10 - 522 psi VIII Div. 1 Air 10 - 522 psi 2 NPS 1.86 sq in VIII Div. 1 Air 2.96 sq in 10 - 522 psi 2.5 NPS VIII Div. 1 Air 5.29 sq in 3 NPS 10 - 522 psi VIII Div. 1 Air 10 - 522 psi 7.34 sq in 4 NPS VIII Div. 1 Air 10 - 494 psi 14.34 sq in 6 NPS VIII Div. 1 Air 5 - 378 psi 26.63 sq in 8 NPS VIII Div. 1 Air 5 - 290 psi 43.53 sq in 10 NPS VIII Div. 1 Air 5 - 248 psi 12 NPS 73.3 sq in VIII Div. 1 Air 5 - 235 psi 100.84 sq in 14 NPS VIII Div. 1 Air 5 - 222 psi 132.21 sq in 16 NPS VIII Div. 1 Air 18 NPS 167.1 sq in 1 - 209 psi VIII Div. 1 Air 20 NPS 1 - 197 psi 206.81 sq in VIII Div. 1 Air 247.7 sq in 22 NPS 1 - 184 psi VIII Div. 1 Air 24 NPS 294.4 sq in 1 - 171 psi VIII Div. 1 Air 346.55 sq in 26 NPS 1 - 158 psi VIII Div. 1 Air 408.06 sq in 1 - 145 psi 28 NPS VIII Div. 1 Air 30 NPS 459.57 sq in 1 - 145 psi VIII Div. 1 Air 32 NPS 527.47 sq in 1 - 145 psi VIII Div. 1 Air 1 - 145 psi 593.93 sq in 34 NPS VIII Div. 1 Air 36 NPS 655.72 sq in 1 - 145 psi VIII Div. 1 Air 1 - 145 psi 742.45 sq in 38 NPS VIII Div. 1 Air 1 - 145 psi 40 NPS 811.36 sq in VIII Div. 1 Air 42 NPS 907.54 sq in 1 - 145 psi VIII Div. 1 Air 44 NPS 983.56 sq in 1 - 145 psi VIII Div. 1 Air 1 - 145 psi 1089.18 sq in 46 NPS VIII Div. 1 Air 1 - 145 psi 1172.32 sq in 48 NPS Page 365 of 812 Effective Date: 2019-05-31

367 Table of Contents Emerson Automation Solutions Final Control UK, Ltd. (BRK) 06006 NB#: Sharp Street, Worsley, Manchester, Lancashire M28 3NA United Kingdom location: Emerson Automation Solutions Final Control UK, Ltd. (BRK) Sharp Street, Worsley, Manchester, Lancashire M28 3NA United Kingdom location: Certification Design Series B Series 06006 or catalog number Number: Safety Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on February 09, 1980 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .857 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Outlet Size Inlet Size Flow Area Lift Set Pressure Range VIII Div. 1 Air 0.062 sq in 0.5 - 1 NPS 1 NPS 0.281 in 0.07 in 15 - 5000 psi VIII Div. 1 Air 15 - 3600 psi 0.375 in 0.11 sq in 0.094 in VIII Div. 1 Air 1 NPS 15 - 5000 psi 1.5 NPS 0.196 sq in 0.125 in 0.5 in VIII Div. 1 Air 1.5 NPS 0.187 in 15 - 2500 psi 2 NPS 0.442 sq in 0.75 in Certification Design Series C Series 06017 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on December 08, 1987 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .509 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size VIII Div. 1 Water 15 - 5000 psi 0.07 in 0.281 in 0.062 sq in 0.5 - 1 NPS 1 NPS VIII Div. 1 Water 0.11 sq in 0.375 in 0.093 in 15 - 3600 psi VIII Div. 1 Water 1 NPS 1.5 NPS 0.196 sq in 0.5 in 0.125 in 15 - 5000 psi VIII Div. 1 Water 15 - 2500 psi 0.187 in 0.75 in 0.442 sq in 2 NPS 1.5 NPS Page 366 of 812 Effective Date: 2019-05-31

368 Table of Contents Emerson Automation Solutions Final Control UK, Ltd. (BRK) 06028 NB#: Sharp Street, Worsley, Manchester, Lancashire M28 3NA United Kingdom location: Certification Design Series WB 100/200 (Liquids) 06028 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on November 07, 1985 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .588 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Media Outlet Size Inlet Size Set Pressure Range Flow Area VIII Div. 1 Water 1 - 1.5 NPS 2, 3 NPS 0.121 sq in [D] 0.393 in 0.098 in 15 - 6000 psi VIII Div. 1 Water [E] 0.524 in 0.132 in 15 - 6000 psi 0.216 sq in VIII Div. 1 Water 1.5 NPS 2, 3 NPS 0.338 sq in [F] 0.656 in 0.164 in 15 - 5000 psi VIII Div. 1 Water 0.211 in 15 - 3600 psi 1.5 - 2 NPS 3 NPS 0.558 sq in [G] 0.843 in VIII Div. 1 Water 0.263 in [H] 1.053 in 0.871 sq in 15 - 3000 psi VIII Div. 1 Water 1.429 sq in [J] 1.349 in 0.337 in 15 - 3000 psi 2 - 3 NPS 3, 4 NPS VIII Div. 1 Water 0.403 in [K] 1.611 in 2.04 sq in 4, 6 NPS 3 NPS 15 - 2500 psi VIII Div. 1 Water 15 - 1500 psi 3 - 4 NPS 4, 6 NPS 3.167 sq in [L] 2.008 in 0.502 in VIII Div. 1 Water 4 NPS 15 - 1200 psi 3.986 sq in 6 NPS 0.564 in [M] 2.255 in VIII Div. 1 Water [N] 2.476 in 0.619 in 15 - 1000 psi 4.817 sq in VIII Div. 1 Water 15 - 1000 psi 0.751 in [P] 3.003 in 7.082 sq in VIII Div. 1 Water 12.266 sq in [Q] 3.951 in 0.988 in 15 - 600 psi 6 NPS 8 NPS VIII Div. 1 Water 8, 10 NPS 17.76 sq in [R] 4.755 in 1.189 in 15 - 300 psi VIII Div. 1 Water 8 NPS 15 - 300 psi 1.515 in [T] 6.061 in 28.86 sq in 10 NPS Page 367 of 812 Effective Date: 2019-05-31

369 Table of Contents Emerson Automation Solutions Final Control UK, Ltd. (BRK) 06039 NB#: Sharp Street, Worsley, Manchester, Lancashire M28 3NA United Kingdom location: Certification Design Series WB 300/400 06039 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on February 09, 1980 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Outlet Size Code Section Inlet Size Media Flow Area Lift VIII Div. 1 Steam 15 - 2900 psi 2, 3 NPS 0.122 sq in 1 - 1.5 NPS 0.098 in [D] 0.393 in VIII Div. 1 Air 15 - 6000 psi VIII Div. 1 Steam [E] 0.524 in 0.132 in 15 - 2900 psi 0.216 sq in VIII Div. 1 Air 15 - 6000 psi VIII Div. 1 Steam 0.164 in 1.5 NPS 2, 3 NPS 0.338 sq in [F] 0.656 in 15 - 2900 psi VIII Div. 1 Air 15 - 5000 psi VIII Div. 1 Steam 1.5 - 2 NPS [G] 0.843 in 0.26 in 3 NPS 15 - 2900 psi 0.558 sq in VIII Div. 1 Air 15 - 3600 psi VIII Div. 1 Steam 15 - 2900 psi 0.263 in [H] 1.053 in 0.871 sq in VIII Div. 1 Air 15 - 3000 psi VIII Div. 1 Steam 1.429 sq in [J] 1.349 in 0.337 in 15 - 2900 psi 2 - 3 NPS 3, 4 NPS VIII Div. 1 Air 15 - 3000 psi VIII Div. 1 Air [K] 1.611 in 3 NPS 2.038 sq in 0.403 in 4, 6 NPS 15 - 2500 psi VIII Div. 1 Steam VIII Div. 1 Air 0.502 in 3 - 4 NPS 15 - 1500 psi 3.167 sq in 4, 6 NPS [L] 2.008 in VIII Div. 1 Steam VIII Div. 1 Air [M] 2.255 in 0.563 in 15 - 1200 psi 4 NPS 6 NPS 3.994 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 1000 psi 0.619 in [N] 2.476 in 4.815 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 1000 psi 0.751 in [P] 3.003 in 7.082 sq in VIII Div. 1 Steam VIII Div. 1 Air 12.26 sq in [Q] 3.951 in 8 NPS 6 NPS 15 - 600 psi 0.988 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 300 psi 1.188 in 17.76 sq in 8, 10 NPS [R] 4.755 in VIII Div. 1 Steam VIII Div. 1 Air [T] 6.061 in 8 NPS 1.515 in 15 - 300 psi 28.86 sq in 10 NPS VIII Div. 1 Steam Page 368 of 812 Effective Date: 2019-05-31

370 Table of Contents NB#: 06062 Emerson Automation Solutions Final Control UK, Ltd. (BRK) location: Sharp Street, Worsley, Manchester, Lancashire M28 3NA United Kingdom Certification Design Series 746-1, JCE/1 06062 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on December 13, 1990 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .738 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Flow Area Outlet Size Media Set Pressure Range Inlet Size VIII Div. 1 Air 15 - 580 psi 0.906 in 0.644 sq in 1.5 NPS 1 NPS 0.227 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 580 psi 0.285 in 1.142 in 1.024 sq in 2 NPS 1.25 NPS VIII Div. 1 Steam VIII Div. 1 Air 15 - 580 psi 0.364 in 2.5 NPS 1.457 in 1.5 NPS 1.667 sq in VIII Div. 1 Steam VIII Div. 1 Air 0.453 in 15 - 580 psi 2 NPS 3 NPS 2.576 sq in 1.811 in VIII Div. 1 Steam VIII Div. 1 Air 2.362 in 0.59 in 15 - 507 psi 2.5 NPS 4 NPS 4.382 sq in VIII Div. 1 Steam VIII Div. 1 Air 2.913 in 0.728 in 15 - 464 psi 6.664 sq in 4 NPS 3 NPS VIII Div. 1 Steam VIII Div. 1 Air 15 - 362 psi 0.905 in 3.622 in 10.303 sq in 6 NPS 4 NPS VIII Div. 1 Steam Design Series Certification 746-3, JCE/3 (Liquids) 06073 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on December 13, 1990 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .482 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Media Set Pressure Range Lift Flow Area Outlet Size VIII Div. 1 Water 1 NPS 15 - 580 psi 0.227 in 0.906 in 0.644 sq in 1.5 NPS VIII Div. 1 Water 15 - 580 psi 0.285 in 1.142 in 1.024 sq in 2 NPS 1.25 NPS VIII Div. 1 Water 0.364 in 15 - 580 psi 2.5 NPS 1.5 NPS 1.667 sq in 1.457 in VIII Div. 1 Water 15 - 580 psi 0.453 in 2.576 sq in 3 NPS 2 NPS 1.811 in VIII Div. 1 Water 2.5 NPS 4 NPS 4.382 sq in 2.362 in 0.59 in 15 - 507 psi VIII Div. 1 Water 4 NPS 15 - 464 psi 0.728 in 2.913 in 6.664 sq in 3 NPS VIII Div. 1 Water 10.303 sq in 3.622 in 0.905 in 15 - 362 psi 4 NPS 6 NPS Page 369 of 812 Effective Date: 2019-05-31

371 Table of Contents Emerson Automation Solutions Final Control UK, Ltd. (BRK) 06084 NB#: Sharp Street, Worsley, Manchester, Lancashire M28 3NA United Kingdom location: Certification Design Series WB 300B 06084 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on October 21, 1991 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .833 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Lift Outlet Size Inlet Size Media Set Pressure Range Code Section VIII Air 15 - 5000 psi 0.164 in [F] 0.656 in 2, 2.5 NPS 1.5 - 2 NPS 0.338 sq in VIII Air 0.558 sq in 2.5, 3 NPS [G] 0.843 in 0.21 in 15 - 3600 psi VIII Air 0.263 in 3 NPS 0.871 sq in [H] 1.053 in 15 - 2750 psi VIII Air 15 - 2700 psi 0.337 in [J] 1.349 in 1.429 sq in 3, 4 NPS 2 - 3 NPS VIII Air [K] 1.611 in 0.402 in 15 - 2160 psi 3 NPS 4, 6 NPS 2.04 sq in VIII Air 3 - 4 NPS 3.167 sq in [L] 2.008 in 0.502 in 15 - 1500 psi 4 ,6 NPS VIII Air 4 NPS 15 - 1100 psi 0.563 in [M] 2.255 in 6 NPS 3.986 sq in VIII Air [N] 2.476 in 4.817 sq in 0.619 in 15 - 1000 psi VIII Air 15 - 1000 psi 0.751 in [P] 3.003 in 7.081 sq in VIII Air 6 NPS 8 NPS 12.265 sq in [Q] 3.951 in 0.987 in 15 - 600 psi VIII Air 17.76 sq in 15 - 300 psi [R] 4.755 in 1.188 in 8, 10 NPS VIII Air 15 - 300 psi [T] 6.061 in 28.85 sq in 10 NPS 8 NPS 1.515 in Design Series Certification 20R (Liquid) (4, 5, 8, 9 pilots) 4FR3, 4FR9, 8FR3, 8FR9 06095 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on October 15, 1996 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .696 Unitless Certified Value: per CC 1945 Certification Provisions: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Code Section Media Flow Area Lift Set Pressure Range VIII Div. 1 Water 29 - 6170 psi 0.102 in [D] 0.656 in 2 NPS 1 - 1.5 NPS 0.164 sq in VIII Div. 1 Water 0.256 sq in [E] 0.656 in 0.159 in 15 - 6170 psi VIII Div. 1 Water 3 NPS 0.212 in 29 - 6170 psi 0.616 sq in 1.5 NPS [G] 1.053 in VIII Div. 1 Water 15 - 6170 psi 2 NPS 0.163 in [G] 1.348 in 0.616 sq in 3 NPS VIII Div. 1 Water [H] 1.348 in 0.232 in 15 - 6170 psi 0.871 sq in VIII Div. 1 Water 1.427 sq in [J] 2.008 in 0.301 in 29 - 3705 psi 3 NPS 4 NPS VIII Div. 1 Water 15 - 3705 psi 0.451 in [K] 2.008 in 2.139 sq in VIII Div. 1 Water 29 - 3705 psi 4 NPS [L] 3 in 0.448 in 6 NPS 3.167 sq in VIII Div. 1 Water 4.307 sq in 29 - 1480 psi 0.609 in [M] 3 in VIII Div. 1 Water 5.162 sq in 15 - 1480 psi 0.73 in [N] 3 in VIII Div. 1 Water 12.864 sq in [Q] 4.755 in 1.147 in 29 - 1480 psi 6 NPS 8 NPS VIII Div. 1 Water 15 - 1480 psi 1.548 in [S] 6.062 in 22.118 sq in 10 NPS 8 NPS Page 370 of 812 Effective Date: 2019-05-31

372 Table of Contents Emerson Automation Solutions Final Control UK, Ltd. (BRK) 06107 NB#: Sharp Street, Worsley, Manchester, Lancashire M28 3NA United Kingdom location: Certification Design Series 20F (Liquid) (B, C, 4, 5, 8, 9 pilots) 4FF3, 4FF9, 8FF3, 8FF9 06107 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on October 15, 1996 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .696 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Lift Inlet Size Set Pressure Range Media Flow Area Outlet Size VIII Div. 1 Water 0.338 sq in 1 - 1.5 NPS 29 - 6170 psi 0.21 in [F] 0.656 in 2 NPS VIII Div. 1 Water [H] 1.053 in 29 - 6170 psi 0.871 sq in 0.3 in 3 NPS 1.5 NPS VIII Div. 1 Water 2 NPS 29 - 6170 psi 3 NPS 1.427 sq in [J] 1.348 in 0.38 in VIII Div. 1 Water 4 NPS 3 NPS 3.167 sq in [L] 2.008 in 0.668 in 29 - 3705 psi VIII Div. 1 Water 6 NPS 1 in 29 - 3705 psi [P] 3 in 4 NPS 7.068 sq in VIII Div. 1 Water 29 - 1480 psi 1.584 in [R] 4.755 in 17.758 sq in 8 NPS 6 NPS VIII Div. 1 Water 2.021 in 29 - 1480 psi 10 NPS [T] 6.062 in 28.86 sq in 8 NPS Certification Design Series 20F(2,4,5,8,9 pilots) 2FF3, 2FF9, 4FF3, 4FF9, 8FF3, 8FF9 06118 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on October 16, 1996 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .849 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: 1.Pop 2.Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Set Pressure Range Outlet Size Inlet Size Lift Flow Area VIII Air 1 - 1.5 NPS 26 - 6170 psi 2 NPS 0.338 sq in [F] 0.656 in 0.164 in VIII Air 26 - 6170 psi [H] 1.053 in 0.871 sq in 3 NPS 1.5 NPS 0.264 in VIII Air 1.427 sq in [J] 1.348 in 0.337 in 26 - 6170 psi 2 NPS 3 NPS VIII Air 3 NPS 26 - 3705 psi 0.585 in [L] 2.008 in 3.167 sq in 4 NPS VIII Air 7.068 sq in 4 NPS 26 - 3705 psi 0.875 in [P] 3 in 6 NPS VIII Air 6 NPS 8 NPS 17.758 sq in [R] 4.755 in 1.386 in 26 - 1480 psi VIII Air 8 NPS 26 - 1480 psi 1.768 in [T] 6.062 in 28.86 sq in 10 NPS Page 371 of 812 Effective Date: 2019-05-31

373 Table of Contents Emerson Automation Solutions Final Control UK, Ltd. (BRK) 06129 NB#: Sharp Street, Worsley, Manchester, Lancashire M28 3NA United Kingdom location: Certification Design Series 20R (2,4,5,8,9 pilots) 2FR3, 2FR9, 4FR3, 4FR9, 8FR3, 8FR9 06129 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on October 15, 1996 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .849 Unitless Certified Value: per CC 1945 Certification Provisions: Air/Gas Test Medium: Air/Gas Certified Medium: 1.Pop 2.Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Lift Inlet Size Code Section Outlet Size Set Pressure Range VIII Air 0.08 in 26 - 6170 psi 1 - 1.5 NPS 2 NPS 0.164 sq in [D] 0.656 in VIII Div. 1 Air 0.256 sq in [E] 0.656 in 26 - 6170 psi 0.125 in VIII Div. 1 Air [G] 1.053 in 26 - 6170 psi 0.616 sq in 0.186 in 3 NPS 1.5 NPS VIII Div. 1 Air 0.145 in 2 NPS 3 NPS 0.616 sq in [G] 1.348 in 15 - 6170 psi VIII Div. 1 Air 0.871 sq in [H] 1.348 in 0.205 in 15 - 6170 psi VIII Div. 1 Air 0.264 in 26 - 3705 psi 3 NPS 1.427 sq in [J] 2.008 in 4 NPS VIII Div. 1 Air 2.139 sq in [K] 2.008 in 0.394 in 15 - 3705 psi VIII Div. 1 Air 0.392 in 26 - 3705 psi 6 NPS 4 NPS [L] 3 in 3.167 sq in VIII Div. 1 Air 4.307 sq in 15 - 3705 psi 0.532 in [M] 3 in VIII Div. 1 Air 5.162 sq in 15 - 3705 psi 0.638 in [N] 3 in VIII Div. 1 Air 12.864 sq in [Q] 4.755 in 1.003 in 26 - 1480 psi 6 NPS 8 NPS VIII Div. 1 Air 0.531 in [S] 6.062 in 22.118 sq in 10 NPS 26 - 1480 psi 8 NPS Design Series Certification D Series, 716H7 06130 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on December 07, 1999 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.55 SCFM/PSIA Certified Value: 7.16 PPH/PSIA Certified Value (alternate medium): Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Media Set Pressure Range Lift Flow Area Outlet Size VIII Div. 1 Air 0.5 - 1 NPS 15 - 740 psi 0.116 in 0.464 in 0.169 sq in 1 NPS VIII Div. 1 Steam Certification Design Series D Series (Liquids), 716H7 06141 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on December 07, 1999 Capacity Tests: Flow Capacity, Flow Factor Method of Establishing Relieving Capacity: 3.25 GPM/SQ.RT. PSID Certified Value: Water Test Medium: Liquid Certified Medium: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Media Set Pressure Range Lift Flow Area Outlet Size VIII Div. 1 Water 0.5 - 1 NPS 15 - 740 psi 0.116 in 0.464 in 0.169 sq in 1 NPS Page 372 of 812 Effective Date: 2019-05-31

374 Table of Contents Emerson Automation Solutions Final Control UK, Ltd. (BRK) 06185 NB#: Sharp Street, Worsley, Manchester, Lancashire M28 3NA United Kingdom location: Certification Design Series 776 06185 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on February 06, 2004 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .737 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size Media VIII Div. 1 Air 15 - 600 psi 0.116 in 0.464 in 0.169 sq in 0.5 - 1 NPS .75, 1 NPS VIII Div. 1 Air 0.75 - 1 NPS 1.25 NPS 0.486 sq in 0.787 in 0.196 in 15 - 560 psi VIII Div. 1 Air 1.5 NPS 0.906 in 1.25 NPS 0.226 in 15 - 500 psi 0.644 sq in VIII Div. 1 Air 1.5 NPS 2 NPS 1.024 sq in 1.142 in 0.286 in 15 - 500 psi VIII Div. 1 Air 2.5 NPS 15 - 450 psi 0.364 in 1.456 in 2 NPS 1.666 sq in Certification Design Series RBH 81010 or catalog number Number: RBH, RBH-T Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on December 04, 1998 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: .5 Unitless Certified Value: Air/Gas Test Medium: Air or gases (Krg) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Set Pressure Range Media Outlet Size Code Section Inlet Size VIII Div. 1 0.5 NPS 87 - 5500 psi 0.3 sq in VIII Div. 1 0.53 sq in 87 - 5500 psi 0.75 NPS VIII Div. 1 1 NPS 29 - 5500 psi 0.86 sq in VIII Div. 1 26 - 5500 psi 1.5 NPS 2.04 sq in VIII Div. 1 2 NPS 3.36 sq in 23 - 5500 psi VIII Div. 1 20 - 3750 psi 2.5 NPS 4.79 sq in VIII Div. 1 3 NPS 18 - 2625 psi 7.39 sq in VIII Div. 1 14.5 - 1950 psi 12.73 sq in 4 NPS VIII Div. 1 14.5 - 900 psi 28.89 sq in 6 NPS VIII Div. 1 8 NPS 14.5 - 750 psi 50.03 sq in VIII Div. 1 10 NPS 14.5 - 600 psi 77.72 sq in VIII Div. 1 113.1 sq in 12 NPS 14.5 - 500 psi VIII Div. 1 14.5 - 400 psi 137.9 sq in 14 NPS VIII Div. 1 182.7 sq in 14.5 - 300 psi 16 NPS VIII Div. 1 14.5 - 250 psi 233.7 sq in 18 NPS VIII Div. 1 14.5 - 200 psi 291 sq in 20 NPS Page 373 of 812 Effective Date: 2019-05-31

375 Table of Contents Emerson Automation Solutions Final Control UK, Ltd. (BRK) 81122 NB#: Sharp Street, Worsley, Manchester, Lancashire M28 3NA United Kingdom location: Certification Design Series SANIVENT 81122 Number: or catalog number Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 05, 2010 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 1.68 Unitless Certified Value: Air Test Medium: Air or gases (Krg) Certified Medium: None Special Service: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size Media VIII Div. 1 130 - 145 psi 1 NPS 0.39 sq in VIII Div. 1 22 - 145 psi 1.08 sq in 1.5 NPS VIII Div. 1 22 - 125 psi 2 NPS 2.16 sq in VIII Div. 1 3.49 sq in 2.5 NPS 22 - 110 psi VIII Div. 1 5.13 sq in 3 NPS 18 - 90 psi VIII Div. 1 18 - 75 psi 9.12 sq in 4 NPS Certification Design Series LRF 81133 or catalog number Number: RBH, RBH-T Holder Designation: Rupture Disk Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on March 04, 2010 Capacity Tests: Resistance Factor, 3 Size, Krgl Method of Establishing Relieving Capacity: 1.39 Unitless Certified Value: Air Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Burst Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Outlet Size Inlet Size Code Section Set Pressure Range Lift VIII Div. 1 130 - 5500 psi 0.85 sq in 1 NPS VIII Div. 1 105 - 5500 psi 1.5 NPS 2 sq in VIII Div. 1 3.28 sq in 75 - 5500 psi 2 NPS VIII Div. 1 2.5 NPS 4.67 sq in 79 - 3750 psi VIII Div. 1 65 - 2625 psi 3 NPS 7.25 sq in VIII Div. 1 55 - 1950 psi 4 NPS 12.42 sq in VIII Div. 1 45 - 900 psi 28.28 sq in 6 NPS VIII Div. 1 48.93 sq in 45 - 750 psi 8 NPS VIII Div. 1 45 - 600 psi 76.97 sq in 10 NPS VIII Div. 1 45 - 500 psi 12 NPS 110.5 sq in VIII Div. 1 14 NPS 45 - 400 psi 135 sq in VIII Div. 1 45 - 300 psi 178.9 sq in 16 NPS VIII Div. 1 45 - 250 psi 228.9 sq in 18 NPS VIII Div. 1 45 - 200 psi 285.1 sq in 20 NPS Page 374 of 812 Effective Date: 2019-05-31

376 Table of Contents 01045 Emerson Automation Solutions Final Control US LP (AGC) NB#: location: 3950 Greenbriar Drive, Stafford, TX 77477 United States Acceptable Abbrev.: EMRT Emerson Automation Solutions Final Control US LP (AGC) location: 3950 Greenbriar Drive, Stafford, TX 77477 United States Acceptable Abbrev.: EMRT Page 375 of 812 Effective Date: 2019-05-31

377 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 01045 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series JOS-E-RL/JBS-E-RL (Restricted Lift version of cert 15208) 01045 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. (Stafford TX) on May 26, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.865 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Outlet Size Inlet Size Set Pressure Range Code Section Lift VIII Div. 1 Air 15 - 15000 psi 0.1244 sq in 0.08 in 0.75 - 1.5 NPS 2 - 3 NPS [D] 0.398 in VIII Div. 1 Steam 15 - 2000 psi VIII Div. 1 Steam 15 - 2000 psi 1 - 1.5 NPS 2 - 3 NPS 0.488 in 0.08 in 0.187 sq in VIII Div. 1 Air 15 - 8490 psi VIII Div. 1 Air 15 - 15000 psi [E] 0.531 in 0.2214 sq in 0.08 in VIII Div. 1 Steam 15 - 2000 psi VIII Div. 1 Air [F] 0.665 in 0.08 in 0.3473 sq in 15 - 15000 psi VIII Div. 1 Steam 15 - 2000 psi VIII Div. 1 Air 15 - 15000 psi 0.08 in 0.5674 sq in 1.5 - 2 NPS 2.5, 3 NPS [G] 0.85 in VIII Div. 1 Steam 15 - 2000 psi VIII Div. 1 Air 0.8874 sq in 3 NPS 0.099 in 15 - 15000 psi [H] 1.063 in VIII Div. 1 Steam 15 - 2000 psi VIII Div. 1 Air 3, 4 NPS 1.453 sq in 0.127 in [J] 1.36 in 2 - 3 NPS 15 - 10000 psi VIII Div. 1 Steam 15 - 2000 psi VIII Div. 1 Air 0.152 in 3 NPS 2.076 sq in 4, 6 NPS 15 - 10000 psi [K] 1.626 in VIII Div. 1 Steam 15 - 2000 psi VIII Div. 1 Steam 0.189 in 15 - 2000 psi 3 - 4 NPS 4, 6 NPS 3.221 sq in [L] 2.025 in VIII Div. 1 Air 15 - 5000 psi VIII Div. 1 Steam 6 NPS 4.065 sq in 0.213 in 15 - 2000 psi [M] 2.275 in VIII Div. 1 Air 15 - 5000 psi VIII Div. 1 Steam 15 - 1000 psi 4 NPS 2.714 sq in 1.859 in 0.18 in 6 NPS VIII Div. 1 Air 15 - 3000 psi VIII Div. 1 Steam 4.9 sq in 15 - 1480 psi [N] 2.498 in 0.234 in VIII Div. 1 Air 15 - 3000 psi VIII Div. 1 Air 5.444 sq in 2.633 in 0.255 in 15 - 2250 psi VIII Div. 1 Steam VIII Div. 1 Steam 7.206 sq in 0.284 in 15 - 1480 psi [P] 3.029 in VIII Div. 1 Air 15 - 3000 psi VIII Div. 1 Steam 0.373 in 15 - 1000 psi 8 NPS 11.045 sq in 3.75 in 6 NPS VIII Div. 1 Air 15 - 3750 psi VIII Div. 1 Air 12.174 sq in 3.937 in 0.373 in 15 - 2250 psi VIII Div. 1 Steam VIII Div. 1 Air 10 NPS 12.236 sq in 0.449 in 15 - 2250 psi 3.947 in VIII Div. 1 Steam VIII Div. 1 Steam 15 - 1480 psi 8 NPS [Q] 3.985 in 0.373 in 12.472 sq in VIII Div. 1 Air 15 - 3000 psi VIII Div. 1 Air 15 - 2250 psi 0.424 in 4.412 in 15.288 sq in VIII Div. 1 Steam VIII Div. 1 Air 0.449 in 8, 10 NPS 18.065 sq in 15 - 1480 psi [R] 4.796 in VIII Div. 1 Steam VIII Div. 1 Air 8 NPS 15 - 2250 psi 18.254 sq in 10 NPS 4.821 in 0.572 in VIII Div. 1 Steam VIII Div. 1 Air 15 - 740 psi 29.359 sq in [T] 6.114 in 0.572 in VIII Div. 1 Steam VIII Div. 1 Air 0.592 in 15 - 740 psi 31.47 sq in [T2] 6.33 in VIII Div. 1 Steam Page 376 of 812 Effective Date: 2019-05-31

378 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 01045 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT ...Continued Orifice [designator] diameter Code Section Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media VIII Div. 1 Air [V] 7.805 in 0.731 in 15 - 325 psi 14, 16 NPS 10 - 12 NPS 47.84 sq in VIII Div. 1 Steam VIII Div. 1 Air 78.08 sq in 0.933 in 12 - 14 NPS 16. 20 NPS 15 - 325 psi [W] 9.971 in VIII Div. 1 Steam Certification Design Series 63B (.312", #5 orifice) 01056 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on December 03, 1975 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.18 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Flow Area Code Section Outlet Size Inlet Size VIII Div. 1 Air 37 - 531 psi 0.5 - 0.75 NPS 1 NPS 0.077 sq in [#5] 0.312 in 0.15 in Design Series Certification 63B (.437", #7 orifice) 01067 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on December 03, 1975 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.37 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 45 - 374 psi 0.16 in [#7] 0.437 in 0.15 sq in 1 NPS 0.75 NPS Page 377 of 812 Effective Date: 2019-05-31

379 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 01089 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series 81, 81P, 83, 86 01089 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Phillips Petroleum on July 08, 1965 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .816 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Lift Media Code Section Flow Area Outlet Size Set Pressure Range VIII Div. 1 Air 20 - 10000 psi 0.5 - 2 NPS .75 - 2 NPS 0.012 sq in [-2] 0.125 in 0.05 in VIII Div. 1 Air [-3] 0.188 in 0.028 sq in 20 - 10000 psi 0.06 in VIII Div. 1 Air [-4] 0.25 in 0.049 sq in 0.09 in 20 - 10000 psi .75 - 2.5 NPS III Air 20 - 5000 psi VIII Div. 1 Steam 20 - 720 psi III Air 20 - 5000 psi 0.11 sq in [-6] 0.375 in 0.12 in 1 - 2.5 NPS VIII Div. 1 Air 20 - 9600 psi III Air 20 - 5000 psi 0.196 sq in 1 - 2.5 NPS 0.16 in 0.75 - 2 NPS [-8] 0.5 in VIII Div. 1 Air 20 - 6000 psi VIII Div. 1 Steam 20 - 720 psi VIII Div. 1 Air 0.28 in 20 - 4040 psi 1.5 NPS 2 NPS 0.307 sq in [F] 0.625 in VIII Div. 1 Air 0.503 sq in 0.34 in 20 - 2990 psi [G] 0.8 in VIII Div. 1 Steam 20 - 720 psi VIII Div. 1 Air [H] 1 in 0.41 in 20 - 2580 psi 1.5 - 2 NPS 3 NPS 0.785 sq in VIII Div. 1 Air 2 NPS 3 NPS 0.503 sq in [G] 0.8 in 0.34 in 2511 - 6000 psi VIII Div. 1 Air 0.46 in [J] 1.28 in 1.287 sq in 20 - 1620 psi VIII Div. 1 Steam 20 - 720 psi Certification Design Series 81P (Liquids) 01102 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on November 26, 1985 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .720 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: 93% of pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Outlet Size Lift Set Pressure Range Media Inlet Size Flow Area III Water [-4] 0.25 in 0.09 in 50 - 5000 psi 0.5 - 2 NPS 1 - 2 NPS 0.049 sq in I & VIII Div. 1 Water 50 - 6000 psi I & VIII Div. 1 Water 0.13 in 0.75 - 2 NPS [-6] 0.375 in 50 - 6000 psi 0.11 sq in 1 - 2 NPS III Water 50 - 5000 psi 0.16 in [-8] 0.5 in 0.196 sq in I & VIII Div. 1 Water 50 - 6000 psi I & VIII Div. 1 Water 50 - 6000 psi 0.34 in [G] 0.8 in 0.503 sq in 2-3 NPS 1.5 - 2 NPS I & VIII Div. 1 Water 1.287 sq in 0.46 in 50 - 1620 psi 3 NPS [J] 1.28 in 2 NPS Page 378 of 812 Effective Date: 2019-05-31

380 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 01113 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Design Series Certification 83F 01113 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on April 14, 1987 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .779 Unitless Certified Value: Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Inlet Size Outlet Size Media Flow Area Set Pressure Range Lift VIII Div. 1 Air 0.75 NPS 0.178 in 15 - 500 psi 1 NPS 0.26 sq in [E] 0.576 in VIII Div. 1 Air 2 NPS 0.66 sq in [G] 0.917 in 0.318 in 1.5 NPS 15 - 500 psi VIII Div. 1 Air 3 NPS 15 - 500 psi 2 NPS 1.697 sq in 0.548 in [J] 1.47 in Design Series Certification 91/94 01124 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on January 18, 1971 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.77 Unitless Certified Value: Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Outlet Size Media Code Section Flow Area Lift Inlet Size VIII Div. 1 Air 2 NPS 3 NPS 2.924 sq in 1.93 in 0.83 in 15 - 50 psi VIII Div. 1 Air 6.243 sq in 15 - 50 psi 4 NPS 2.82 in 1.2 in 3 NPS VIII Div. 1 Air 1.46 in 3.627 in 10.326 sq in 6 NPS 4 NPS 15 - 50 psi VIII Div. 1 Air 15 - 50 psi 1.88 in 5.32 in 22.217 sq in 8 NPS 6 NPS VIII Div. 1 Air 8 NPS 7.1 in 2.52 in 15 - 50 psi 10 NPS 39.571 sq in VIII Div. 1 Air 12 NPS 3.02 in 15 - 50 psi 10 NPS 8.5 in 56.5 sq in VIII Div. 1 Air 12 NPS 3.8 in 89.874 sq in 15 - 50 psi 16 NPS 10.7 in Certification Design Series 93 01135 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Phillips Petroleum on November 30, 1966 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .845 Unitless Certified Value: Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Outlet Size Inlet Size Media Flow Area VIII Div. 1 Air 1.927 in 1.06 in 15 - 50 psi 2 NPS 3 NPS 2.29 sq in VIII Div. 1 Air 2.81 in 5.16 sq in 4 NPS 3 NPS 1.24 in 15 - 50 psi VIII Div. 1 Air 15 - 50 psi 8.74 sq in 4 NPS 3.627 in 1.57 in 6 NPS VIII Div. 1 Air 15 - 50 psi 2.26 in 5.31 in 19.56 sq in 8 NPS 6 NPS VIII Div. 1 Air 15 - 50 psi 10 NPS 8 NPS 7.1 in 3.12 in 36.4 sq in VIII Div. 1 Air 8.5 in 3.02 in 15 - 30 psi 10 NPS 12 NPS 51 sq in VIII Div. 1 Air 15 - 30 psi 4.71 in 10.7 in 84 sq in 16 NPS 12 NPS Page 379 of 812 Effective Date: 2019-05-31

381 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 01146 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series 95 01146 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on July 30, 1980 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .852 Unitless Certified Value: Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Code Section Outlet Size Inlet Size Set Pressure Range Media VIII Div. 1 Air 1.93 in 0.96 in 15 - 150 psi 2 NPS 3 NPS 2.926 sq in VIII Div. 1 Air 4 NPS 6.246 sq in 2.82 in 1.23 in 15 - 150 psi 3 NPS VIII Div. 1 Air 4 NPS 6 NPS 15 - 150 psi 1.82 in 3.625 in 10.321 sq in VIII Div. 1 Air 5.31 in 2.2 in 15 - 150 psi 6 NPS 8 NPS 22.145 sq in Page 380 of 812 Effective Date: 2019-05-31

382 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 01247 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series 727 01247 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on August 19, 1987 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .788 Unitless Certified Value: Gas Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Outlet Size Lift Set Pressure Range Media Code Section Inlet Size VIII Div. 1 Air 2 NPS 0.25 sq in [E] 0.564 in 1.5 NPS 15 - 1480 psi 0.058 in VIII Div. 1 Steam VIII Div. 1 Air 0.629 sq in 15 - 1480 psi 2 NPS 3 NPS 0.14 in [G] 0.895 in VIII Div. 1 Steam VIII Div. 1 Air 0.981 sq in 0.224 in 15 - 1480 psi [H] 1.118 in VIII Div. 1 Steam VIII Div. 1 Air 0.65 in 1.635 sq in [J] 1.443 in 15 - 1480 psi VIII Div. 1 Steam VIII Div. 1 Air 4 NPS [J] 1.443 in 0.275 in 15 - 1480 psi 3 NPS 1.635 sq in VIII Div. 1 Steam VIII Div. 1 Air 2.298 sq in 0.41 in [K] 1.711 in 15 - 1480 psi VIII Div. 1 Steam VIII Div. 1 Air [L] 2.128 in 0.751 in 15 - 1480 psi 3.557 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 1480 psi 4 NPS 0.374 in [L] 2.128 in 3.557 sq in 6 NPS VIII Div. 1 Steam VIII Div. 1 Air 15 - 1480 psi 0.659 in [M] 2.395 in 4.505 sq in VIII Div. 1 Steam VIII Div. 1 Air 5.425 sq in 15 - 1480 psi 0.824 in [N] 2.628 in VIII Div. 1 Steam VIII Div. 1 Air 1.536 in 15 - 1480 psi 7.911 sq in [P] 3.174 in VIII Div. 1 Steam VIII Div. 1 Air 1.302 in 13.813 sq in 8 NPS 6 NPS 15 - 1480 psi [Q] 4.194 in VIII Div. 1 Steam VIII Div. 1 Air 2.304 in 15 - 1480 psi [R] 5.046 in 20 sq in VIII Div. 1 Steam VIII Div. 1 Air [RR] 5.41 in 2.304 in 15 - 1480 psi 22.99 sq in VIII Div. 1 Steam VIII Div. 1 Air [T] 6.433 in 2.943 in 15 - 1480 psi 8 NPS 10 NPS 32.5 sq in VIII Div. 1 Steam Page 381 of 812 Effective Date: 2019-05-31

383 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 01258 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series 9340/9390 01258 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on September 08, 1989 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.629 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: 1.Pop 2.Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Air 0.545 in 15 - 50 psi 2 NPS 3 NPS 3.35 sq in 2.067 in VIII Div. 1 Air 4 NPS 3 NPS 7.39 sq in 3.068 in 0.8 in 15 - 50 psi VIII Div. 1 Air 15 - 50 psi 4 NPS 12.73 sq in 6 NPS 4.026 in 1.05 in VIII Div. 1 Air 1.619 in 6.065 in 28.89 sq in 8 NPS 6 NPS 15 - 50 psi VIII Div. 1 Air 7.981 in 2.125 in 15 - 50 psi 8 NPS 10 NPS 50 sq in VIII Div. 1 Air 10 NPS 12 NPS 78.85 sq in 10.02 in 2.675 in 15 - 50 psi VIII Div. 1 Air 15 - 50 psi 12 in 16 NPS 3.25 in 113 sq in 12 NPS Certification Design Series 61 01269 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on December 22, 1992 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.77 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Inlet Size Code Section Media Lift Set Pressure Range VIII Air 30 - 500 psi 0.175 in 0.375 in 0.11 sq in 1 NPS 0.5 NPS Page 382 of 812 Effective Date: 2019-05-31

384 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 01292 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series 243/249/443/449/546/843/849/943/5046/5049/8043/8049 01292 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. (Stafford TX) on August 08, 1997 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: 1.Pop 2.Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Lift Media Code Section Flow Area Outlet Size Set Pressure Range VIII Air 15 - 15000 psi 1 - 1.5 NPS 2 NPS 0.357 sq in [F] 0.674 in 0.25 in VIII Div. 1 Steam 15 - 720 psi VIII Air 15 - 10600 psi 0.446 in 0.913 sq in 2, 3 NPS 1.5 NPS [H] 1.078 in VIII Steam 25 - 720 psi VIII Air 1.496 sq in 15 - 15000 psi 2 NPS 3 NPS 0.637 in [J] 1.38 in VIII Steam 15 - 720 psi VIII Air 1.155 in 15 - 10600 psi 3 NPS 4 NPS 3.317 sq in [L] 2.055 in VIII Steam 15 - 720 psi VIII Air 1.62 in 4 NPS 15 - 10600 psi 7.645 sq in 6 NPS [P] 3.12 in VIII Steam 15 - 720 psi VIII Air 2.435 in 15 - 10600 psi 6 NPS 8, 10 NPS 18.597 sq in [R] 4.866 in VIII Steam 15 - 720 psi VIII Air 15 - 10600 psi 8 NPS 10 NPS 30.582 sq in [T] 6.24 in 3.12 in VIII Steam 15 - 720 psi Design Series Certification 253/259/453/459/853/859/953/959/5059/8053/8059 01304 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. (Stafford TX) on July 31, 1997 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .627 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: 1.Pop 2.Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Flow Area Set Pressure Range Lift Inlet Size Outlet Size VIII Div. 1 Air 15 - 15000 psi [D] 0.674 in 0.205 sq in 2 NPS 1 - 1.5 NPS 0.079 in VIII Div. 1 Air 0.137 in 15 - 15000 psi 0.356 sq in [E] 0.674 in VIII Div. 1 Air 1.5 NPS 2, 3 NPS 15 - 10600 psi 0.241 in [G] 1.078 in 0.831 sq in VIII Div. 1 Air 0.191 in 15 - 15000 psi 2 NPS 0.85 sq in [G] 1.38 in 3 NPS VIII Div. 1 Air [H] 1.38 in 0.295 in 15 - 15000 psi 1.312 sq in VIII Div. 1 Air [J] 2.055 in 2.132 sq in 3 NPS 3 NPS 0.323 in 15 - 10600 psi VIII Div. 1 Air [K] 2.055 in 4 NPS 0.461 in 15 - 10600 psi 3.043 sq in VIII Div. 1 Air 15 - 10600 psi 0.477 in [L] 3.12 in 4.729 sq in 6 NPS 4 NPS VIII Div. 1 Air 5.959 sq in 0.601 in 15 - 10600 psi [M] 3.12 in VIII Div. 1 Air [N] 3.12 in 0.725 in 15 - 10600 psi 7.188 sq in VIII Div. 1 Air 15 - 10600 psi 1.185 in [Q] 4.866 in 18.294 sq in 8, 10 NPS 6 NPS Page 383 of 812 Effective Date: 2019-05-31

385 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 01315 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series 263/269/463/469/566/863/869/963/969/5066/5069 01315 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. (Stafford TX) on July 30, 1997 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .860 Unitless Certified Value: Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: 1.Pop 2.Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Code Section Media Set Pressure Range Lift Inlet Size Outlet Size VIII Div. 1 Air 15 - 10600 psi 0.96 in 1.496 sq in 2 NPS 1 - 1.5 NPS 1.38 in VIII Div. 1 Steam 15 - 720 psi VIII Div. 1 Air 2 NPS 3 NPS 2.895 sq in 1.155 in 15 - 10600 psi 1.92 in VIII Div. 1 Steam 15 - 720 psi VIII Div. 1 Air 15 - 10600 psi 1.62 in 2.928 in 6.733 sq in 4 NPS 3 NPS VIII Div. 1 Steam 15 - 720 psi VIII Div. 1 Air 10.758 sq in 4 NPS 6 NPS 3.701 in 2.035 in 15 - 10600 psi VIII Div. 1 Steam 15 - 2220 psi VIII Div. 1 Air 5.45 in 23.328 sq in 8 NPS 6 NPS 3 in 15 - 10600 psi VIII Div. 1 Steam 15 - 720 psi VIII Div. 1 Air 15 - 10600 psi 32.17 sq in 6.4 in 3.52 in 8 NPS 8 NPS VIII Div. 1 Steam 15 - 720 psi VIII Div. 1 Air 10 NPS 15 - 10600 psi 36.605 sq in 6.827 in 3.755 in VIII Div. 1 Steam 15 - 720 psi VIII Div. 1 Air 6.912 in 37.523 sq in 3.802 in 15 - 1480 psi VIII Div. 1 Steam 15 - 720 psi VIII Div. 1 Air 7.5 in 4.125 in 15 - 1480 psi 44.179 sq in VIII Div. 1 Steam 15 - 720 psi VIII Div. 1 Air 9.575 in 5.35 in 15 - 10600 psi 10 NPS 14 NPS 72.006 sq in VIII Div. 1 Steam 15 - 720 psi Certification Design Series 453/459/853/859/953/959/5059 (Liquids) 01326 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on August 05, 1997 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .491 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Water 15 - 7600 psi 2 NPS 0.221 sq in [D] 0.674 in 1 - 1.5 NPS 0.085 in VIII Water 15 - 7600 psi 0.137 in [E] 0.674 in 0.356 sq in VIII Water 0.264 in [G] 1.078 in 15 - 7600 psi 1.5 NPS 0.911 sq in 2, 3 NPS VIII Water 15 - 7600 psi 0.226 in [G] 1.38 in 1.005 sq in 3 NPS 2 NPS VIII Water [H] 1.38 in 1.495 sq in 0.336 in 15 - 7600 psi VIII Water 4 NPS 0.39 in [J] 2.055 in 15 - 7600 psi 3 NPS 2.574 sq in VIII Water 0.502 in [K] 2.055 in 15 - 7600 psi 3.313 sq in VIII Water 15 - 7600 psi 0.576 in [L] 3 in 5.711 sq in 6 NPS 4 NPS VIII Water [M] 3 in 0.644 in 15 - 7600 psi 6.385 sq in VIII Water 15 - 7600 psi 0.712 in [N] 3 in 7.059 sq in VIII Water 15.885 sq in 1.029 in 15 - 7600 psi 8, 10 NPS [Q] 4.5 in 6 NPS Page 384 of 812 Effective Date: 2019-05-31

386 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 01337 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series 443/449/546/843/849/943/949/5046/5049(Liquids) 01337 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on August 05, 1997 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .767 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Outlet Size Code Section Lift Set Pressure Range Inlet Size VIII Div. 1 Water 2 NPS 15 - 7600 psi 0.21 in [F] 0.674 in 0.357 sq in 1 - 1.5 NPS VIII Div. 1 Water [H] 1.078 in 15 - 7600 psi 0.913 sq in 2, 3 NPS 0.51 in 1.5 NPS VIII Div. 1 Water 1.496 sq in 2 NPS 3 NPS [J] 1.38 in 0.82 in 15 - 7600 psi VIII Div. 1 Water 4 NPS [L] 2.055 in 1.155 in 15 - 7600 psi 3 NPS 3.317 sq in VIII Div. 1 Water 4 NPS 6 NPS 7.069 sq in [P] 3 in 1.62 in 15 - 7600 psi VIII Div. 1 Water 15 - 7600 psi 6 NPS 15.904 sq in [R] 4.5 in 2.435 in 8, 10 NPS VIII Div. 1 Water 8 NPS 10 NPS 28.274 sq in [T] 6 in 15 - 7600 psi 3.12 in Design Series Certification 463/469/566/863/869/963/969/5066/5069 (Liquids) 01348 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on August 27, 1997 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .712 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Lift Set Pressure Range Media Code Section Inlet Size VIII Water 1.5 NPS 2 NPS 1.496 sq in 1.38 in 0.96 in 15 - 7600 psi VIII Water 3 NPS 2 NPS 1.155 in 2.895 sq in 15 - 7600 psi 1.92 in VIII Water 1.315 in 2.928 in 6.733 sq in 4 NPS 3 NPS 15 - 7600 psi VIII Water 3.701 in 2.035 in 15 - 7600 psi 4 NPS 6 NPS 10.758 sq in VIII Water 8 NPS 23.328 sq in 5.45 in 3 in 15 - 7600 psi 6 NPS VIII Water 32.17 sq in 15 - 7600 psi 8 NPS 8 NPS 6.4 in 3.52 in VIII Water 10 NPS 15 - 7600 psi 44.179 sq in 7.5 in 4.125 in VIII Div. 1 Water 9.575 in 5.35 in 15 - 7600 psi 10 NPS 14 NPS 72.006 sq in Page 385 of 812 Effective Date: 2019-05-31

387 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 01382 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series JLT-JOS-RL/JLT-JBS-RL (Restricted Lift version of Certification 15512) 01382 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. (Stafford TX) on October 13, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .870 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Code Section Outlet Size Inlet Size Media Set Pressure Range VIII Div. 1 Air 15 - 6170 psi 0.08 in [D] 0.398 in 2 - 3 NPS 0.75 - 1.5 NPS 0.1244 sq in VIII Div. 1 Air 0.2214 sq in 1 - 1.5 NPS 2 - 3 NPS [E] 0.531 in 0.082 in 15 - 6170 psi VIII Div. 1 Air [F] 0.665 in 15 - 6170 psi 0.3473 sq in 0.103 in VIII Div. 1 Air 1.5 - 2 NPS 2.5, 3 NPS 0.5674 sq in [G] 0.85 in 0.131 in 15 - 6170 psi VIII Div. 1 Air 0.892 in 0.6949 sq in 0.137 in 15 - 2500 psi 3 NPS VIII Div. 1 Air 15 - 3705 psi 0.164 in [H] 1.063 in 0.8874 sq in VIII Div. 1 Air [J] 1.36 in 0.21 in 15 - 3705 psi 2 - 3 NPS 3, 4 NPS 1.453 sq in VIII Div. 1 Air 3 NPS 4, 6 NPS 2.076 sq in [K] 1.626 in 0.251 in 15 - 3705 psi VIII Div. 1 Air 3 - 4 NPS 15 - 3705 psi 3.221 sq in 0.313 in 4, 6 NPS [L] 2.025 in VIII Div. 1 Air 15 - 2220 psi 0.351 in [M] 2.275 in 4.065 sq in 6 NPS VIII Div. 1 Air 4 NPS 6 NPS 4.9 sq in [N] 2.498 in 0.386 in 15 - 1480 psi VIII Div. 1 Air 15 - 1480 psi 0.468 in [P] 3.029 in 7.205 sq in VIII Div. 1 Air 7.997 sq in [P2] 3.191 in 0.493 in 15 - 1500 psi VIII Div. 1 Air [Q] 3.985 in 6 NPS 8 NPS 12.472 sq in 15 - 1480 psi 0.616 in VIII Div. 1 Air 15 - 1480 psi 0.741 in [R] 4.796 in 18.065 sq in 8, 10 NPS VIII Div. 1 Air [T] 6.114 in 0.944 in 15 - 740 psi 8 NPS 10, 12 NPS 29.359 sq in Page 386 of 812 Effective Date: 2019-05-31

388 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 01393 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series JLT-JOS-RL/JLT-JBS-RL (Liquids) (Restricted lift version of Certification 15095) 01393 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. (Stafford TX) on October 14, 2015 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .656 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Inlet Size Flow Area Outlet Size Code Section Media Set Pressure Range I & VIII Div. 1 Water 15 - 6170 psi [D] 0.398 in 0.75 - 1.5 NPS 2 - 3 NPS 0.08 in 0.1244 sq in III I & VIII Div. 1 Water 0.082 in 15 - 6170 psi 1 - 1.5 NPS 2 - 3 NPS 0.2214 sq in [E] 0.531 in III I & VIII Div. 1 Water 0.3473 sq in [F] 0.665 in 0.103 in 15 - 6170 psi III I & VIII Div. 1 Water 15 - 6170 psi 1.5 - 2 NPS 0.5674 sq in [G] 0.85 in 0.131 in 2.5, 3 NPS III I & VIII Div. 1 Water 0.6249 sq in 0.892 in 0.137 in 3 NPS 15 - 2500 psi III I & VIII Div. 1 Water 0.164 in 15 - 3705 psi 0.8874 sq in [H] 1.063 in III I & VIII Div. 1 Water [J] 1.36 in 0.21 in 15 - 3705 psi 2 - 3 NPS 3, 4 NPS 1.453 sq in III I & VIII Div. 1 Water [K] 1.626 in 2.076 sq in 4, 6 NPS 3 NPS 15 - 3705 psi 0.251 in III I & VIII Div. 1 Water 15 - 3705 psi 0.313 in 3 - 4 NPS 4, 6 NPS 3.221 sq in [L] 2.025 in III I & VIII Div. 1 Water 4.065 sq in 6 NPS 15 - 2220 psi [M] 2.275 in 0.351 in III I & VIII Div. 1 Water 0.386 in 15 - 1480 psi 4 NPS 6 NPS 4.9 sq in [N] 2.498 in III I & VIII Div. 1 Water 15 - 1480 psi 0.468 in [P] 3.029 in 7.205 sq in III I & VIII Div. 1 Water [P2] 3.191 in 0.493 in 15 - 1500 psi 7.997 sq in I & VIII Div. 1 Water 12.472 sq in [Q] 3.985 in 0.616 in 15 - 1480 psi 8 NPS 6 NPS I & VIII Div. 1 Water 8, 10 NPS 18.065 sq in 15 - 1480 psi 0.741 in [R] 4.796 in III I & VIII Div. 1 Water [T] 6.114 in 0.944 in 15 - 740 psi 8 NPS 10, 12 NPS 29.359 sq in III Page 387 of 812 Effective Date: 2019-05-31

389 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 01562 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series 243/249/443/449/843/849-RL (Restriced Lift version of Cert No. 01292) 01562 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. (Stafford TX) on May 24, 2017 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Air Test Medium: Air/Gas Certified Medium: None Special Service: 1.Pop 3.Initial Audible Discharge Set Pressure Definition: Adjustable and Fixed for Mod. Pilot Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Outlet Size Code Section Lift Set Pressure Range Inlet Size VIII Div. 1 Air 0.357 sq in 15 - 15000 psi 0.08 in [F] 0.674 in 2 NPS 1 - 1.5 NPS VIII Div. 1 Air [H] 1.078 in 15 - 10600 psi 0.913 sq in 2, 3 NPS 0.134 in 1.5 NPS VIII Div. 1 Air 3 NPS 2 NPS 1.496 sq in [J] 1.38 in 0.193 in 15 - 15000 psi VIII Div. 1 Air 0.347 in 15 - 10600 psi 3.317 sq in 3 NPS 4 NPS [L] 2.055 in VIII Div. 1 Air 4 NPS 6 NPS 7.645 sq in [P] 3.12 in 0.486 in 15 - 10600 psi VIII Div. 1 Air 15 - 10600 psi 6 NPS 18.597 sq in 8, 10 NPS [R] 4.866 in 0.731 in VIII Div. 1 Air 0.936 in 15 - 10600 psi 8 NPS 10 NPS [T] 6.24 in 30.582 sq in Design Series Certification 443/449/843/849-RL (Restricted Lift version of Cert No. 01337) - Liquid 01573 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. (Stafford TX) on June 09, 2017 Capacity Tests: .767 Unitless Certified Value: Liquid Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Outlet Size Code Section Flow Area Lift Set Pressure Range Inlet Size VIII Div. 1 Water 0.357 sq in 15 - 7600 psi 0.08 in [F] 0.674 in 2 NPS 1 - 1.5 NPS VIII Div. 1 Water 15 - 7600 psi 0.913 sq in 0.154 in 2, 3 NPS [H] 1.078 in 1.5 NPS VIII Div. 1 Water 15 - 7600 psi 0.246 in [J] 1.38 in 1.496 sq in 3 NPS 2 NPS VIII Div. 1 Water 4 NPS 15 - 7600 psi 3 NPS 0.347 in [L] 2.055 in 3.317 sq in VIII Div. 1 Water 15 - 7600 psi 0.486 in [P] 3 in 7.069 sq in 6 NPS 4 NPS VIII Div. 1 Water [R] 4.5 in 0.731 in 15 - 7600 psi 6 NPS 8, 10 NPS 15.904 sq in VIII Div. 1 Water 15 - 7600 psi 0.936 in [T] 6 in 28.274 sq in 20 NPS 7 NPS Page 388 of 812 Effective Date: 2019-05-31

390 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 15006 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series H Series (HCI, HSJ, HCA, HA, HB, HC, HCB, HCP, HJO, HN, HNA, HNB, HNP, HS, HSA, HSB, 15006 Number: or catalog number HSC, HSP) Safety Valve Type Classification: Sec. I at Ohio State University (Robinson Laboratory) on September 01, 1939 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Adjustable Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Set Pressure Range Media Code Section Lift I Steam 15 - 500 psi 0.094 in [D] 0.375 in 1.5 NPS 0.75 NPS 0.11 sq in I Steam 0.196 sq in [E] 0.5 in 0.125 in 15 - 500 psi I Steam 0.156 in 0.307 sq in 1 - 1.5 NPS 2 - 3 NPS [F] 0.625 in 15 - 3100 psi I Steam 15 - 3100 psi 0.2 in [G] 0.8 in 0.503 sq in 2.5, 3 NPS 1 - 2 NPS I Steam 3 NPS 1.05 in 0.262 in 1.5 NPS 15 - 3100 psi 0.865 sq in I Steam 0.994 sq in [H2] 1.125 in 0.281 in 15 - 3100 psi I Steam [H] 1 in 15 - 5000 psi 1.5 - 2 NPS 3, 4, 6 NPS 0.785 sq in 0.25 in I Steam 15 - 3100 psi 0.338 in [J2] 1.35 in 1.431 sq in 4 NPS 2 NPS I Steam [J] 1.281 in 0.32 in 15 - 5000 psi 1.288 sq in 3, 4, 6 NPS 2 - 3 NPS I Steam 15 - 6000 psi 0.45 in [K2] 1.8 in 2.545 sq in 6 NPS 2.5 NPS I Steam 0.383 in 15 - 6000 psi 2.5 - 3 NPS 4, 6 NPS 1.84 sq in [K] 1.531 in I Steam 3 NPS 6 NPS 15 - 3100 psi 0.516 in [L2] 2.062 in 3.341 sq in I Steam 6, 8 NPS [M2] 2.25 in 0.563 in 3.976 sq in 15 - 6000 psi I Steam [L] 1.906 in 0.476 in 15 - 3100 psi 3 - 4 NPS 4, 6 NPS 2.853 sq in I Steam 15 - 6000 psi 0.535 in [M] 2.14 in 3.6 sq in 6, 8 NPS I Steam 4 NPS [N] 2.351 in 0.588 in 15 - 3100 psi 6 NPS 4.341 sq in I Steam 15 - 1500 psi 0.712 in [P] 2.85 in 6.38 sq in I Steam 0.75 in 7.07 sq in [P2] 3 in 15 - 3100 psi I Steam 6 NPS 8 NPS 15 - 1500 psi 0.937 in [Q] 3.75 in 11.045 sq in I Steam [Q2] 3.95 in 0.988 in 12.25 sq in 15 - 3100 psi I Steam 8, 10 NPS 16 sq in [R] 4.513 in 1.128 in 15 - 3100 psi I Steam 1.239 in 10 NPS 19.29 sq in [RR] 4.956 in 15 - 3100 psi I Steam 10, 12 NPS [T] 5.75 in 1.437 in 26 sq in 15 - 500 psi 8 NPS I Steam 15 - 2000 psi 1.5 in 6 in 28.274 sq in 12, 14 NPS I Steam 7.5 in 1.875 in 15 - 500 psi 10 NPS 14 NPS 44.18 sq in I Steam 9 in 63.62 sq in 16 NPS 12 NPS 2.25 in 15 - 500 psi I Steam 15 - 500 psi 86.59 sq in 14 NPS 10.5 in 2.625 in 18 NPS I Steam 15 - 500 psi 2.753 in 11.01 in 95.21 sq in 18, 20 NPS 16 NPS I Steam 114.04 sq in 3.02 in 15 - 500 psi 12.05 in I Steam 13.5 in 3.375 in 15 - 500 psi 18 NPS 24 NPS 143.14 sq in I Steam 15 - 500 psi 3.75 in 15 in 176.71 sq in 24 NPS 20 NPS Page 389 of 812 Effective Date: 2019-05-31

391 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 15039 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series HE 15039 or catalog number Number: Safety Valve Type Classification: Sec. I at Crosby Valve & Gage on November 15, 1970 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .8775 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Dual Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Media Inlet Size Set Pressure Range Lift Outlet Size I Steam 1.5 NPS 2.5 NPS 0.307 sq in 0.625 in 0.156 in 15 - 3100 psi I Steam 0.2 in 15 - 3100 psi 0.503 sq in 0.8 in I Steam 3 NPS 0.785 sq in [H] 1 in 0.25 in 15 - 3100 psi I Steam 15 - 3100 psi 2 NPS 1.288 sq in 4 NPS [J] 1.281 in 0.32 in I Steam 15 - 3100 psi [K] 1.531 in 1.84 sq in 6 NPS 2.5 NPS 0.382 in I Steam 15 - 3100 psi 0.45 in [K2] 1.8 in 2.545 sq in I Steam 3.6 sq in 3 NPS 6 NPS 15 - 3100 psi [M] 2.14 in 0.535 in I Steam 3.976 sq in [M2] 2.25 in 0.562 in 15 - 3100 psi I Steam 0.712 in 6 NPS 6.38 sq in 2.85 in 15 - 3100 psi 4 NPS I Steam 0.75 in 15 - 3100 psi 7.069 sq in [P2] 3 in I Steam 15 - 3100 psi 0.937 in 11.045 sq in 8 NPS 6 NPS 3.75 in I Steam [R] 4.513 in 1.128 in 15 - 1500 psi 6 - 8 NPS 8, 10 NPS 16 sq in I Steam 10, 12, 14 NPS 19.369 sq in [R3] 4.966 in 1.242 in 15 - 3100 psi 8 NPS I Steam [R5] 5.183 in 21.1 sq in 15 - 3100 psi 1.295 in I Steam [T2] 6.808 in 1.707 in 15 - 3100 psi 10 NPS 16 NPS 36.4 sq in Page 390 of 812 Effective Date: 2019-05-31

392 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 15095 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series JLT (Liquids) 15095 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on February 05, 1980 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .656 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Inlet Size Flow Area Outlet Size Code Section Media Set Pressure Range I & VIII Div. 1 Water 15 - 6170 psi [D] 0.398 in 0.75 - 1.5 NPS 2 - 3 NPS 0.151 in 0.1244 sq in III I & VIII Div. 1 Water 0.205 in 15 - 6170 psi 1 - 1.5 NPS 2 - 3 NPS 0.2214 sq in [E] 0.531 in III I & VIII Div. 1 Water 0.3473 sq in [F] 0.665 in 0.257 in 15 - 6170 psi III I & VIII Div. 1 Water 15 - 6170 psi 1.5 - 2 NPS 0.5674 sq in [G] 0.85 in 0.328 in 2.5, 3 NPS III I & VIII Div. 1 Water 0.6249 sq in 0.892 in 0.342 in 3 NPS 15 - 2500 psi III I & VIII Div. 1 Water 0.41 in 15 - 3705 psi 0.8874 sq in [H] 1.063 in III I & VIII Div. 1 Water [J] 1.36 in 0.525 in 15 - 3705 psi 2 - 3 NPS 3, 4 NPS 1.453 sq in III I & VIII Div. 1 Water [K] 1.626 in 2.076 sq in 4, 6 NPS 3 NPS 15 - 3705 psi 0.628 in III I & VIII Div. 1 Water 15 - 3705 psi 0.782 in 3 - 4 NPS 4, 6 NPS 3.221 sq in [L] 2.025 in III I & VIII Div. 1 Water 4.065 sq in 6 NPS 15 - 2220 psi [M] 2.275 in 0.878 in III I & VIII Div. 1 Water 0.964 in 15 - 1480 psi 4 NPS 6 NPS 4.9 sq in [N] 2.498 in III I & VIII Div. 1 Water 15 - 1480 psi 1.169 in [P] 3.029 in 7.205 sq in III I & VIII Div. 1 Water [P2] 3.191 in 1.232 in 15 - 1500 psi 7.997 sq in I & VIII Div. 1 Water 12.472 sq in [Q] 3.985 in 1.539 in 15 - 1480 psi 8 NPS 6 NPS I & VIII Div. 1 Water 8, 10 NPS 18.065 sq in 15 - 1480 psi 1.852 in [R] 4.796 in III I & VIII Div. 1 Water [T] 6.114 in 2.361 in 15 - 740 psi 8 NPS 10, 12 NPS 29.359 sq in III Page 391 of 812 Effective Date: 2019-05-31

393 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 15208 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series JOS-E/JBS-E/JOS-H-E 8400 AC/AB 15208 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on April 01, 1975 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .865 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Outlet Size Inlet Size Set Pressure Range Code Section Lift III & VIII Div.1 Air 15 - 15000 psi 0.1244 sq in 0.121 in 0.75 - 1.5 NPS 2 - 3 NPS [D] 0.398 in III & VIII Div.1 Steam 15 - 2000 psi VIII Div. 1 Steam 15 - 2000 psi 1 - 1.5 NPS 2 - 3 NPS 0.488 in 0.151 in 0.187 sq in VIII Div. 1 Air 15 - 8490 psi III & VIII Div.1 Air 15 - 15000 psi [E] 0.531 in 0.2214 sq in 0.165 in III & VIII Div.1 Steam 15 - 2000 psi III & VIII Div.1 Air [F] 0.665 in 0.207 in 0.3473 sq in 15 - 15000 psi III & VIII Div.1 Steam 15 - 2000 psi III & VIII Div.1 Air 15 - 15000 psi 0.265 in 0.5674 sq in 1.5 - 2 NPS 2.5, 3 NPS [G] 0.85 in III & VIII Div.1 Steam 15 - 2000 psi III & VIII Div.1 Air 0.8874 sq in 3 NPS 0.331 in 15 - 15000 psi [H] 1.063 in III & VIII Div.1 Steam 15 - 2000 psi III & VIII Div.1 Air 3, 4 NPS 1.453 sq in 0.424 in [J] 1.36 in 2 - 3 NPS 15 - 10000 psi III & VIII Div.1 Steam 15 - 2000 psi III & VIII Div.1 Air 0.507 in 3 NPS 2.076 sq in 4, 6 NPS 15 - 10000 psi [K] 1.626 in III & VIII Div.1 Steam 15 - 2000 psi III & VIII Div.1 Steam 0.631 in 15 - 2000 psi 3 - 4 NPS 4, 6 NPS 3.221 sq in [L] 2.025 in III & VIII Div.1 Air 15 - 5000 psi III & VIII Div.1 Steam 6 NPS 4.065 sq in 0.709 in 15 - 2000 psi [M] 2.275 in III & VIII Div.1 Air 15 - 5000 psi III & VIII Div.1 Steam 15 - 1000 psi 4 NPS 2.714 sq in 1.859 in 0.601 in 6 NPS III & VIII Div.1 Air 15 - 3000 psi III & VIII Div.1 Steam 4.9 sq in 15 - 1480 psi [N] 2.498 in 0.779 in III & VIII Div.1 Air 15 - 3000 psi III & VIII Div.1 Air 5.444 sq in 2.633 in 0.85 in 15 - 2250 psi III & VIII Div.1 Steam III & VIII Div.1 Steam 7.206 sq in 0.945 in 15 - 1480 psi [P] 3.029 in III & VIII Div.1 Air 15 - 3000 psi III & VIII Div.1 Steam 1.243 in 15 - 1000 psi 8 NPS 11.045 sq in 3.75 in 6 NPS III & VIII Div.1 Air 15 - 3750 psi III & VIII Div.1 Air 12.174 sq in 3.937 in 1.243 in 15 - 2250 psi III & VIII Div.1 Steam III & VIII Div.1 Air 10 NPS 12.236 sq in 1.496 in 15 - 2250 psi 3.947 in III & VIII Div.1 Steam III & VIII Div.1 Steam 15 - 1480 psi 8 NPS [Q] 3.985 in 1.243 in 12.472 sq in III & VIII Div.1 Air 15 - 3000 psi III & VIII Div.1 Air 15 - 2250 psi 1.414 in 4.412 in 15.288 sq in III & VIII Div.1 Steam III & VIII Div.1 Air 1.496 in 8, 10 NPS 18.065 sq in 15 - 1480 psi [R] 4.796 in III & VIII Div.1 Steam III & VIII Div.1 Air 8 NPS 15 - 2250 psi 18.254 sq in 10 NPS 4.821 in 1.907 in III & VIII Div.1 Steam III & VIII Div.1 Air 15 - 740 psi 29.359 sq in [T] 6.114 in 1.907 in III & VIII Div.1 Steam III & VIII Div.1 Air 1.974 in 15 - 740 psi 31.47 sq in [T2] 6.33 in III & VIII Div.1 Steam Page 392 of 812 Effective Date: 2019-05-31

394 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 15208 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT ...Continued Orifice [designator] diameter Inlet Size Outlet Size Code Section Flow Area Media Lift Set Pressure Range VIII Div. 1 Air 10 - 12 NPS [V] 7.805 in 14, 16 NPS 2.435 in 15 - 325 psi 47.84 sq in VIII Div. 1 Steam VIII Div. 1 Air 3.111 in 12 - 14 NPS [W] 9.971 in 15 - 325 psi 78.08 sq in 16. 20 NPS VIII Div. 1 Steam Design Series Certification JQU - 1.5 (with breaking pin) 15275 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on May 01, 1978 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 9.26 Unitless Certified Value: Steam Test Medium: Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Lift Inlet Size Code Section Set Pressure Range Media VIII Div. 1 Air 0.26 in 15 - 375 psi 1.5 NPS 4 NPS 0.849 sq in 1.04 in Certification Design Series JQU - 1.5 (without breaking pin) 15286 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on May 01, 1978 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 9.43 PPH/PSIA Certified Value: 3.36 SCFM/PSIA Certified Value (alternate medium): Steam Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Flow Area Outlet Size Lift Set Pressure Range Media VIII Air 0.26 in 15 - 375 psi 1.5 NPS 4 NPS 0.849 sq in 1.04 in Certification Design Series JQU - 4 (with breaking pin) 15297 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Phillips Petroleum on July 06, 1959 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 39.8 SCFM/PSIA Certified Value: Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Inlet Size Outlet Size Set Pressure Range Media Flow Area VIII Div. 1 Air 2 in 0.5 in 50 - 375 psi 4 NPS 6 NPS 3.141 sq in Page 393 of 812 Effective Date: 2019-05-31

395 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 15354 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series PVR-3 15354 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on July 14, 1980 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 47.13 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Flow Area Outlet Size Code Section Lift Set Pressure Range Inlet Size VIII Div. 1 Air 4 NPS 3 NPS 3.757 sq in 2.187 in 0.8 in 15 - 125 psi Design Series Certification PVR-4 15365 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on June 26, 1981 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 87.57 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Flow Area Media Outlet Size Inlet Size Lift Code Section VIII Div. 1 Air 1.125 in 15 - 125 psi 4 NPS 5 NPS 7.67 sq in 3.125 in Design Series Certification 900 Series, 7700, SNC 15411 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on February 14, 1990 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Air Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Flow Area Outlet Size Inlet Size Lift Media Code Section VIII Div. 1 Air 15 - 10000 psi 0.5 - 1 NPS .5 - 1 NPS 0.074 in [#10] 0.265 in 0.0551 sq in III & VIII Div.1 Steam 15 - 2900 psi VIII Div. 1 Air [#5] 0.328 in 0.106 in 1 - 1.5 NPS 0.0845 sq in 15 - 10000 psi III & VIII Div.1 Steam 15 - 2900 psi VIII Div. 1 Air 0.1244 sq in 0.128 in 15 - 10000 psi [#6] 0.398 in III & VIII Div.1 Steam 15 - 2900 psi III & VIII Div.1 Steam 0.17 in 15 - 2900 psi 1.5 NPS 1 - 1.5 NPS 0.2198 sq in [#7] 0.529 in VIII Div. 1 Air 15 - 5000 psi III & VIII Div.1 Steam 0.274 in [#9] 0.85 in 0.5674 sq in 2.5 NPS 1.5 NPS 15 - 2900 psi VIII Div. 1 Air 15 - 5000 psi III & VIII Div.1 Steam [#8] 0.665 in 0.215 in 15 - 2900 psi 1.5 - 2 NPS 2 NPS 0.3473 sq in VIII Div. 1 Air 15 - 5000 psi Page 394 of 812 Effective Date: 2019-05-31

396 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 15466 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series 800 15466 Number: or catalog number Safety Relief Valve Type Classification: Sec. III at Crosby Valve & Gage on August 08, 1991 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .877 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Set Pressure Range Media Code Section Inlet Size Outlet Size Lift VIII Div. 1 Air 1 NPS 0.1244 sq in [#6] 0.398 in 0.128 in 0.75 - 1 NPS 15 - 10000 psi III Steam 15 - 2900 psi VIII Div. 1 III Steam 0.17 in 15 - 2900 psi 1 - 1.5 NPS 1, 1.5 NPS 0.2198 sq in [#7] 0.529 in VIII Div. 1 VIII Div. 1 Air 15 - 5000 psi III & VIII Div.1 Steam 0.215 in 1 - 2 NPS 1.5, 2 NPS 0.3473 sq in [#8] 0.665 in 15 - 2900 psi VIII Div. 1 Air 15 - 5000 psi III Steam 0.5674 sq in 15 - 2900 psi 0.274 in 1.5 NPS 2.5 NPS [#9] 0.85 in VIII Div. 1 VIII Div. 1 Air 15 - 5000 psi Design Series Certification 900 Series (Liquid), 7700, SNC 15499 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on February 09, 1990 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .6615 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Media Set Pressure Range Lift Inlet Size Flow Area Code Section I & VIII Div. 1 Water 15 - 10000 psi [#10] 0.265 in 0.0551 sq in .5 - 1 NPS 0.5 - 1 NPS 0.074 in III I & VIII Div. 1 Water 0.106 in 1 - 1.5 NPS 0.0845 sq in 15 - 10000 psi [#5] 0.328 in III I & VIII Div. 1 Water 15 - 10000 psi 0.1244 sq in [#6] 0.398 in 0.128 in III I & VIII Div. 1 Water [#7] 0.529 in 0.17 in 15 - 5000 psi 1 - 1.5 NPS 1.5 NPS 0.2198 sq in III I & VIII Div. 1 Water 0.613 in 0.265 in 15 - 5000 psi 1.5 - 2 NPS 0.2951 sq in I & VIII Div. 1 Water 0.5674 sq in [#9] 0.85 in 1.5 NPS 2.5 NPS 15 - 5000 psi 0.274 in III I & VIII Div. 1 Water [#8] 0.665 in 0.215 in 15 - 5000 psi 1.5 - 2 NPS 2 NPS 0.3473 sq in III Page 395 of 812 Effective Date: 2019-05-31

397 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 15501 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series BP 15501 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on August 24, 1995 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .841 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Inlet Size Code Section Outlet Size Set Pressure Range Media VIII Air 50 - 3000 psi 0.75 - 1 NPS 1 NPS 0.0539 sq in [#4] 0.262 in 0.06 in VIII Air 0.085 in 0.0929 sq in [#5] 0.344 in 50 - 3000 psi VIII Air 0.098 in [#5A] 0.381 in 50 - 3000 psi 0.114 sq in VIII Air 0.112 in 50 - 3000 psi 0.1364 sq in [#6] 0.417 in Design Series Certification JLT-JOS, JLT-JBS, 8500, ACL/ABL 15512 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on June 28, 1994 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .870 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Code Section Outlet Size Flow Area Lift Set Pressure Range Media VIII Div. 1 Air 0.151 in 15 - 6170 psi 2 - 3 NPS [D] 0.398 in 0.75 - 1.5 NPS 0.1244 sq in VIII Div. 1 Air [E] 0.531 in 0.205 in 15 - 6170 psi 1 - 1.5 NPS 2 - 3 NPS 0.2214 sq in VIII Div. 1 Air 15 - 6170 psi 0.257 in [F] 0.665 in 0.3473 sq in VIII Div. 1 Air 2.5, 3 NPS 15 - 6170 psi 1.5 - 2 NPS 0.328 in 0.5674 sq in [G] 0.85 in VIII Div. 1 Air [H] 1.063 in 3 NPS 0.8874 sq in 0.41 in 15 - 3705 psi VIII Div. 1 Air 0.525 in 15 - 3705 psi 3, 4 NPS 2 - 3 NPS [J] 1.36 in 1.453 sq in VIII Div. 1 Air 3 NPS 4, 6 NPS 2.076 sq in [K] 1.626 in 0.628 in 15 - 3705 psi VIII Div. 1 Air 3.221 sq in 4, 6 NPS 15 - 3705 psi [L] 2.025 in 0.782 in 3 - 4 NPS VIII Div. 1 Air 15 - 2220 psi 0.878 in [M] 2.275 in 4.065 sq in 6 NPS VIII Div. 1 Air [N] 2.498 in 0.964 in 15 - 1480 psi 4 NPS 6 NPS 4.9 sq in VIII Div. 1 Air 7.205 sq in [P] 3.029 in 1.169 in 15 - 1480 psi VIII Div. 1 Air 1.539 in 15 - 1480 psi 8 NPS [Q] 3.985 in 6 NPS 12.472 sq in VIII Div. 1 Air 15 - 1480 psi 1.852 in [R] 4.796 in 18.065 sq in 8, 10 NPS VIII Div. 1 Air [T] 6.114 in 2.361 in 15 - 740 psi 8 NPS 10, 12 NPS 29.359 sq in Page 396 of 812 Effective Date: 2019-05-31

398 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 15534 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series BP (Liquids) 15534 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at Crosby Valve & Gage on September 15, 1995 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .631 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Code Section Outlet Size Inlet Size Set Pressure Range Media I & VIII Div. 1 Water [#4] 0.262 in 0.06 in 50 - 3000 psi 0.75 - 1 NPS 1 NPS 0.0539 sq in I & VIII Div. 1 Water 0.085 in 50 - 3000 psi 0.0929 sq in [#5] 0.344 in I & VIII Div. 1 Water 50 - 3000 psi 0.098 in 0.114 sq in [#5A] 0.381 in I & VIII Div. 1 Water 50 - 3000 psi 0.112 in [#6] 0.417 in 0.1364 sq in Page 397 of 812 Effective Date: 2019-05-31

399 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 15567 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series H Series (Restricted Lift version of Cert # 15006) 15567 or catalog number Number: Safety Valve Type Classification: Sec. I at Crosby Valve & Gage on August 06, 1996 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: per CC 1923 &/or 1945 Certification Provisions: Steam Test Medium: Steam Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Dual Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Inlet Size Code Section Flow Area Lift Set Pressure Range Media I Steam 15 - 500 psi 0.08 in 0.375 in 1.5 NPS 0.75 NPS 0.11 sq in I Steam 0.196 sq in 0.5 in 0.08 in 15 - 500 psi I Steam 1 - 1.5 NPS 2, 2.5, 3 NPS 0.307 sq in 0.625 in 15 - 3100 psi 0.08 in I Steam 15 - 3100 psi 0.08 in 0.8 in 0.503 sq in 2.5, 3 NPS 1 - 2 NPS I Steam 1.5 NPS 3 NPS 0.865 sq in 1.05 in 0.08 in 15 - 3100 psi I Steam 0.084 in 15 - 3100 psi 0.994 sq in 1.125 in I Steam 15 - 3100 psi 1.5 - 2 NPS 3, 4 NPS 0.785 sq in 0.08 in 1 in I Steam 2 NPS 0.101 in 1.431 sq in 15 - 3100 psi 4 NPS 1.35 in I Steam 0.096 in 1.281 in 0.288 sq in 3,4,6 NPS 2 - 3 NPS 15 - 5000 psi I Steam 2.5 NPS 6 NPS 2.545 sq in 1.8 in 0.135 in 15 - 3100 psi I Steam 1.84 sq in 15 - 3100 psi 0.115 in 4, 6 NPS 2.5 - 3 NPS 1.531 in I Steam 3.341 sq in 6 NPS 3 NPS 2.062 in 15 - 3100 psi 0.155 in I Steam 3.976 sq in 0.169 in 15 - 3100 psi 2.25 in I Steam 1.906 in 0.143 in 15 - 3100 psi 3 - 4 NPS 4, 6 NPS 2.853 sq in I Steam 15 - 5000 psi 0.161 in 2.14 in 3.6 sq in 6 NPS I Steam 4 NPS 2.351 in 0.176 in 15 - 3100 psi 6 NPS 4.341 sq in I Steam 15 - 1500 psi 0.213 in 2.85 in 6.38 sq in I Steam 0.225 in 7.07 sq in 3 in 15 - 3100 psi I Steam 15 - 1500 psi 0.296 in 3.75 in 11.045 sq in 8 NPS 6 NPS I Steam 8, 10 NPS 16 sq in 4.513 in 0.338 in 15 - 1200 psi I Steam 15 - 3100 psi 4.956 in 19.29 sq in 10 NPS 0.371 in I Steam 8 NPS 5.75 in 10, 12 NPS 26 sq in 15 - 500 psi 0.431 in I Steam 12, 14 NPS 15 - 2000 psi 28.274 sq in 6 in 0.45 in I Steam 7.5 in 0.562 in 15 - 500 psi 10 NPS 14 NPS 44.18 sq in I Steam 9 in 63.62 sq in 16 NPS 12 NPS 0.675 in 15 - 500 psi I Steam 15 - 500 psi 86.59 sq in 14 NPS 10.5 in 0.787 in 18 NPS I Steam 15 - 500 psi 0.826 in 11.01 in 95.21 sq in 18, 20 NPS 16 NPS I Steam 114.04 sq in 0.906 in 15 - 500 psi 12.05 in I Steam 13.5 in 1.012 in 15 - 500 psi 18 NPS 24 NPS 143.14 sq in I Steam 15 - 500 psi 1.125 in 15 in 176.71 sq in 24 NPS 20 NPS Page 398 of 812 Effective Date: 2019-05-31

400 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 15589 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series HL, HSL 15589 Number: or catalog number Safety Valve Type Classification: Sec. I at Crosby Valve & Gage on November 03, 1999 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.869 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: None Special Service: Pop Set Pressure Definition: Adjustable by Dual Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Flow Area Media Code Section Outlet Size Lift Inlet Size I & VIII Div. 1 Steam 1.5 NPS 1.25 - 2 NPS 0.339 sq in 15 - 725 psi 0.164 in [F] 0.657 in I & VIII Div. 1 Steam 0.21 in [G] 0.839 in 15 - 725 psi 0.553 sq in I & VIII Div. 1 Steam 0.263 in 15 - 725 psi 1.5 - 2.5 NPS 2.5 NPS 0.868 sq in [H] 1.051 in I & VIII Div. 1 Steam [J] 1.3 in 1.327 sq in 0.325 in 15 - 725 psi I & VIII Div. 1 Steam 0.404 in 15 - 725 psi 2.046 sq in 2 - 3 NPS 4 NPS [K] 1.614 in I & VIII Div. 1 Steam 2.5 - 4 NPS 6 NPS 3.167 sq in [L] 2.008 in 0.502 in 15 - 725 psi I & VIII Div. 1 Steam 15 - 725 psi 3 NPS 3.955 sq in 6 NPS [M] 2.244 in 0.561 in I & VIII Div. 1 Steam 0.62 in [N] 2.48 in 4.831 sq in 6 NPS 4 NPS 15 - 725 psi I & VIII Div. 1 Steam [P] 2.992 in 0.748 in 15 - 725 psi 7.031 sq in I & VIII Div. 1 Steam 6 NPS 8 NPS 11.045 sq in [QQ] 3.75 in 15 - 725 psi 0.937 in I & VIII Div. 1 Steam 0.984 in 12.174 sq in 15 - 725 psi [Q] 3.937 in Design Series Certification LCP 36368 or catalog number Number: Pilot Operated Pressure Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on March 01, 1999 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .86 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Media Flow Area Outlet Size Inlet Size Code Section VIII Div. 1 Air 1 in 0.5 in 25 - 2220 psi 1 NPS 2 NPS 0.785 sq in VIII Div. 1 Air 2 NPS 1.227 sq in 1.25 in 0.625 in 25 - 2220 psi 1.25 NPS VIII Div. 1 Air 1.767 sq in 25 - 2220 psi 1.5 NPS 2 NPS 1.5 in 0.99 in VIII Div. 1 Air 2 NPS 3.142 sq in 2 in 1.1 in 3 NPS 25 - 2220 psi VIII Div. 1 Air 3 in 1.75 in 25 - 1480 psi 3 NPS 4 NPS 7.069 sq in Page 399 of 812 Effective Date: 2019-05-31

401 Table of Contents Emerson Automation Solutions Final Control US LP (AGC) 36458 NB#: 3950 Greenbriar Drive, Stafford, TX 77477 United States location: Acceptable Abbrev.: EMRT Certification Design Series 5200 Series (Water K = 0.674) 36458 Number: or catalog number Pilot Operated Pressure Relief Valve Type Classification: Sec. I & VIII Div. 1 at National Board T L (Worthington) on August 05, 2011 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: 0.878 Unitless Certified Value: 0.674 Unitless Certified Value (alternate medium): Steam/Water Test Medium: Steam, Air/Gas & Liquid Certified Medium: 1.Initial Audible Discharge 3.First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Set Pressure Range Media Code Section Inlet Size Outlet Size Lift VIII Div. 1 Air 2 - 3 NPS 0.347 sq in [F] 0.665 in 0.207 in 1 - 1.5 NPS 15 - 6170 psi I & VIII Div. 1 Steam I Water VIII Div. 1 Air 0.265 in 15 - 6170 psi 1.5 - 2 NPS 2.5, 3 NPS 0.5674 sq in [G] 0.85 in I & VIII Div. 1 Steam I Water VIII Div. 1 Air 3 NPS 0.887 sq in [H] 1.063 in 0.331 in 15 - 3705 psi I & VIII Div. 1 Steam I Water VIII Div. 1 Air 15 - 3705 psi 0.424 in 3, 4 NPS 2 - 3 NPS [J] 1.36 in 1.453 sq in I & VIII Div. 1 Steam I Water VIII Div. 1 Air 15 - 3705 psi [K] 1.626 in 2.076 sq in 4 NPS 2.5 - 3 NPS 0.507 in I & VIII Div. 1 Steam I Water VIII Div. 1 Air 0.631 in [L] 2.025 in 3.221 sq in 4, 6 NPS 15 - 3705 psi 3 - 4 NPS I & VIII Div. 1 Steam I Water VIII Div. 1 Air 4 NPS 0.709 in 3.6 sq in 6 NPS [M] 2.141 in 15 - 2220 psi I & VIII Div. 1 Steam I Water VIII Div. 1 Air [N] 2.351 in 15 - 1480 psi 4.34 sq in 0.779 in I & VIII Div. 1 Steam I Water VIII Div. 1 Air 15 - 1480 psi [P] 3.029 in 1.263 in 7.206 sq in I & VIII Div. 1 Steam I Water VIII Div. 1 Air [Q] 3.985 in 1.243 in 15 - 1480 psi 6 NPS 8 NPS 12.472 sq in I & VIII Div. 1 Steam I Water VIII Div. 1 Air 2 in 15 - 1480 psi 18.065 sq in 8, 10 NPS [R] 4.796 in I & VIII Div. 1 Steam I Water VIII Div. 1 Air [T] 6.114 in 8 NPS 10 NPS 15 - 1480 psi 2.55 in 29.359 sq in I & VIII Div. 1 Steam I Water Page 400 of 812 Effective Date: 2019-05-31

402 Table of Contents Emerson Automation Solutions Final Control, US LP (KBM) 36043 NB#: 953 Old US Highway 70, Black Mountain, NC 28711 United States location: Acceptable Abbrev.: EMRN Emerson Automation Solutions Final Control, US LP (KBM) location: 953 Old US Highway 70, Black Mountain, NC 28711 United States Acceptable Abbrev.: EMRN Certification Design Series Kunkle 189, 363, 389 36043 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Ohio State University (Robinson Laboratory) on April 15, 1958 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .874 Unitless Certified Value: Air Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Inlet Size Code Section Media Set Pressure Range Lift Outlet Size VIII Div. 1 Air 50 - 2500 psi 0.031 in 0.5 in 0.034 sq in .75 NPS 0.5 - 0.75 NPS Page 401 of 812 Effective Date: 2019-05-31

403 Table of Contents Emerson Automation Solutions Final Control, US LP (KBM) 36076 NB#: 953 Old US Highway 70, Black Mountain, NC 28711 United States location: Acceptable Abbrev.: EMRN Certification Design Series 300,600 36076 Number: or catalog number Safety Valve Type Classification: Sec. I at Ohio State University (Robinson Laboratory) on February 10, 1961 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable by Dual Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Media Flow Area Code Section Inlet Size Lift Set Pressure Range VIII Air [F] 0.625 in 1.25 NPS 1.5 NPS 0.307 sq in 0.156 in 15 - 1000 psi I Steam VIII VIII Air 0.503 sq in 15 - 1000 psi 0.2 in [G] 0.8 in I Steam VIII VIII Air 1.5 NPS 2.5 NPS 0.785 sq in 0.25 in 15 - 1000 psi [H] 1 in I Steam VIII VIII Air 1.287 sq in 15 - 1000 psi [J] 1.28 in 0.32 in I Steam VIII VIII Air 2 NPS 3 NPS 1.839 sq in [K] 1.53 in 0.383 in 15 - 1000 psi I Steam VIII VIII Air 15 - 1000 psi 0.477 in [L] 1.906 in 2.853 sq in 4 NPS 2.5 NPS I Steam VIII VIII Air 15 - 1000 psi 3 NPS 0.535 in [M] 2.14 in 3.597 sq in 4 NPS I Steam VIII VIII Air 15 - 750 psi 4.34 sq in [N] 2.35 in 0.588 in 6 NPS 4 NPS I Steam VIII VIII Air 6.38 sq in 15 - 750 psi [P] 2.85 in 0.713 in I Steam VIII VIII Air 15 - 600 psi 0.938 in [Q] 3.75 in 11.045 sq in 6 NPS 8 NPS I Steam VIII Design Series Certification 330. 330S, 333S 36087 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Ohio State University (Robinson Laboratory) on June 14, 1972 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .026 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Code Section Media Set Pressure Range Lift Outlet Size Inlet Size VIII Div. 1 Air 1000 - 7500 psi 0.05 in 0.047 in 0.25 - 0.5 NPS Page 402 of 812 Effective Date: 2019-05-31

404 Table of Contents Emerson Automation Solutions Final Control, US LP (KBM) 36098 NB#: 953 Old US Highway 70, Black Mountain, NC 28711 United States location: Acceptable Abbrev.: EMRN Certification Design Series 920, 921, 927, Agco A (High Temp. water) 36098 or catalog number Number: Safety Valve Type Classification: Sec. I at Ohio State University (Robinson Laboratory) on May 19, 1969 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: Organic fluid vaporizers Special Service: Pop Set Pressure Definition: Adjustable by Single Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Code Section Outlet Size Inlet Size Media Set Pressure Range I Steam 15 - 1400 psi 0.106 in [D] 0.393 in .75, 1 NPS 0.5 - 1 NPS 0.1213 sq in I Steam 0.75 - 1.25 NPS 1.25 NPS 0.2157 sq in [E] 0.524 in 0.142 in 15 - 1100 psi I Steam 1.5 NPS [F] 0.655 in 1 - 1.5 NPS 15 - 1100 psi 0.177 in 0.3369 sq in I Steam 15 - 1100 psi 1.25 - 2 NPS 2 NPS 0.553 sq in [G] 0.839 in 0.227 in I Steam 2.5 NPS 1.5 - 2 NPS [H] 1.049 in 0.283 in 15 - 1000 psi 0.864 sq in I Steam 0.363 in 15 - 800 psi 2 - 2.5 NPS 3 NPS 1.415 sq in [J] 1.342 in Certification Design Series 910 to 919 36100 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on May 19, 1969 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Lift Inlet Size Code Section Set Pressure Range Media Outlet Size VIII Div. 1 Air 0.5 - 1 NPS .75, 1 NPS 0.1213 sq in [D] 0.393 in 0.106 in 15 - 1400 psi VIII Div. 1 Steam VIII Div. 1 Air 1.25 NPS 0.2157 sq in [E] 0.524 in 0.75 - 1.25 NPS 0.142 in 15 - 1100 psi VIII Div. 1 Steam VIII Div. 1 Air [F] 0.655 in 0.177 in 15 - 1100 psi 1 - 1.5 NPS 1.5 NPS 0.3369 sq in VIII Div. 1 Steam VIII Div. 1 Air 15 - 1100 psi 0.227 in 1.25 - 2 NPS 2 NPS 0.553 sq in [G] 0.839 in VIII Div. 1 Steam VIII Div. 1 Air 0.283 in 15 - 1000 psi 1.5 - 2 NPS [H] 1.049 in 0.864 sq in 2.5 NPS VIII Div. 1 Steam VIII Div. 1 Air [J] 1.342 in 0.363 in 15 - 800 psi 2 - 2.5 NPS 3 NPS 1.415 sq in VIII Div. 1 Steam Page 403 of 812 Effective Date: 2019-05-31

405 Table of Contents Emerson Automation Solutions Final Control, US LP (KBM) 36111 NB#: 953 Old US Highway 70, Black Mountain, NC 28711 United States location: Acceptable Abbrev.: EMRN Certification Design Series 910 to 919 (Sect. VIII Liquid), 928 and 929 (Sect. I Liquid) 36111 Number: or catalog number Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on May 08, 1985 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .710 Unitless Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Inlet Size Code Section Outlet Size Set Pressure Range Media I & VIII Div. 1 Water 15 - 1400 psi 0.5 - 1 NPS .75 , 1 NPS 0.1213 sq in [D] 0.393 in 0.126 in I & VIII Div. 1 Water 15 - 1000 psi 0.168 in [E] 0.524 in 0.2157 sq in 1.25 NPS 0.75 - 1.25 NPS I & VIII Div. 1 Water 0.21 in 15 - 700 psi 1 - 1.5 NPS 1.5 NPS 0.3369 sq in [F] 0.655 in I & VIII Div. 1 Water 2 NPS 1.25 - 2 NPS 0.553 sq in [G] 0.839 in 0.268 in 15 - 600 psi I & VIII Div. 1 Water 15 - 500 psi 1.5 - 2 NPS 0.864 sq in [H] 1.049 in 0.336 in 2.5 NPS I & VIII Div. 1 Water 2 - 2.5 NPS 3 NPS 1.415 sq in [J] 1.342 in 0.429 in 15 - 500 psi Certification Design Series Kunkle Fig. 930 36122 or catalog number Number: Safety Valve Type Classification: Sec. IV at National Board T L (Picaway) on April 13, 1975 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .818 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Inlet Size Lift Set Pressure Range IV Steam 15 - 15 psi 2 NPS 2 NPS 2.164 sq in 1.66 in 0.498 in IV Steam 2.5 NPS 1.98 in 2.5 NPS 0.594 in 15 - 15 psi 3.079 sq in IV Steam 0.738 in 15 - 15 psi 3 NPS 3 NPS 4.753 sq in 2.46 in Design Series Certification 1, 2 36223 Number: or catalog number Safety Valve Type Classification: Sec. VIII Div. 1 at Ohio State University (Robinson Laboratory) on July 01, 1953 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .823 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Outlet Size Set Pressure Range Lift Flow Area Inlet Size VIII Air 15 - 250 psi 0.029 in 0.049 sq in .75, Top NPS 0.5 - 0.75 NPS 0.75 in VIII Steam VIII Air 1 NPS 1 in 15 - 250 psi 0.038 in 1, Top NPS 0.0844 sq in VIII Steam Page 404 of 812 Effective Date: 2019-05-31

406 Table of Contents Emerson Automation Solutions Final Control, US LP (KBM) 36267 NB#: 953 Old US Highway 70, Black Mountain, NC 28711 United States location: Acceptable Abbrev.: EMRN Certification Design Series Kunkle 264, 265, 266 & 267 36267 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Ohio State University (Robinson Laboratory) on July 20, 1956 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .766 Unitless Certified Value: Steam & Air/Gas Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Outlet Size Lift Set Pressure Range Media Code Section Inlet Size VIII Div. 1 Steam .75, 1 NPS 0.11 sq in 0.375 in 0.5 - 1 NPS 15 - 2000 psi 0.115 in VIII Div. 1 Air 15 - 3300 psi Certification Design Series Kunkle 337 36278 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on February 22, 1982 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .86 Unitless Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size Media VIII Div. 1 Air 15 - 60 psi 0.612 in 1.562 in 2 NPS 2 NPS 1.916 sq in VIII Div. 1 Air 1.883 in 0.755 in 15 - 60 psi 2.5 NPS 2.5 NPS 2.786 sq in VIII Div. 1 Air 15 - 60 psi 3 NPS 3 NPS 4.037 sq in 2.267 in 0.91 in Design Series Certification Kunkle 537 36289 Number: or catalog number Safety Relief Valve Type Classification: Sec. IV at National Board T L (Picaway) on March 29, 1990 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .806 Unitless Certified Value: Steam Test Medium: Saturated Water Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Flow Area Outlet Size Set Pressure Range Media Code Section Lift IV Steam 0.824 in 0.33 in 15 - 160 psi 0.75 NPS 1 NPS 0.533 sq in IV Steam 1.25 NPS 0.833 sq in 1.03 in 0.412 in 15 - 160 psi 1 NPS IV Steam 1.5 NPS 2 NPS 15 - 160 psi 0.6 in 1.5 in 1.767 sq in IV Steam 2 in 0.82 in 15 - 160 psi 2 NPS 2.5 NPS 3.142 sq in Page 405 of 812 Effective Date: 2019-05-31

407 Table of Contents Emerson Automation Solutions Final Control, US LP (KBM) 36290 NB#: 953 Old US Highway 70, Black Mountain, NC 28711 United States location: Acceptable Abbrev.: EMRN Certification Design Series Kunkle 548-A (.295 Orifice) 36290 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Kunkle (Fort Wayne, IN) on May 20, 1988 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.0 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Flow Area Inlet Size Code Section Set Pressure Range Outlet Size Media VIII Air 15 - 400 psi 0.25 - 0.375 NPS Side 0.068 sq in 0.295 in 0.126 in Design Series Certification Kunkle 541-C/542-C/548-C (.422 Orifice) 36302 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Kunkle (Fort Wayne, IN) on May 20, 1988 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.0 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Media Code Section Set Pressure Range VIII Div. 1 Air Side 0.14 sq in 0.422 in 0.2 in 15 - 400 psi 0.5 - 0.75 NPS Design Series Certification Kunkle 6933, 6934, 6935, 6254 36313 Number: or catalog number Safety Valve Type Classification: Sec. IV at National Board T L (Picaway) on October 31, 1984 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam Test Medium: Steam Certified Medium: Pop Set Pressure Definition: Adjustable by Dual Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media Code Section IV Steam 15 - 15 psi 0.5 - 0.75 NPS 0.121 sq in [D] 0.393 in 0.094 in .75 NPS IV Steam 15 - 15 psi 0.75 - 1 NPS 1 NPS 0.216 sq in [E] 0.524 in 0.125 in IV Air 1.25 NPS 1 - 1.25 NPS [F] 0.654 in 0.156 in 15 - 15 psi 0.336 sq in IV Steam 0.2 in 15 - 15 psi 1.25 - 1.5 NPS 1.5 NPS 0.554 sq in [G] 0.84 in IV Steam 15 - 15 psi 0.25 in [H] 1.048 in 0.863 sq in 2 NPS 1.5 - 2 NPS IV Steam 15 - 15 psi 0.32 in [J] 1.342 in 1.414 sq in 2.5 NPS 1.5 - 2.5 NPS IV Steam 2 - 3 NPS [K] 1.605 in 2.022 sq in 0.432 in 15 - 15 psi 3 NPS IV Steam 15 - 15 psi [L] 1.999 in 3.138 sq in 4 NPS 2.5 - 4 NPS 0.539 in IV Steam 3 - 4 NPS 4 NPS 15 - 15 psi 0.605 in [M] 2.246 in 3.96 sq in IV Steam 0.664 in 15 - 15 psi 4 NPS [N] 2.466 in 6 NPS 4.774 sq in IV Steam [P] 2.99 in 0.805 in 15 - 15 psi 7.018 sq in Page 406 of 812 Effective Date: 2019-05-31

408 Table of Contents Emerson Automation Solutions Final Control, US LP (KBM) 36324 NB#: 953 Old US Highway 70, Black Mountain, NC 28711 United States location: Acceptable Abbrev.: EMRN Certification Design Series Kunkle 6000, 6252 Series 36324 or catalog number Number: Safety Valve Type Classification: Sec. I at National Board T L (Picaway) on March 24, 1982 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .878 Unitless Certified Value: Steam Test Medium: Steam & Air/Gas Certified Medium: Pop Set Pressure Definition: Adjustable by Dual Ring Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Outlet Size Lift Set Pressure Range Media Code Section Inlet Size VIII Air .75 NPS 0.121 sq in [D] 0.393 in 0.094 in 0.5 - 0.75 NPS 15 - 300 psi I Steam VIII VIII Air 0.216 sq in 15 - 300 psi 0.75 - 1 NPS 1, 1.25 NPS 0.125 in [E] 0.524 in I Steam VIII VIII Air 0.156 in 15 - 300 psi 1 - 1.25 NPS 1.25, 1.5 NPS 0.336 sq in [F] 0.654 in I Steam VIII VIII Air 0.2 in 1.25 - 1.5 NPS 1.5, 2 NPS 0.554 sq in [G] 0.84 in 15 - 300 psi I Steam VIII VIII Air 1.5 - 2 NPS 15 - 300 psi 2, 2.5 NPS 0.863 sq in [H] 1.048 in 0.25 in I Steam VIII VIII Air [J] 1.342 in 0.32 in 15 - 300 psi 1.5 - 2.5 NPS 2 .5, 3 NPS 1.414 sq in I Steam VIII VIII Air 0.432 in [K] 1.605 in 2.022 sq in 3 NPS 15 - 250 psi 2 - 3 NPS I Steam VIII VIII Air 2.5 - 4 NPS 4 NPS 3.138 sq in 0.539 in [L] 1.999 in 15 - 250 psi I Steam VIII VIII Air 4 NPS 3.96 sq in 3 - 4 NPS [M] 2.246 in 15 - 250 psi 0.605 in I Steam VIII VIII Air 0.664 in 15 - 250 psi 4 NPS 6 NPS 4.774 sq in [N] 2.466 in I Steam VIII VIII Air 15 - 250 psi 0.805 in [P] 2.99 in 7.018 sq in I Steam VIII VIII Air 6 NPS 8 NPS 15 - 250 psi 1.06 in [Q] 3.935 in 12.155 sq in I Steam VIII VIII Air [R] 4.735 in 1.276 in 15 - 250 psi 17.6 sq in I Steam VIII Page 407 of 812 Effective Date: 2019-05-31

409 Table of Contents Emerson Automation Solutions Final Control, US LP (KBM) 36335 NB#: 953 Old US Highway 70, Black Mountain, NC 28711 United States location: Acceptable Abbrev.: EMRN Certification Design Series Kunkle 30 36335 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Kunkle (Fort Wayne, IN) on December 18, 1989 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .186 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Media Flow Area Inlet Size Code Section Lift Set Pressure Range VIII Div. 1 Air Side 0.25 NPS 0.157 in 0.1 in 60 - 4000 psi Design Series Certification C776 36425 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. on July 15, 2002 Capacity Tests: Flow Capacity, K Method of Establishing Relieving Capacity: .790 Unitless Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Initial Audible Discharge Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Outlet Size Set Pressure Range Inlet Size Media Lift Flow Area VIII Div. 1 Air 15 - 600 psi .75, 1 NPS 0.169 sq in 0.5 - 0.75 NPS 0.116 in 0.465 in VIII Div. 1 Air 0.787 in 0.197 in 15 - 600 psi 0.75 - 1 NPS 1.25 NPS 0.486 sq in VIII Div. 1 Air 1 NPS 1.25 NPS 0.34 sq in 0.658 in 0.164 in 15 - 500 psi VIII Div. 1 Air 0.645 sq in 15 - 500 psi 0.906 in 0.227 in 1.5 NPS 1.25 NPS VIII Div. 1 Air 15 - 500 psi 0.286 in 1.142 in 1.024 sq in 2 NPS 1.5 NPS VIII Div. 1 Air 2 - 2.5 NPS 2.5 NPS 1.667 sq in 1.457 in 0.364 in 15 - 500 psi Certification Design Series Kunkle 541-A/542-A (.295 orifice) 36469 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. (Stafford TX) on December 14, 2010 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.0 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Code Section Outlet Size Flow Area Set Pressure Range Media Inlet Size VIII Div. 1 Air 0.295 in 0.126 in 15 - 200 psi 0.25 NPS Side 0.068 sq in Page 408 of 812 Effective Date: 2019-05-31

410 Table of Contents Emerson Automation Solutions Final Control, US LP (KBM) 36470 NB#: 953 Old US Highway 70, Black Mountain, NC 28711 United States location: Acceptable Abbrev.: EMRN Certification Design Series 82 Series D Orifice 36470 Number: or catalog number Safety Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. (Stafford TX) on March 07, 2012 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.03 SCFM/PSIA Certified Value: Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 [D] 0.402 in 0.101 in 15 - 1500 psi 0.75 - 1 NPS 1 NPS 0.127 sq in Design Series Certification 82 Series E Orifice 36481 or catalog number Number: Safety Valve Type Classification: Sec. VIII at Anderson Greenwood & Co. (Stafford TX) on March 07, 2012 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.47 SCFM/PSIA Certified Value: Gas Test Medium: Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Outlet Size Flow Area Code Section Inlet Size VIII Div. 1 Air 15 - 1500 psi 0.75 - 1 NPS 1 NPS 0.221 sq in [E] 0.53 in 0.133 in Design Series Certification Cash C600 36492 Number: or catalog number Safety Valve Type Classification: Sec. VIII Div. 1 at Anderson Greenwood & Co. (Stafford TX) on March 11, 2015 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 0.792 SCFM/PSIA Certified Value: Gas Test Medium: Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 90 - 600 psi 0.072 in 0.289 in 0.065 sq in Top 0.25 - 0.5 NPS VIII Div. 1 Air 0.065 sq in 0.072 in 90 - 600 psi Top 0.289 in 0.5625 in Page 409 of 812 Effective Date: 2019-05-31

411 Table of Contents Emerson Process Management Regulator Technologies, Inc. (FCF) 22262 NB#: Avenida Industrias No. 6025, Parque Industrial FINSA, Nuevo Laredo, Tamaulipas 88275 Mexico location: Acceptable Abbrev.: Fromex S.A. de C.V. Emerson Process Management Regulator Technologies, Inc. (FCF) location: Avenida Industrias No. 6025, Parque Industrial FINSA, Nuevo Laredo, Tamaulipas 88275 Mexico Acceptable Abbrev.: Fromex S.A. de C.V. Certification Design Series H722/ H822 22262 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on October 21, 2002 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 10.2 SCFM/PSIA Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Inlet Size Flow Area Outlet Size Code Section Media VIII Div. 1 Air 1.09 in 2 NPS Top 0.823 sq in 100 - 400 psi Certification Design Series H732/H832/H732F3/H832F3/H732A/H832A 22273 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on January 03, 2003 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 28.0 SCFM/PSIA Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Set Pressure Range Outlet Size Inlet Size Media Flow Area Code Section VIII Div. 1 Air 100 - 400 psi 3 NPS 1.84 in Top 2.463 sq in Design Series Certification H282/ H284/ H882/ H884/ H5112/ H5114/ H8112/ H8114/H5118/H8118 22284 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on November 07, 2002 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 30.9 SCFM/PSIA Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Inlet Size Outlet Size Flow Area Lift Set Pressure Range VIII Div. 1 Air Top 2.463 sq in 100 - 400 psi 2 NPS Page 410 of 812 Effective Date: 2019-05-31

412 Table of Contents Emerson Process Management Regulator Technologies, Inc. (FCF) 22295 NB#: Avenida Industrias No. 6025, Parque Industrial FINSA, Nuevo Laredo, Tamaulipas 88275 Mexico location: Acceptable Abbrev.: Fromex S.A. de C.V. Certification Design Series H733/H833/H733F3/H833F3 22295 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on April 23, 2013 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 29.77 SCFM/PSIA Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Code Section Media Flow Area Lift Set Pressure Range VIII Div. 1 100 - 400 psi 1.84 in 2.463 sq in Top 3 NPS Page 411 of 812 Effective Date: 2019-05-31

413 Table of Contents Enertech, A Business Unit of Curtiss-Wright Flow Control Company (ECW) 00662 NB#: 2950 E. Birch Street, location: Acceptable Abbrev.: Enertech Enertech, A Business Unit of Curtiss-Wright Flow Control Company (ECW) location: 2950 E. Birch Street, Acceptable Abbrev.: Enertech Certification Design Series NV51-1 00662 or catalog number Number: Relief Valve Type Classification: Sec. III NB at National Board T L (Worthington) on December 07, 2015 Capacity Tests: Flow Capacity, 1 valve method Method of Establishing Relieving Capacity: 6.3 GPM Certified Value: Water Test Medium: Liquid Certified Medium: None Special Service: First Steady Stream Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Inlet Size Code Section Media Set Pressure Range Lift Outlet Size III NB Water 50 - 50 psi 0.1 in 0.519 in 0.075 in .5 in 0.5 in Page 412 of 812 Effective Date: 2019-05-31

414 Table of Contents Engineered Controls International, LLC (REG) 46000 NB#: 100 Rego Drive, Elon, NC 27244 United States location: Acceptable Abbrev.: ECII, RegO Engineered Controls International, LLC (REG) 100 Rego Drive, Elon, NC 27244 United States location: Acceptable Abbrev.: ECII, RegO Certification Design Series AA3130A250 46000 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on February 09, 1981 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 1706 SCFM Certified Value: Air/Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media Code Section VIII Div. 1 Air 0.734 in 0.75 NPS Top 0.423 sq in 0.184 in 250 - psi Certification Design Series AA3130UA250 46011 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on August 30, 1978 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 1838 SCFM Certified Value: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Flow Area Outlet Size Lift Set Pressure Range Media Code Section VIII Div. 1 Air 0.75 NPS 250 - psi 0.184 in 0.423 sq in 0.734 in Top Certification Design Series AA3130UA265 46022 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on August 30, 1978 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 1912 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size Media VIII Div. 1 Air 0.734 in 0.184 in 265 - psi 0.75 NPS Top 0.423 sq in Page 413 of 812 Effective Date: 2019-05-31

415 Table of Contents Engineered Controls International, LLC (REG) 46033 NB#: 100 Rego Drive, Elon, NC 27244 United States location: Acceptable Abbrev.: ECII, RegO Certification Design Series 3131 (20% OP) 46033 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on February 27, 1981 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 6.161 SCFM/PSIA Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Outlet Size Inlet Size Set Pressure Range Lift Flow Area VIII Air Top 0.75 NPS 0.423 sq in 0.734 in 225 - 290 psi Certification Design Series AA3135A150 46055 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Rego (Chicago IL) on February 20, 1980 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 2969 SCFM Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Set Pressure Range Media Code Section Inlet Size Flow Area Outlet Size VIII Div. 1 Air Top 1.234 in 0.309 in 1.25 NPS 150 - psi 1.196 sq in Design Series Certification AA3135A300 46066 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Rego (Chicago IL) on February 20, 1980 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 5733 SCFM Certified Value: Air/Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size Media VIII Div. 1 Air 1.159 in 0.288 in 300 - psi 1.25 NPS Top 1.055 sq in Page 414 of 812 Effective Date: 2019-05-31

416 Table of Contents Engineered Controls International, LLC (REG) 46077 NB#: 100 Rego Drive, Elon, NC 27244 United States location: Acceptable Abbrev.: ECII, RegO Certification Design Series A3149 (20% OP) 46077 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Rego (Chicago IL) on February 09, 1981 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 29.086 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Air 0.41 in 200 - 358 psi 2.5 NPS Top 2.11 sq in 1.641 in Design Series Certification 7534 (20% OP) 46099 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on February 09, 1981 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 33.12 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Flow Area Outlet Size Lift Set Pressure Range Media Code Section VIII Div. 1 Air Top 2 NPS 225 - 290 psi 1.843 in 2.472 sq in Design Series Certification 7583 (20% OP) 46101 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on January 21, 1981 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 5.74 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Inlet Size Code Section Media Lift Set Pressure Range VIII Div. 1 Air 225 - 290 psi 0.199 in 0.795 in 0.374 sq in Top 0.75 NPS Page 415 of 812 Effective Date: 2019-05-31

417 Table of Contents Engineered Controls International, LLC (REG) 46112 NB#: 100 Rego Drive, Elon, NC 27244 United States location: Acceptable Abbrev.: ECII, RegO Certification Design Series A8434G 46112 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on April 29, 1988 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 3456 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Outlet Size Inlet Size Set Pressure Range Lift Flow Area VIII Air 0.7234 sq in 2 NPS Top 1.015 in 0.254 in 250 - 250 psi Certification Design Series A8434N 46123 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Rego (Chicago IL) on January 22, 1983 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 3659 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Code Section Lift Flow Area Inlet Size Outlet Size Set Pressure Range VIII Div. 1 Air 265 - psi 0.254 in 1.015 in 2 NPS Top 0.7324 sq in Certification Design Series A8436G, VA8436G 46134 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on May 02, 1988 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 9598 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Outlet Size Code Section Inlet Size Lift Flow Area VIII Air 1.766 in 0.442 in 250 - 250 psi 3 NPS Top 2.253 sq in Page 416 of 812 Effective Date: 2019-05-31

418 Table of Contents Engineered Controls International, LLC (REG) 46145 NB#: 100 Rego Drive, Elon, NC 27244 United States location: Acceptable Abbrev.: ECII, RegO Certification Design Series A8436N, VA8436N (20% OP) 46145 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Rego (Chicago IL) on January 21, 1981 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 9839 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Air/Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Air 3 NPS Top 2.253 sq in 1.766 in 265 - 265 psi Design Series Certification 8543 (20% OP) 46156 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Rego (Chicago IL) on May 24, 1982 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 4.45 SCFM/PSIA Certified Value: Air Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 225 - 312 psi 1.25 NPS Top 0.304 sq in 0.65 in 0.163 in Design Series Certification 8544 (20% OP) 46167 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Rego (Chicago IL) on December 20, 1985 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.979 SCFM/PSIA Certified Value: Air Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Code Section Media Set Pressure Range Lift Inlet Size Flow Area VIII Div. 1 Air 1.25 NPS 229 - 386 psi 0.143 in 0.57 in 0.228 sq in Top Page 417 of 812 Effective Date: 2019-05-31

419 Table of Contents Engineered Controls International, LLC (REG) 46178 NB#: 100 Rego Drive, Elon, NC 27244 United States location: Acceptable Abbrev.: ECII, RegO Certification Design Series 8684 (20% OP) 46178 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on January 22, 1981 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 8.15 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Media Inlet Size Set Pressure Range Lift Outlet Size VIII Div. 1 Air 0.593 sq in 1 NPS Top 0.921 in 0.305 in 225 - 290 psi Certification Design Series 8685 (20% OP) 46189 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on January 22, 1981 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 12.82 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Lift Set Pressure Range Media Code Section Inlet Size Flow Area Outlet Size VIII Div. 1 Air Top 1.218 in 0.305 in 1.25 NPS 225 - 290 psi 1.06 sq in Design Series Certification B-19434B & C-19434B 46190 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Rego (Chicago IL) on June 28, 1983 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.744 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size Media VIII Div. 1 Air 235 - 300 psi 0.5 NPS Side 0.118 sq in 0.387 in Page 418 of 812 Effective Date: 2019-05-31

420 Table of Contents Engineered Controls International, LLC (REG) 46213 NB#: 100 Rego Drive, Elon, NC 27244 United States location: Acceptable Abbrev.: ECII, RegO Certification Design Series UA3149A 46213 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on May 17, 1994 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 28.4 SCFM/PSIA Certified Value: Air Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Flow Area Inlet Size Outlet Size Code Section Media Lift VIII Div. 1 Air 0.41 in 303 - 358 psi 2.5 NPS Top 2.11 sq in 1.641 in Design Series Certification AA3135 (20% OP) 46268 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on October 13, 2000 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 19.25 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Flow Area Outlet Size Lift Set Pressure Range Media Code Section VIII Div. 1 Air Top 225 - 265 psi 0.309 in 1.25 NPS 1.234 in 1.196 sq in Design Series Certification PRV19430 , PRV29430 46279 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on February 11, 2000 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .783 SCFM/PSIA Certified Value: Air Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Inlet Size Code Section Lift Set Pressure Range Media VIII Div. 1 Air 90 - 600 psi 0.281 in 0.062 sq in Top 0.25 - 0.5 NPS Page 419 of 812 Effective Date: 2019-05-31

421 Table of Contents Engineered Controls International, LLC (REG) 46291 NB#: 100 Rego Drive, Elon, NC 27244 United States location: Acceptable Abbrev.: ECII, RegO Certification Design Series A3149 (20% OP) 46291 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on August 20, 2002 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 32.66 SCFM/PSIA Certified Value: Air/Gas Test Medium: Gas Certified Medium: Non-refrigerated liquified compressed gases Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Air 0.41 in 55 - 150 psi 2.5 NPS Top 2.11 sq in 1.641 in Design Series Certification AA3135A (20% OP) 46303 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on December 03, 2003 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 14.8 SCFM/PSIA Certified Value: Air Test Medium: Gas Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air Top 1.25 NPS 1.053 sq in 1.234 in 0.288 in 50 - 140 psi Design Series Certification 6555 Series 46314 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on December 05, 2005 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 700 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Gas Test Medium: Gas Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Lift Outlet Size Media Set Pressure Range Flow Area Code Section VIII Div. 1 Air 250 psi 0.143 in 0.57 in 0.255 sq in Top 0.75 NPS Page 420 of 812 Effective Date: 2019-05-31

422 Table of Contents Engineered Controls International, LLC (REG) 46325 NB#: 100 Rego Drive, Elon, NC 27244 United States location: Acceptable Abbrev.: ECII, RegO Certification Design Series B-19434B350-375 & C-19434B350-375 46325 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on November 27, 2001 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.778 SCFM/PSIA Certified Value: Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Air 0.5 NPS Top 0.118 sq in 0.387 in 325 - 375 psi Certification Design Series 8546T (20% OP) 46336 or catalog number Number: Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on July 18, 2008 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 792 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Gas Test Medium: Gas Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 312 psi 0.75 NPS 0.45 in 0.159 sq in Top Certification Design Series 8546G (20% OP) 46347 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on July 18, 2008 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 651 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Gas Test Medium: Gas Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Code Section Media Set Pressure Range Flow Area Lift VIII Div. 1 Air 250 psi 0.45 in 0.159 sq in Top 0.75 NPS Page 421 of 812 Effective Date: 2019-05-31

423 Table of Contents Engineered Controls International, LLC (REG) 46358 NB#: 100 Rego Drive, Elon, NC 27244 United States location: Acceptable Abbrev.: ECII, RegO Certification Design Series 3135 (20% OP) 46358 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on October 22, 2010 Capacity Tests: Flow Capacity, 3 valve average Method of Establishing Relieving Capacity: 5343 SCFM Certified Value: Cert. @ 20% OP Certification Provisions: Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Air 1.25 NPS Top 1.055 sq in 1.159 in 250 psi Design Series Certification AR4106A, AR5106A 46369 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on February 07, 2012 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.56 SCFM/PSIA Certified Value: Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 75 - 400 psi 0.75 NPS 1 NPS 0.135 sq in 0.415 in 0.104 in Design Series Certification AR4108A, AR5108A 46370 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on February 07, 2012 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 3.46 SCFM/PSIA Certified Value: Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 75 - 425 psi 0.191 in 0.593 in 0.276 sq in 1.25 NPS 1 NPS Page 422 of 812 Effective Date: 2019-05-31

424 Table of Contents Engineered Controls International, LLC (REG) 46381 NB#: 100 Rego Drive, Elon, NC 27244 United States location: Acceptable Abbrev.: ECII, RegO Certification Design Series AR4112A, AR5112A 46381 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on February 07, 2012 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 7.86 SCFM/PSIA Certified Value: Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Flow Area Inlet Size Outlet Size Code Section Media Lift VIII Div. 1 Air 0.248 in 80 - 425 psi 1.5 NPS 2 NPS 0.65 sq in 0.91 in Design Series Certification AR4104A, AR5104A 46392 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on June 06, 2013 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.40 SCFM/PSIA Certified Value: Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 0.5 NPS 1 NPS 0.135 sq in 0.415 in 0.104 in 75 - 500 psi Design Series Certification NG9008M 46404 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Engineered Controls on January 29, 2014 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.026 SCFM/PSIA Certified Value: Cert. @ 20% OP Certification Provisions: Gas Test Medium: Gas Certified Medium: None Special Service: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Flow Area Inlet Size Code Section Media Set Pressure Range Lift Outlet Size VIII Div. 1 Air 230 - 415 psi 0.281 in 0.062 3/8 0.5 Page 423 of 812 Effective Date: 2019-05-31

425 Table of Contents Engineered Controls International, LLC (REG) 46415 NB#: 100 Rego Drive, Elon, NC 27244 United States location: Acceptable Abbrev.: ECII, RegO Certification Design Series PRV19430, PRV29430 (Low Pressure) 46415 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on October 16, 2017 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 0.750 SCFM/PSIA Certified Value: Gas Test Medium: Gas Certified Medium: Start-to-Leak Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 15 - 89 psi 0.281 in 0.062 sq in Top 0.25 - 0.5 NPS Page 424 of 812 Effective Date: 2019-05-31

426 Table of Contents Enviro Valve Inc (ENV) 58025 NB#: 807 N. Sycamore Ave., Broken Arrow, OK 74012 United States location: Acceptable Abbrev.: EnviroValve Enviro Valve Inc (ENV) location: 807 N. Sycamore Ave., Broken Arrow, OK 74012 United States Acceptable Abbrev.: EnviroValve Certification Design Series EVSP 58025 Number: or catalog number Breaking Bar Non-reclosing Device Type Classification: Sec. VIII Div. 1 at National Board T L (Worthington) on July 18, 2013 Capacity Tests: Resistance Factor, 3 Size, Krg Method of Establishing Relieving Capacity: 3.71 Unitless Certified Value: Air/Gas Test Medium: Air or gases, and liquid (Krgl) Certified Medium: Breaking Pressure Set Pressure Definition: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Media Outlet Size Inlet Size Set Pressure Range Lift Flow Area VIII Div. 1 15 - 45 psi 8 NPS 8 NPS 24.2 sq in 7.3 in VIII Div. 1 7.3 in 25.13 sq in 5 - 15 psi VIII Div. 1 10 NPS 10 NPS 43.95 sq in 9.31 in 15 - 45 psi VIII Div. 1 45.52 sq in 9.33 in 5 - 15 psi VIII Div. 1 11.2 in 12 NPS 70.99 sq in 15 - 45 psi 12 NPS VIII Div. 1 72.69 sq in 11.23 in 5 - 15 psi VIII Div. 1 12.38 in 15 - 45 psi 14 NPS 14 NPS 87.29 sq in VIII Div. 1 5 - 15 psi 12.41 in 89 sq in VIII Div. 1 14.28 in 16 NPS 16 NPS 118.86 sq in 15 - 45 psi VIII Div. 1 119.95 sq in 14.3 in 5 - 15 psi VIII Div. 1 15 - 45 psi 16.21 in 18 NPS 18 NPS 159.36 sq in VIII Div. 1 5 - 15 psi 16.21 in 160.12 sq in VIII Div. 1 18.12 in 201.91 sq in 20 NPS 20 NPS 15 - 45 psi VIII Div. 1 202.47 sq in 18.12 in 5 - 15 psi VIII Div. 1 24 NPS 15 - 45 psi 24 NPS 310.41 sq in 21.95 in VIII Div. 1 311.54 sq in 5 - 15 psi 21.95 in VIII Div. 1 26.83 in 5 - 30 psi 30 NPS 30 NPS 437.48 sq in Page 425 of 812 Effective Date: 2019-05-31

427 Table of Contents F. C. Kingston Company (KNG) 35008 NB#: 23201 Normandie Avenue, Torrance, CA 90501 United States location: Acceptable Abbrev.: Kingston F. C. Kingston Company (KNG) location: 23201 Normandie Avenue, Torrance, CA 90501 United States Acceptable Abbrev.: Kingston Certification Design Series 110C 35008 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Ladewig Valve Company on November 01, 1967 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .59 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Inlet Size Outlet Size Flow Area Lift Set Pressure Range Media Code Section VIII Air 25 - 600 psi Side 0.069 sq in 0.296 in 0.25 - 0.375 NPS 0.074 in Design Series Certification 112C (.250" Orif.) 35019 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Phillips Petroleum on February 11, 1966 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .51 SCFM/PSIA Certified Value: Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Set Pressure Range Media Code Section Flow Area Outlet Size Inlet Size Lift VIII Div. 1 Air 0.062 in 0.25 in 0.049 sq in 25 - 300 psi 0.25 - 0.375 NPS Side Certification Design Series 112C (.375" Orif.) 35020 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Phillips Petroleum on February 11, 1966 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .78 SCFM/PSIA Certified Value: Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Outlet Size Flow Area Inlet Size Code Section Media Lift Set Pressure Range VIII Div. 1 Air 25 - 300 psi 0.094 in 0.375 in 0.11 sq in Side 0.5 NPS Page 426 of 812 Effective Date: 2019-05-31

428 Table of Contents F. C. Kingston Company (KNG) 35031 NB#: 23201 Normandie Avenue, Torrance, CA 90501 United States location: Acceptable Abbrev.: Kingston Certification Design Series Fig. 114 (.437" Orif.) 35031 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at National Board T L (Picaway) on January 17, 1982 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 1.6 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Flow Area Outlet Size Media Set Pressure Range Lift Inlet Size VIII Div. 1 Air 0.144 in 25 - 250 psi 0.75 NPS Side 0.15 sq in 0.437 in Design Series Certification Fig. 114 (.625" Orif.) 35042 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Phillips Petroleum on January 17, 1962 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: 2.37 SCFM/PSIA Certified Value: Air/Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Media Set Pressure Range Lift Code Section Flow Area Outlet Size Inlet Size VIII Div. 1 Air 25 - 250 psi 1 NPS Side 0.307 sq in 0.625 in 0.156 in Design Series Certification Fig. 114 & 115 (.219" Orif.) 35053 Number: or catalog number Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Phillips Petroleum on May 08, 1961 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .52 SCFM/PSIA Certified Value: 1.46 PPH/PSIA Certified Value (alternate medium): Gas Test Medium: Steam & Air/Gas Certified Medium: None Special Service: Pop Set Pressure Definition: Fixed Blowdown: Scope of Nominal Size and Set Pressure Ranges: Orifice [designator] diameter Code Section Set Pressure Range Lift Inlet Size Flow Area Outlet Size Media VIII Div. 1 Air Side 0.25 NPS 25 - 300 psi 0.055 in 0.219 in 0.038 sq in VIII Div. 1 Steam 35 - 50 psi Page 427 of 812 Effective Date: 2019-05-31

429 Table of Contents F. C. Kingston Company (KNG) 35064 NB#: 23201 Normandie Avenue, Torrance, CA 90501 United States location: Acceptable Abbrev.: Kingston Certification Design Series Fig. 114 & 115 (.265 Orif.) 35064 or catalog number Number: Safety Relief Valve Type Classification: Sec. VIII Div. 1 at Phillips Petroleum on October 23, 1961 Capacity Tests: Flow Capacity, Slope Method of Establishing Relieving Capacity: .69 SCFM/PSIA Certified Value: Gas Test Medium: Air/Gas Certified Medium: Pop Set Pressure De